1. THESE PLANS PERTAIN ONLY TO THE STRUGIURt, iNvLUUrrvU MmIll m1W I- - - -
BASE RAIL ANCHORAGE. OTHER DESIGN ISSUES, INCLUDING BUT NOT LIMITED TO PLUMBING, ELECTRICAL, INGRESS/EGRESS, PROPERTY
SET -BACKS, FINISH FLOOR ELEVATION AND SLOPE, OR OTHER LOCAL ZONING REQUIREMENTS ARE THE RESPONSIBILITY OF OTHERS.
2. THIS STRUCTURE IS DESIGNED AS A NON -HABITABLE UTILITY/STORAGE BUILDING (RISK CATEGORY 1) CAPABLE OF SUPPORTING DEAD
LOAD OF THE STRUCTURE AND APPLICABLE LIVE AND WIND LOADS. IMPROVEMENTS NOT SPECIFICALLY ADDRESSED HEREIN, INCLUDING
DOORS, WINDOWS, OR OTHER COMPONENTS NOT LISTED IN THE FBC APPROVED PRODUCTS LIST, AND NOT PROVIDED AND INSTALLED
BY CARPORTS ANYWHERE, INC., WHICH EXERT ADDITIONAL LOADS ON THE STRUCTURE SHALL BE AT THE OWNER'S RISK. CARPORTS
ANYWHERE NOR THE ENGINEERING DESIGN SHALL NOT BE RESPONSIBLE FOR STRUCTURAL DAMAGE OR FAILURE DUE TO THE
APPLICATION OF ADDITIONAL LOADS.
3. THIS BUILDING IS EXEMPT FROM THE FBC ENERGY CONSERVATION CODE PER SECTION C101.4.2.
4. ALL STEEL TUBING SHALL BE 50 KSI STEEL AND MEETS/EXCEEDS GALVANIZATION PER ASTM A1003/A1003M-15.
5. PLUMBING, ELECTRICAL, INGRESS/EGRESS, PROPERTY SET -BACKS, AND/OR OTHER LOCAL CODE REQUIREMENTS ARE THE
RESPONSIBILITY OF THE OWNER.
6. ROOF AND WALL SHEATHING SECURED WITH #12-140" SELF -DRILLING SCREWS WITH SEAL WASHERS ® 6" O.C. MAX.
7. FIELD FRAMING CONNECTIONS SECURED WITH #12-14x3/4" SELF -DRILLING SCREWS.
8. ALL SHOP FRAMING CONNECTIONS ARE TO BE WELDED. NO WELDING ONSITE. ALL WELDING DONE IN SHOP BY A CERTIFIED WELDER.
9. CONCRETE EXPANSIONS ANCHORS ARE TO BE MINIMUM 1/2" DIAMETER & 2,50OLB TENSILE STRENGTH.
10. 12 OR 14GA. FRAMING IS 2.5"x2.5" TUBE STEEL. NIPPLES ARE 2.25"x2.25" TUBE STEEL.
R318 ANDR T
181 OFATED 0COVERED THE 217FLORIDA BUILDING I CODE,06TH EDITIONT PER SECTION
CONCRETE:
-MINIMUM 2.500 PSI COMPRESSIVE STRENGTH AT 28 DAYS
-ALL OPEN AREAS
OF CONCWAY RETE
ROM UT STRU
CTURE
THE PROPOSED STRUCTURE SHALL BE
DESIGNED TO
REINFORCING STEEL (REBAR) REQUIREMENTS:
-MINIMUM GRADE 40 STEEL
-REBAR MAY BE BENT IN SHOP OR FIELD PROVIDED:
-THE REBAR IS BENT COLD
-THE DIAMETER OF THE BEND MEASURED ON THE INSIDE DOES NOT EXCEED
6-13AR DIAMETERS: AND
-REINFORCEMENT PARTIALLY EMBEDDED IN CONCRETE SHALL NOT BE FIELD BENT
CELL EXCEPT IN THESESES WHERE REBAR MAY DOWELS NEED TO BE BE BENT NOT TO EXCEED TO ALIGN TO SLOPE OF H1 A VERTICAL
HORIZONTALLY TO 6" VERTICALLY.
-COVER:
-2" COVER MINIMUM WHERE THE CONCRETE IS CAST AGAINST AND PERMANENTLY
IN CONTACT WITH SOIL OR WEATHER, AND 1j" ELSEWHERE. REBAR EMBEDDED IN
GROUTED CELLS SHALL HAVE A MINIMUM CLEAR DISTANCE OF I" FOR FINE
GROUT, AND }" FOR COARSE GROUT BETWEEN REBAR AND ANY FACE OF A CELL.
REBAR USED IN MASONRY WALLS SHALL HAVE A MASONRY COVER (INCLUDING
GROUT) OF NOT LESS THAN 2" FOR MASONRY UNITS WITH FACE EXPOSED TO
EARTH OR WEATHER, AND 1j" FOR MASONRY UNITS NOT EXPOSED TO EARTH OR
WEATHER.
GALVANIZATON:
EXPOSEDCCESSORIES TO WEATHERS HALLEIN BE GALVANIZED ED INRIOR CONSTRUCTION AND ACCORDANCEWITH ASTMTA 5E3TLY
CLASS 13-2. METAL PLATE CONNECTORS, SCREWS, BOLTS, AND NAILS EXPOSED
DIRECTLY TO WEATHER SHALL BE STAINLESS STEEL OR HOT DIPPED GALVANIZED.
MIN. 2,500 PSI 4" CONCRETE SLAB WITH 10GA. W.W.F. (OR
FIBER MESH) AND 12"x12" REINFORCED FOOTER PERIMETER �-12"x12" REINFORCED FOOTER
mm
I
SWINGING TI
7. lJ DOOR
ril
C;0DE pLiF��
. Q ,oe c®uNly
B®cc
as
J"x5}" EXPANSION ANCHOR WITHIN 6" :t";: `Lm
OF EACH POST/TRUSS ALONG SIDES
AND EVERY OTHER END -WALL POST �J r y7G
2" MIN. BASE RAIL
GRAD i
- „� N 2,500 PSI 4" CONCRETI
SLAB WITH 10GA. W.W.F
OR FIBER MESH
---12„
(2) #5 REBAR ® 6" O.C.
MINIMUM SOIL BEARING CONTINUOUS WITH MINIMUM
MINIMUM
500 PSF(TYP.) 12" OVERLAP SPLICE
CONCRETE FOUNDATION/BASE RAIL
ANCHOR DETAIL
2 5" PLAN VIEW DOOR FRAMING
'RECESS
4 OOR WIDT
ELEVATION VIEW
DOOR FRAMING
" RECESS
75"T 4" OOR WID
4
OPTIONAL ROLL —UP DOOR
CONCRETE SPLASH —GUARD RECESS
3
r
i
i
i
i
� Z
i
O
'
i
r
r
i
i
i
i
i
i
O
ROLL4UP o
CODE VERSION
FBC 2017 6th Edition
ASCE-7-10
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II-B
RISK CATEGORY
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
UTILITY, U
WIND SPEED
Vult-150mph
EXPOSURE
B
ENCLOSURE
ENCLOSED
INTERNAL PRESSURE COEFF.
+/- 0.18
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
1OPSF
ROOF LIVE LOAD
OPSF OR 3001b P.L.
FLOOR DEAD LOAD
1OPSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALS,FLOOR,ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
1,200 SQ. FT.
MTB
8/9/20
7901 Santana Ave., Ft. Pierce
401 X 30'W X 10-H
O Cf
I �
Cn
I
r
I
I
w
rSheet-
m
8/ 1 1 /20
Matthew T. Baldwin P.E.
Florida License #64608
CA-1 OF 4
ROLL —UP
DOOR
12
Q3
' O.C.
I 0
SWINGING
DOOR
—11 " I 3-11 I 3'-11j'—
'0'-0"-
LEFT/RIGHT SIDE WALL
m
a.
_. `•1•i A:i:. G
g 0 0 0 1
,-�
CODE INFORMATION
CODE VERSION
FBC 2017 6th Edition
ASCE-7-10
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
nrri i.A'mry IUTIUTY.
U
INTERNAL PRESSURE COEFF.
+/— 0.18
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
1OPSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
1OPSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS,FLOOR,ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
1,200 SQ. FT.
MTB
8/9/20
7901 Santana Ave., Ft. Pierce
40'L X 30'W X 10'H
V)
L ij
0
Z
w 8/11/20
Id
Matthew T. Baldwin P.E.
L J Florida License #64608
n I Sheet- CA-2 OF 4
SWINGING
DOOR
12
LEFT/RIGHT SIDE WALL
CODE VERSION
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
UTILITY, U
WIND SPEED
Vuit-150mph
INTERNAL PRESSURE COEFF.
+/— 0.18
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
1OPSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
1OPSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS,FLOOR,ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
1,200 S 1. FT.
REVISIONS
om/ I nFSCRIPTON DATE I BY
MTB
8/9/20
7901 Santana Ave., Ft. Pierce
401 X 30'W X 1O'H
W I fjl
i l
Q
W
Lj 8/ 1 1 /20
A pie Matthew iT.s Baldwin P.E.
LLJ Florida License #64608
asr! a w
Sheet: CA-3 OF 4
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
SCREWS 14xj" SELF —DRILLING
JEI NIPPLE TO I NIPPLE
BASE RAIL BASE I
POST TO BASE RAIL
CONNECTION
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14x4"
SELF —DRILLING SCREWS
NON-STRUCTURAL HEADER OR
WINDOW RAIL TO POST DETAIL
INTERIOR
#12-14x4" SELF —DRILLING
SCREWS ® 10" O.C. MAX.,
3" MAX. FROM CORNERS
HORIZONTALLY/ 4" MAX.
FROM CORNERS VERTICALL`
EXTERIOR
DOOR FRAME TO POST
CONNECTION
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
SC) 12 14xj" SELF —DRILLING
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14)j"
SELF —DRILLING SCREWS
END POST TO BASE RAIL
CONNECTION
ill
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14x1"
SELF —DRILLING SCREWS
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14x1"
SELF —DRILLING SCREWS
SINGLE OR DOUBLETS
INTERMEDIATE POST TO
HEADER/BASE RAIL/OR HEADER CONNECTION
WINDOW RAIL DETAIL DETAIL OPTION 1
2"x2"x2" 16 GA. ANGLE CLIP SECURED
WITH (4) #12-14x4" SELF —DRILLING
MAX. SPACIN
r--3" MIN.
MAX. SP*CING
VARIES
SIDE WALL ROLL —UP
DOOR/FRAME OUT
HEADER DETAIL
INSTALL PER MANUFACTURERS INSTRUCTIONS
#14x1" SELF —DRILLING
SCREWS ® 6" O.C. MAX.
& 6" MAX. FROM CORNERS
ROLL -UP DOOR TO
POST CONNECTION
DESIGN PRESSURES
- 150 Mph
ROOF
+ 19.3/-41.4
WALLS
+20.0/-22.2
DOORS
+20.0/-22.2
WINDOWS
+20.0/-22.2
1
2
3
4
5
ZONE
+9.3
-21.9
+12.3
-35.1
+19.3
-41.4
+18.8
-21.9
+20.0
-22.2
26 GAUGE ROOF SHEATHING SECURED WITH
(1)#12-14xj" SELF —DRILLING SCREWS
'2-1-2-1' (6" D.C. (9" O.C. MAX.))
1" 16 GAUGE FURRING CHANNEL
48" O.C. MAX. SECURED WITH
(2)#12-141" SELF —DRILLING
SCREWS TO EACH RAFTER.
ROOF PANEL CONNECTION
VERTICAL SHEATHING OPTION
TO
T 1Z
U" C16 HANNEL BRACE, MIN.
24" UP TO 7' POST, MIN
48" OVER 7' POST. MIN.
45' TO MAX. 60' FROM
HORIZ. (EXCLUDE
END —WALLS). SECURED
WITH (4)#12-14x1"
SELF —DRILLING SCREWS.
VMINIMUM 6" TS NIPPLE, NIPPLE
SECURED TO WALL POST WITH
SCREWS 14xj" SELF —DRILLING
BOX EAVE RAFTER TO
POST CONNECTION DETAIL
NI
TO T
MINIMUM 6" TS NIPPLE, NIPPLEAlm
SECURED TO WALL POST WITH
SCREWS 14xj" SELF —DRILLING.
SINGLE OR DOUBLETS
HEADER CONNECTION DETAIL
OPTION 2
MINIMUM 6" TS NIPPLE.
NIPPLE SECURED TO WALL
POST WITH (4)#12-14xj"
SELF —DRILLING SCREWS
POST TO TRUSS
CONNECTION
NIPPLE
TRUSSED RAFTER
CONNECTION DETAIL
APPROVED PRODUCTS
APPROVAL NO.
ROOF SHEATHING
Carports Anywhere
FL27402.1—R1
Hampton Rib Roof Panel
WALL SHEATHING
Carports Anywhere
FL27403.1
Hampton Rib Wall Panel
SWINGING DOOR
ELIXER DOOR AND METAL COMPANY
FL17996.5
407 STEEL DOOR
ROLL —UP DOOR
JANUS INTERNATIONAL CORPORATION
FL21450.3
SERIES 3100
CODE INFORMATION
CODE VERSION
FBC 2017 6th Edition,
ASCE-7-10
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
UTILITY, U
WIND SPEED
Vult-150mph
EXPOSURE
B
ENCLOSURE
ENCLOSED
INTERNAL PRESSURE COEFF.
+/— 0.18
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
tOPSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
10PSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS,FLOOR,ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
IND
SQUARE FOOTAGE
11,200 SQ. FT.
REVISIONS
REV
DESCRIPTON
DATE
BY
DRAWN BY. MTB
DATE: 8/9/20
LOCAnoN: 7901 Santana Ave., Ft. Pierce
SIZE: 40'L X 30'W X ID'H
J
Q
8/ 1 1 /20
Matthew T. Baldwin P.E.
Florida License #64608
<
ui LLJ
o
Sheet. CA-4 OF 4