HomeMy WebLinkAboutFire District Plan Review FormSAINT LUCIE COUNTY FIRE DISTRICT
PLAN REVIEW FORM
5160 N.W. Milner Drive
a
Port Saint Lucie, FL 34983
3.` x
Telephone: 772-621-3322
0 DISjQ`
Fax: 772-621-3604
Web Address: www.slcfd.com
Building Dept. PSL FMO Permit # B-14-163
Project Name Savanna Club Community Center BLDG Permit # 1405-0345
Address 3492 CrabApple Drive City I Port St Luice
Contractor Commercial Contracting Division Inc. (772) 34 0- 1889
Address 709 S.E 5th Street City Stuart
State Florida Zip 34952 �,' Telephone (772) 340 1889
Y. Architect/Engineer Cross Roads Architecure Telephone (772) 287-7330
Occupancy Type Assembly Construction Type 112 Square Feet 14,348
OccupaniLoad 479per plans Number of Stories I1 Access Box Required Access Key Switch Required
:1.
AFS Per;nit Required FA Permit Required FFP Permit Required
General Notes
1. An electronic copy of the construction documents submitted on a CD is required. The file format shall be .pdf only.
2. All revisions, including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all inspections.
4. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
S. Failed inspections require payment of fee prior to rescheduling of further inspections.
6. Penetrations through rated assemblies shall be of the proper UL design. Design criteria shall be submitted with the construction plans.
7. Fire alarm panels shall be located indoors within air conditioned space.
8. Plans and construction are subject to corrections in the field to maintain code compliance.
9. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity.
10. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE FLORIDA FIRE PREVENTION CODE, 2010 EDITION IS CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See General Notes Above and Required Revisions Below
Notes;
1. A separate review and permit is required for the installation or alteration of the Fire Alarm, Fire Sprinkler, and Fixed Fire
Protection Systems.
2. In accordance with Life Safety Code Section 12.2.2.2.3, Assembly Occupancies with an occupant load greater than 100 persons
require panic hardware or fire exit hardware on the required means of egress doors.
Page C of Reviewed by Tony Jerger Date 7/16/2014