HomeMy WebLinkAboutResponse to Comments; ElectricalFortFierce Engineering, tnc.
1 Dependable Mechanical, Electrical & Plumbing Design
CA# 28173
June 26, 2014
To: St. Lucie County, Planning & Development Services, Building & Code Regulation
Division
RE: Permit Number 1405-0345, 3492 Crabapple Dr. Project, Savanna Club, Reply to
Electric Comment:
Comment: Raceway from F.P.L. to meter shows 3 inch, minimum size for 4-500KCM,
per N.E. Code is 3.5 inch, also nipple from meter to wireway, minimum should be 3.5
inch.
Reply: On Sheet E-4, in the riser diagram the conduit diameter in the two locations cited
in the comment has been increased to 3.5 inches.
Sincerely,
Timothy C. Trewyn, PE FL 61580
Electrical Engineer
315 South Th Street ♦ Fort Pierce, FL 34950 ♦ Phone 772-672-4636 ♦ Fax 772-672-4637
www.fp-eng.com
l\10.1.10.3H\Volume_ITt Pic= Engineering\ 13 Projects\13006-04 Savanna ClubTont spondence\reply to electric wmmentdoc