HomeMy WebLinkAboutFire Prevention Plan ReviewST LUCIE COUNTY FIRE DISTRICT
BUREAU OF FIRE PREVENTION
PLAN REVIEW
2400 Rhode Island Avenue
Ft Pierce, FL 34950
( Y. ew Construction ( )Tenant Improvement
Jurisdiction:
SLC
Occupancy:
Savanna Club Garage # 1
Address:
1800 Savanna Club Blvd.
Contractor
Jerjo Inc.
Contractor's Address:
3535 windsor Place
State:
Florida
Arch itect/Engineer:
Wayne Berenbaum
Building Owner:
Occupancy Type:
Storage
Gross sq ft:
4,270
Occupant Load:
Construction Type:
Telephone: 561-462-2312
FAX: 561-462-2323
( )Addition ( )Renovation/alterations ( )Shell Only
F.P.B.:
B-01-296
Building Dept:
21090656
Number of stories:
1
Phone #
561-994-3005
City:
Boca Raton
Zip Code:
33496
Phone #
561-470-8457
Review Date:
11/28/2001
Automatic sprinklers:
Net sq ft:
Based On:
SBCCI Type:
V unp
NOTE
1. All revisions must be in compliance before the final inspection.
2. The Fire Marshal requires 24 hour notice on all inspections.
3. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
4. Permit fees are required to be paid in full prior to any inspections.
5. Failed inspections require payment of fee prior to rescheduling of further inspections.
6. A copy of the required revision/s have been transmitted to the Architect () Contractor ( ).
7. Penetrations through rated assemblies shall be of proper UL design.
8. 'UL design criteria shall be submitted with the construction plans.
REVISIONS REQUIRED
ACCESS BOX IS REQUIRED ( ) ACCESS KEY SWITCH REQUIRED ( )
1. There is a descrepancy on the wall type legend on sheet A1.5 and sheet S3.1. Sheet A1.5 indicates
"W1" as a non -rated wall. Sheet S3.1 "W1" indicates a 1-hr rated wall.
A 1-hr separation wall between individual tenants shall be applied. The wall shall be constructed from the
floor to the underside of the roof deck and sealed properly at the termination point or the tenant
separation walls shall terminate at a 1-hr. rated ceiling with no unprotected openings.
2. Provide one 2A-10B:C rated fire extinguisher -on each elevation. Protect from the elements.
3. Draftstopping is required at intervals not to exceed 3000 sq. ft.
K
Reviewed by: �� Date: 11/28/2001