HomeMy WebLinkAboutFoundation Plan & DetailsSTRUCTURAL NOTES: * SOIL BEARING CAPACITY MIN. 2500 PSF * ALL STRUCTURAL CONCRETE SHALL DEVELOP A MIN. COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS. * ALL REINFORCING STEEL SHALL BE GRADE 60 MEETING ASTM SPECS A-615 * MIN. GONG. PROTECTION FOR RE -BARS: FTGS:3" BEAMS: 1\" SLABS:1" * LAP REINFORCING BARS 30INCHES MINIMUM EXPOSURE "C" - 170 MPH 3 SEC GUST 0 O NOTE: THE FOUNDATION/PIER SYSTEM IS DESIGNED TO RESIST FLOOD ELEMENTS OF FLOTATION, COLLAPSE AND LATERAL MOVEMENT PER FEMA CRITERIA FOR EXPOSURE "C" LOCATIONS. ACCESS DOORS TO BE BUILT ON A 1 " X 2" OPEN BACK FRAME SECURED WITH # 10 X 2" SHEET METAL SCREWS, WITH A HALF-Z WRAP (#8 X 3/4" TEKS ON THE FACE); DOOR SLAB IS SCREEN DOOR MAINFRAME #10 X 1" SHEET METAL SCREWS INTO AN INTERNAL ALUMINUM CORNER WITH .024 STUCCO COIL FOR THE FACE OF THE DOOR. ATTACHES TO FRAME WITH 2 STANDARD SCREEN DOOR OFFSET HINGES, STANDARD SCREEN DOOR LATCH FOR HARDWARE. . SECTION B-B SCALE: 3/4" = 1'-0" 2X SYP - TIE DOWN STRAP - PER SPECIFICATIONS I -BEAM - 8"XB"X 16"- CBS BLOCK PIERS 4' SLAB W/ RB SEE TIE -DOWN/ PIER REQUIREMENTS MICS2 ANCHOR [SEE DETAIL) IN CONCRETE THICKENED EDGE: 8"D X 8"W W/ [1 ] #5 RB CONT CONCRETE EXTENSION REQUIRED ALONG ENTIRE LENGTH OF CARPORT (FOR FUTURE IMPROVEMENT) %W" WEDGE ANCHOR (RED HEAD) V c1 0 N HYDRO VENT 151 THIS SIDE PROVIDE 3OX30 ALUM ACCESS - _r=� r� � —i— � ia .=tom=r I rl INDING #5 SEE STAIR DETAIL 5] THI SIDE S. DECK DETAILS : GH 40'-O" PROVIDE 30X30 ALUM ACCESS PROVIDE 5/8" CEMENT 1 HOUR WALL ON ZERO LOT LINE SIDE TIE-DOWN/PIER REQUIREMENTS SCALE: 1/4" = 1'-O" UNIT TO BE TIED DOWN - PROVIDE (2) #9 X 24" DECK SCREWS TOE -NAILED AT EACH VERTICAL MEMBER OF KNEE WALL SLAB IS EXISTING. CONTRACTOR TO SA WALL COMPLIES WITH UNIT MANUFACTURER'S PERIMETER EXISTING SLAB FOR NEW FOOTINGS. W LOCKING R IREMENT HYDRO VENT "q� ME PLAN 2X4 P.T. SYP KNEE WALL W/ STUDS 0 16" DC W/ Y,"5AW TAP -CONS @ 24" OC 1 [BOTTOM PLATE] W/ f' COX PLYWOOD W/ 5/8' CEME BOARD W/ HARD[ LAP SIDING UNIT WT. 360 LBS. Q Z 35.3 #�Ff m j N�o L CUIE9W_L6/1F11L:KtNtU tUUL: /-7 n 8"D X B°W W/ (1 ] #5 RB CONT �IAQ� 16Ay 5\ n I SECTION A -A SCALE: 3/4" = 1'-0" II TECH IN PART # 59002 STRAP/SWIVEL — CONNECTOR SOME HOMES MAY HAVE FACTORY BRACKETS WELDED TO THE [-BEAMS FOR LONGITUDINAL ANCHORS. ATTACH THE STRAP/SWIVEL CONNECTOR TO THE FACTORY BRACKETS USING A 2' GRADE 5 BOLT & NUT. ANCHORS/TIES MUST BE INSTALLED TO PROVIDE A 45❑ OR LOWER STRAP ANGLE. CONCRETE [1) Y4' X 2Ya LG. TAPCON PER BLOCK & 121 AT CONCRETE: 180 LBS. PIER DETAIL B-BOLT B-BOLT CONDENSING UNIT SIMPSON MSTC52 8X16 BLOCK 4 COURSE [2) #14 SHEET METAL SCREWS TO CONDENSING UNIT. 200 LB. SHEER WORKING CAPACITY %'x7" WEDGE ANCHOR I -I (REDHEAD] p I I I 1 I I I J A L_J MICS2 ANCHOR f3Y: TIE: DOWN ENGINEERI43 bvm UPLIFT PER 'DEVICE IS 4,750 LBS POST PICKE 1 X2%" NOTES. HAND RA 2-GALV. BOLTS %/ l 1 X 2-3/4 LG. W/ HEX. SO. NECK W/ NUTS N.T.S. TENSION BOLT LABELED [A] FOR FRAME ATTACHMENT ONLY. TENSION BOLT LABELED [B VERTICAL TENSION. # 10 S.S.S. MIN. 2" EMBEDMENT. 4-REO'D. COMPOSITE DECKING RAILING BASE N.T.S. HYDRO VENT (5) THIS SIDE T LANDING HYDRO VENT (5) THIS S1DE 40'-U' 1,4„ V-4" 1, 5'4" 5-4" 51,44 5'-4" 51-411 5,-4„ V 4, —(0 ° - — - ° - -- n -----° -- ° --- o ---- ° - - ° D O O - ---- - ----II, -- ---- ---- - ��,.-� I PROVIDE Y2" MACHINE BOLT THRU I -BEAM JJ [ W/ (2) TIE DOWN STRAPS AT BOLT (2) MICS2 ANCHORS AT CONCRETE AS SHOWN 1 (SEE TIE DOWN ENGINEERING 1 FOR AILED INFORM J 9i y -la -------------- - ------ gamy �O-°°la °°°a [J O5'-4" -9 4'_9? 4'_ 1= 4'-5z" 4'-51, 4,-5z„ 4'-5�' 4'-1z" 5' 3" Tc� --- ®----- ----- — 8------t -- E: O PROVIDE Yz" MACHINE BOLT THRU I -BEAM W/ (2) TIE DOWN STRAPS AT BOLT (2) MICS2 ANCHORS AT CONCRETE 1 AS SHOWN (SEE TIE DOWN ENGINEERING FOR DETAILED INFORMATION] Q 1 C - -- - - ----- ----- - ----- - -� � 0 ° --- ° --- ° --- ° --- ° - ° --- ° --- ° 0 Q 1'-4" 5'-2" 5'-2" 5'-2' 5'-2" 5'-2' 5'_2" 5'-2" 1'-4" 1 T R MU SCALE: 1/4" = 1'-0 CROSS HATCHING DENOTES SQ. FT. FOR VENT CALC'S HYDRO VENTS IN KNEE WALL TO BE MODEL FS 1608 (80.7 SQ. IN. NET) PER 322.2.2. (1) SO. IN. FOR EACH SO. FT. OF ENCLOSED AREA. EACH VENT COVERS 80 SQ. FT. PER PRODUCT APPROVAL. 838 SO. FT. / 80 = 10 VENTS PER 408.2. EXCEPTION (1) SQ. FT. SEE STAIR DETAIL PER 150D SO. FT. OF FLOOR ARE WITH VAPOR BARRIER. (1) SQ. FT. = 144 SO. IN. Lucle C0130 C LTI-WIDE TIE- N PLACENE -��AtEWE vlv PLANS A Np INSI SITE OR ALL MATERIAL BELOW FLOOD MUST BE CONSTRUCTED WITH FLOOD RESISTANT MATERIAL, IN ACCORDANCE WITH SECTION R322 OF THE 2017 (6TH EDITION) RESIDENTIAL BUILDING CODE. 4X4 SYP POST VINYL POST 2X6 SYP DECK VINYL RAIL JOISTS @ 16" OC m NET VENT AREA IS 80 SQ. IN. X COMPOSITE DECKING I I 3.3ya 144 / SO = 2 VENTS ATTACHED W/ (2) #10 2X6 SYP STRINGER GALV DECK SCREWS m AT EACH BEARING POINT 3'-6' 241 O X 1" NON -CORROSIVE S.M.S. @ EACH PICKET CONNECTION. TOP PLATE TO POST & POST TO CHANNEL W/ #10 X 1-X" S.M.S. IL DETAIL 2X8 SYP STRINGER VINYL PICKETS 2X COMPOSITE DECKING ATTACHED W/ [2) #10 DECK FRAMING DETAIL EACH BEARINGCK AT EACH BEARING POINT POINT 2X12 SYP STRINGER SCALE: 1/4" = 1'-0" 2X12 SYP STEP 2X6 SYP STRINGER I. •I: SIMPSON LU28 AT STAIR 1 XB SYP W/ STRINGERS TO 2X8 DECK DECK SCREWS JOIST SUPPORTS OR (2) %" GALV LAG SCREWS Ls' X 3° GALV. AT STRINGER TO POST /- HEX SCREWS SIMPSON FACE MOUNT HANGERLU26 2X6 SYP DECK JOISTS @ 16" OC LENGTH VARIES 2X COMPOSITE DECKING ATTACHED W/ [2) #1 O GALV DECK SCREWS AT EACH BEARING POINT SIMPSON MTS12 --- STRAP ° ro 2X8 SYP DECK JOIST SUPPORT W/ [21 %" GALV LAG SCREWS VINYL 2X2 RAIL POST AT GARAGE DECK OR ATTACHEO TO VINYL (2) Y2" GALV MACHINE BOLTS — CASTERS AT EXTERIOR DECKS #8 GALV SCREWS Y" S.S.S. MIN. 1" CONCRETE (21 EACH SIDE EMBEDMENT. 4-REQ'D. 3v WEDGE ANCHOR 4X4 SYP POST ATTACHED TO CONC W/ 3" EMBEDMENT MIN W/ SIMPSON AB44 POST BASE 2X6 SYP RINGER DECK CONNECTION DETAIL SCALE: 1/2" 1'-0" 4X4 PT POST W/ SIMPSON A844 4-REG'D. R GLE APCONS TREAD + V NOSE STAIR DETAIL NOTE: -- N.T.S. - HANDRAIL BRACKETS OR BALUSTERS SHALL NOT BE CONSIDERED TO BE OBSTRUCTIONS TO GRASPABILTTY. BOTTOM OF HANDRAIL SHALL CONTINUE TO SLOPE FOR A DISTANCE OF THE DEPTH OF ONE TREAD FROM BOTTOM RISER. HANDRAIL HAS CIRCULAR CROSS-SECTION W/ 1-Y4" TO 2" DIMENSION. NOTE: GUARDRAIL SHALL COMPLY W/ FBC 2017 (6TH EDITION) TYPICAL ELEVATIONS FOR DECKS N7.5. (FOR VISUAL PURPOSES ONLY) THIS SETUP HAS BEEN DESIGNED -OR A FLOOD ZONE INSTALLATION DESIGN CODE FBC - 2017 (iDTH EDITION) LBJ Architecture AA20005774 W SW HAMILL AV[nU[ PORT SAIM LUCK rL. 34953 772-800-5700 www.16 ar(hite(ture.(om A.. Ar OF FLO w ?A Is�ERED P4G�l�G B E EPT u� �0 o W Q O a DO(UMfnT DATE: 08.13.2020 RIVISIOnS: M TOUR MOV155 MAlr Rut nx■ 6 WMA" (Orwm WRECEIVED J OCT 1.3- 2020 P8rmltdng. Department LLU St. Lucie County G q ❑ CD M �^� Iq W CO ®c LLI ` J Er LUG ❑ < z Cc ® O LE Uj CE Cco Q (0 M Cn Jf f SMICT TITLE: FOUNDATION PLAN & DETAILS SnffT fIU116fR: