HomeMy WebLinkAboutBldg plans, 0508Finish Columns with
5/8" thick cut coral
Finished stucco bands
Union Corrugating Co. 26 ga. 5V crimp metal roofing
FL#: 1211A Attach roofing to deck using #9 x 1.5"
wood screws with washer Per Approval over 30 lb Felt
underlayment installed with min. 4" side laps
and C end laps fastened with corrosion resistant tin\
caps with 11/4" ring shank nails spaced L" o.c.
at all laps and two staggered rows 12" o.c. in field.
Roof deck to be 19/32 CDX plywood nailed to
trusses with 8d x 2.5" long ring shank nails per sheeting
attachment detail on roof plan
Max allowable uplift = 89.8 psf
5/8" thick light textured O EE
stucco on typical concrete
block construction
5/8" thick x 8"w cut
coral finished stucco bands
RIGHT ELE\/ATION
12
4 SLOPE
SCALE: 1/4" = 1'-0"
Union Corrugating Co. 21 ga. 5V crimp metal roofing
FLU: 1211A Attach roofing to deck using 49 x 1.5"
wood screws with washer Per Approval over 30 lb felt
underlayment installed with min. 4" side laps
and 6" end laps fastened with corrosion resistant tin
caps with 1 1/4" ring shank nails spaced C o.c.
at all laps and two stagggered rows 12" o.c. in field.
Roof deck to be 19/32 CDX plywood nailed to
trusses with 8d x 2.5 long ring shank nails per sheeting
attachment detail on roof plan
Max allowable uplift = 85.8 psf
12
SLOPE],4
8'-I" T.O.B.
0'-0" = Finished Floor
=L=V/-TION ?NOT=S:
Union Corrugating Co. 26 ga. 5V crimp metal roofing
FLU; 7211.4 Attach roofing to deck using #9 x 1.5"
wood screws with washer Per Approval over 30 lb felt
underlayment installed with min. 4" side laps
and L" end laps fastened with corrosion resistant tin
caps with 1 1/4" ring shank nails spaced 6" o.c.
at all laps and two staggered rows 12" c.c. in field.
Roof deck to be 19/32 CDX plywood nailed to
trusses with 8d x 2.5" long ring shank nails per sheeting
attachment detail on roof plan
Max allowable uplift = 85.8 psf
12
� SLO�r
Finish=o1um`=swit7
5/8" thick cut coral
finished stucco bands
O
5/8" thick light textured
stucco on typical concrete
block construction
REAR ELE\/ATION
Overhangs at 1'-0" unless otherwise noted on Roof Plan
Roof pitch at -4.12 unless otherwise noted
Any changes to this plan Shall be submitted to the architect
for approval in writing prior to starting construction.
Return ALL Stucco Bands Into LUindow or Door.
12
4 1 SLOPE
SCALE: 1/4" = 1'-0"
Union Corrugating Co. 21 ga. 5V crimp metal roofing
FLU: 1211.4 Attach roofing to deck using #9 x 1.5"
wood screws with washer Per Approval over 30 lb felt
underlayment installed with min. 4" side laps
and L" end laps fastened with corrosion resistant tin
caps with 1 1/4" ring shank nails spaced 6" o.c.
at all laps and two staggered rows 12" o.c. in field.
Roof deck to be 19/32 CDX plywood nailed to
trusses with Bid x 2.5" long ring shank nails per sheeting
attachment detail on roof plan
Max allowable uplift = 85.8 psF
12
TERNhI l t i FiG/1I IV�t,v li ncwulrstu
CONCEALED FASTENERS A ATTACHMENTS
ARE THE RESPONS15LD Of THE
COfifRACTOR OF if 0
ALL MANUFACTURES LABLES SHOWING
U FACTORS AND SHGC COMPLIANCE
WITH FBC ENERGY CODE MUST
REMAIN ON ALL DOORS AND WINDOWS
UNTIL INSPECTIONS ARE APPROVED
THESE PLANS AND ALL PROPOSED WORK
ARE SUBJECT TO ANY CORRECTIONS
REQUIRED BY. FIELD INSPECTORS THAT
OZ" MAYBE NECESSARY; IN 0ADER TO
CAMPI.YWITH ALL APPLICABLE CODES.
5/8" thick x 8%1 cut
coral finished stucco bands
0 5 03
L iC rF rf)LTNTv RU0,Dr:r- "I'VISION
VI eA, 14�i JK* 75 vt;lVl' 11L �Vlv(
LNS AND PERMIT MUST BE KEPT ON JO
NO LNSPECTION IV1LL BE NL4DE.
1/8" Thick cut coral stucco over paper
backed wire lath nailed to substrate through
one layer of 15 lb Felt using Bid nails. Substrate
to be 19/32" CDX Plywood nailed at 6" o.c.
in field and edges with IOd ring shank galvanized
nails into truss webbing.
8'-1" T.O.B.
2
5/8" thick x 8"w cut H. 5/8" thick x 8"W cut
® cbcoral finished stucco bands
oral finished stucco ands ®®a 10
3 3 ®®®® 5/8" thick x 8"w ci
coral finished stucco
5/8" thick light textured ®®®® - B
stucco on typical concrete Duffoupc
block construction Ah Garage Finished Floor
-O'-4" A.F.F. 5/8" thick light textured Finish Columns with
Finished Floor " = stucco on typical concrete 5/8" thick cut coral
block construction finished stucco bands
LEFT ELEVATION FRONT ELEVATI0N
SCALE: 1/4" = I'-O"
SCALE: I/4" = I'-O"
r
product Approval Submittal Affidavit
Opening Schedule Swing Doors, Overhead Doors. Sliding Doors,
Windows & Skylights
Opening
Type
NOA/FL
NUMBER
Product
Model
Manufacturer
Glass
Attachment method
TEST
Date
Design Pressure
of Approved Tests
1.2.3
t4
FLU 11499.2
Single Hung
Series 185
Mi Windows
and doors
3/I4" dia. Tapcons w/ min. 1 1/4" penetration at L" max.
from each corner and 19" o.c. thereafter thru PT Buck
into solid filled CMU wall
+41,2/-50.0 psf
A
IL-0330.02
Overhead
Garage Door
Model 824
9'-4" max. width
W-O" max height
DAB
I
Install track to buck per product approval and per
manufacturer's recomendatione.
lAttach Buck to wall using 3/8" x L" anchor bolts at 18" o.c.
10-9-21
+50.0/-60.0 psf
B
FLU 15221.1
Fiberglass
9
Smooth Wood rein
g
series o fiberglass
P18spro/Nanya
Plastics Corp.
Elco I/4" dia. tapcon with min 1.25" embedment at G" max
from corners and Iq" o.c. thereafter in jambs.
Pressure based on SCHLAGE hardware.
+ 45.0 PSF
-
C
FLU 15332.2
Sliding Glass
Door
Series 420
Mi Windows
and doors
3/I6" dia. Tapcons w/ min. 1 1/4" penetration at L" max.
from each corner and 19" c.c. thereafter thru PT Buck
into solid filled CMU wall
+
- 40.0 PSF
Product
NOA FL
/
NUMBER
Model #
Manufacturer
Attachment Method
TEST
Date
Design Pressure
of Approved Tests
Mullions
FLU 15353.2
5164
vertical mullion
Mi Windows
and doors
For CMU use4) 3(I6" dia. tapcons with min 1 1/4"
penetration wit anc ors located per proauct approval drawings.
MFG TO PROVIDE REBAR IN MULL
+ 44.2 PSF
-
Roof
FLU 1211.4
5V Crim p
Metal Roofing
INSTALLATION
METHOD: A -IS
Union Corrugating Co
Union Corrugating Co 24 ga. 5v crimp metal roofing attached to deck using
a9 x 1.5" wood screws with washer per approval over Titanium UDL 25plus
underlayment installed with min. q" side lass and 6' end laps fastened with
corrosion resistant tin caps and with 1.25 nng shank nails spaced 4' o.c. at all
laps and two staggered rows 12" o.c. in field9 Attached deck per sheeting
attachment detail on roof plan
FIELD:
-85.8 PSF
Edge and Perimeter;
-113.1 PSF
Siding
Stucco on Block
-
Soffit
15-1021.02
Model T4 t vented
Vim I Soffit
Kagcan
Installed using any approved anchors as shown in product approval.
Contractor to strictly adhere to the product approval for the use
f
4-20-21
+55.0/-35.0 PSF
Hurricane
Panels
FI# 1501L.2
24 Gauge
Storm Panels
Global Protection
Products LLC
Installed using any approved anchors as shown in product approval.
Contractoer to strictly adhere to the rproduct approval for the use
of fastI
+55.5/-12.0 PSF
have reviewed the above and approved it by my seal below. ( Architect or Engineer of Record )
1/2" drywall ceiling on truss bottom cord
2" x 4' top plate
1/2" drywall on
2" x 4" studs at IL" O.C.
base -board II II / 2 x 4" P.T. bottom plate
\ 4" concrete slab with fibermesh OR
L"xL" 410/10 WWM on L mil Visqueen over
clean compacted termite treated fill
Interior Non -Bearing Partition
ALL CONTRACTOR WARRANTIES BEGIN WHEN THE CLOSING
OCCURS BETWEEN THE BUYER AND WYNNE BUILDING CORP.
AND WILL CONTINUE FOR ONE YEAR FROM THAT DATE
PERMITTING INFORMATION (FORM 100)
Florida Building Code Residential: 5th Edition and ASCE 1-10 for Wind Loading
Building Design is: Enclosed Risk Categorg: II Wind Velocity: 165 mph ultimate
Mean Roof Height:__IIi2�" Roof Pitch: 4:12
Internal Pressure coefficient: ±0.18
Subjectabditg to damage from: Weathering: Negligible Termites: Veru Heavu
Width of Roof End Zone: 3'-4" Wind Speed: 1L5 mph ultimate
Wind Exposure Classification: C 1.21 x O.L = 0.12L
Adjustment factor for Exposure Height: ASO design
Load Combination: ASCE 1-10 Section 2.4 DL+LL: DL+O.LWL: 0.6DL+O.6WL
Components t Cladding Wind Pressure (NET) Roof Zone: I. +20.L/-32.6 oaf
Roof Zone: 2. +20.6/-51.0 psf
Roof Zone: 3. +20.4/-84.0 oaf
Components t Cladding Wall End Zone Width: 3'-4"
Components t Cladding Wind Pressure (NET) Wall Zone: 4.+35.8/-38.1 psf
Wall Zone: S. +3S.8/-41.8 oaf
Components t Cladding Wind Pressure (NET) on Garage Door: +32.0/-40.3 oaf
Shear Walls Considered For Structure? Yes
Continuous Load Path Provided? es
Are Components an Cladding Details Provided? Yes
Minimum Soil Bearing Pressure:2,500 psi, Presumptive: X Bg Test: psi
This Building Shall Have the Following:
APPROVED SHUTTERS: )� IMPACT GLASS: BOTH: NEITHER:
ROOF LIVE LOAD: 31 oaf ROOF DEAD LOAD: 10 psf
FLOOR LIVE LOAD: ' S_ psf FLOOR DEAD LOAD: 10 oaf
JOB ADDRESS:
nLS
Braden it Braden AIA, PEA JJynne Building Corp. Date Drawn Revisions Sheet Comm #
Architects - Planners 12-8-14
41-1 S.E. Coconut Avenue a �, I + On 299 GARAGE Drawn by:
Tel : ni2) 281-8258 ` 1.
FT
BFax : (112) 281-8283 Spanish Lakes Checked b
E-mail: bradenaia comcast.net St. Lucre Count Florida y
Stuart. FL 34994 #AACCO0032 I�.R-B. OF 5
_.._ . AC
= Roof Zone I
Walls Zone 4
ES = Roof Zone 2
Walls Zone 5
END ZONE
Corner Zones
Roof Zone 3
nms
FLOOR f"L A N 4L�li _ CRASH POST DETAIL
TYPICAL NOTES: SCALE 1/4" = 1'-O"
I. Contractor to verify ALL notes and dimensions p Steel prior to Ste high by 4° diameter
el crash post. Floor
proceeding with work. Flange with 4 - 3/8"
2. Contractor to STRICTLY enforce ALL OSHA Requirements. expansion bolts into
51ab (3/8°t so ksi steel plate)
3. ALL Lumber to be used as Beam, Rafters, etc... to have
a minimum 1,400 P.S.I. fiber stress. `
4. No dissimilar metals to touch. 2%," 2
5, ALL Concrete used for slabs shall be min. 2,500 PSI concrete. %° %_
ALL Concrete used for vertical filled cells, Cont. tie beams etc.. to -�
shall be 3,000 P.S.I. concrete and/or 4,000 P.S.I. grout mix m s3/e°° 21
,
(o. Drywall at ceilings shall be leveled and attached to bottom chord 9'
of trusses with screws per FBC R102.3.5. ° °
7. ALL wood in contact with concrete shall be pressure treated.
8. ALL wall dimensions are nominal and not finished wall or stud dimensions.
9. ALL plumbing fixtures to be low flow.
10. Contractor to Provide Drain at water heater in accordance
with the current edition of the Florida Plumbing Code.
II_ Contractor to Provide a 2'-8" wide door at one bathroom for 2%2' 2y,"
handicap accessibility requirements. r2'
12. Lowest finished floor to be set by Governing Building Department
surveyor to set in field.
13. Separation between residence and garage shall be per FBC R302.6
14. Door between garage and residence shall be 1-3/4"t 20 min. rated door
w.H. = Water Heater
15. Wall and Ceiling shall have a flame -spread classification of not greater than 200 per FBC R302.9.1
14. Wall and ceiling finishes Shall have a smoke -developed index of not greater than 490 per FBC R302.9.2
17. All exposed attic insulation materials Installed on attic floors shall have a critical radiant I" x 6" P.T. Buck nailed to
flux not less than 0.12 watt per square centimeter. Exposed foam plastic insulation block with case hardened nails
materials exposed on the underside of the roof deck or on the attic walls shall comply prior to door attachment
with F.B.C. R316 - see permit info box of code edition
18. G psum board material shall conform to ASTM C36, C19, C4-15, C514, C630, C931
AID, C1002, C1047,C117.1, CII-18, C1278, C1395, or C1396 and shall be installed
according to the following: (FBC R102.3.5)
Drywall
Thickness
Location
Orientation
Framing
Member
Max.
of fasteners
spacing
Nail sizing options for
installation of drywall into
Spacing
Maximum
wood framing members
Nails
Screws
2" x min. thickness
Ceiling
Perpendicular
24"
7"
12"
13ga 1 3/8" long with 19/64" head
OR
0.098" diameter x 1 1/4" long
annular -ringed or Sidcooler nail
i2
OR
Walls
Either
16"
8'
I6"
0.080" dial x 1 5/8" long with
Direction
15/64 head
OR
Ggpsum board nail 0.013C die.
X 1 5/8" with 9/32" head.
Ceiling
Perpendicular
24"
7
12"
13ga I S/8"011oong with 19/64" head
0.098" diameter x 1 3/8" long
annular -ringed or 6d cooler nail
e
OR
0.092 dia. X 1 1/8" long with
Walls
Either
I6"
8"
16"
Direction
1/'" head
OR
Ggpsum board nail 0.0915" dia.
x 1 1/8" with 19/44" head.
Install SGD thru buck into
block with 3/14" tap -con with
1 1/2" penetration at 6" o.c. max.
from each corner and 20." o.c. max
thereafter at head per product approval
Use 3/I6" tap -con with
1 1/2" penetration at 6" o.c. max.
from each corner and 20" o.c. max
thereafter at sill per product ii!pprc
19. ALL ceramic tile surfaces installed shall conform to ASTM A108.1 thru A108.6,
A108.1, A118.1, A118.3, A136.1 and A13-1.1
20. Cement, fiber -cement or glass mat gypsum backers in accordance with ASTM
C1288, C1325, OR C11-18 and installed I.A.W. manufacturers recommendations shall
be used as backer for the wall tile in tub areas and wall panels in shower areas.
21. Insulation including facings such a,§ retarders or vapor permeable members installed
within floor -ceiling assemblies, roof -ceiling assemblies, wall, crawl spaces and attics
shall have a flame spread index not to exceed 25 with an accompanyin smoke
developed index not to exceed 450 when tested in accordance with ASTM E 84_
Insulation shall comply with F.B.C. R316.
Union Corrugating Co. 26 ga. 5V crimp metal roofingg
FLU; 1211.4 Attach roofing to deck using 49 x I.5"
wood screws with washer Per Approval over 30 lb felt
underlayment installed with min. 4" side laps
and 6" end laps fastened with corrosion resistant tin
caps with 1 1/4" ring shank nails spaced 6" o.c.
at all laps and two stagggered rows 12" o.c. in field.
Roof deck to be 19/32 CDX plywood nailed to
trusses with 8d x 2.5" long ring shank nails per s1ree. ng
attachment detail on roof plan
Max allowable uplift = 85.8 par
Simpson HETA 20 or equal
hurricane anchor at each truss 12
with (10) I .) x I rtin nails
( 24" o.c.) suppporting Max.
18101ba. upllrt
Aluminum Drip -
Edge d Fascia
2" x 6" sub -Fascia
Kagcan full o vent vingl soffit installed
using 1/8" dia shank x 15" long gale.
roofing nails with 3/8" dia. head per
product approval - see chart sheet Ul
5/8" thick light textured
stucco on typical concrete \
block construction 0°
95 bar vert. will
30" overlap -
at each filled cell
W.T.r
PRE-ENGINEERED TRUSSES
at 24"o.c. TYPICAL
(shop drawings bg manufacturer)
yR-30 blown fiberglass
in bottom chord of trusses
-1/2" drywall with smooth finish
Two rows of beam block filled with concrete
_and (1) #5 bar Cont. in each row. Substitute
precast lintel filled with concrete and (1)95
bar cunt. for bottom row over openings
1/2" drywall over 1" x furringg
strips at 14" o.c. with R4.1 PI -foil
-insulation on typical 8" Block walls
All drywall to be installed per FBC R T02.3.1
and shall meet all pertaining ASTM codes.
Mortar to be Type M" onlyy proportioned per FBC R601.1
and Mortar Joints shall comply with FBC R601.2.1.
Provide Our-O-Rock at all wet areas (ex. showers, tubs etc...)
Fill cell with concrete and
(U 45 bar vert. (typical).
-Max. spacing shall not exceed
48" unless otherwise noted
see Foundation plan notes For
spacing at openings
4" concrete slab with fibermesh OR
6""" #10/10 WWM on 6 mil Visqueen over
/clean compacted termite treated fill
�-
'
14" x 14" Concrete footing
14" with (2) #5 bars cost. and #5
TY F i C A L S E C T I O N transverse bars at 48" o.c.
Scale : 1/2" = l'-O"
ottom Tra
Masonry Beam
0140
Sliding Door
At Masonry Wall
N.T.S.
Head
fixed door
sliding door
1 1/2"
Sill
Detail
NTS
AREA
CALCULATIONS
Living A/C
= 1,414 sq.
ft.
Front Porch
= Is sq.
ft.
Rear Porch
= 1% sq.
ft.
Garage
= 321 sq.
ft.
Total Under Roof= 2,124 sq. ft.
2" VTR
JIL
I
I
I
21' VTR
Master r��L JI
Bath
2
Lev. . I
2"hr
Lev.
2" VTR
3' JIL
I
2' 3"
shwr.
Kit. sink
Kitchen 2
i
Lev. ri
Li
3"
W.C.
Bath 92 Sher.
3"
C.O. To Septic
fi LUMBING RISER
1" x 6" P.T. Buck nailed to C
block with case hardened nails -1
prior to door attachment u
Masonry Wall
ypical Flooring
Install SGD thru buck into
block with 3/16" tap -con with
1 1/2" penetration at 6" o.c. max.
from each corner and 20." o.c. max
thereafter at Jambs per product approval lamp
Door Schedule
Mark
Size
Rough Opening
Door Description
PRESSURE ZONE
A
9'-O" X l'-O°
108" x 84"
Overhead Garage Door
ZONE 4
B
3'-0" X 6'-e"
41 %4"x 83%"
Fiberglass Panel - Inswing
ZONE 4
C
6'-O" X 6'-8"
14" x 81 /2" or race"
Sliding Glass Door
ZONE 4
D
2'-0" X 6'-8"
Solid Core - Wood
- 6-Panel -Bi-Fold
Finished 24" x 81 %'
E
2'-6" X 6'-8"
Solid Core - Wood
- 6-Panel
F
5'-0" X 6'-8"
Solid Core - Wood
- 6-Panel - Bi-Fold
G
2'-8" x C-8" x I %4"
Solid Core Wood, Steel, or Masonite Door
H
2'-8" X 6'-8"
Solid Core - Wood
- 6-Panel
J
2'-6" X 6'-8"
Solid Core - Wood
- 6-Panel - Bi-Fold
K
2'-8" X C-8"
Solid Core - Wood
- 6-Panel - Bi-Fold
ALL Exterior doors to withstand pressures stated In permit info
box on sheet 91
GARAGE DOOR SPECIFIED IN PRODUCT APPROVAL FORM AND SHALL
WITHSTAND THE PRESSURES STATED IN PERMIT INFO BOX ON SHEET 41
All rough opening dimensions to be verified by :Ontractor
with manufacturers specs prior to construction
_J_ I0'-01. 12; _ 10'-0.1 2"
��° ❑° �° E0 E0
EGRESS
iv
O
-
o
12" x 12" concrete column block filled
O
with concrete and (2) #1 bars vert. tied
Into lintels above
-
2 e Covered Porch
O
00 O DO D D 00
° c o
0
MASTER I
UUC
BEDROOM
ao a� u
B'-0" to �Y/9 8'-0" A.F.F.
fn
Vaulted eihng
Flat
tLin
Ceiling
GREAy7
o
ROOM
I
Rod d heif
21'-8" I
-
hl B
n Vanity to e s I
\v
34 Y2„hig I N
w
I CD
° 8'-Ol to 9'-8" A.F.F. ry
O
rr r [1� below clountee-�osll
p Vlaulted Ceding
C L O E T
DINING
_
LINEN rJ F\ R O O M
Rod d Shelf 8" `I�
Q
OCABINE �
w
�\�
,A T H I
-
O
u1
° vanity to be
O
� I 34 I / high
o3i4„
o
High wall °
<ITCHE�I
Vent
Dryer
through
wall
I O I_I/2
_ _
A. rk Z7verrnang
O ~ 8'-O" elfin °
Flat Ceding
°
Upper cabinets to D
174
2" Filler
3'-o"4" (3 IF
1 v extend over Ref.
of. -- Ii n - I E B T H
° rayeBq
i enmg 1
d Shelf O D
- -- - - -i
W. H. w ® ry`
R-II Bette naulaUon to `r E tz!:
ttl
4"� Steel Ballard I
See detail on this sheet $
F �7
to
I
Provide auto 22" x 54" , 1�" O I O
cw
0 closer Attic Access
l 9
m
with light I Q
w - - - - - J 3 22" _ 8'-0' A.F.F.
ISO Amp Flat Ceiling
v p
Meter
P nel 4 6'-O" 3'-6"
m
��
I
W © SECOND m
IO3 n c
m
O
GARAGE E ERGEN Y BEDROOM I
EGRESS
O '-4'
m
A F F 00 MT 00
Flat Ceiling 0 3
CV
ry I
CE
O
r-----------------i EGRESS
Block wall in O
-
garage to be I _ O Q
struck block I T
O
- COVERED
I 12" x 12" concrete column block filled
14'-6"
I I DRC with concrete and (2) tt7 3ars vert. tied
O
I into lintels abo e
A)
1 7' 2„ 12'-6„ 6„
I ® I
o
O °
°0 °O ❑° ❑° ° F 5 5 O
(V
I
2'-8„4„
F
Install windows thru buck into
block with 3/16" tap -con with
1 1/2" penetration at 6" o.c. max.
from each corner and 20." o.c. max
thereafter at ambs and 20" o.c. max.
Exterior race at head and sill per product approval
of wall ----\ / \ Buck to be I" x 4" PT
I"x4" P.T. Buck nailed to
lock with case hardened nails
D e t a I 1 a t W I n d OW S prior to window attachment
Braden t Braden AIA. FA
Architects - Planners
411 S.E. Coconut Avenue
Tel : (1l2) 281-8258
Fax : (172) 281-8283
E-mail: bradenaia8comcast.net
Stuart_ FL 3499G UAAC000032
NTS
Wynne Building Corp.
Carlton 299
Spanish Lakes
St. Lucie County Florida
INSTALL VULKEM BLOCK SEALANT
ON ALL JAMB, HEADER, AND
SILL BLOCK PRIOR TO BUCK
INSTALLATION
Attach buck to block wall with
1/4" dia. Elco conc Screws with min.
1 1/4" penetration at 12" o.c. max
and 4" max from each corner thru
Exterior face 2" x 6" PT Buck
of wall
cries "''
71T
#8 Wood screws thru jamb into buck
at each hinge and 15" o.c. max and
l) P t All At n nnr prior to door attachment
NTS
Date Drawn : Revisions Sheet Comm 4
12-8-IL
GARAGE Drawn by:
LEFT 2. I�-300
c.c.u.
Checked by:
D.R.B. OF 5
b I KUCU I U1ilz�/-�L INS
I.
ALL FOOTING ARE DESIGNED FOR A MINIMUM OF 2,500 PSF SOIL
9.
SLOPE ALL PORCH SLABS, COVERED WALK, ETC. AWAY
BEARING CAPACITY. IF ANY SUB -SOIL, MUCK OR NON -UNIFORM
FROM HOUSE TO DRAINS (IF PROVIDED) PER PLANS
CONDITIONS EXIST, REPORT TO ARCHITECT AND OBTAIN
PROPER ENGINEERING DATA FOR DESIGN.
2•
ALL SLABS AND FOOTINGS TO BE A MINIMUM 2,500 PSI AT 28 DAYS
10•
DESIGN LOADS ARE AS FOLLOWS:
ALL COLUMNS, FILLED CELLS, AND BEAMS SHALL BE MIN, 3000 PSI
ROOF (DL+LL) = 41 PSF
BE 3000 PSI OR 4,000 PSI GROUT MIX AT 28 DAYS
WIND VELOCITY = PER PERMIT INFO BOX ON SHEET #I
EXPOSURE ="C"
3.
POISON SOIL AND COVER W/ 6 MIL. VISQUEEN WITHIN 24 HOURS, NO
SOIL POISONING TO BE ACCOMPLISHED OUTSIDE OF FOUNDATION.
IL
ALL REINFORCING STEEL SHALL BE GRADE 60, MEETING ASTM A-16, t
4
GROUND FLOOR SLAB TO BE A MINIMUM 4" THICK W/ 6X6 10/10
A-35 SPECIFICATIONS. ALL ANCHOR TO BE A - 301 STEEL.
WELDED WIRE MESH REINFORCING ON 6 MIL. POLYETHYLENE VAPOR
BARRIER ON TERMITE TREATED, CLEAN MACHINE COMPACTED FILL
12•
ALL DOWELS, SLEEVES, CONDUITS, INSERTS, BLOCKOUTS, ANCHOR
(MINIMUM 95% DENSITY). LAP POLYETHYLENE 12" MINIMUM. FIBERMESH
BOLTS AND FRAMES SHALL BE IN PLACE PRIOR TO POURING CONCRETE.
MIX MAY BE SUBSTITUTED FOR WELDED WIRE MESH.
FOR OPENINGS AND SPECIAL FEATURES OMITTED ON THESE PLANS,
5•
SEE ARCHITECTURAL OR MECHANICAL PLANS WHERE APPLICABLE.
LOT TO BE CLEARED OF ALL SMALL PLANT GROWTH AND DEBRIS
BEFORE FILL IS BROUGHT IN. FILL TO BE SPREAD IN 12" LAYERS AND
MACHINE COMPACTED TO A MINIMUM OF 2500 PSI IN AREA OF
13.
MINIMUM CONCRETE PROTECTION FOR REINFORCING BARS:
BUILDING CONSTRUCTION
FOOTING: 3"
BEAMS: I-I/2"
6.
TEST FOR FILL COMPACTION MINIMUMS PRIOR TO FORMING SLAB.
-1.
GENERAL CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS AND
14•
LAP ALL REINFORCING STEEL A MINIMUM OF 48 BAR DIAMETERS.
DIMENSIONS. BRING ANY DISCREPANCIES OR OMISSIONS TO THE
IS.
USE STRUCTURAL GRADE WOOD WITH A MiNIMUM Fb OF 1600 PSI
ATTENTION OF THE ARCHITECT.
8.
GARAGE FLOORS TO BE SMOOTH TROWEL FiNISH (SLOPPED PER
16.
ALL STANDARD LUMBER SHALL BE SYP WITH A MINIMUM Fb OF 1000
PSI OF NO.2 SOUTHERN PINE, UNLESS NOTED OTHERWISE.
FOUNDATION PLAN). PROVIDE 1-1/2" RECESS FOR OVERHEAD DOOR
17•
ALL LUMBER IN CONTACT WiTH ANY CONCRETE OR MASONRY SHALL BE
I
FO L �l D /4%� T � O �l F L � N
PRESSURE TREATED. FASTENERS TO HAVE MIN. G185 RATING.
I. Any changes to plans must be submitted to the architect
for approval before proceeding with construction.
2. Contractor shall be responsible for verification of all
notation and dimensions before starting construction.
3. Soil conditions assumed to be 2500 psf. Should any other conditions be
encountered, the architect shall be notified in writing for revision
4. Verify all recess thickness at showers, tile, etc....
S. Contractor to provide filled cell With concrete and 1 95 bar vert, at '48"
O.C. max. Provide (1) filled cell on each side of openings upp to 5'—II" wide.
Provide (2) filled cells on each side of openings from 6'—O" to 9'—II"
and Provide (3) filled cells on each side of openings from 10'—O" and up
Contractor to see plans for any other condition used. Foundation walls
shall have filled cells at 2,4" o.c. unless otherwise noted (see section)
b. Contractor to provide for Form Board Survey — Form Board Survey
to be provided to Truss Company prior to truss construction
7. Contractor to provide for soil test prior to construction and provide
a copy of soil test to architect for review prior to construction
8. ALL Reinforcing steel shall be grade 60, meeting ASTM A-16 and
A-3S specifications. ALL Anchors to be A-301 steel.
9. Provide a minimum Of 3" concrete protection at footings and
1-1/2" concrete protection at beams for ALL reinforcing bars.
tt5 bar vert. w/
30" overlap SEE TYPICAL
at each filled cell ECTIONS
4" concrete alab with fibermesh OR
6"xC 410/10 WWM on 10 and Visqueen over
clean compacted termite treated fill
Grade
14"w x 14"d concrete monolithic
footing with (2) 95 bars cont.
14"
TYPICAL FOOTING DETAIL,
SCALE 1/2" = I'-O"
4" concrete slab with fibermesh OR
6 x6 #10/10 WWM on 10 mil Visqueen over
clean compacted termite treated fill
45 bar cont.
Step per
o . foundation plan
— 7
10" (2) #5 bars cont. bottom steel
12"
DETAIL AT GARAGE STEPDOWN
SCALE 1/2" = 1'-0"
12" x 12" concrete column
block filled with concrete
and (2) #1 bars vert. tied
into lintels above
Top of footer
14" below finished floor
,Verify house slab
height in field
�IIIIIII�
30"x30"xl6" concrete
column footing with (4)
- 95 bars each way
30"
OLUMN FOOTING DETAIL
SCALE 1/2" = 1'-0"
Thicken edge to 8"x8"
with concrete and
one #5 bar continuous
GRADE
co
SCALE: 1/4" = I'-O"
Termite Protection for New
Construction.
Soil treatment used for subterranean termite prevention
Inside the foundation perimeter shall be done after all
excavation, backfllling and compaction is complete.
If soil area is disturbed after Initial chemical soil treatment
area shall be re -treated with a chemical soil treatment
including spaces boxed or framed.
Treatment must be In accordance with the rules and laws
established by the Florida Department of Agriculture and
consumer services.
Protective sleeves around metallic piping penetrating
concrete slab on grade floors shall not be of cellulose
containing materials and shall receive application of
termicide In annular space between sleeve and pipe.
4" concrete slab with Fibermesh OR
6 x6" 410/10 WWM on 10 mil Visqueen over
clean compacted termite treated fill
PORCH SLAB EDGE DETAIL
SCALE 1/2"
#5 bar vert. w/
30" overlap
at each filled cell SEE TYPICAL
,SECTIONS
Adjust curb height --,,--SECTIONS
/
based on gar. floor 4" concrete slab with fibermesh OR
slope. 6"x6" #10/10 WWM on 10 mil Visqueen over
#5 bar in curb clean compacted termite treated fill
o'-o° 9 F.F.
Grade L.
� � _ •'r - . ' .III I—
E
II 14"w x 14"d concrete monolithic
footing with (2) #5 bars cont.
14"
GARAGE CURB DETAIL
SCALE 1/2"
2" x 6"
PT wood secured
with \
3/8"dia.
x 6" anchor bolt
at 18" o.c.
overhead door track secured to
wood
jamb per manufacturer's product
approval
Garage
Door Jamb
Detail
GARAGE
DOOR TO WITHSTAND PRESSURES STATED
NTS
IN PERMIT
INFO BOX ON
SHEET #l. SEE PRODUCT
APPROVAL FORM FOR MANUFACTURER MAKE AND MODEL.
Filled Cell Masonry Column with One
#5 From Footing To Tie Beam
Conc. Fill To Be 3000 PSI
See Floor Plan For Location
Single Filled Cell Column
NTS
Filled Cell Masonry Column With One
1*5 From Footing To Beam Each.
Conc. Fill To Be 3000 PSi
See Floor Plan For Location
Double Filled Cell Column
NTS
Braden it Braden AI A, FA
Architects - Planners
411 S.E. Coconut Avenue
Tel : (112) 281-8258
Fax : (172) 281-8283
E-mail: bradenaia8comcast.net
Stuart, FL 34996 UAAC000032
u
v
4'-0"
211 I IIJILJ
r--— —_�_�_ll_�__ UI ° D C
-----�
I FI
---
I I
I I
36'-0"
10'-0"'
12"
Rear Patio/Slab
to be poured annaratc n I
a From the house slab, U F41
Thicken footing to 24 Cff
I FI 24"w x 14"d x 24"L
under filled cells r )
I under girder bearing. Q _
I C1, o0 0 00 0 0 oC
OI----------------- C Rear Patio/Slab to — — — — 1
be flush with bottom or
sliding door recess. FI
Slope 1/2"
1
Ellf
I �-
I I `-
I
I '
I F-
I I IC
Ef FI IC
I
H B I Vanitg to be I
--34)2°high 14" concrete slab with fibermesh OR
O 6"x6" 1*10,/10 WWM on 6 mll Visqueen over I E
clean compacted termite treated fill
I FI I
I I
I ° 1
I;-
o I FI I F_.
I Ilo
I I�
Steel Ballard
filled w/ F5 Concrete
moo_ I I j0I
OI 0�� I IOIa� IC
I
I E I L I
I 35 I FI
I `Et! I I I
� E
I FI I C
L—
� 17.
� I
o aUr ° .+ 1
0o FI
I m\r
I ;tea
O I "
I Z: u �y — FI I
I
u� c F5 I = — — 0
Q,CL
W I = o o ;-;-;-�-�-�oo0
� U I
ua
L F41
I �'-2'" 12'-6"
O — Fb Recess for — — — — u O F4 r l r
OO 00 Garoor
— age DI F
o° oo --- °--------- 0
116
12" x 12" concrete column block fille
q"-O3'-5" with concrete and (2) #1 bars vert. ti
into lintels above
N
H.B.
FOOTING
SCHEDULE
Mark
size
Description
FI
14"W
x 14"D
MONOLITHIC FOOTING
WITH 2 #5 BARS CONTINUOUS
F
12"W
X 12"D
MONOLITHIC FOOTING
WITH (2) #5 BARS CONTINUOUS
30"
x 30" x 16"D
COLUMN FOOTING WITH (4) #5 BARS EACH WAY
8"W
x 8"D
THICKEN SLAB EDGE
WITH 1 45 BAR CONTINUOUS
14"W
x 14"D
FS
With
Curb at Garage
MONOLITHIC FOOTING
WITH 2 #5 BARS CONTINUOUS - CURB a 0'-0"
1116nne Building Corp. Date Drawn : Revisions : Sheet
12-8-16
Carlton 299 GLEFT� Drawn by:
Spanish Lakes C.C.U. 3
Checked by:
St. Lucie County Florida
D.R.B. OF 5
Comm #
I�-300
ROOF SHEETING;
ATTACHMENT 1DETAIL
I. Minimum Nail Size = 8d ring shank (min. 2.5" long)
2. Minimum Screw Size = 48 x 2"
3. Minimum Sheathing Thickness 19/32" CDX Plywood
4. Use nails or screws based on pressure for roof stated
in permit info box on these plans for zone 3
Kew
Area
Edge
Field
Fastener
Pressure
Zone I
6"
6"
8d ring shank
45 psf
Zone 2
4"
6"
8d ring shank
% psf
Zone 3
4"
4"
8d ring shank
84 psf
** Zone 3a
6"
6"
48 wood screw
112.5 psf
** Use nails or screws based on pressure for roof stated
in permit info box on these plans for zone 3
Concrete
/ Lintel
Column
to
Verify with Plan
Provide a5 bars with min. 48 bar
diameters overlap Into beam. Tie
Filled cell steel into continuous
beam block steel.
Provide #S bar set in pre -cast
lintel Into beam where length of
the opening calls for it.
Provide Cast -Crete
SUS-OB/OT precast ---_ -� --
lintel set in mortar '., _
Min. 8" Bearing -- - - -I--- ---- -
12"x 12"
Column Block
\ i# Rebar
Rebar 48 Bar Dia.
Min. Overlap
Lint&l Attachm&nt
NTS
Additional Precast Lintel
tt5 are,
! .-ly' ^t CLEAR
Lintel
Length
Bar
length
-
Clear
Span
u u
A
Bars
Ili
B
Bars
2'-8"
2,43
'`�
2'-10"
-1
none
3'-6"
3'-4"
2'-2"
2,43
none
SFS-OBAT SF8-IBAT 8F8-IB/2T
Addtional
4'-0"
3'-10"
2'-8"
2,#3
none
- tt5 tiare
CLEAR' ; .":,�
�,...:
4'-6"
4'-4"
3'-2"
2,33
none
Row of "H'
? •' Block Above
5'-2"
4'-0"
2,#3
none
•'."."�:�� Precast Lintel
2,#4
none
r y
'• Additonal ."
6'-6"
2,#4
none
#5 bars ,y
1' 6"
7O"
6 2
2, 5
none
8FIL-IBAT 8FI4-I15/2T
8'-4"
�'-10"
1'-O"
2,45
none
NOTES:
ALL reinrorcing steel Is grade 60.
I. min. coverage of steel -Ls"
2. min. bearing requmed is ea. end=8"
3. standard for reinf. steel-ASTM A615
TYPICAL LINTEL SECTION
( PRECAST CONCRETE )
LINTEL SCHEDULE
Mark
Window
or Do
Unit
Width
Lintel
Size
Cast -Crete
S ecificatfon
Rows of
"H" Block
Above
"
Bottom
steel
81ze
Top
Steel
Size
Max.
Gravity
Load
(PLF)
Max.
Uplift
Load
(PLF)
Max.
Lateral
Load
(PLP)
L22
2'-2"
3'-L"
8128-OB/7
1
#5
3049
151.9
1024
L31
2'-6"
2'-8"
3'-1"
4'-O'
8F8-OB/IT
1
tt5
25LI
1363
1L3
L45
4'-5"
5'-10"
BF8-013/7
1
#5
1105
909
339
L50
5'-O"
L'-L"
SIPS-OBAT
1
#5
1238
835
121
L40
6'-8"
T-6"
SF8-OB/IT
1
#5
1011
121
534
L80
8'-O"
9'-4"
8F8-IB/2T
I
tt5
2
35
152
591
512
1_90
"1
10'-6"
SF8-IB/2T
I
tt5
2
#5
643
530
1 401
L905
T-0"
10'-6"
SFIL-I13/2T
ONE
1
tt5
2
tt5
1533
1183
401
LI00
10'-0'
II'-4"
SF8-IB/2T
I 1
05
2
#5
582
494
452
LIOOB
10'-0"
11'-4"
8FIL-IB/2T
ONE
I
tt5
2
1 #5
MLL
1028
452
L120
12'-0"
13'-4"
SF8-IB/2T
I
tt5
2
#5
411
426
324
L120B
12'-O"
IV-4"
8F16-I15/2T
ONE
1
tt5
2
#5
1015
110
324
LI40
14'-O"
IS'-4"
8FIL-IB/2T
ONE
I
tt5
2
#5
1250
L09
259
LILO
I6'-0"
m'-4"
8FS-IB/217
I
tt5
2
#5
300
192
194
LILOB
III
IT-4"
8FIL-IB/2T
ONE
1
tt5
2
#5
950
500
194
- ALL LINTELS SHALL BE MADE BY CAST-CRETE.
- LINTELS SHALL BE FILLED SOLID WITH 3000 PSI CONCRETE
- REFER TO CAST-CRETE CATALOG FOR ALL INFORMATION REGARDING
LINTEL CONSTRUCTION, HANDLING INFORMATION. AND SAFE LOAD REQ.
REQUIREMENTS
- LINTELS OVER 14'-O" LONG ARE TO BE PRESTRESSED.
Provide PT Buck
attached per jamb
letails into filled c
4" Pre -cast
Sill k
Filled Cell
Provide 45 bars with min. 48 bar
diameters overlap in filled cell. Tie
filled cell steel into continuous
rooter steel.
Poured Concrete or
concrete block wall
C B S I A L L Scale: 1/2" = 1'-0"
SINGLE PLY REAR GIRDER TRUSS
Nail 2" x 4" blocking to vert. leg of
truss with IOd x 1.5' nails at 4" o.c.
Install Simpson MGT into wall usingg
5/8" dia. threaded rod set min. 12"
into wet beam and (22) IOd nails into truss
/
Poured Concrete or \
concrete block wall
Concrete Anchors f
Manufacturers Specs
3LOCKING DETAIL Flush raUnt
)ER STRAPPING
TER BEARING POINT
1/8" thick light textured stucco installed per
ASTM C 926 over ASTM D type 2 paper backed
wire lath nailed to substrate through one layer of
ASTM D Tggpe 2 felt paper using 8d nails. Substrate
to be 19/32' COX Plywood nailed at 6" o.c. in field -
and edges with IOd ring shank nails into studs.
Union Corrugating Co. 26 ga. SV crimp metal roofing
III 1211A Attach rooring to deck using #9 x 1.5"
wood screws with washer Per Approval over 30 lb felt
underlagment installed with min. 4" side laps
and 6" end laps fastened with corrosion resistant tin
caps with 1 1/4" ring shank nails spaced 6" o.c.
at sll laps and two staggciered rows 12" o.c. in field.
Roof deck to be 19/32 COX plywood nailed to
trusses with 8d x 2.5" long ring shank nails per sheeting
attachment detail on roof plan
Max allowable uplift = 85.8 psf
12
Simpson HETA 20 or equal
hurricane anchor at each truss 4
with 60) IOd x 1 1/2" nails
( 8lo 24" o.c.) supporting Max.
1bs. uplift
Aluminum Drip _
Edge t Fascia 1/2" thick stucco on 3/8" hi -rib lath
2" x 6" Sub -Fascia r
Kaycan full o vent vingl soffit installed J.
using 1/8' dia shank x 15" long gelv.
roofing nails with 3/8" dia. head per
product approval - see chart sheet #I
12" x 12" concrete column
block filled with concrete
and (2) 41 bars vert. tied
into lintels above
thicken edge to 8"x8"
with concrete and
one 45 bar continuous
BEYOND
Aluminum Drip
Edge i Fascia
Flash and Counter
flash
Nail ledger to
gable end truss
with (2) IOd ds
at each web
Top of footer
16" below Finished floor
2" attached Co horizontal end vertical wood
framing with Wells or ateplea to provide
no lees than I-3/4" penetration into
horizontal wood framing and 3/4" penetration
into vertical wood Praming memhare
5/8" thick fight textured
stucco on typical concrete
block construction
Varies - see plan
tt5 bar vert. w/
30" overlap
at each Filled cell
Rear Patio/Slab to
be Flush with bottom of
sliding door recess.
yl
Step per foundation plan
� Slope per foundation plan 'r
r>r
e Anchors Per
Wrens spew
I/q"Max.
I
jAluminum Panel
I saes per manufacturer
i
' ��ypic I st d D,3<af
x
i
I
' l/e" x 3/32" WiFlg Nut w/
I a appropriate weshar and spacing
I u `v per manufacturer's Details
I
� J L
i
I a
I x _
i
I
I
I 1
i
i I as�
i
Stud Detail
I Stud w/ Die Cast Zinc NTs
j Nickel Plated Wmk Nut
ter Detail
1,
nits
Brace Gable end
with 2" x 4" S P tt Y 2
ert back nailed to bottom
Of top chords using (2) IOd
nails at each truss
PRE-ENGINEEI WOOD TRUSSES
9 24"o-c. TYPICAL
( shop drawings by manufacturer )
N
W
� X
L �
r
O � to
CV �
� L
�Q as
n�
_0 N u)
U
O co
will p O
ems= °D O
� u N �
L QL
f I—
w
Brace Gable end
with 2" x 4" SYP 42 min.
8ft back Waited to bottom
of Lop chords using (2) IOd
Halls at each truss
1
"\R-30 blown fiberglass
in bottom chord of trusses
I/2" drywall with smooth finish 0
Two rows of beam block filled with concrete
and (I) #5 bar cont. in each row. Substitute
precast lintel felled with concrete and (D #p,
bar cont. for bottom row over openings
I/2" drwall over I" x furring
steps at 19" o.c. with R4.1 fi-foil
insulation on typical 8" Block walls
_ All drywall to be installed per FBC R102.3.1
and shall meet all pertaining ASTM codes.
n Mortar to be Type "M" only proportioned er FBC RbOl.l
and Mortar Joints shall comply with FBC �601.2.1.
Provide Our-O-Rock at all wet areas (ex. showers, tubs etc...)
Strap truss to wall
00
Brace Gable end
with 2" x 4" SYP 42 min.
8ft back Waited to bottom
of Lop chords using (2) IOd
Halls at each truss
1
"\R-30 blown fiberglass
in bottom chord of trusses
I/2" drywall with smooth finish 0
Two rows of beam block filled with concrete
and (I) #5 bar cont. in each row. Substitute
precast lintel felled with concrete and (D #p,
bar cont. for bottom row over openings
I/2" drwall over I" x furring
steps at 19" o.c. with R4.1 fi-foil
insulation on typical 8" Block walls
_ All drywall to be installed per FBC R102.3.1
and shall meet all pertaining ASTM codes.
n Mortar to be Type "M" only proportioned er FBC RbOl.l
and Mortar Joints shall comply with FBC �601.2.1.
Provide Our-O-Rock at all wet areas (ex. showers, tubs etc...)
Strap truss to wall
00
using Simpson MGT with
Simpson
HETA 20
5/8' dia.
Into beam
threaded
either wet
rod with min 12" embedment
set or in epoxy with
hurricane anchor
at each truss
(22) IOd
truss leg
Wads into
detail
truss. Add blocking to
this
( 24 o.c.)
supporting Max.
per
on sheet
HETA 20� 1810
16s linlirt
iv
LLO
BI
BI
O
I
LIO
BI
�
ll.i
— O
J
N
LI00
BI
L90
O W I
12 I
'4 SLOPE I gl L45
12„
I �
(L/
BI I I — 7
I I �E 2
� LOP �
I Q o BI
I
N�
(
IW N
�.
':',
L31 BI I
n� B L45
4L
�"
I
I
Union Corrugating Co. 26 a. 5V trim metal roofin
N
wood screws with washer Per Approval over 30 lb f
underlayment
t � x
Q
z
IN
LU
Fill cell with concrete and ROOF
O O � � L �
(U #5 bar vert. (typicaU.
Max. spacing shall not exceed /�
wood 48" unless otherwise noted — OVERHANGS AT 1 O UNLESS OTHERWISE NOTED ON THIS SHEET
Base see foundation plan notes for — ROOF PITCH AT �(':12 UNLESS OTHERWISE NOTED ON THIS SHEET
J spacing at openings — III i.� ^ n L�
4" concrete slab with fibermesh OR TRUSS SHOP DRAWINGS TO BE PROVIDED BY 11/-'LNUFt-tCTUI\ER
6"xL" #10/10 WWM on 6 mil Viaqueen over
clean compacted termite treated fill ANY CHANGES T O T H I S
I
11111111111111111111i�1 •:. :; IIIIIIIIII�IIIIIIIIIIIIIIIIIiiiilllli�i�llll�iiillllliii
I I•
14 FI
Typical Section at Front Forc�h
Scale I/2" = I'— "
Braden t Braden ,41,4, P,4
Architects — Planners
417 S.E. Coconut Avenue
Tel (172) 281-8258
Fax (1�2) 287-8283
E—mail: bradenalas'comcast.net
Stuart. FL 34996 #AAC000032
PLAN SHALL BE SUBMITTED TO THE
ARCHITECT FOR APPROVAL IN WRITING PRIOR TO STARTING CONSTRUCTION.
— ALL TRUSS TO TRUSS CONNECTIONS BY
TRUSS MANUFACTURER
— ARCHITECT TO REVIEW TRUSS SHOP DRAWINGS PRIOR
TO CONSTRUCTION FOR LAYOUT AND UPLIFT VERIFICATION
— CONTRACTOR TO PROVIDE FOR FORM BOARD SURVEY AND TO PROVIDE
FORY BOARD SURVEY TO TRUSS COMPANY PRIOR TO TRUSS CONSTRUCTION
Wgnne Building Corp. Date Drawn : Revisions: Sheet Comm #
12-8-1
6
Car 1 t on 2 99 LEFT Drawn by:
Spanish Lakes Checked by:
St. Lucie County Florida D.R.B. OF 9 ,
11111111111111111111i�1 •:. :; IIIIIIIIII�IIIIIIIIIIIIIIIIIiiiilllli�i�llll�iiillllliii
I I•
14 FI
Typical Section at Front Forc�h
Scale I/2" = I'— "
Braden t Braden ,41,4, P,4
Architects — Planners
417 S.E. Coconut Avenue
Tel (172) 281-8258
Fax (1�2) 287-8283
E—mail: bradenalas'comcast.net
Stuart. FL 34996 #AAC000032
PLAN SHALL BE SUBMITTED TO THE
ARCHITECT FOR APPROVAL IN WRITING PRIOR TO STARTING CONSTRUCTION.
— ALL TRUSS TO TRUSS CONNECTIONS BY
TRUSS MANUFACTURER
— ARCHITECT TO REVIEW TRUSS SHOP DRAWINGS PRIOR
TO CONSTRUCTION FOR LAYOUT AND UPLIFT VERIFICATION
— CONTRACTOR TO PROVIDE FOR FORM BOARD SURVEY AND TO PROVIDE
FORY BOARD SURVEY TO TRUSS COMPANY PRIOR TO TRUSS CONSTRUCTION
Wgnne Building Corp. Date Drawn : Revisions: Sheet Comm #
12-8-1
6
Car 1 t on 2 99 LEFT Drawn by:
Spanish Lakes Checked by:
St. Lucie County Florida D.R.B. OF 9 ,
PANEL
"A"
arc#
Description
Wire Load BR Pales
Poles
BR
Load
Wire
Description
circ#
2
40
1.0 kw
#8
A/C comp
1
2
AHU
#10
3.5
kw
30
2
3
5
4
L
2
2
30
4.5 kw
#10
40 gal, water HTR
Range
96
12.0
kw
50
�
e
I
20
1.8 kw
412
Pump
9
10
Dr er
tt10
5.0
kw
30
2
II
12
1
20
1.5 kw
#12
13
14
Dishwasher
a12
1.2
kw
20
1
1
20
1.5 kw
#12
Microwave
Is
ib
Refrrgerator
#12
1.2
kw
20
1
1
20
1.5 kw
#12
Kitchen S.A.C.
Il
I8
Recepts
#12
20
1
I
20
1.5 kw
#12
Kitchen S.A.C.
19
20
Recepts
412
a0
1
1
20
1.2 kw
#12
Clothes Washer
21
22
Recepts
#12
20
1
20
0.81 kw
#12
Garage Door Opener
23
24
Recepts
#12
20
1
1
20
1A kw
#12
25
26
Recepts
Recepts
#12
20
1
1
20
1.92 kw
#12
2-1
28
#12
20
1
1
20
#12
General Lighting
29
30
Recepts
#12
20
1
1
20
#12
General Lighting
31
32
Recepts
Exterior GFCI
#12
20
1
I
20
tt12
General Lighting
33
34
#12
20
20
#12
General Lighting
35
36
Bathroom GFI
912
20
I
1
20
912
Smoke Detectors
3T
38
General Lighting
#12
20
I
1
20
#12
Bathroom GFI
39
40
General Lighting
#12
20
1
ar,Arl
41
42
spare
PANEL "A" LOAD CALCULATION SHEET
Load Description Qt .
Watts
Total(Watts)
General Lighting (3. watts sq. ft)
Small_ Appliance. Circult(s).... . . ............
Range ...... .................. ......... ....................
Refrigerator .....
Microwave.....................................................
Dish Washer
......................... .. ...........................
Clothes Washer
Clothes ..Dryer .................... .. .. ........
Water Heater
Water. _Pump ..... .. .................... ....................
Garage Door Opener . . .. . .. . ...... . . _ ..................
.....
.. ..
I135
3
5,205
2
1,500
3,000
1
12,000
12,000
1
1,200
1,200
I
1,500
1,500
1
1,200
1,200
1
1,200
1,200
1
5.000
5,000
1
4,500
4,500
1
1,800
1,800
1
810
810
Total
Watts
31,415
First 10000 Watts
e100%
1
10,000
10,000
Remainder
21,415 840%
1
0
10,9L4
Electric Heat or A/C 10,000 996%
1
10,000
10,000
Calculated Load
Watts
30,964
Voltage
240
Calculated Wattage
Divided bg Voltage =
Total Amps
Panel Sze Required =
129.03
150 Amps
l=lectrlcal S mbol Legend
$
Single Pole Switch
®
Recessed Can Light
53
Double Pole Switch
®
Egeball Recessed
1
Pe
Push Button Switch
Exhaust Fan
Duplex Outlet
Ceiling Mounted Light
Special Receptacle
o-
I Wall Mounted Light
WaterprooterrlLpLtfff ground fault circuit
Light with Pull Chain (attic)
®
Floor Duplex Outlet
©
Computer Connection Jack
Fc-F1
Carbon Monoxide Detector
Flood Light
TQ
Thermostat
m
Electrical Panel
©
Central Vac
u
Electrical Meter
®
Smoke Detector
Ceiling fan
©
Television Jack
Telephone Jack
ACC
A/C Disconnect
®
I x 4 Florescent Light
®
2 x 4 Florescent Light
SPKR
Speaker Hook -Up
❑i
Intercom
Q
IN
110 CFM I I PATIO/SLAB
12x8x8
MASUB/A
BED
GORE, 'T
ROOM
110 I
12
I
x12x9
C nter Registers
IL3 CFM oceiling fan IL3 CFM
IOxIOx I IOxlOxl
12x12x9 B/A �I�I
C
E
Yent_thcLL ____
Soffit
AiC
Meter
150 Amp
Panel
:FM 140 CFM
xL FVVL 12x12x1
1- ro
12"
I 1 \
o �
I =.
Q
L- - - - - -T -
w.H.
I 22" x 54' ,
I Attic Access
with light
-- - - -
�
G14RAGE
r-----------------i
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
MF CubNiCbi i bYni iT
SCALE: 1/4" = 1'-011
Electric Notes:
I.
Use copper wire onlg, no aluminum.
I-1. It is not the intent of these plans to show every minor detail
2.
Provide and wire all required smoke detectors.
or construction. The contractor shall furnish and install
3.
Contractor to verify location of electrical
all items for a complete electrical system and provide all
service and provider.
the requirements necessary for the equipment to be placed in
4.
ALL paddle fans shall be on a rheostat.
proper working order.
S.
ALL bath and kitchen receptacles to be GFI protected.
18, All work shall be done in accordance with the N.E.C. and
6.
ALL exterior outlets to be WP/GFI protected.
shall comply with all local codes and ordinances, and shall
1.
Recessed cans to be installed per NFPA requirements,
meet all standard requirements of the local electric utility
8.
AFCI receptacles are required in all rooms except
and telephone company.
Kitchen, Bathrooms, and Garage.
9.
A/C Return Air Balance Must comply w/ FBC RM16
19. The electrical system shall be completely and effectively
10.
A/C Refriggerant lines that are run thru slabs must be
as required by the latest edition of the N.E.C.
sleeved in PVC
grounded
11.
ALL A/C Equipment shall comply with energy calculation
20. All material shall be new and shall bear underwriters'
12.
All work shall be performed by a licensed electrical
labels where applicable.
contractor, the completed system shall be fullg operative.
13.
Contractor shall pay for all fees, permits, tasting, and
21. All equipment and panel sizes shall be verified before
inspections including blower testing where required.
ordering. The contractor shall provide circuit routings to
A.
All work shall be coordinated with other trades to avoid
suit the job conditions.
interference with the progress of construction.
19.
All required insurance shall be provided for protection
22. Furnish and install all fixtures as called for on the plans
against the public liability and property damage for the
or as selected by others.
duration of the work.
16.
Contractor shall guarantee all materials and workmanship
23. All raceways and pipes placed in or through any concrete
free of defects for a period of not less tfian two years from
slab shall be spaced a minimum of three diameters of the
the date of acceptance or certificate of o(§cupancy, or one
largest conduit or pipe from any other service.
year from closing sale of house.
Correction of defects shall be completed without additional
2-4. All exposed wire below 9'-1" shall be installed in metal EMT
charge and shall include replacements or repolr of any
conduit.
other phase of installation that may have been damaged.
25. Dryer Vents to be installed per FBC RMIS02
DINING
ROOM
c
I 12 FM
?2�A1 ex 4 /�
a � I
W, I
#�?(Z)I
S q.i j 83 CFM
Q `yI I 12x6xl
IL
Lc' _t--
3 CF
SECOND
BEDROOM
I
12xl2x8
�1 B/A = Balanced Air
COVERED
PORCH
ent --- - SO_ f t thru
O= THERMOSTAT LOCATION
A/C
^disc.
LJ I
150
#2/0 Aluminum feed AMP
MCB
1 ''/2' Conduit PANEL
2" PVC ( FP
2" rigid service FFL I Ba e,#cunt pPaEtta r i e slab
ELECTRICAL RISER
- Contractor shall use AL-CU Larding lugs. NITS
- Contractor shall torque lugs I.A.W.
manufacturers recommendations which
shall be verified prior to construction
Braden It Braden AIA, FA
Architects - Planners
411 S.E. Coconut Avenue
Tel : (172) 287-8258
Fax : (772) 287-8283
E-mail: bradenaiamcomcast.net
Stuart. FL 3499( UAAC000032
Exhaust Duct
Thru Soffit
4" Exhaust
Duct Thru
Wall
Install owleArn
under disc
rot shown
clarity
Q
FA IC
Meter
0
I
v
MASS7ER
BEDROOM
16" I
I(CLO&E 1
PATIO/SLAB
,.Covered Porch-,
\ 1
\ I
w.p. GFI
CARE Smoke / Carbon T
Monoxide Detector R O M
Combo
s I
CM I
I
= II
II
I I
I I
I I DINING
e
me;
ul
--
4I��
22" x 5"
\ I Attic Access \ _
with light
L I \
J Lt- \SECOND
ISO Am Optional BEDROOM
Panel PCA panel location
Pull chaml ® S TV
\ \ light in attic
42"h GFJ
Garage / \
Door
I /
Opener /
r-----------------i / I
I
I
w.p. GFI
I 1
I I
I
I f�COORRH [:�
LECTRICr',L P_,^,�
SCALE: 1/4"
Attic Ventin Calculations FBC 230°I.�f
Total Attic Space = 2124 sq. ft.
Venting Ratio VISO = 14.16 sq. ft. required
Frovide A Continuous Vented Soffit
WUnne Building Corp.
Carlton 299
Spanish Lakes
St. Lucie County Florida
Post Light with /A"� o
Photo cell c
w�
0
I
N
Date Drawn Revisions Sheet
GARAGE 12-8-16
LEFT Drawn by:
c.c.u. F -
Checked by:
D.R.B. OF 5
Exhaust D ct
-Thru Sof it
Wire For
Front Post
Light
Comm 4
1 I�-300
Especial
SAFETY WARNING
ifies Life Safety Warnings that should be read
ntion by all persons installing trusses.
ENEMIES
30' Span or less & 30' to 60' Span A
0 degrees Spree er Bar
or less
*_ 1/2 —109 t—APProx 2/3 to--►
T Line span approx. Lne t/2 of Span
g REFER TO Lnot
REFER TO BCS� Truss must be set this way ied.
Truss must be set this way if crane used. This is on example, truss atch.
is an example. your truss may not match.Insist crane operator sets truss this way. Insist crane operator setss way.
MULTIPLE PLY TRUSSES MUST BE
ASTENED TOGETHER PER ENGINEERING
BEFORE SETTING. REFER TO
ENGINEERING DRAWING TO DETERMINE
IF MULTIPLE PLY.
Carrying Girder
For Truss to Truss
Connections see
hanger/connector ails must be as
shown. Guide tabs 0
schedule in engineering Dome angle nails.
package.
Carried Truss
SEAT PLATES BY CHAMBERS
M
n
12
4.00 F_
8�'
12 2.00
upset=1/4" heel=315/16"
PLUMB CUT END -
2 x 4 Top Chord
WALL HEIGHT 8'
END DETAIL: TYPICAL VAULT
upset=1/4" heel=315/16"
PLUMB CUT END
2 x 4 Top Chord
WALL HEIGHT 8'
TYPICAL END DETAIL
INDICATES LOAD BEARING
REQUIRED BY TRUSSES
SUPPLIED BY BUILDER
AT A HEIGHT OF 8'-0"
ABOVE FINISHED FLOOR
TRUSSES FOR THE FIRST MODEL SHOULD BE SHIPPED AND SUCCESSFULLY SET BEFORE ANY MORE TRUSSES ARE BUILT FOR THAT MODEL.
�► ARRANGE WITH CRANE OPERATOR IN ADVANCE FOR A SPREADER BAR OF 18' - 24' IN LENGTH
Do not stand on trusses until they are braced per BCSI & properly nailed to straps & hangers - - -/
5PAGING NOTE
ALL TRUSSES ARE TO BE SET
AT 2'-01 ON CENTER
EXCEPT AS NOTED
AIR HAIVE:>I—NEE F-v NOTE
UNLESS NOTED ELSEWHERE ON THIS LAYOUT, THESE TRUSSES
ARE NOT DESIGNED FOR AIR HANDLERS IN THE ROOF OR FOR
ANY OTHER A/C REQUIREMENTS. THIS MAY BE IN CONFLICT
WITH BUILDING CODE AND A/C DESIGN REQUIREMENTS.
CONSULT WITH BUILDING DEPARTMENT AND A/C CONTRACTOR.
11110
Killr
A
Al
A2
A3
A4
A4
A4
A4
r
A4
iFA
GRA +VO
ATA
ATA
ATA
ATA
ATA
ATA
ATA
ATA
ATB
10,
�ll �II III m
4
io
All load bearing walls, headers,
beams & lintels must be in place
at indicated height before trusses
Q are installed. AL
MIM11MIM',IMIMIM1®
////.I/////1%//�%//%;%////.;/////;/DSO
10,
INVERTED'%/" WEBS AT CENTER
W/4' B.C. PANNEL. LOAD W/ (2)
50# POINT LOADS PER TRUSS FOR A/H/U
91
Is
1010
,t✓19
J2
J4
J6
ALI
a
I I I I I
16_10" ' 6-4" I T-4" I 111-6" I
GARAGE LEFT
N
N
in
iO
�
7
:-
N
N
DON'T LIFT TRUSSES
WITH SPANS LONGER THAN
30' BY THE PEAK.
CONSULT BCSI
22' 14'
I I
I I
ppm
+Va
INVERTEP'v" WEBS AT CENTER
W/g' B.C. PANNEL. LOAD W/ (2)
50# POINT LOADS PER TRUSS FOR A/H/U
�-
� I���i101�1■�ISi�
�nsssa�le�
pit
---------------Ease
FABRICATION AGREEMENT'
TRUSSES CANNOT BE STARTED UNTIL THIS AGREEMENT IS SIGNED A RETURNED
The kpal description of the Property where the busses will be Installed Is:
e,underaigned ackrawledges and agrees:
`-!. Trusses wig to made In strict aceordence r 111a truce Placsment diagram layout,
wtJ11h'1thesoleauglofllyfordeterminingsucceaefu1lots, tic otthebueaea.
3 All dlmenalona N this layout have been verMed by tl e undersigned.
- S, Unlads written nodce la Previdad by cortiged matt to Chamber T usa witilln on (10,
days of delivery Ne undersigned agrees that no badtd:rgeo wN be altowed. In tin avant
such writer noflae Is funllshed Chambers Tme she have three (3) bu��pI�lreas days In which
b Degln repaks required, p't0 wbstllW other truaeaa, et Chambers oPaon.
4 a undersigned arkrawiedges rscelpt of "SC311.03' summarysheet by TPI & WrCA.
bslNery Is to jab alte. tt b the btryers'roepoml6lllly to make the Job she cuRable for
tie qry Chambers Truss has the Bole auNorlty to nothe wgsbRRy of the Job sqe oy e
Cdpdn of the Job slue for delivery. Chambero Truce wltl be roapon:lu for dump delhrery arty.
Ths.biya• k rosponelbls for addltlonel daMery expenses ti Chambers Trues has to rodeihnr
begalrae Job slte u rat prepared for dalNery tt btryar Is not prepared for delivery of busses.
Suyesle rsapone@le to Chem6ere Tnss for towlntj Coate due to She conditions
:*9:, Rube as sham b per�raph 7 baba b sub]ed to dnngs R any changes am. made In
Jhl■,Jsydlr A Sq0 per hour tea for reNsions may be charged M ChambersTruss. '
-.E,;Thb b e PURCFIASE ORDER to Chambers"Tuna of the sum agreed to, or If III
.pg, ant a reasorisbb pd�. Invoice wiq be made on delivery and paid within terms of nig
onfddlhrery. Invoce may be made at scheduled date o del It boyar cannot accept
8ellvery'of febdcatad to saes. Ths undanlpned agrees to pay Chambers.TNsa accept
.own Va fee for collections In event odf payment not time made. 1.1/2 %per month selvlca
'charge will be added for all sums not paid In terms
;3: Signature or Initials anywhere on this sheet comtitutes agreement to ON terms herein.
:;:9. In waelderatlon of Chambers Truss extending credit for this material the undersigned
IindogdPoonatly Duarenlsea payment when due of any and all Indebtedness owed to
Chambers Trustsbyprry entry receiving material and the undersigned agrees to pay such
Indebtedness Including attorneys fees, If default in payment for materiel be made by the
Aciplant. 1.
10; In the event of any litigation concerning this agreement the Rama fumtahed hereunder
:or payments retenad to herein, the. parties agree that the sole venue (or arty such action will -
be6ablt Ulde County, Florida.
114.0ealgn responsibilities are per "'Notional Standard And Recommended Guidelines On
�Responsibilities For Ctatabuctlon Using Metal Plate Connected Wood Trustee
ANS}I/rPW4TCA 4-2002- -
DA
8tL3NED ,.
IME
`,'iWaltiple ply trusses must be fastened together per engineering
4kWiore they are set, failure to do so can result -In roof collapse.'
@Riiporary and permanent bracing are required and can save life
?:�.tand property and Is the responsibility of the truss erector.
$°tidy the contents of the Information packet Included on delivery
�i:� before setting trusses.
-i,wi.-Tiim smuatbeadardbmeedperdeslgniopmvwd"&damage
;; ,. Trusses must be set plumb and aqupro
'
'Do riot bet bunks or stack of plywood, roofing material or any
..Rther q,91h , ntrated loads on trusses, this can cause collapse.
iDO NOT SET TRUSSES USING THIS LAYOUT
- USE LAYOUT DELIVERED WITH TRUSSES TO SET TRUSSES
-;::::CHAMBERS TRUSS "INC
s'.
3105 Oleander Avenue
i Fort Plercej Florida 34882-6423
x' 800-551-5932 n,
p8)tPloms 772.485-2012 Fax 772466-8711
7'ViIiio Beach 772-569.2012 Stuart • 772-286.3302
Ic<xiw' WobSitseCHAMBERSTRUSS.COM
The Architect's or Architect's representative's
shop drawing approval is NOT a
"double check" of the contractor.
The contractor shall remain responsible
for checking field measurements and
other construction criteria. Architect's
approval covers general roof shape,
review of truss strapping, and loading on
structure from gra j ty and uplift loads and
their res t! a locations.
Approved By.
92.0/93.2 MITEK 4.2 Braden S. Braden A.I.A. P.A.
DESIGN CRITERIA
County SAINT LUCIE
Building Department ST LUCIE COUNTY
Wind Design Criteria ASCE 7-2010
Wind Design Method Main Wind Force Resisting
Roofing Material Shingle or Shake
Loading in PSF Roof R.D.L.
Top Chord Live 20
Top Chord Dead 7 4.2
Bottom Chord Live 10 Non -Concurrent
Bottom Chord Dead 10 3
TOTAL Load 37 7.2
Duration Factor 1.25
Wind Speed 165mph
Top Chord C.B. Sheeting by builder.
Bottom Chord C.B. Sheeting by builder.
Highest Mean Height 12'-0"
Building Type ENCLOSED
Building Category II:Non Restrictive
Exposure Category C
Barrier Island No
Conforms to FBC 2014
R.D.L.=Restrainin Dead Load C.B =Conticuous Bracin
Verify DESIGN CRITERIA shown above with the
building department and your engineer.
Design Criteria is the responsibility of the
Buildinq Designer and/or Engineer of Record.
ry Chambers Truss Inc. Drawing Name: L111412
W Scale: 1 /4 = 1'
73 total trusses, 14 different trusses.
MI 4: RLC ACAD: RLG Reviewed By:_0eA'-0y7r,
Date:11/14/16
FOR
WYNNE DEVELOPMENT CORP.
DESCRIPTION:
GARAGE RIGHT P ARLTON 299
PAGE 1 of 1 CUSTOMER INITIALS EACH PAGE
14 TRUSS DRAWINGS ARE ATTACHED TO LAYOUT M11412 -73971