FORM R405-2014
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
: Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: WYNNE THE GRAND CARLTON 299 Builder Name: WYNNE DEVELOPMENT
Street: THE CARLTON 299 Permit Office: ST.LUCIE COUNTY
City,State,Zip: FT.PIERCE,FL, Permit Number:
Owner: \ Jurisdiction:
Design Location: FL,Fort Pierce County:: ST.LUCIE COUNTY(Florida Climate Zone 2)
1. New construction or existing New(From Plans) 9. Wall Types(1250.0 sqft.) Insulation Area
2. Single family or multiple family Single-family a.Concrete Block-Ext Insul,Exterior R=4.1 1250.00 ft2
b.N/A R= ft2
3. Number of units,if multiple family 1 c.NIA R= ft2
4. Number of Bedrooms 2 d.N/A R= ft2
10.Ceiling Types (1474.0 sqft.) Insulation Area
5. Is this a worst case? Yes a.Under Attic(Vented) R=30.0 1474.00 ft2
6. Conditioned floor area above grade,(ft2) 1474 b.N/A R= ft2
Conditioned floor area below grade(ft2) 0 c.N/A R= ft2
11.Ducts R, ft2
7. Windows(139.7 sqft.) Description Area a.Sup:Attic,Ret:Attic,AH:Attic 6, 325
a. U-Factor: Sgl,U=0.55 99.74 ft2
SHGC: SHGC=0.25
b. U-Factor. Sgl,U=0.54 40.00 ft2 12.Cooling systems kBtu/hr Efficiency
SHGC: SHGC=0.25 a.Central Unit 34.8 SEER:15.00
c. U-Factor: N/A ft2
SHGC: 13.Heating systems kBtu/hr Efficiency
d. U-Factor: N/A ft2 a.Electric Heat Pump 34.8 HSPF,8.50
SHGC:
Area Weighted Average Overhang Depth: 4.381 ft.
Area Weighted Average SHGC: 0.250 14.Hot water systems
8. Floor Types (1473.5 sqft.) Insulation Area a.Electric Cap:40 gallons
a.Slab-On-Grade Edge Insulation R=0.0 1473.50 ft2 b. Conservation features EF:0.950
b.N/A R= ft2 None
c.N/A R= ft2 15.Credits CF,Pstat
Glass/Floor Area: 0.095 Total Proposed Modified Loads: 45.94
Total Baseline Loads: 47.92 PASS
I hereby certify that the plans and specifications covered by Review of the plans and O�-fKE SATE
this calculation are in compliance with the Florida Energy specifications covered by this 1+ r Off,
Code. calculation indicates compliance ���,,,'
with the Florida Energy Code. �- �,«„ -=` _
PREPARED BY: Before construction is completed
DATE: I�y�-i lQ this building will be inspected for
compliance with Section 553.908 * �_
I hereby certify that this building, as designed,is in compliance Florida Statutes.
with the Florida Energy Code. COD WE
OWNER/AG N BUILDING OFFICIAL:
DATE: DATE: II
u
- Compliance requires certification by the air handier unit manufacturer that the air handler enclosure qualifies as
certified factory-sealed in accordance with R403.2.2.1.
-Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and an envelope leakage
test report in accordance with R402.4.1.2.
11/14/2016 9:03 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 5
FORM R405-2014
PROJECT
Title: WYNNE THE GRAND CARL Bedrooms: 2 Address Type: Street Address
Building Type: User Conditioned Area: 1474 Lot#
Owner: l Total Stories: 1 Block/SubDivision:
#of Units: 1 Worst Case: Yes PlatBook:
Builder Name: WYNNE DEVELOPMENT Rotate Angle: 180 Street: THE CARLTON 299
Permit Office: ST.LUCIE COUNTY Cross Ventilation: No County: ST.LUCIE COUNTY
Jurisdiction: Whole House Fan: No City,State,Zip: FT.PIERCE;
Family Type: Single-family FL,
New/Existing: New(From Plans)
Comment:
CLIMATE
IECC Design Temp Int Design Temp Heating Design Daily Temp
\/ Design Location TMY Site Zone 97.5% 2.5% Winter Summer Degree Days Moisture Range
FL,Fort Pierce FL VERO_BEACH_MUNI 2 39 90 70 75 299 62 Low
BLOCKS
Number Name Area Volume
1 Entire House 1474 11792
SPACES
Number Name Area Volume Kitchen Occupants Bedrooms InfilID Finished Cooled Heated
1 BEDROOM 266 2128 No 0 1 1 Yes Yes Yes
2 WIC 63 504 No 0 1 No Yes Yes
3 MASTER BATH 63 504 No 0 1 Yes Yes Yes
4 M.BATH 56 448 No 0 1 Yes Yes Yes
5 KITCHEN 192 1536 Yes 0 1 No Yes Yes
6 BATH 45 360 No 0 1 Yes Yes Yes
7 BEDROOM 2 204 1632 No 0 1 1 Yes Yes Yes
8 ENTRY 55 440 No 0 1 Yes Yes i Yes
9 LAUNDRY 42 336 No 0 1 Yes Yes Yes
10 GREAT/DINING 488 3904 No 0 1 Yes Yes j Yes
FLOORS
# Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet
1 Slab-On-Grade Edge Insulatio BEDROOM 43 ft 0 266 ft2 ____ 0 1 0
2 Slab-On-Grade Edge Insulatio WIC 1 ft 0 63 ft2 __-- 0 1 0
3SIab-On-Grade Edge Insulatio MASTER BATH 9 ft 0 63 ft2 0 1 'I 0
4SIab-On-Grade Edge Insulatio M.BATH 8 ft 0 56 ft2 0 1 I� 0
5Slab-On-Grade Edge Insulatio KITCHEN 1 ft 0 192 ft2 0 1 0
6 Slab-On-Grade Edge Insulatio BATH 5 ft 0 45 ft2 0 1 0
7 Slab-On-Grade Edge Insulatio BEDROOM 2 32.2 ft 0 203.5 ft2 0 1 0
11/14/2016 9:03 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 2 of 5
I
FORM R405-2014
FLOORS
# Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet
8 Slab-On-Grade Edge Insulatio ENTRY 7 ft 0 55 ft2 - 0 1 0
9 Slab-On-Grade Edge Insulatio LAUNDRY 6 ft 0 42 ft2 ___ 0 1 0
10SIab-On-Grade Edge Insulatio GREAT/DINING 46 ft 0 488 ft2 0 11 0
ROOF
Roof Gable Roof Solar SA Emitt Emitt Deck Pitch
# Type Materials Area Area Color Absor. Tested Tested Insul. (deg)
1 Gable or Shed Metal 1553 ft2 246 ft2 Light 0.6 No 0.9 No 0 18.4
ATTIC
V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC
1 Full attic Vented 150 1474 ft2 N N
CEILING
# Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type
1 Under Attic(Vented) BEDROOM 30 Blown 266 ft2 0.1 Wood
2 Under Attic(Vented) WIC 30 Blown 63 ft2 0.1 Wood
3 Under Attic(Vented) MASTER BATH 30 Blown 63 ft2 0.1 Wood
4 Under Attic(Vented) M.BATH 30 Blown 56 ft2 0.1 Wood
5 Under Attic(Vented) KITCHEN 30 Blown 192 ft2 0.1 Wood
6 Under Attic(Vented) BATH 30 Blown 45 ft2 0.1 Wood
7 Under Attic(Vented) BEDROOM 2 30 Blown 204 ft2 0.1 Wood
8 Under Attic(Vented) ENTRY 30 Blown 55 ft2 0.1 Wood
9 Under Attic(Vented) LAUNDRY 30 Blown 42 ft2 0.1 Wood
10 Under Attic(Vented) GREAT/DINING 30 Blown 488 ft2 0.1 Wood
WALLS
Adjacent !1 Cavity Width Height Sheathing Framing Solar Below
Type Space R-Value Et In Ft In Area R-Value-Fraction-A °
1 NE=>SW Exterior Concrete Block-Ext InsiMEDROOM 4.1 10 0 8 0 80.0 ft2 0 0 0.5 0
2 SW=>NE Exterior Concrete Block-Ext InsfEDROOM 4.1 19 0 8 0 152.0 ft2 0 0 0.5 0
3 NW=>SE Exterior Concrete Block-Ext InsBEDROOM 4.1 14 0 8 0 112.0 ft2 0 0 0:5 0
4 SW=>NE Exterior Concrete Block-Ext InddASTER BA 4.1 9 0 8 0 72.0 ft2 0 0 0.5 0
5 SW=>NE Exterior Concrete Block-Ext InsuM.BATH 4.1 8 0 8 0 64.0 ft2 0 0 0.5 0
_ 6 NE=>SW Exterior Concrete Block-Ext Insul BATH 4.1 5 0 8 0 40.0 ft2 0 0 015 0
7 NE=>SW Exterior Concrete Block-Ext InSEDROOM 2 4.1 16 0 8 0 128.0 ft2 0 0 015 0
8 SE=>NW Exterior Concrete Block-Ext InfiffDROOM 2 4.1 10 0 8 0 80.0 ft2 0 0 0
1I5 0
9 S=>N Exterior Concrete Block-Ext IndKDROOM 2 4.1 4 3 8 0 34.0 ft2 0 0 0!5 0
10 SW=>NE Exterior Concrete Block-Ext InQEDROOM 2 4.1 2 0 8 0 16.0 ft2 0 0 0:5 0
11 SE=>NW Exterior Concrete Block-Ext Insul ENTRY 4.1 6 0 8 0 48.0 ft2 0 0 0.5 0
i
12 SW=>NE Exterior Concrete Block-Ext Insul ENTRY 4.1 1 0 8 0 8.0 ft2 0 0 0.5 0
11/14/2016 9:03 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 3 of 5
i
FORM R405-2014
WALLS
Adjacent Cav
Space ity Width Height Sheathing Framing Solar Below
[lie Ft In Ft In Area R--VaI,,e Fraction Absor Grade%
13 SW=>NE Exterior Concrete Block-Ext InsillAUNDRY 4.1 6 0 8 0 48.0 ft2 0 0 0!5 0
I
14 NE=>SW Exterior Concrete Block-Ext InsGREAT/DINI 4.1 26 0 8 0 208.0 ft2 0 0 015 0
15 NW=>SE Exterior Concrete Block-Ext InsGREAT/DINI 4.1 20 0 8 0 160.0 ft2 0 0 0!5 0
DOORS
# Omt Door Type Space Storms U-Value Width Height Area
Ft In Ft In
1 SE=>NW Insulated ENTRY None .39 3 1 7 21.6 ft2
WINDOWS
Orientation shown is the entered orientation => changed to Worst Case.
Wall Overhang
v # Omt ID Frame Panes NFRC U-Factor SHGC Area Depth Separation Int Shade Screening
1 NW=>SE 3 Metal Low-E Single Yes 0.55 0.25 32.9 ft2 2 ft 0 in 1 ft 4 in Drapes/blinds Exterior 5
2 SW=>NE 5 Metal Low-E Single Yes 0.55 0.25 6.9 ft2 2 ft 0 in 1 ft 4 in None None
3 SE=>NW 8 Metal Low-E Single Yes 0.55 0.25 23.2 ft2 6 ft 0 in 1 ft 4 in None None
4 NE=>SW14 Metal Low-E Single Yes 0.55 0.25 36.8 ft2 2 ft 0 in 1 ft 4 in None None
5 NW=>SE15 Metal Low-E Single Yes 0.54 0.25 40.0 ft2 8 ft 0 in 1 ft 4 in None None
GARAGE
# Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation
1 320 ft2 384 ft2 20 ft 8 ft 11
I
INFILTRATION
# Scope Method SLA CFM 50 ELA EgLA ACH ACH 50
1 Wholehouse Proposed ACH(50) .000356 1375.7 75.53 142.04 .2598 7
HEATING SYSTEM I'
# System Type Subtype Efficiency Capacity Block,' Ducts
1 Electric Heat Pump Split HSPF:8.5 34.8 kBtu/hr 1 sys#1
COOLING SYSTEM
# System Type Subtype Efficiency Capacity Air Flow SHR Block!; Ducts
1 Central Unit Split SEER: 15 34.8 kBtu/hr cfm 0.8 1 ;I sys#1
HOT WATER SYSTEM
# System Type SubTpe Location EF Cap Use SetPnt Conservation
1 Electric None Garage 0.95 40 gal 60.9 gal 120 deg None
�I
11/14/2016 9:03 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 4 of 5
FORM R405-2014
SOLAR HOT WATER SYSTEM
FSEC Collector Storage
Cert # Company Name System Model# Collector Model# Area Volume FEF
None None ! ft2
DUCTS
—Supply— —Return— Air CFM 25 CFM25 HVAC#
V # Location R-Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool
1 Attic 6 325 ft2 Attic 105 ft2 Default Leakage Attic (Default) (Default) 1 1
TEMPERATURES
Programable Thermostat:Y Ceiling Fans:
CoolingJan Feb Mar A r Ma Jun Jul Au X Se Oct Nov, Dec
Heatin Jan Feb Mar Apr May Jun Jul Aug Sep �X�Oct Nov
ki
Nov, Dec Venting Jan Feb Mar
Thermostat Schedule: HERS 2006 Reference Hours
'Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12
Cooling(WD) AM 78 78 78 78 78 78 78 78 80 80 80' 80
PM 80 80 78 78 78 78 78 78 78 78 78- 78
Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78
PM 78 78 78 78 78 78 78 78 78 78 78 78
LH"ea
WD) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66', 66
u
it
i
i
11/14/2016 9:03 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software 3age 5 of 5
I
y
Ii
FORM R405-2014
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
i
Project Name: WYNNE THE GRAND CARLTON 299 Builder Name: WYNNE DEVELOPMENT
Street: THE CARLTON 299 Permit Office: ST.LUCIE COUNTY
City,State,Zip: FT.PIERCE,FL, Permit Number.
Owner: Jurisdiction:
Design Location: FL,Fort Pierce
COMPONENT CRITERIA CHECK
Air barrier and thermal barrier A continuous air barrier shall be installed in the building envelope.
Exterior thermal envelope contains a continuous barrier.
Breaks or joints in the air barrier shall be sealed.
Air-permeable insulation shall not be used as a sealing material.
Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with the
insulation and any gaps in the air barrier shall be sealed.
Access openings,drop down stairs or knee wall doors to unconditioned
attic spaces shall be sealed.
Comers and headers shall be insulated and the junction of the foundation
Walls and sill plate shall be sealed.
The junction of the top plate and the top or exterior walls shall be sealed.
Exterior thermal envelope insulation for framed walls shall be installed in
substantial contact and continuous alignment with the air barrier.
Knee walls shall be sealed.
Windows, skylights and doors The space between window/door jambs and framing and skylights and
framing shall be sealed.
Rim joists Rim joists are insulated and include an air barrier.
Floors (including above-garage Insulation shall be installed to maintain permanent contact with underside
and cantilevered floors) of subfloor decking.
The air barrier shall be installed at any exposed edge of insulation.
Crawl space walls Where provided in lieu of floor insulation, insulation shall be permanently
attached to the crawlspace walls.
Exposed earth in unvented crawl spaces shall be covered with a Class I
vapor retarder with overlapping joints taped.
Shafts, penetrations Duct shafts, utility penetrations,and flue shaft openings to exterior or
unconditioned space shall be sealed.
Narrow cavities Batts in narrow cavities shall be cut to fit,or narrow cavities shall be filled
by insulation that on installation readily conforms to the available cavity
spaces.
Garage separation Air sealing shall be provided between the garage and conditioned spaces.
Recessed lighting Recessed light fixtures installed in the building thermal envelope shall be
air tight, IC rated,and sealed to the drywall.
Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in
exterior walls,or insulation that on installation readily conforms to available
space shall extend behind piping and wiring.
Shower/tub on exterior wall Exterior walls adjacent to showers and tubs shall be insulated and the air 'I
barrier installed separating them from the showers and tubs.
Electrical/phone box on The air barrier shall be installed behind electrical or communication boxes or
air sealed boxes shall be installed.
HVAC register boots j HVAC register boots that penetrate building thermal envelope shall be
sealed to the sub-floor or drywall.
Fireplace An air barrier shall be installed on fireplace walls. Fireplaces shall have
gasketed doors
11/14/2016 9:03 AM EnergyGauge@ USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 1
�I
li
III
FORM R405-2014
ENERGY PERFORMANCE LEVEL (EPL)
DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 96
The lower the EnergyPerformance Index, the more efficient the home.
THE CARLTON 299, FT. PIERCE, FL,
1. New construction or existing New(From Plans) 9. Wall Types Insulation Area
2. Single family or multiple family Single-family a.Concrete Block-Ext Insul,Exterior R=4.1 1250.00 ft2
9 Y P Y 9 Y b.N/A R= ft2
3. Number of units,if multiple family 1 c.N/A R= ft2
4. Number of Bedrooms 2 d.N/A R= ft2
5. Is this a worst case? Yes 10.Ceiling Types Insulation Area a.Under Attic(Vented) R=30.0 1474.00 ft2
6. Conditioned floor area(ft2) 1474 b.N/A R= ft2
7. Windows- Description Area c.NIA R= ft22
a. U-Factor: Sgl,U=0.55 99.74 ft2 11.Ducts R 1! ft
a.Sup:Attic,Ret:Attic,AH:Attic 6 1 325
SHGC: SHGC=0.25
b. U-Factor: Sgl,U=0.54 40.00 ft2
SHGC: SHGC=0.25 12.Cooling systems kBtu/hr Efficiency
c. U-Factor: N/A ft2 a.Central Unit 34.8 SEER:15.00
SHGC:
d. U-Factor: N/A ft2 13.Heating systems kBtu/hr Efficiency
SHGC: a.Electric Heat Pump 34.8 HSPF:8.50
Area Weighted Average Overhang Depth: 4.381 ft.
Area Weighted Average SHGC: 0.250
8. Floor Types Insulation Area 14.Hot water systems
Cap:40 gallons
a.Slab-On-Grade Edge Insulation R=0.0 1473.60 ft2 a.Electric ER 0.95
b.N/A R= ft2 C.N/A R= ft2 b. Conservation features
None
15.Credits CF,Pstat
1 certify that this home has complied with the Florida Energy Efficiency Code for Building FTKE SpA?
Construction through the above energy saving features which will be installed (or exceeded) 4V0 ,Foy
in this home before final inspection. Otherwise, a new EPL Display Card will be completed
P P Y P
based on installed Code compliant features.
Builder Signature: ¢� Date: �
Address of New Home: �� tC�\� City/FL Zip: �
72 WE
*Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient
mortgage(EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at(321)
638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For
information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support
staff.
**Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
i
11/14/2016 9:03 AM I EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compliant Software Page 1 of 1
I �
I I
-� wr1ghts0ft
Project Summary
Date:
Bifire W ouse By:
.
QUICK CALLS, INC.
317 ST.LUC MIN. FT.PIERCE;FL34946.Phone:772=46"799.Fax 772-466-6796 Email;QUICKCALCS@AOL.COM
Project Information
For: WYNNE DEVELOPMENT
THE CARLTON 299, FT. PIERCE, FL
Notes:
I .
Design Information
Weather. Fort Pierce, FL, US
Winter Design Conditions. Summer. Design Conditions
Outside db 42 OF Outside db 90 OF
Inside db 70 OF Inside db 75 OF
Design-TD 28 OF Design TD 15 OF .
Daily range L
Relative humidity 50 .%.
Moisture.difference 61 gr/lb
Heating.Summary. Sensible.Cooling Equipment Load Sizing
Structure 18492 Btuh. Structure 16942. Btuh
Ducts 5653 Btuh Ducts 8537: Btuh'
Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh.
Equipment load 24145 Btuh Use manufacturer's data n
Rate/swing multiplier. 0.95
Infiltration Equipment sensible load . 24205 Btuh
Method simplified Latent Cooling.Equipment Load Sizing
Construction quality Average
Fireplaces 0 Structure 1888: Btuh
Ducts 2321 . Btuh
Heating Cooling Central vent(0 cfm) 0 Btuh
Area(ftz) 1474 1474 Equipment latent load - 4209 Btuh
Volume(fta) 11788 11788
Air changes/hour 0.45 0.23 Equipment total load 28414 Btuh
Equiv.AVF(cfm) 88 45 Req:total.capacity at.0.70.SHR 2.9:ton.
Heating Equipment Summary Cooling Equipment Summary
Make Carrier Make Carver
Trade CARRIER AIR CONDITIONING Trade CARRIERAIR CONDITIONING:
Model 25HBC536A"030 Cond 25HBC53fiA*030
AHRI ref, 7914585 Coil FX4DN(B,F)037
AHRI ref 7914585
Efficiency 8.5 HSPF Efficiency 12.0 EER, 15 SEER
Heating input Sensible cooling. 24360. Btuh
Heating output. 34600 Btuh @ 47OF Latent cooling 10440.; Btuh-
Temperature rise 27 OF Total cooling 34800 Btuh
Actual-airflow 1160 cfm Actual.air flow 1160. cfm .
Air flow factor ! 0.048 cfm/Btuh Air flow factor 0.046 cfm/Btuh
Static pressure . 0 in H2O Static pressure 0 in H2O. "
Space thermostat Load sensible heat ratio 0.86
Calculations.approved byACCA to meet all requirements of Manual J 8th Ed
wri htsoft` I'' 2016-Nov-1409:16:33
ACA
9 Right-Suite®Universal 2017.17.0.03 RSUD8101 page t
...Wrightsoft WAC\WYNNE-THE GRAND CARLTON-299.rup Calc=MJ8 Front Door faces: N
1-wrightsoft Right4J.®Worksheet -Job:
Entire House Date:
QUICK CALCS, INC. By:
317 ST..LUCIE'LN.,FT.PIERCE,FL 34946IPhone:772-466-6799 Fax 772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name Entire.House BEDROOM
2 E)posed wall 156.2 ft 43.0 ft
3 Room.height 8.0 ft d 8.0 ft heWcool'l
4 Room dimensions 14.0 x 19.0 ft
5 Room area 1473.5 W 266.0 ft2.
Ty Construction U-value Or HTM Area (ft) Load Area (ft2 Load
number (Btuh/ft2-°F) (Btuh/ft?) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat TC001. Gross N/P/S Heat Cool Gross N/P/S Heat Cdol
6 >,11l� 13A-0ocs 0 143 ne :- 4 00: 2 55, 456 4.16 1674 •1064 80 80 320 204
__ r 1A Glom _> 1270 ne _35,56` 7,043> 36 :'0 1.344 2662 0 _ A 0
13A-4ocs 0'143 se 4.00 2 55 128 83 331 210 0 0 0 0
1Ac1om 1.270 se 3556 3477 24 24 848 829 0 0 0 0
11 11130 0.390 se 1092 1131- 22 22 236 244 0 . 0 0 0
;:r.W_. 13A-0ocs p=143 . s ; 4 00;i 2'55: 34. 34 0 :?_ 0 0' ; 0:
V�/ 13A-4ocs 0.143 sw 4.00 2.55 360 353 1414 899 152 152 664 "'387
i G 1Aclom 1.270 sw 35.56 42.91 7 5 247 298 0 0 0 0
13A1tocs 0 943 nw 4 00" 2 55 272 199 795 505 112 78 318' 202
1Ac1om 1 270 nw 35 56 r 45 24? 33 0 1162 1478 33 0 I 1162. ;,1418
1Ac1omdv 1270,nw, , 35 56;i. 70 43` 41 0, 1451 2874 0. 0 0 0:
P 12C Osw 0.091 2.55 1.28 19,2 192 489 246 0 0 0 0.
C, "1,6AOmd 0032 -i 0 90;; 23.2; 1474, .1474 ;-1320. ::;3419 266 265 23$ 617i
F 22A4DI 0.989 27.69 0.00 1474 156 4325 - 0 266 43 119.1; 0
6 c)AFD e:xursion 1382 686
Envelope loss/gain - 15771 16197 3838 3574
12 a): Infiltration 2721 745 749 205
b) Room ventilation ..0 0 0 .0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 0
Subtotal pines 6 to.13) 18492 16942 4587 h3779
Less exfemal'load 0 0 0 i1 0
Less transfer 0 .0 0 11 0
Redistribution 0 0 0 ,. 0
14 Subtotal 18492 16942 4587 13779
15 Duct loads 31% 50% 5653 . 8537 31% 50% 1402 j,1905
TTTotal room load 24145 25479 5989 `5684
Air required(cfm) 1160 1160 288 259
Calculations approved byACCA to meet all requirements of Manual J.8th Ed.
wcightsoit� 2016-Nov-14 09:16:33
rA Right-Suite@ Universal 201717.0.03 RSU08101 Page
...Wrightsoft WAC\WYNNE-THE GRAND CARLTON-299.rup 'Calc=MJ8 -Front Door faces: N
Y
-wr ghtsoft Right,,,J Worksheet Job:
Date:
Entire House
By:
QUICK CALCS,INC.
317 ST.LUCIE LN.,FT.PIERCE,FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email:QUICKCALCS@AOL,COM
1 Room name WIC MASTER BATH
2 Exposed wall 0 ft 9.0 ft 11
3 Room height 8.0 ft heat/cool 8.0 ft heat/cool
4 Room dimensions 7.0 x 9.0 ft 7.0 ,X. 9.0 ft
5 Room area 63.0 ft2 63.0 ft2
Ty Construction U-value Or HTM AreaLoad
number- (BtuWft�°F). (Btuh/ftz) or perimeter (ft) (Btuh): or�perimet r (ft) (Btuh)
Heat Coot Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 ' 13A-0ops 0-143 ne: 4 00 2 5S 0 0 0 0 0 0= A 0
1=270 , iU
13A-4ocs 0.143 :se 4.00 2.55. 0 0 0 0 0 0 0 0
—G 1Aclom 1.270 se 35.56 34.77 0 0 0 - 0 0 0 0 0
11 L—D, 11D0 0,390 se 10.92 - 11.31 0 0 0 0 0 0 0 , 0
`W , 13A�ocs . 1Z143 s_' 4 00 255. "•0 0. 0_ 0
y! 13AAocs 0.143 sw. 4 00 2.55 0 0 0 0 72 72 288 183
I—G 1Ac1om 1.270 sw 35.56 42.91 0 0 0 0 0 0 0 0
13A1iocs 0`143 nw 4 00! 2 55 0 0 0 0 0 0 0 0
1A c1om 1270 nw 35 56 45 24 0 0 0 0 0 0 0 0
0 , 0. 0
„P 12C-Osw 0.091 -. 2.55 .1.28 0 0 0 0 0 0 0 0
:96A30md,
F 22A tpl 0.989 27.69 0.00 63 0 0 0 63 8 249 0
6 c)AED excursion: -2 -4
Envelope loss/gain 56 145 594 '1 325
12 a): Infiltration : 0 . 0 157 11 43
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 ;I, 0
Appliances/other 0 0
Subtotal Qines 6 to 13) ,56 145 751 . . f 366
Less external load 0 0 0 0
Less:transfer .. 9 0 0 0
Redistribution 0 0 0 0
14 .Subtotal 56 145 751 ;, 36B
15 Duct loads 31% 50% 17 73 31% 50% 230 186
Total doom'load 74 217 980 554
'Air required.(cfm) 4 10 47 25
Calculations approved bVACCA to-meet all requirements of Manual J.8th Ed..
- wrightsoft'�A Right-Suite®Universal 2017 17.0.03 RSU08101 M16-Nov-14 OJ:16:33;Page 2
...Wrighisoft HVACIWYNNE-THE GRAND CARLTON•299.rup Calc=MJ8 .Front Door faces: N.
i
- -wraghtsoft° Right-M Worksheet Job:
Enure House
Date:
QUICK CALCS, INC. By:
317 ST.LUCIE LN.,FT.PIERCE,FL 34946-Phone:772466-6799 Fax 772466-6796 Email:QUICKCALCS@!A0L.00M
1 Room name M.BATH KrrCHEN
2 Exposed wall 8.0 ft 0 ff
3 Room height 8.0 ft heat/cool 8.0 ft heat/cool
4 Room dimensions 7.0 x 8.0 ft 1.0 x 192.0 ft-
5 Room area 56.0 ftz 1920 ftz
Ty . Construction U-value Or HTM Area (ftz) - I Load Area (ftz) Load
number` (Btuh/ftz-°F) (13tuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross NIP/S Heat Cool Gross N/P/S Heat Cool
6 13A�tocs 0 143 ne 4 00`ir 0 0 0
.1Ac1om, _1'270 ne; 35:5E ... 70.43 0 0. 0 0
13AAocs 0.143 se 4.00 2:55 0 0 0 0 0 0 0 0
1Ao1om 1.276 se 35.56 34.77 0 0 0 0 0 0 0 0
11 _�—D 11DO 0.390 -se 10.92 11.31 0 0 0 0 0 0 0 0
43, s>;+ .4_.. p
V�! 13A.4ocs 0.143 sw 4.00 2.55 64 57 228 145 0 0 0 0
�G 1A-c1om 1.270 sw 35.56 42.91 7 5 247 298 0 _ 0 0 0
13AAocs 0143 nw = 4,00 255 0 0 0 0 0 _
1A c1om 1270 nw 35F56 45 24 A 0 0 0
nw: ,35.56.. 7043 0 0 0 0 0 0
P 12G-0sw 0.091 2.55 128 0 0 0 0 64 64 163 82
C _16A�Omd • 0032 232': 192^'': 192 172 445'
F 22AADI 0.989 _ 27.69 0.00. 56 8 222 0. 192 0 0 0
W.
wz
I
I
6 o)AED excursion' 224 ' -6
Envelope loss/gain 747 797 335 i; 522
12 a) Infiltration 139. 38 0 0
t) Room.ventilation, p p p p
13 Internal gains: Occupants-@ 230 0 0 0 0
Appliances/other 0 0
Subtotal Qines 6 to 13). 886 . 835 335 522
Less odemal load 0 0 0 p
Less:transfer 0 0 0 0
Redistribution 0 .0 0 0
14 Subtotal 886 835 335 522
15 Duct loads 31% 50% 271. 421 31%1 50%1 102 263
Total room load 1157 1256 438 784
Air required(cfm) 56 57 21 l .36
I
J
Calculations approved byACCA to meet:all requirements of Manual J 8th Ed.
Aft4- wrightsoft' .2016-Nov-14 09:16:33
Right-Suite®Universal 2017 17.0.03 RSU08101 age 3
..Mrightsoft WACIWYNNE-THE GRAND CARLTON-299.rup Calc=MJ8 Front Door faces: N
i i
y
hW@ Worksheet wri.9 htsoff Rig Job:
Y �
Entire House Date:
QUICK CALCS, INC. By.
317 ST.LUCIE LN.,FT.PIERCE,FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email:QUICKCALCS AOL.COM-
1 Room name BATH BEDROOM 2
2 Exposed wall 5.0 ft 32.2 ft
3 Room height- 8.0 ft heaticool 8.0 ft heat/cool4 Room dimensions 9.0 x 5.0 ft 1.0 x 203.5. ft
5 Room area 45.0 ft= 203.5 ftz
Ty Construction U-value Or HTM Area (ft') Load Area (ft') Load
number (Btuh/ft2-°F) (Ptuh/ft2) or perimeter (ft) (Btuh). or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool .Gross WKS Heat Cool
6 13A-0ocs 0;'143 ne 4 00' 2 55= 40 40 160 102 = 128 128`= 513; 326
:1Ac1om 1;270 ne: •' 35.56` 70`43 A 0 0...
13AAocs 0.143 se 4.00. 2.55 0 0 0 0 80 56 225 143
1Aclom 1.270 se 35.56 34.77 0 0 0 0 24 24. 848 829
11 11D0 0.390 se 10.92 11.31 0 0 0 0 0 0 .0 0
W :, 13A4ocs'e". O'143..s.. ' 4.00l s 2.55 0. 0 0 :;-. ..` 34,"- 34;: 136 86
0
VI! 13A-4ocs 0.143 sw 4.00 2.55 0 0 0 0 16 16 64 41
Y-G 1Ac1om 1.270 sw 35.56 42.91 0 0 0 0 0 0 0 0
13A flocs 0143 0 0 0 0 0
1Ac1om 1270 nw 35 56' 45 24 0 0 0 0 0 0 : 0; 0',
1Qc1omd ,.1 270 .nw. _ 35.56 .70.43 0:. 0 _0. 0 0
P 12C Osw 0.091 2 55 1 28 0 0 0 0 0 0 0 0
C fi A 30md 0`032_, 0.90 232 '45 45 " 40 104 204;+ 182 4]2.
F 22A-tpl 0.989 27 69. 0.00 45 5 138 0 204 32 891 0
n.
M.
6 c)AED excursion: -3 -23
Envelope loss/gain 339 204 2859 1874
12 a). Infi@ration . 87 24 561 154
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 0
Subtotal Vines 6 to 13) 426 227 3420 !2028
Less extemal load 0 0 .0 0
Less transfer 0. 0 0 . 0
Redistribution 0 - 0 0 0
14 Subtotal 426 227 3420 2028
15 Duct loads 31% 50% 130 115 31% 50%1 1046 1022
Total room load' ! 556 342 4465 3050
Air required(cfm) .27 16 1 215 139
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
- ,wcighitsoft- Right-Suite®Universal 2017 17.0.03 RSU0810t M16-Nov-1406:16:33
Zek Page 4
...Wdghtsoft WAC\WYNNE-THE GRAND CARLTONmMxup Calc='MJB•'Front Door faces: N
i I
- -wrilghtsoft° Right-JO Worksheet Job:
Entire House Date:
By:
QUICK CALCS INC.
' 317 ST..LUCIE LN.,F.T.PIERCE;FL 34946 Phone:7MA66-6799 Fax 772-466-6796 Email;QUICKCALCS@AOL:GOM
1 Room name ENTRY LAUNDRY
2 E>¢rosed wall ENTRY
ft 6.0 ft
3 Room height 8.0 ft heat/cool 8.0 ft heattcool
4. Room dimensions 1.0 x 55.0 ft 7.0. x 6.0 ft
5 Room area 55.0 ft2 42.0 ft2.
Ty Construction U-value Or HTM Area (ft-) Load Area. (ft2) Load
number (Btuh/ft2-°F) (Btuh/ft2) or
perimeter (ft) (Btuh). or perimeter. (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat. Cool
6yJ 13A flocs 0143 ne 4 00 - 2.% Q "0 0 0 0 p 0; p
-1Ac1om,.." 1270-ne.;:. 35 70.43 0
13A4ocs 0.143 .se .4.00 2.55 48 26 106 67 0 0 0 0
1A-c1om 1.270 se 35.56 34.77 0 0 0 .0 .0 0 0 0
11 r—D ;11D0 0390 se 10.92 11.31 _ 22 22 236 N4 0 0_ 0 0
13A flocs 0:143 s. 4.00_ 2'55 0 0 0 . p; 0
VJ/ 13A4ocs 0.143 sw 4.00 255 8 8 32 20 48 48 192 122
r G IA-c1om 1.270 sw 35.56. 42.91 0 0 0 0 0 0 0 0
13A�tocs 0143 nw 4 00 255 'o 0 0 0 0 0 0 0
AA`c1om° 1 270 nw 35 56 45 24° 0 :.0 ;_ 0 0 0 0 0 0;
1.270 nw..: ..35.56 - 70 43: - .0 0. 0 0 0: , _0
P 12C-0sw 0.091 255 1.28 72 72 183 92 56 66 143 72
C 16A30mtl" 0€032 0.90; 2,32 55 55 49 128 42 42 38 9.7
F 22A tpl 0.989 27.69 0.00 55 7 194 0 42 6 166 0
F.
k .
L,
6 c)AED excursion -7 -4
Envelope loss/gain 800 545 539 288
12 a) Infiltration 122 33 104 29
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 ..o
Subtotal(lines 6 to.13) 922 578 643 . - 316
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 922 578 643 316
15 Duct loads 31% 50% 282 292 31% 50% 197 1159
Total room load 1204 870 840 '476
Air required(cfm) 58 40 40 22
Calculations approved byACCA to meet all requirements of Manual J.8th Ed.
-114114-,wrightsoft' M16-Nov=14 06:16:33
. A Right-Suite®Universal 2017 17.0.03 RSU08101 Page 5
...Wrightsoft WACIWYNNE-THE GRAND CARLTON-299.rup Calc=MJ8 Front Door faces: N
I
- -wr gmso. -W Right=JO Worksheet Job:
Entire House Date:.
By:
QUICK CALCS, INC.
317 ST.LUCIE LN.,F.T.PIERCE,FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name GREAT/DINING
2 Exposed wall. 46.0 ft
3 Room height 8.0 ft heat/cool
4 . Room dimensions 1.0 x 488.0 ft
5 Room area 488.0 ft'
Ty .Construction U-value. Or HTM Area (W) Load Area perimeter
Load
number (Btuhlft�,-F) (Btuh/ft2) or perimeter (ft) (Btuh) or
Heat Cool Gross N/P/S Heat I Cool Gross N/P/S Heat. Cool
Ld
6 13A-0ocs .t 0"149 ne 4 00 2 55 _ 208 1:70 681 : 433
,1Ao1 om, 1.270 s,ne. :' 35 56,:. 70.43 38 0 1344 :2662. -
11 1113A4ocs 0.143 se 4.00 2.55 0 0 0 .0
IA-clom 1.270 se 35.56 34.77 0 0 0 0
-3D 11D0 0.390 se 10.92;. 11.31 0 0 0 0
0143 . s, - 4 0Q;.?: 2:55 :0 - 0
VI! 13A4ocs 6.143 sw 4.00 2.55 0 0 0 0
�G 1Aclom 1.270 sw 35 56 42.91 0 0 0 0
13A-0ocs 0143 nw : 4 00 ' 2 55; 169 119 477 303
1A�1am 1 270 nw 35 56 45 24' 0 -0 0 0
1Aclomd, A.
nw,..- 3b56 70,43 4;1 0 1451 2874
P 12C-0sw 0.091 2.55 1.28 0 0 0 0
C 16A30md *'_ 0a)32 0 90 2.32 488 488 . ?437 .-.1132
F 22Atpl 0.989 _ - 27.69 0.00 488 46 1274,. 0
pt
I .
of
6 c)AED excursion 519
Envelope loss/gain 5665 7923
12 a). Infiltration . 801 219
b) Room ventilation 0 0
13 Internal gains: Occupants @ 230. 0 0
Appliances/other 0
Subtotal(lines 6 to,13) 6466 8142
Less extemal'load 0 0
Less transfer 0. 0
Redistribution 0 0
14 Subtotal 6466 8142
15 Duct loads 31% 50% 1977 4103
Total room load 8443 12246
Air required(cfm) 406 558
i
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
. P. .wrightsoftr 2016-Nov-14 09:16:33
Right-Suite®Universal 2017 17.0.03 RSU08101 Page 6
...Wrightsoft WAC\WYNNE-THE GRAND CARLTON-299.rup Calc=MJ8 Front Door faces: N