HomeMy WebLinkAboutHVAC Load AnalysisSavanna Club Community Center
HVAC Load Analysis
for
Savanna Club
3492 Crabapple Drive
Port St. Lucie, Florida
CQMM4RCTAL,
%MolV1VAC.'HVAC:LoADs
00%toIIIClg►pDf
G 3 . S V0'&
b
79 2
0
:�=
.��
ATE F o Wq
• as •
Prepared By:
Eric J. Svoboda, PE
Fort Pierce Engineering, Inc.
315 South 7th Street
Fort Pierce, FL 34950
772-672-4636
Wednesday, September 18, 2013
Chvac FuII:Comme'rcial HVAC Loads Calculation Program
t , I
Elite Software Development, Inc.
3
.,
Savanna Club Community
Center, i
Page 2
Building Summary Loads
Building peaks in August at 4pm.
Bldg Load] , ."Ar"ea -� FSen '%Tot
Lat ;Sen
Net ` `
%Net
Description ., ,,, Quan. Loss .. Loss
GainM „-,` Gain
. Gain :,m '"
°` Gain
Roof 13,687
15,041
11.89
0 19,285
19,285
4.67
Wall 6,692
20,979
16.58
0 15,044
15,044
3.64
Glass 700
19,173
15.15
0 45,590
45,590
11.03
Floor Slab 616
12,603
9.96
0 0
0
0.00
Skin Loads
67,796
53.57
0 79,919
79,919
19.34
Lighting 22,791
0
0.00
0 77,766
77,766
18.82
Equipment 16,753
0
0.00
0 57,164
57,164
13.83
People 240
0
0.00
39,852 60,165
100,017
24.20
Partition 0
0
0.00
0 0
0
0.00
Cool. Pret. 0
0
0.00
0 0
0
0.00
Heat. Pret. 0
0
0.00
0 0
0
0.00
Cool. Vent. 1,650
0
0.00
59,312 36,267
95,579
23.13
Heat. Vent. 1,650
58,753
46.43
0 0
0
0.00
Cool.lnfil. 0
0
0.00
0 0
0
0.00
Heat.lnfil. 0
0
0.00
0 0
0
0.00
Draw-Thru Fan 0
0
0.00
0 2,788
2,788
0.67
Blow-Thru Fan 0
0
0.00
0 0
0
0.00
Reserve Cap. 0
0
0.00
0 0
0
0.00
Reheat Cap. 0
0
0.00
0 0
0
0.00
Supply Duct 0
0
0.00
0 0
0
0.00
Return Duct 0
0
0.00
0 0
0
0.00
Misc. Supply 0
0
0.00
0 0
0
0.00
Misc. Return 0
0
0.00
0 0
0
0.00
Building Totals 126,549 100.00
Y
99,164 314,070
413,233
100.00
ilding R� I
S
Seri`
Net
` /oNet-
Mmma[y;�°il
�.� .Loss.? :L"oss.i �Gai a °. ,,Gain i
��� A, C.Gaih
Gain i
Ventilation 58,753
46.43
59,312 36,267
95,579
23.13
Infiltration 0
0.00
0 0
0
0.00
Pretreated Air 0
0.00
0 0
0
0.00
Zone Loads 67,796
53.57
39,852 275,014
314,866
76.20
Plenum Loads 0
0.00
0 0
0
0.00
Fan & Duct Loads 0
0.00
0 2,788
2,788
0.67
Building Totals 126,549
100.00
99,164 314,070
413,233
100.00
Cheek• Fi ores.
i
Total Building Supply Air (based on a 22°
TD):
11,649 CFM
Total Building Vent. Air (14.16% of Supply):
1,650 CFM
Total Conditioned Air Space:
13,687 Sq.ft
Supply Air Per Unit Area:
0.8511 CFM/Sq.ft
Area Per Cooling Capacity:
397.5 Sq.ft/Ton
Cooling Capacity Per Area:
0.0025 Tons/Sq.ft
Heating Capacity Per Area:
9.25 Btuh/Sq.ft
Total Heating Required With Outside Air:
126,549 Btuh
Total Cooling Required With Outside Air:
34.44 Tons
Z:\ ...\Savanna Club Heat Load.CHV Wednesday, September 18, 2013, 11:53 AM
Chva'c-"IT"I�uIICommercial HVAC€Loads Calculation Program _ r� 4 ", ° Elite Software Development, Inc:
"3 't >r�,
Savanna Grub Commumty;Center
Pa e 3"
Air Handler #1- AHU 1 - Summary Loads
ZnLoss�,�SenlGam
. s:� ,� i.,,!.` ,� d,.,, �s 3` .wt C i�+ :. Np ��'k'v'�'c ,� �,: w � "� f� � �,d a..„ G; � � , 4 :, � � �. � ^` ..�^ "€ .,' ��" '� � 3 x� '' •.'�•
Nod ,ZonePeak Tlrne APeope Ht F CI CFMa
:n h w..,r �9 �r" g},._ S Exh ,} iReq CFMy:Req CFM
�a�.;,Voluce,.�,C�FM/S_ ft��CFM%S.ftb�xa= PWExhAct.C°FM..�:Act�CFIVL;
1 Kitchen 560 2,242 22,731 1,600 Direct Direct
4pm August 8 104 1,038 0 120 120
5,600 0.19 1.85 0 86 192
2 Mechanical Room 124 135 1,542 1,965 0 Direct Direct
9pm August 0 71 90 0 35 35
1,620 0.53 0.66 0 60 17
3 Storage 122 240 2,122 2,610 0 Direct Direct
6pm August 0 98 119 0 62 62
2,880 0.41 0.50 0 82 22
4 Men 120 56 62 749 75 Direct Direct
3pm August 0 3 34 0 12 12
560 0.05 0.61 0 2 6
5 Women 121 56 468 1,020 75 Direct Direct
3pm August 0 22 47 0 12 12
560 0.39 0.83 0 18 9
6 Hall 40 44 535 53 Direct Direct
3pm August 0 2 24 0 9 9
400 0.05 0.61 0 2 5
Zone Peak Totals: 1,087 6,480 29,610 1,803
Total Zones: 6 9 300 1,353 0 250 250
` Unique Zones: 6 11,620 0.28 1.24 0 250 250
v
Z:\ ...\Savanna Club Heat Load.CHV Wednesday, September 18, 2013, 11:53 AM
Cfivac `FuU'Commec�alaHVAC Loads Calculation Programs Elite Software Developme`nt;.lnc.
�Savanna Club CorrtmuriityCenter
f
Pa e.4�
Air Handler01- AHU 1 - Total Load Summar
Air Handler Description: AHU 1 Constant Volume -Proportion
Supply Air Fan: Draw-Thru with program estimated horsepower of
0.13 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.94 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in August.
Outdoor Conditions: Clg: 94' DB, 78° WB, 120.06 grains, Htg: 42' DB
Indoor Conditions: Clg: 75' DB, 50% RH, Htg: 75' DB
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 6,480 Btuh
Infiltration sensible loss: 0 Btuh 0
CFM
Outside Air sensible loss: 8,902 Btuh 250
CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss:
15,382 Btuh
Heating Supply Air: 6,480 / (.999 X 1.08 X 20) = 300
CFM
Winter Vent Outside Air (83.3% of supply) = 250
CFM
Zone space sensible gain: 29,410 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 324 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil:
29,734 Btuh
'Cooling Supply Air: 29,734 / (.999 X 1.1 X 20) = 1,353
CFM
Summer Vent Outside Air (18.5% of supply) = 250
CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 5,220 Btuh 250
CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil:
5,220 Btuh
Total sensible gain on air handling system:
34,954 Btuh
Zone space latent gain: 1,803 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 9,264 Btuh
Total latent gain on air handling system:
11,067 Btuh
Total system sensible and latent gain:
46,022 Btuh
�"IN'F ar P "N"w""""e
..m'c.d
CleckrFi uresxa 4`
Total Air Handler Supply Air (based on a 206 TD): 1,353
CFM
Total Air Handler Vent. Air (18.48% of Supply): 250
CFM
Total Conditioned Air Space: 1,087
Sq.ft
Supply Air Per Unit Area: 1.2445
CFM/Sq.ft
Area Per Cooling Capacity: 283.4
Sq.ft/Ton
Cooling Capacity Per Area: 0.0035
Tons/Sq.ft
Heating Capacity Per Area: 14.15
Btuh/Sq.ft
Total Heating Required With Outside Air: 15,382
Btuh
Total Cooling Required With Outside Air: 3.84
Tons
Z:\ ...\Savanna Club Heat Load.CHV Wednesday, September 18, 2013, 11:53 AM
-,D
$6-Vanda'LlUb Community Center
(COiwnercIaFHVAV---LoadsEfitd.'SO�aidpvelojiment, Inc
Calculation
Page 5
Air Handler #2 - AHU 2 & 3 - Summary Loads
n
Ve cr" I
A'
Clg
'n,
Zone
Exh!Reo.CFM
keq.CFM
FFExh
C' Act.'Q rUji
Abt.CFM,,
, L
7 Banquet Room
5,400
25,702
128,336
18,900
Direct
Direct
4pm August
180
1,191
5,357
0
596
596
70,200
0.22
0.99
0
592
597
. . . . . ....... ..... ........ .........
8 Ice
... ......... .... ............... . ............
25
27
... . . ........... - . ............... .. ...... .
293
... ......
0
. ... ...... .. ..
Direct
. .. .. ......
Direct
3pm August
0
1
12
0
2
2
250
0.05
0.49
0
1
1
9 AN
20
312
442
0
Direct
Direct
9pm August
0
14
18
0
2
2
.... . .. ... ... ...... . . . . . . . . .......
240
. .. .
0.72
. . . ....... . ................... ... I ----
. . .... .... 0.92
0
. ........ . . ...... . ...
7
2
Zone Peak Totals:
5,445
26,042
129,070
18,900
Total Zones: 3
180
1,207
5,388
0
600
600
Unique Zones: 3
70,690
0.22
0.99
0
600
600
Z:\ ... \Savanna Club Heat Load.CHV
Wednesday, September 18, 2013, 11:53 AM
. • '�V -��
Chvac Full Commercial HVAG 16aft Calculatwn'P_ rogram
Elite SoftvVare Development, Inc.
Savanna Club Community Center
1
Pa e 6 r
Air Handler #2 - AHU 2 & 3 - Total Load Summa
Air Handler Description: AHU 2 & 3 Constant Volume - Proportion
Supply Air Fan: Draw-Thru with program estimated horsepower
of
0.51 HP
Fan Input: 0% motor and fan efficiency with 0 in. water
across the fan
Sensible Heat Ratio: 0.87
--- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 4pm in August.
Outdoor Conditions: Clg: 950 DB, 78' WB, 118.35 grains, Htg:
420 DB
Indoor Conditions: Clg: 75' DB, 50% RH, Htg: 750 DB
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 26,042 Btuh
Infiltration sensible loss: 0 Btuh
0
CFM
Outside Air sensible loss: 21,365 Btuh
600
CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss:
47,407 Btuh
Heating Supply Air: 26,042 / (.999 X 1.08 X 20) =
1,207
CFM
Winter Vent Outside Air (49.7% of supply) =
600
CFM
Zone space sensible gain: 128,979 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 1,290 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil:
130,268 Btuh
"Cooling Supply Air: 130,268 / (.999 X 1.1 X 22) =
5,388
CFM
Summer Vent Outside Air (11.1 % of supply) =
600
CFM
• Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 13,188 Btuh
600
CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil:
13,188 Btuh
Total sensible gain on air handling system:
143,456 Btuh
Zone space latent gain: 18,900 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 21,568 Btuh
Total latent gain on air handling system:
40,468 Btuh
Total system sensible and latent gain:
183,924 Btuh
{
-.;-,±ter 7-7
CheckFi ures�x s s
Total Air Handler Supply Air (based on a 22° TD):
5,388
CFM
Total Air Handler Vent. Air (11.14% of Supply):
600
CFM
Total Conditioned Air Space:
5,445
Sq.ft
Supply Air Per Unit Area:
0.9895
CFM/Sq.ft
Area Per Cooling Capacity:
355.3
Sq.ft/Ton
Cooling Capacity Per Area:
0.0028
Tons/Sq.ft
Heating Capacity Per Area:
8.71
Btuh/Sq.ft
Total Heating Required With Outside Air:
47,407
Btuh
Total Cooling Required With Outside Air:
15.33
Tons
Z:\ ...\Savanna Club Heat Load.CHV Wednesday, September 18, 2013, 11:53 AM
Chvac Full:Commerc�al HVAC Loads Calculation Program Elite Software Development, Inc.
Sayanna�Club Comm nity:Center )
Pa a"7
Air Handler #3 - AHU 4 Summary Loads
10
Storage 114
240
2,122
3,761
0
Direct
Direct
9pm August
0
98
162
0
30
30
2,400
0.41
0.67
0
52
24
11
Card Room 112
650
3,971
18,827
2,000
Direct
Direct
4pm August
10
184
810
0
81
81
6,500
0.28
1.25
0
97
122
12
Meeting Room 115
500
2,778
9,754
2,000
Direct
Direct
3pm August
10
129
420
0
62
62
1
5,000
0.26
0.84
0
68
63
...... ... - .... -
13
.... ...... ._ ...... _. _....... ... ...............
DVD Room
........ -
280
_. _ ...... _- _....
308
-_ _._-._ ........-
3,746
_
373
_ _ ..._ ...- _
Direct
-- ... ..
Direct
3pm August
2
14
161
0
35
35
2,800
0.05
0.58
0
7
24
14
Meeting Room 116
260
1,429
4,752
800
Direct
Direct
3pm August
4
66
204
0
32
32
2,600
0.25
0.79
0
35
31
15
Library 110
270
297
3,612
360
Direct
Direct
3pm August
2
14
155
0
34
34
2,700
0.05
0.58
0
7
23
16
Office 118
200
1,189
3,336
267
Direct
Direct
3pm August
1
55
144
0
25
25
2,000
0.28
0.72
0
29
22
17
Entry / Hall
820
4,332
14,084
600
Direct
Direct
1pm August
3
201
606
0
102
102
8,200
0.24
0.74
0
106
91
Zone Peak Totals:
3,220
16,425
61,871
6,400
Total Zones: 8
32
761
2,662
0
400
400
Unique Zones: 8
32,200
0.24
0.83
0
400
400
Z:\ ...\Savanna Club Heat Load.CHV Wednesday, September 18, 2013, 11:53 AM
i �.A - zy
Chvac - Full Commercial HVAC Loads Calculation Program ,
s
Elite Software Development, Inc.
Savanna Club.. -Community Center
Pae8i
Air Handler #3 - AHU 4 - Total Load Summary
Air Handler Description: AHU 4 Constant Volume - Proportion
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.25 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.90
--- This
system occurs
1 time(s) in the building. ---
Air System Peak Time: 4pm in August.
Outdoor Conditions: Clg: 95' DB, 78° WB, 118.35 grains, Htg:
420 DB
Indoor Conditions: Clg: 750 DB, 50% RH, Htg: 750 DB
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside
air.
Zone Space sensible loss: 16,425 Btuh
Infiltration sensible loss: 0 Btuh
0
CFM
Outside Air sensible loss: 14,243 Btuh
400
CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss:
30,668 Btuh
Heating Supply Air: 16,425 / (.999 X 1.08 X 20) =
761
CFM
Winter Vent Outside Air (52.6% of supply) =
400
CFM
Zone space sensible gain: 60,794 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 637 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil:
61,431 Btuh
'Cooling Supply Air: 61,431 / (.999 X 1.1 X 21) =
2,662
CFM
Summer Vent Outside Air (15.0% of supply) =
400
CFM
,Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 8,792 Btuh
400
CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil:
8,792 Btuh
Total sensible gain on air handling system:
70,223 Btuh
Zone space latent gain: 6,400 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 14,379 Btuh
Total latent gain on air handling system:
20,779 Btuh
Total system sensible and latent gain:
91,002 Btuh
Check r Fqdres
Total Air Handler Supply Air (based on a 21 ° TD):
2,662
CFM
Total Air Handler Vent. Air (15.03% of Supply):
400
CFM
Total Conditioned Air Space:
3,220
Sq.ft
Supply Air Per Unit Area:
0.8266
CFM/Sq.ft
Area Per Cooling Capacity:
424.6
Sq.ft/Ton
Cooling Capacity Per Area:
0.0024
Tons/Sq.ft
Heating Capacity Per Area:
9.52
Btuh/Sq.ft
Total Heating Required With Outside Air:
30,668
Btuh
Total Cooling Required With Outside Air:
7.58
Tons
Z:\ ...\Savanna Club Heat Load.CHV Wednesday, September 18, 2013, 11:53 AM
Chvac' Full>COmmercial;HVAC Loads Calculation Program
- Elite'Softvirare Development, lnc.
Savanna Club Community Center
Page 9
Air Handler #4 - AHU 5 - Summary
Loads
ZW
gescription '
Area
4Htg
Loss
Sen 'Gain-,
tat'Gan' !
Htg O A "
CI9.0A.
No,
Zone3Peak Time
;People
Htg CFM
Clg CFM
S:Exh ��
Req CFM
Req:CFM
!�
Volume.
t.°- CFM/S ft .:;.CFM/S
ft
,. ,,... 1N.Exh 'aI
: Act:CF:M
Act:GFM
18
Men 102
476
1,336
6,584
635
Direct
Direct
4pm August
3
62
259
0
45
45
4,760
0.13
0.54
0
28
46
19
Women 125
476
1,336
6,584
635
Direct
Direct
4pm August
3
62
259
0
45
45
4,760
0.13
0.54
0
28
46
20
Lobby
435
3,715
9,503
580
Direct
Direct
1 pm August
3
172
374
0
41
41
4,350
0.40
0.86
0
79
67
21
Janitor
90
680
880
0
Direct
Direct
6pm August
0
31
35
0
9
9
900
0.35
0.39
0
14
6
22
Game Storage
144
1,088
1,407
0
Direct
Direct
6pm August
0
50
55
0
16
16
1,728
0.35
0.39
0
23
10
23
Excersise Room
1,040
3,429
20,693
10,900
Direct
Direct
3pm August
10
159
815
0
99
99
10,400
0.15
0.78
0
73
145
----
24
--- — —
Club Storage 104
- -....-................. ... .---.-........_-.......---
1,274
7,266
11,379
0
Direct
Direct
4pm August
0
337
448
0
145
145
15,288
0.26
0.35
0
154
80
Zone Peak Totals:
3,935
18,849
57,030
12,749
Total Zones: 7
19
873
2,247
0
400
400
Unique Zones: 7
42,186
0.22
0.57
0
400
400
Z:\ ...\Savanna Club Heat Load.CHV Wednesday, September 18, 2013, 11:53 AM
Ch'vac Fdll�Commercial.HVAC Loads Calculation Program',;
k.
Elite Software Development, Inc. '
"x
n
$avanna�Club Community Center
'Rae,10
Air Handler #4 - AHU 5 - Total Load Summar
Air Handler Description: AHU 5 Constant Volume - Proportion
Supply Air Fan: Draw-Thru with program estimated horsepower of
0.21 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.82
--- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 3pm in August.
Outdoor Conditions: Clg: 95' DB, 78' WB, 117.61 grains, Htg:
42' DB
Indoor Conditions: Clg: 75' DB, 50% RH, Htg: 75' DB
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 18,849 Btuh
Infiltration sensible loss: 0 Btuh
0
CFM
Outside Air sensible loss: 14,243 Btuh
400
CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss:
33,093 Btuh
Heating Supply Air: 18,849 / (.999 X 1.08 X 20) =
873
CFM
Winter Vent Outside Air (45.8% of supply) =
400
CFM
Zone space sensible gain: 56,252 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 538 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil:
56,790 Btuh
'Cooling Supply Air: 56,790 / (.999 X 1.1 X 23) =
2,247
CFM
Summer Vent Outside Air (17.8% of supply) =
400
CFM
. Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 8,792 Btuh
400
CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil:
8,792 Btuh
Total sensible gain on air handling system:
65,582 Btuh
Zone space latent gain: 12,749 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 14,379 Btuh
Total latent gain on air handling system:
27,128 Btuh
Total system sensible and latent gain:
92,710 Btuh
Total Air Handler Supply Air (based on a 23' TD):
2,247
CFM
Total Air Handler Vent. Air (17.80% of Supply):
400
CFM
Total Conditioned Air Space:
3,935
Sq.ft
Supply Air Per Unit Area:
0.5709
CFM/Sq.ft
Area Per Cooling Capacity:
509.3
Sq.ft/Ton
Cooling Capacity Per Area:
0.0020
Tons/Sq.ft
Heating Capacity Per Area:
8.41
Btuh/Sq.ft
Total Heating Required With Outside Air:
33,093
Btuh
Total Cooling Required With Outside Air:
7.73
Tons
Z:\ ...\Savanna Club Heat Load.CHV Wednesday, September 18, 2013, 11:53 AM