HomeMy WebLinkAboutbuilding plans (2)HC GENERAL NOTES 1. HOLES: Holes are by others unless otherwise indicated. Fields -cut holes thru the units may not cut prestressed strands without prior written approval from Pre -Cast Specialties Inc. Engineering Department. 2. VERTICAL RISERS: The general contractor shall insure that vertical risers, etc., do not interfere with placement of Hollow Core units. 3. HANDLING: Hollow Core units may not be lifted by inserting hooks, bars or other lifting devices into the voids, and may not be inverted. Hallow Core units must be lifted l'-O" from the end only. 4. DIMENSIONS AND DETAILS: The customer and/or his agent will be responsible for all dimension and details taken from the contract drawings and shown hereon. PCSI will not be responsible for any changes made after approval of these drawings. 5. ROOF UNITS: Slight vertical movement of precast concrete roof units is anticipated but can be reduced by proper insulation. PCSI recommends a physical separation of the plaster at the intersection of non -bearing walls and ceilings. 6. CAMBER: Camber is an inherent condition in all prestressed flexural members and the general contractor shall make allowances for some. If additional thickness of topping is needed for leveling purposes, contact our engineering department for approval. Highest estimated camber at time of erection: 3/4 7. CONCRETE: Strength of concrete shall be a minimum of 6000 psi at 28 days. Structural topping where specified shall be of 4000 psi 28 day strength concrete, reinforced with 6 x 6 - 10/10 welded wire mesh. or fiber reinforced concrete. The thickness of such topping shall be a minimum of 2 inches at the center of the span and may vary due to camber or deflection from the center to the supports as required for a level surface. The topping pour and all materials required some are by others. 8. GROUTING: All joints between slabs shall be fully packed with a pourable grout consisting of 1 part Portland Cement to 3 parts clean sand. The grouted deck shall be allowed to cure before removing any leveling shores, cutting any holes or applying any further construction loads. THE OPERATION OF GROUTING THE HOLLOW CORE SLABS KEYWAYS MUST BE PERFORMED REGARDLESS OF ANY TOPPING BEING APPLIED TO HOLLOW CORE SLABS. 9. PRESTRESSED STRANDS: Strands to be 7 wire, 7/16" dia., tensioned to 21700 lbs. each for 6" planks. (7 wire, 1/2" dia., tensioned to 28900 lbs. for 8" & 10" planks). The number of strands are indicated by the first two digits following the letter HC or US in the designation. 10. TOLERANCES: Width Full Width Units ± 1/4" Length ± 1" Saw Cut Units ± 1/2" Thickness ± 1/4" Split Units ± 1 1/2" Deviation From Square ± 1" 11. DESIGN LOADS: 2nd. FLOOR: 6" U.S. W/100 P.S.F. (L.L.= 80 P.S.F. + D.L.= 20 P.S.F.) & ± 3" `.,LOPPED TOPPING (BALCONY) 8" U.S. W/65 P.S.F. (L.L.= 40 P.S.F. + D.L.= 25 P.S.F.) & ± 3" i OPPING 3rd. FLOOR: 6" U.S. W/100 P.S.F. (L.L.= 80 P.S.F. + D.L.= 20 P.S.F.) & ± 3" c)LOPPED TOPPING (BALCONY) fill U.S. W/65 P.S.F. (L.L.= 40 P.S.F. + D.L.= 25 P.S.F.) & ± 5" TOPPING 8" U.S. W/65 F.S.F. (L.L.= 40 P.S.F. + D.L.= 25 P.S.F.) & ± 3" TOPPING 4th. FLOOR: 8" U.S. W/100 P.S.F. (L.L.= 80 P.S.F. + D.L.= 20 P.S.F.) & ± 3 1/4 " SLOPPED TOPPING (BALCONY) 8" U.S. W/65 P.S.F. (L.L.= 40 P.S.F. + D.L.= 25 P.S.F.) & ± 6 1/4 91 TOPPING 12. Minor cracking (hairline and tension) will occur in precast/prestressed concrete created by shrinkage of concrete and temporary loads during production, transportation or erection without being structurally detrimental to the units. These cracks have no structural significance and does not affect durability of these units. Cracking should not be cause for rejection, when properly repaired. 13. FIRE RESISTANCE: All Precast/Prestressed concrete products shown on these shop drawings have a maximum fire resistance of one (1) hour, unless indicated otherwise 14. All Precast/Arestressed concrete products shown on these shop drawings are structural quality, any rework/firtishing necessary for final architectural appearance is by others. 15. TIE BEAMS: Tie 'beams must be true, level and free of knots. If precast perimeter beams or knockout blocks are used, they must be COMPLETELY FILLED. 16. ACCESS: General Contractor agrees to provide and maintain for the duration of precast installation, stabilized access, acceptable to PCSI so trucks and cranes can move under their own power to various points of erection with no overhead obstruction. Customer accepts all liability for deliveries beyond the curb line, including all underground utilities and cost for loss of time. PCSI reserves the right to stop deliveries and/or erection in the event such conditions are not provided. A THIS SYMBOL INDICATES SAWCUT OR SPLIT EDGE OF HOLLOW CORE PLANKS, - WHERE STRUCTURAL TOPPING IS TO BE APPLIED, PLANKS ARE TO BE THOROUGHLY CLEANED AND PREPARED BY G.C. PRIOR TO TOPPING TO INSURE ADEQUATE BOND STRENGTH. - TIE BEAMS MUST BE TRUE, LEVEL AND FREE OF KNOTS. IF PRECAST PERIMETER BEAMS OR KNOCKOUT BLOCKS ARE USED, THEY MUST BE COMPLETELY FILLED. - ALL NON BEARING WALLS SHOULD BE HELD DOWN 1" UNTIL SLABS ARE SET AND GROUTED AND ALL DEAD LOADS ARE APPLIED TO THE SLABS BEFORE DRY PACKING THE GAP BETWEEN THE NON BEARING WALL AND THE SLAB. - Dowels must be placed in the beams in a manner to allow the proper bearing of our product as detailed in our different sections. Non compliance with this item may delay the erection of these product with additional cost to the General Contractor. - SAFETY REQUIREMENTS: ALL SAFETY RAILING AND HOLE PROTECTION VIA SECURED PLYWOOD ARE BY G.C. IMMEDIATELY AFTER PRECAST/ PRESTRESSED MATERIALS ARE INSTALLED. GROUTING WILL NOT TAKE PLACE UNTIL ALL HOLES & RAILING ARE IN PLACE BY G.C. MINIMUM BEARING: 2" BEARING IS STRUCTURALLY ACCEPTABLE, GENERAL CONTRACTOR MUST ADD 2 #5 REBAR 03'-0" LONG WITH 6" HOOK AT EDGE POUR PER SLAB. BEARING LESS THAN 2" MUST BE APPROVED BY PCSI ENGINEER. - SPLIT SLABS (NARROW DOWN): DUE TO MANUFACTURING & CONSTRUCTION TOLERANCES THERE MAY BE A GAPS BETWEEN SLABS AND OR WALLS. FIELD SPLIT SLABS WILL HAVE A ROUGH EDGE GAP, ALL GAPS SHALL BE FORMED AND POURED BY CONTRACTOR. CUTOUTS/NOTCHOUTS: TOLERANCE GAPS MAY OCCUR AROUND COLUMNS, BEAMS REBAR, PIPES, ETC. THESE GAPS SHALL. BE FORMED AND POURED BY CONTRACTOR. loll 11A I' I� 4 -O I. 5'-5" I� 0 5 -5" 4'-2" P. 8 ALLOWABLE LOADS with no topping I topping Rev. 6 1/4"TOPP TOTAL 3" bN 19 0 ED-ATE HOLLOW CORE (US) SCHEDULE ALLOWABLE LOA[S Mark Unit No. Req. 4th. FL L(inches) total length W(inches Length Width Remarks with topping no topping 30 8" US-068 2 325 650 48 27' 1" 4' 0" 100 30A 8" US-068 1 325 325 32.5 27' 1" 2' 81/2" SAWCUT 31 8" US-048 1 270.5 270.5 48 22' 61/2" 4' 0" 32A $" US-038 11 52.5 1 52.5 1 34.5 1 4' 4 1/2" 2' 101/2"1 SAWCUT 328 8" US-038 1 1 1 52.5 1 52.5 1 27.5 1 4' 41/2" 1 2' 31/2" 1 SAWCUT 33 1 8" US-068 33A 8" US-068 34 8" US-048 34A 8" US-048 34B 8" US-048 34C 8" US-048 35 8" US-038 36 8" US-038 3 325 975 48 27' 1" 4' 0" 1 325 325 25.5 27' 1" 2' 11/2" SAWCUT 1 271 271 48 22' 7" 4' 0" 1 271 271 48 22' 7" 410" W/C.O. 1 271 271 48 22' 7" 4' 0" W/C.O. 1 271 271 26 22' 7" 2' 2" SAWCUT 1 4&5 48.5 48 4' 1/2" 4' O„ 1 157 157 48 13' 1" 4' 0" 16 3940 328' 4" 4'-02., 5,-5„ 5'-5" 4'-2" .I 11D 4'-02" 5,-5„ 00 I 34B DESCRIPTION - REVISIONS - ENGR. - CHECKED BY DRAWN J.C. DATE SEAL DATE DATE 5/16/17 TOTAL HOLLOW CORE (US) SCHEDULE Rei Mark Unit No. Req. 2nd. FL L(inches) t le Ital gth W(Iinches Length Width 1A 6" US-037 1 86.5 1115.5 48 7' 2 1/2" 4' 0" 1B 6" US-037 1 86.5 16.5 43 7' 2 1/2" 3' 7" 1C g" US-037 1 86.5 16.5 48 7' 2 1/2" 4' 0" 1D 6" US-037 1 86.5 E 6.5 1 34 7' 21/2" 1 2' 10" 1E 6" US-037 1 86.5 E 6.5 48 7' 2 1/2" 4' 0" 1F 6" US-037 1 86.5 16.5 44 7' 2 1/2" 3' 8" 1G 6" US-037 1 86.5 6.5 48 7' 2 1/2" 4' 0" 10 8" US-048 3 325 975 48 27' 1" 4' 0" 10A 8",US-048 1 325 325 35.5 27' 1" 2' 111/2" 10B 8" US-048 1 325 325 27.5 27' 1" 2' 3 1/2" 10C 8" US-048 1 325 325 25.5 27' 1" 2' 1 1/2" 10D 8" US-048 1 325 325 42 27' 1" 3' 6" 11A 8" US-038 1 271 271 1 48 22' 7" 4' 0" 11B 8" US-038 1 271 g71 48 22' 7" 4' 0" 11C 8" US-038 1 271 71 48 22' 7" 4' 0" 11D 8" US-038 1 271 71 48 22' 7" 4' 0" 11E 8" US-038 1 271 71 32.5 22' 7" 1 2' 8 1/2" 12 8" US-038 1 49 49 48 4' 1" 4' 0" 13 8" US-038 1 157 157 48 13' 1" 4' 0" 14A 8" US-038 1 52.5 52.5 32.5 4' 4 1/2" 2' 8 1/2" 14B 8" US-038 1 52.5 S2.5 28.5 4' 4 1/2" 2' 4 1/2" 15 8" US-038 I 1 j 231 231 48 19' 3" 1 4' 0" 24 1 j 345 ALLOWABLE LOADS HOLLOW CORE (US) SCHEDULE with topping no topping Rev. Mark Unit No. Req 3rd. FL L(inches) total length W(inches Len;hJ Wii 100 1 6" US-037 2 86.5 173 48 7' 2 1/2" 4' 1D 6" US-037 1 86.5 86.5 34 7' 21/2" 2' 1 I 5"TOPP 2 6" US-037 1 86.5 86.5 1 48 7' 21/2" 4' 2A 6" US-037 1 86.5 86.5 43 7' 21/2" 3' 65 10 8" US-048 3 325 975 48 27' 1" 4' 10A 8" US-048 1 325 325 35.5 27' 1" 2' 11 10B 8" US-048 1 325 325 27.5 27' 1" 2' 3 10C 8" US-048 1 325 325 25.5 27' 1" 2' 1 10D 8" US-048 1 325 325 42 27' 1" 3' 11 8" US-038 2 271 542 48 22' 7" 4' 11A 8" US-038 1 271 271 48 22' 7" 4' 11B 8" US-038 1 271 271 48 22' 7", 4' 11E 8" US-038 1 271 271 32.5 22' 7" 2' 8 12 8" US-038 1 49 49 48 4' 1" 4' 13 8" US-038 1 157 157 48 13' 1" 4' 14A 8" US-038 1 52.5 52.5 32.5 4' 41/2" 2' 8 14B 8" US-038 1 52.5 52.5 32.5 4' 41/2" 2' 8 15 8" US-038 1 231 231 48 19' 3" 4' 16 8" US-038 1 94.5 94.5 48 7' 10 1/2" 4' 16A 8" US-038 1 94.5 94.5 41 7' 10 1/2" 3' TOTAL 1 1 24 4534 377' 10" MISCELLANEOUS MATERIALS SCHEDULE REV. MK. NO. MATERIAL No Required REMARKS 2nd. 3rd. I 4th. M-A 1/801xY07" KOROLATH STRIPS 48 48 32 T^^<-, "EDWORKTHESE PIM's pN9 A.! REOUIfic;L dY ?III.') INOPICTnP?i+ THAT MAY bs N4nRI%aAI`1Y IN OADEn TO COMPLY Ofhi 1111 A'PPLICA31.E 00DAL. APPROVED DRAWINGS 06 26 17 CONCEALED FASTENERS OR iTTACHIN ARE THE RESPONSIBILI OF THE CONTRACTOR OF R1 CORD PROJECT: KOTHAKOTA RESIDENCE 5116 WATERSONG WAY , FT. PIERCE CONTR.: HARRIS HOMES TEL.: (772) 828-8288 RECEI`."D JUL 1 ' 2017 1' pR N-6 iti IIXT1oN WILL PRE-CAST/PRESTRE'. JOHN P McGREW FLORIDA P.E. NO: 2( APPROVED DATE SHEET NO. 6/22/17 1.0 S P E C I A, Pre -Cast Spec 380 N.E. 48th. St. Pompa HONE: (954) 781-4040 t-1oa-dtll 27'-10' 00 I no .:" ;:' C 7'-4' El 1 10'-6' 7'-4' 8 3 f� 9 1B 3 1F 1A a I 1C o 1D 1E E� I'M/y V~I/M (U mil 1* 1 — 7 LAP — — I I 10A � I 3 I A, 2'-3j' 10B I I � I I I I i I 10 I I I I 1 I 3'-9j, 3'-5R' " 4'-8" J311 12'-6" If W12 50 I 11A I II 3 I �----I I I I13 l x II II 12 II II a 13 I I II II II � I I I I 2II L----- I 3 I I 11 B �" I I N I 1 1 5 _1� 4'-2' uti-y M` 12 8" 1 8 II 11C I LO cu 14A 11 3 t t D I I I 2'-8j, 174 r5_ 3 1 I 1 I 14B 1 W12x5o 6 O �. 3 .2'-1�' 10D I I L — — — — — — — .3'-6" 15 � I I i--------- 2' LAP--� 3' 3 7'-2` I /I NORTN SECOND FLOOR FRAMING PLAN SCALE: 1 /4"-1 ' -0" 8 ° U.S. W/65 P.S.F. 2& t 3" TOPPING 6° U.S. W/100 P.S.F. & t 3" SLOPPED TOPPING O� A (1 I r 0 a' 7'-4' 27'-10' 10'-6' 7' _r' + + +7/-/ X,4�Z)l i 3 5 1`A I + 2A TE 1 3D +04F CL' II I 15 K2'-ll ' 1 1 1' LAP 7 — — — — — 3 t0A 3 I 1 2 -3j' 10B I n I I I I I 1 I 3 I 10 I I 1 1 e• 12'-6' 8' W12x50 E4� 1 I 3 II I— — — — ­ 1 I 1 �7 I x III II 3 12 I I I I'T 1f10 0 I Lo 1 II II � L I 2 3 I I I I II I I II I 11B � 1 I I I I III I II I I X 14A I 1 3 5 11 2'-aj' 3 1 I 14B I W12x50 I I I toD I 3'-6- - — — — — — — — — 2' LAP--H NORM T H I 7'-2" 8' RD FLOOR FRAMING PLAN 8 ° U.S. W/65 P.S.F. 2& f 3" TOPPING 6" U.S. W/100 P.S.F. & t 3" SLOPED TOPPING 0 - I _ DATE DESCRIPTION BY —REVISIONS— SCALE: 1/4"=l'-0 ++++++ 6" U.S. W/65 P.S.F. + & f 5" TOPPING ENGR. DATE CHECKED - DATE DRAWN J. C. DATE 5/16/17 SEAL PROJECT: KOTHAKOTA RESIDENCE 5116 WATERSONG WAY, FORT PIERCE CONTR.: HARRIS HOMES TEL.: (772) 828-8288 06 26 17 JOHN P. MCGRI FLORIDA P.E. Ni APPROVED DATIS HEET NO, WO 6/22/17 2.0 1 P i A L < Pre -Cast Specialti 1380 N.E. 48th. St, Pompano Bead PHONE, (954) 761-4040 FAX, 9' 27'-10' 0 0 M ID i 0 8" U.S. W/100 P.S.F. y0l& f 6 1/4" TOPPING ++++++ 8" U.S. W/100 P.S.F. +++ & t 3 1/4" TO 2" SLOPED TOPPING 8' 26'-6' 13 3 ram— —F -:F-- I+ + + + + + 30A + + + + + + 1 + + + + + + + + + + + + VTI + + + + + 30 + + + + + 1+ + + + W o + + + + + + + J I+ + + + o + + + + + + + 1 I + + + + + + + + + + + N 1+ + W+ + + + + + + + W + + + I I+ + M + + + + + +17771'7Z7 +M + + 1 — Il I -711 1 I I 33 I 33A 2 -1' 3'- 16' ' 33 1 W12X5o I 1 34A r 1I� X I I + + + 3 r 35 I I I I I 36 3" ITEP + + + + 13 I 34B I lj" O.A. SLOPE + � I I I 1 22" 34C I + + + 1 I I I I I 34 + + + x — — — — - - /1 + + + 1 32A Ian,— I+ I W 1 2'-10 " 1te �- + _0 + + M + + + 31 + + + + + + + + + + I + 1 I+ 32B 2'-3j' +I 1 + 2" O.A. SLOPE + + + 2" 0.A. SLOPE I I I I I L-------� I I I I I I I I I I — — — — — — — — ----------� I I 7'-2' 18'-8' N —A co M NORTH FOURTH FLOOR FRAMING PLAN SCALE: 1/4"=1'-0" Z� - - ESCPTION - DATE DRIBY — REVISIONS ' CDX SHEATHING ROOF ON TOP OF H.C, LOAD=500 #/L.F. " CDX SHEATHING ROOF ON TOP OF H.C, LOAD=500 #/L.F, ENGR. DATE CHECKED DATE DRAW!:::::::54/16/17 J.C. APPROVED DRAWINGS 06 26 17 PROJECT: KOTHAKOTA RESIDENCE 5116 WATERSONG WAY, FORT PIERCE CONTR.: HARRIS HOMES TEL.: (772) 828-8288 PRE-CAST/PRESTF JOHN P. McGRE FLORIDA P.E. N( APPROVED DATrSHE—ET W04P/2.1 PRE Pre -Cast Speci t �y 1380 N.E. 48th, St. Pompano BeacY PHONE; (954) 781-4040 FAXi 9° TOPPING f G.C.) (2)#5 CONT. TYPICAL AROUND PERIMETER (BY G.C.) • a #4 BAR (6'k18")---�U.S. GROUTED IN CORE ONE PER PLANK 3 1 2" 33 4" BRG. (BY G.C.) DOUBLE BOND BEAM OR POURED CONC. TIE BEAM (BY G.C.) 1 SECTION 3 SCALE: 3/4" = 1'-0" SLOPPED TO PIN (BY G.C. #4 BAR (6"x24") CAST IN TOPPING 0 48" O.C.(BY G.C.) f3" TOPPIN (BY G.C. 8" U.S. 6" U.S. ° 3" t 1 2" BRG LAP VARIES e' POURED cON •G STEPPED #4 BAR (6"x18") ) GROUTED IN CORE ONE PER PLANK u - (BY G.C.) SECTION 3 SCALE: 3/4" ". ',1' " TOPPING f G.C.) CONT. TYPOICAL �2)#5 BY G.G.)1/2"Ox6" STUDS WELDED TO STEE8" U.S. BEAM 0 48" O.C(BY G.C.)t 3 4" BRG. #4 BAR (6"x1 GROUTED IN CORE (BY G.C.) ONE PER PLANK (BY G.C.) 2 SECTION 3 SCALE: 3/4" = 1'-O" SLOPPED TO PING (BY G.C. (2)#5 CONT. TYPICAL AROUND PERIMETER — (BY G.C.) •. a a a #4 BAR (6"x18")-/ '\-6" U.S. GROUTED IN CORE ONE PER PLANK 3 1 2"f 3 4" BRG. (BY G.C.) �a? DOUBLE BOND BEAM OR POURED CONC. TIE BEAM (BY G.C.) a SECTION 3 SCALE: 3/4" = 1'-0" 12 SECTION 3 SCALE: 3/4" = 1'-0" #4 BAR (6%24") CAST IN TOPPING 0 48" O.C.(BY G.C.) (2)#5 CONT. TYPICAL AROUND PERIMETER (BY G.C.) OPPING Y G.C.) \-8" U.S. :: C, �.. - LAP VARIES DOUBLE BOND BEAM OR POURED CONC. TIE BEAM (BY G.C.) 3 SECTION 3 SCALE: 3/4" = 1'-0" SLOPPED TOPPING (BY G.C.) 00 00 6" U.S. LAP VARIES LAP VARIES CONC. BEAM W/REINF. (by others) 9 SECTION 3 SCALE: 3/4" = 1'-0" #4 BAR (6"x24") CAST IN TOPPING 0 48" O.C.(BY G.C.) SLOPPED TOPPING (BY G.C.) (2)#5 CONT. TYPICAL00 - ¢, - - e AROUND PERIMETER (BY G.C.) \-8" U.S. LAP VARIES DOUBLE BOND BEAM OR POURED CONC. TIE BEAM (BY G.C.) 13 SECTION 3 SCALE: 3/4" = 1'—O" #4 BAR (6"x24") CAST IN TOPPING t3" TOPPIN 0 48" O.C.(BY G.C.) (BY G.C.) �BY#G.C�NT. TYPICAL n • O� 1 /2"0x6" STUDS WELDED TO STEEL 8" U.S. BEAM 0 48" O.C. (BY G.C.) LAP VARIES W12x50 (BY G.C.) 4 SECTION 3 SCALE: 3/4" = 1'-O" AROOPERIMET TYPICAL R AROUND (BY G.C.) 'ED TOPPING IY G.C.) i" U.S. LIES 10 SECTION 3 SCALE: 3/4 1'-0" SLOPPED TOPPING (BY G.C.) 8" U,S._j 8" U.S. 3"t 1 2" BR 3"t 1 2" BRG. 1/2"Ox6" STUDS WELDED TO W12x50 BEAM 0 2'-0" O.C. AND (BY G.C.) #4 BAR HORIZONTAL IN CORE, ONE PER PLANK. (BY G.C.) 14 SECTION 3 SCALE: 3/4" = 1'-0" DESCRIPTION — REVISIONS — ENGR. JCHECKED BYDRAWN J.C. t3" TOPPIN (BY G.C.� 8" U.S J 8" U.S. '2" BR I �� 3" t 1 /2" BRG. G� JL / 1/2%6" STUDS WELDED TO W12x50 BEAM 0 2'-0" O.C. AND (BY G.C.) #4 BAR HORIZONTAL IN CORE, ONE PER PLANK. (BY G.C.) 5 SECTION 3 SCALE: 3/4" = 1'-O" DATE SEAL DATE DATE 5/16/17 t5" TOPPING (BY G.C.) 6" U.S. —,7.— 8" U.S.; LAP VARIES-/ #4 BAR (6"x24") CAST IN TOPPING 0 48" O.C.(BY G.C.) t3 TOPPIN (BY G.C-� \-8" U.S, b . ' ° LAP VARIES a. POURED CONC. #4 BAR (6'k18") ( TIE BEAM (BY G.C.) GROUTED IN CORE ONE PER PLANK (BY G.C.) 11 SECTION 3 SCALE: 3/4" = 1'-0" SLOPPED TOPPIN( (BY G.C.) (2)#5 CONT. TYPICAL _ AROUND PERIMETER (BY G.C.) t3" TOPPIN (BY G.C.) p00 � 8" U.S. LAP VARIES W12x5O (BY G.C.) SECTION SCALE: 3/4" = 1'-0" #4 BAR \�8" U.S. GROUTED IN CORE ONE PER PLANK 3 1 2"t 3/4" BRI. (BY G.C.) DOUBLE BOND BEAM OR POURED CONC. TIE BEAM (BY G.C.) 15 SECTION 3 SCALE: 3/4" = 1'-0" (APPROVED DRAWINGS 06 26 1'7 PROJECT: KOTHAKOTA RESIDENCE 5116 WATERSONG WAY , FT. PIERCE CONTR.: HARRIS HOMES TEL (772) 828-8288 PRE-CAST/PRESTRES JOHN P McGREW P. FLORIDA P.E. NO: 266 APPROVED DATE SHEET NO. 8/22/17 3.0 PR Pre —Cast Specialtie. 1380 N.E. 48th. St. Pompano Bec PHONE: (954) 781-4040 FAX: