Loading...
HomeMy WebLinkAboutTesting, Adjusting & Balancing ReportOMEGA TEST AND BALANCE ,v,v^,A CERTIFIED INDEPENDENT TESTAND BALANCE COMPANY .. v­ 126 WISTERIA AVENUE, FORT PIERCE, FLORIDA 34982 CELL (772)216-7632 TABB CERTIFICATION NO. BB032001C WWW.OMEGATESTANDBALANCE.ORG omega maniacS320020yahooxom 15 TESTING, ADJUSTING,, AND BALANCING REPORT SAVANNA CLUB COMMUNITY CENTER 3492 CRABAPPLE DRIVE PORT ST. LUCIE, FLORIDA 34952 MECHANICAL ENGINEER: FORT PIERCE ENGINEERING 315 SOUTH 7 TH STREET FORT PIERCE, FLORIDA 34950 MECHANICAL CONTRACTOR: DS AIR CONDITIONING 1501SE DECKER AVENUE, #121 STUART,FLORIDA34994 READINGS BY: HUGH A. GRIMES, T.A.B.B. CERTIFIED CONTRACTOR/SUPERVISOR/TECHNICIAN APRIL 22, 2015 --ALL WORKPERFORMED INACCORDANCE WITH TASSISMA CNA STANDARDSAND PROCEDURES— TARD Techmiftlan Name; laugh c"imes TV '103261" T . IESTIN . e' 'Np OMEGA TEST AND BALANCE, INC. NNNA CERTIFIED INDEPENDENT TESTAND BALANCE COMPANY-,~ 126 WISTERIA AVENUE, FORT PIERCE, FLORIDA 34982 CELL (772)216-7632 TABB CERTIFICATION NO. BB032001C/BB032002S/BB1032610T WWW.OMEGATESTANDBALANCE.ORG omega maniac5320020vahoo.com SAVANNA CLUB COMMUNITY CENTER TEST AND BALANCE INSTRUMENTS SHORTRIDGE SERIES 8400 FLOWHOOD W/ADM860 AIR DATA MULTIMETER RANGE: ACCURACY: CALIBRATION DATE: 0 TO 61 IN H.G 0.05% FS OCTOBER 51 2014 CHECK -IT DIGITAL PSYCHROMETER —MODEL #622 RANGE: ACCURACY: CALIBRATION DATE: SHORTRIDGE ADT446 TEMPROBE RANGE: ACCURACY: CALIBRATION DATE: FLUKE 322 CLAMP METER 350 TO 2050 F, 50/o TO 100% RH t 2° f 1 DIGIT t 3% OCTOBER 51 2014 -200 TO 1800 F f 0.50 FROM 320 TO 1580 F OCTOBER 51 2014 HUGH A. GRIMES, CERTIFIED T.A.B.B. CONTRACTOR/SUPERVISOR/TECHNICIAN --ALL WORKPERFORMED INACCORDANCE WITH TABB/SMACNA STANDARDSAND PROCEDURES— Vic. o.a�oo. � �F 'Trt4w: AEW/�rwl 'I?ia1.B1377echniciaB lVaaaex'Hugh Gt9mea _ MABB W: BH10326107' ��' ,g - Haplratloa DaW 32/31f2016.. . 1 SAVANNA CLUB COMMUNITY CENTER AIRHANDLING UNITS fUNITt" . AHU-1 AHU=2 .. AHU-3" MAID: CARRIER CARRIER CARRIER MODEL FX40NF061L00ACAA 40RUAA08A2A6AOAOAO 40RUAA08A2A6AOAOAO SERIAL 061SA86847 0614UO4021 0514UO2988 SHEAVE DD 8 X 1 8 X 1 BELTS DD A39 A39 FILTERS 22X25X1 16X2OX2 16X2OX2 MOTOR!, MAK E/FR DD GE/56HZ GE/56HZ HP/RPM 3/4 1 NA 2.41 NA 2.41 NA V/ PH/ HZ 208-230/ 1/60 208-230/3/60 208-230/3/60 FLA/SF 6.0/ 1.15 6.9-6.7/ 1.15 6.9-6.7/ 1.15 SHEAVE DD 4.0 X 7/8 4.0 X 7/8 CL DD 17.5 17.5 HEAT ELECTRIC ELECTRIC ELECTRIC EVAPORATOR DESIGN I ACTUAL "- DESIGNI ACTUAL ' DESION I ACTUAL S/A CFM 1300 1407 2700 2778 2700 2722 O/A CFM 250 231 300 279 300 281 R/A CFM 105011176 240012499 2400 2441 EXT. SP .2 .26 .8 .60 .8 .65 DISC. SP NA 1.14 NA 1.34 NA 1.37 SUCT. SP NA J -.12 NA 1 -.26 NA 1 -.28 OAT DB/WB NA 184.7/76.1 NA 84.7/76.1 NA 84.7/76.1 RAT DB/WB 77.9/66.0 1 72.3/61.4 76.8/64.7 1 71.4/60.9 76.8/64.7 1 72.3/61.8 LAT DB/WB 59.0/55.9 53.1/52.8 54.5/53.7 52.1/51.1 54.5/53.7 53.2/52.6 FAN RPM NA NA NAI NA NA NA VOLTS 2081211 208 1 211/210/211 208 1 211/211/211 AMPS 6.015.8 6.9 1 3.8/3.6/3.5 6.9 1 3.6/3.6/3.5 CONDENSOR' 1 1 MAKE CARRIER CARRIER CARRIER MODEL 38AUZA05AOB5AOAOAO 38AUZA08AOBSAOAOAO 38AUZA08AOBSAOAOAO SERIAL 5118254C11455 5114C90556 5114C88451 V/PH/HZ 208/3/60 208-230/3/60 208-230/3/60 RLA 22.5 25.0 25.0 LO PRESSURE 145 150 155 HI PRESSURE 325 315 320 REFRIGERANT 410A 410A 410A FAN/HP/RPM '/a /825 2/NA 2/NA V/ PH/ HZ/A 20811 60 208-230 1/60/ 1.5 208-230/ 1 60/ 1.5 CC HEAT AMPS .1 .1 .1 REMARKS: ---OUTSIDE MECHANICAL ROOM FOR AHU 1-3 NEED SUPPLY OUTLET INSTALLED TO PREVENT UNIT CONDENSATION. NONE SHOWN ON PLANS. ALL WORKPERFORMED INACCORDANCE WITH TASS/SMACNA STANDARDSAND PROCEDURES TABB Technician Name: Hugh Grimes. . TABBMD. HB103Z610T Esolradon Daces.12/31/2016 SAVANNA CLUB COMMUNITY CENTER AIR OUTLETS AHU-1 ADDRESS OUTLET NUMBER TYPE SIZE DESIGN CFM PRE. CFM FINAL CFM 122 1 CD 8 200 233 216 121 2 CD 6 50 97 53 120 3 CD 6 50 136 54 123 4 CD 10 250 258 268 123 5 CD 10 250 269 277 123 6 CD 10 250 255 267 123 7 CD 10 250 285 272 1300 1407 REMARKS: ALL WORKPERFORMED INACCORDANCE WITH TABB/SMACNA STANDARDSAND PROCEDURES TABB Technician Name. Hugh Gslmes. . . TABB n>. nBiu32b30T ' Eaoiratlon Date::12/3Y/2016 SAVANNA CLUB COMMUNITY CENTER AIR OUTLETS AHU-2 ADDRESS OUTLET NUMBER TYPE SIZE DESIGN CFM PRE. CFM FINAL CFM 119 1 CD 10 270 288 281 119 2 CD 10 270 281 273 119 3 CD 10 270 279 288 119 4 CD 10 270 269 276 119 5 CD 10 270 261 279 119 6 CD 10 270 261 274 119 7 CD 10 270 249 266 119 8 CD 10 270 266 274 119 9 CD 10 270 271 279 119 10 CD 10 270 281 288 2700 2778 REMARKS: ALL WORKPERFORMED INACCORDANCE WITH TASS/SMACNA STANDARDSAND PROCEDURES S"17a93OZfd ONV Sa2fVONd1S MO MS/99b'1 H1IN1 HONVaZfOOOV NI O3NMO-l2fgd V2/OM 77d :S)INVW321 ZZZZ OOLZ £LZ TtiZ OLZ OT as OT 6TT LLZ £SZ OLZ OT as 6 6TT 99Z £TZ OLZ OT CID 8 6TT £LZ ££Z OLZ OT CID L 6TT 89Z TVZ OLZ OT aj 9 61T 8LZ 6£Z OLZ Ot da S 6TT ZLZ 6SZ OLZ Ot a:) tF 6TT L9Z T£Z OLZ OT a3 £ 6TT 9LZ ZZZ OLZ Ot a:) Z 6TT ZLZ TTZ OLZ OT a3 T 6TT Wd3 IVNIA WAD '311d Wd3 N9IS3a 3ZIS MA1 2139W(1N 1311nO SS3aaan £-nHtl sia*lino bin 2131N33 ,UlNnWWo:) imn VNNVAVS SAVANNA CLUB COMMUNITY CENTER AIRHANDLING UNITS ;UNITS AHU-4 :. , .:: AHU-5 MAKE CARRIER CARRIER MODEL 40RUAA08A2A6AOAOAO 40RUAA06A2A6AOAOAO SERIAL 0511U02888 0514U02986 SHEAVE 8 X 1 7.5 X 1 BELTS A39 A39 FILTERS 16 X 20 X 2 16 X 20 X2 iMOTOR� MAKE/FR GE/56HZ GE/56HZ HP/RPM 2.41 NA 2.41 NA V/PH/HZ 208-230/3/60 208-230/3/60 FLA/SF 6.9-6.7/ 1.15 6.9-6.7/ 1.15 SHEAVE 4.0 X 7/8 3.75 X 718 CL 17.5 17.5 HEAT ELECTRIC ELECTRIC EVAPORA70R _ ° DESIGN :ACTUAL DESIGN (ACTUAL ,- S/A CFM 2700 2832 0/A CFM 400 379 R/A CFM 230012453 EXT. SP .8 .66 DISC. SP NA .36 SUCT. SP NA 1 -.30 OAT DB/WB NA 84.7/76.1 RAT DB/WB 77.4/65.4 1 72.2/60.8 LAT DS/WB 55.2/54.3 51.6/50.4 FAN RPM NA NA VOLTS 2081211/210/209 AMPS 6.9 1 3.7/3.9/4.0 '�CpNDENSOR MAID CARRIER MODEL 38AUZA0SAOBSAOAOAO SERIAL 5114C92114 V/PH/HZ 208-23013/60 RLA 25.0 LO PRESSURE 155 HI PRESSURE 315 REFRIGERANT 410A FAN/HP/RPM 2/NA V/PH/HZ/A 208-230/1/60/1.5 CC HEAT AMPS .1 REMARKS: 2400 2503 400 371 200012132 .8 .59 NA 1.32 NA 1 -.27 NA 84.7/76.1 77.9/65.9 1 71.6/60.4 54.6 53.7 51.1 50.6 NA NA 2081211/211/210 6.9 1 3.1/2.9/2.8 .1 CARRIER 38AUZA08AOB5AOAOA0 5114C91381 208-230/3/60 25.0 150 320 410A .1 1.5 ALL WORKPERFORMED INACCORDANCE WITH TASS/SMACNA STANDARDSAND PROCEDURES SAVANNA CLUB COMMUNITY CENTER AIR OUTLETS AHU-4 ADDRESS OUTLET NUMBER TYPE SIZE DESIGN CFM PRE. CFM FINAL CFM 101 1 CD 8 200 241 209 118 2 CD 8 150 193 159 116 3 CD 8 200 213 219 115 4 CD 10 225 252 239 115 5 CD 10 225 278 244 113 6 CD 8 150 199 161 112 7 CD 8 200 166 194 112 8 CD 8 200 154 261 112 9 CD 8 200 180 191 111 10 CD 8 175 173 177 110 it CD 8 175 169 181 108 12 CD 8 200 177 211 109 13 CD 8 200 150 196 112 14 CD 8 200 176 190 2700 2832 REMARKS: ALL WORKPERfORMED INACCORDANCE WITH TASHISMACNA STANDAROSAND PROCEDURES SAVANNA CLUB COMMUNITY CENTER AIR OUTLETS AHU-5 ADDRESS OUTLET NUMBER TYPE SIZE DESIGN CFM PRE, CFM FINAL CFM 104 1 CD 8 225 226 248 104 2 CD 8 225 244 245 103 3 CD 8 150 170 163 103 4 CD 8 150 180 162 103 5 CD 8 150 183 161 107 6 CD 8 50 101 53 108 7 CD 8 200 173 192 108 8 CD 8 200 211 201 102 9 CD 10 300 303 291 125 10 CD 10 300 183 303 103 11 CD 8 150 136 165 103 12 CD 8 150 201 160 103 13 CD 8 150 203 159 2400 2503 REMARKS: ALL WORKPERIFORMED INACCORDANCE WITH TASS/SMACNA STANDARDSAND PROCEDURES