HomeMy WebLinkAboutplanU'
Ll
0
D
/ SPRINKLER RISER
(SEE DETAIL THIS SHT.)
SPRINKLER PIPING PLAN 1st. R.
SCALE: 3/16" = 11-011
GENERALNOTES
1.) ALL WORK TO CONFORM TO NFPA-13R AND LOCAL AUTHORITIES HAVING JURISDICTION.
2.) SPRINKLER RISER PIPING TO BE $CH. 10 WITH GROOVED ENDS AND GROOVED
FITTINGS.
3.) ALL CONCEALED PIPING FEEDING UNITS SHALL BE CPVC WITH SLIP FITTINS AND
RESIDENTIAL SPRINKLERS.
4.) ALLAREAS SHALL BE SPRINKLED:
EXCEPTION-1.SPRINKLERS SHALL NOT BE REQUIRED IN BATHROOMS UNDER 55sq.ft.
EXCEPTION•2.SPRINKLERS SHALL NOT BE REQUIRED IN CLO., LINEN CLO., OR PANTRIES
WITHIN THE DWELLING UNIT WHERE THE AREA DOES NOT EXCEED 24sq.ft.
EXCEPTION-3.SPRINKLERS SHALL NOT BE REQUIRED INANY GARAGES, PORCHES,
BALCONIES, CORR. AND OR STAIRS THAT ARE OPEN AND ATTACHED.
EXCEPTION-4.SPRINKLERS SHALL NOT BE REQUIRED INATTICS OR CRAWL SPACES
THAT ARE NOT USED OR INTENDED FOR LIVING PURPOSES.
5.) HANGERS TO BE LISTED AND APPROVED TWO HOLE STRAPS FOR CPVC PIPING
SPRINKLER PIPING PLAN 2nd. FI.
SCALE: 3/16" = 1'-01I
GMIGE
1-6WTERFLOW PIARM GINITCII
V
GRAN VALVE
1 INCH FIGURE 515 RISER MANIFOLD
REV. # I DATE I DESCRIPTION
7 I FIRE SPRINKLER PIPING PLAN AND DETAILS
SPRINKLER PIPING PLAN 3rd. R.
SCALE: 3116" = T-0"
f m I OFIRE
RT.1I11%ENPT
R
}IW
(0241
ME TT (IDRO�) O
O °OHP
022I5I Im)
SUTETE
PPLY I 2-M-
PORT,I'NPT 00,9-)
MODEL RSV-1 I-TYCO RESMENTIAL DOMESM SHUTOFF VALVE
91TIA111111
JOB NUMBER:
DRAWN BY:
on Mom
S127C17
Shelly Schuyler
I— SCALE: 3/16" = 1'-13"
SPRINKLER PIPING PLAN 4TH. FI.
SCALE: 3/16" = 91-011
Kothakota Residence
(At Watersong)
LOT 5 Watersong way
Fort Pierce,FL 34949
CONCRETE DECK
HILTI PIN
CPVC PIPING
PIPE STRAP
PER
IPE MANUFACTURES SPEC
TWO HOLE PIPE
STRAP
REMOTE AREA
REMOTEAREANAME
Residential IS
FPA-13D
DENSITY
0.050gpm/
for (2 HEAD DESIGN)
TOTAL HEADS FLOWING
2
K-FACTOR
4.9
SYSTEM FLOW DEMAND
26.36
SYSTEM PRESSURE DEMAND
56.236
BASE of RISER - GPM
26.35
BASE of RISER - PSI
56.236
SAFETY MARGIN- PSI
+6.764 (13.
6)
• 44 — TYCO 1/2", CI
SERIIES LFII
RECEk':D AUG 10 2017
PIPING TO EXISTING
NEW CEILING
I?vz-oo1%
ST. LUCTE COUNTY B11,J i
RFVIF.WED FOR Q
INSPECTION WILL
.ED PENDENT SPRINKLER
PENDENT, K=4.2, 155 DEGREE
TgESE PLAN'
ARESUBJEC
REQUIRED
MAY BE NEC
COMPLY Wv
CONCEALED FASTENEF
ARETHERESPON
COVIACTOF
FIRE
SI