HomeMy WebLinkAboutFire Prevention Plan Reviewf
ST LUCIE COUNTY FIRE DISTRICT
BUREAU OF FIRE PREVENTION
PLAN REVIEW
2400 Rhode Island Avenue
Ft Pierce, FL 34950
f
F "&4w Construction ( )Tenant Improvement
Jurisdiction:
Occupancy:
Address:
Contractor
Contractor's Address:
State:
-Architect/Engineer:
Building Owner:
Occupancy Type:
Gross sq ft:
Occupant Load:
Construction Type:
Telephone: 561-462-2312
FAX: 561-462-2323
( )Addition ( )Renovation/alterations ( )Shell Only
SLC
Savanna Club Apts. Bldg. N
1900-1930 Savanna Club Blvd.
Jerome Rich
3535 Windsor Place
Florida
Wayne Berenbaum
Apartments
15,725
F.P.B.:
B-01-246
Building Dept:
21090646
Number of stories:
2
Phone #
561-994-3005
City:
Boca Raton
Zip Code:
33496
Phone #
561-470-8457
Review Date:
10/17/2001
Automatic sprinklers:
Net sq ft:
Based On:
SBCCI Type:
V unp
NOTE
1. All revisions must be in compliance before the final inspection.
2. The Fire Marshal requires 24 hour notice on all inspections.
3. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
4. Permit fees are required to be paid in full prior to any inspections.
5. Failed inspections require payment of fee prior to rescheduling of further inspections.
6. A copy of the required revision/s have been transmitted to the Architect () Contractor ( ).
7. Penetrations through rated assemblies shall be of proper UL design.
8. UL design criteria shall be submitted with the construction plans.
REVISIONS REQUIRED
KNOX BOX IS REQUIRED () KNOX KEY SWITCH REQUIRED ( )
1. A separate permit is required for the installation of the fire alarm system. Installation shall be in
accordance with NFPA 72, 1999 edition.
If the fire alarm panel is located on the exterior of the building it shall be protected from the elements and
vandalism.
2. All bedroom windows shall be egress windows. NFPA 101-30.2.1 and 101-24.2.2.3 c
3. Minimum fire extinguisher classification is 2A-10B:C
Reviewed by: y Date:
10/17/2001
11