HomeMy WebLinkAboutApproved PlansGENERAL NOTES 1. For pool plan, size, deck, and special details, see Contractor's Pool Plan. 2. Pool Walls shall be 5" thick and Floors shall be 6' thick and shall be pneumatically applied Concrete with a Compressive Strength of 3,000 psi in 28 days. Concrete: Decks shall be 2,500 psi. Concrete construction will conform to ACI Standard 318. 3;• 3. All Pool design, construction and workmanship shall be in conformity with the requirements of Florida Building Code, 5th Edition, 2014 (FBC) Accessibility; FEC Building; FBC Residential, and; ANSI/NSPI-3, ANSI/APSP/ICC-4, ANSI/APSP/ICC-5;ANSI/APSP/ICC-6 and ANSI/APSP-7; ANSI/APSP-15 and the Adopted National Electric Code 2011 (NEC) and Chapter 42 and Chapter 45 of the 5th Edition of the FBC, Residential. 4. All Pool Piping to be Schedule 40 PVC, bearing the mark of NSF Approval unless otherwise noted. 5. All Reinforcing Steel to conform to ASTM 615, Grade 40. Reinforcing shall be #3 bars at 12" on center in each direction, w/ 15" lap joints in walls and floors up to 6'. Where the pool depth is over Eft (measured vertically down from the Waterline), use #3 bars at 6' on center in each direction in the areas that exceed Eft in depth. STEPS 6" WATER LINE TILES � o POOL LIGHT COPING DRAIN COVER/GRATE MUST CONFORM TO THE LATEST EDITION OF ANSI/ASME 112.19.8 POOL STEPS: ' '.., . .: . RISERS: 12" MAX. . is DUAL SUCTION OUTLET AND APPROVED GRATE TREAD: 10" MIN. (240 SQ. IN. MIN.) WITH 3'-0" OF SEPARATION CENTER UNE TO CENTER UNE OR APPROVED CHANNEL DRAIN POOL SECTION SET O CENTER POF STEEL GRID AT THE (LONGITUDINAL) OINT CONCRETE DECK (OPTIONAL) W/ SLIP RESISTANT TOPPING ON COMPACTED GROUND W/ ALL N Concrete is cast against Bare Earth without a Separation Barrier, the minimum 1-#3 BAR CONT. IN 5° THK WALL. cover shall be 3'. With a Barrier (Steeltex) between Concrete and Earth, the (USE 2-#3 BARS CONT. IN 8°x8' minimum cover shall be 1Yz"•BOND BEAMS) 6. All Metallic Pool Pittings within 5' of the inside wall and deck reinforcing steel to be bonded to the Pool Reinforcing Steel with #8 AWG Copper Wire. The #8 Copper Wire to be run internally and externally with the NEC approved PVC Light Conduit form the Light Niche to the Junction Bax. Completion of the pool grounding to the Electrical Panel Ground to be by Electrician. 7. Bond all Sheathed Cables, Raceways, Metal Piping and all Fixed Metal Parts not separated by a permanent barrier, if within 5'-0° Horizontally from Water and 12'-0" Vertically of Maximum Water Level. 8. Equipotential Bonding to be accomplished in accordance with Article 680 of the Adopted National Electrical Code 2011 (NEC). 9. Pool or Patio shall bear only on Rock or Clean Sand, which shall be compacted to provide a Structurally Safe Bearing Capacity. Any Unsuitable Material encountered in excavation shall be removed in its entirety and the area shall be backfilled with STEELTEX acceptable material and properly compacted. Where unsuitable Material cannot be removed, the pool must be redesigned. 10. The Contractor must protect Existing Structures from failure by acceptable methods if required. The Engineer accepts no responsibility for the safety of Existing Structures. 11. The Design Engineer assumes no responsibility for pool construction in Easements or Required Setback areas. Pool Contractor and/or Owner shall verify the layout and WATER all dimesions shown prior to construction. UNE R 12. Contractor shall determine the location of all Utilities in relation to the Pool and Its Equipment and ensure minimum clearances in accordance with Local Regulations and Ordinances. 13. Contractor shall provide adequate Temporary Fencing around the construction area m to prevent unauthorized entry into the Pool Area. 14. N a water suppy, is provided, a minimum 3' Atmospheric Break will be provided. 15. All Structural, Filtration and Electrical details outlined in these drawings also relate % ORGANIC MATERIAL REMOVED. 4' NOM. THK. W/ FIBER MESH OR 5' NOM. THK. W/ #3 REBARS. S� 4'-0" JUNCTION BOX (BY OTHERS) m TO TRANSFORMER m (BY OTHERS) 2-#3 BARS CONT. IN 8"X8' BOND BEAM MARBLE `U.L. APPROVED 120 VAC/30OW POOL PLASTER LIGHT W/ GFI OR 12V/40OW MAX. POOL FINISH LIGHT W/ LOW WATER CUT-OFF IN U.L APPROVED GREY PLASTIC FORMING SHELL OR APPROVED EQUAL W/ #8 AWG BOND WIRE PER N.E.C. ZONAL) #3 BARS 0 12° O.C. EACH WAY POOL STRUCTURAL DETAILS DISTANCE LESS PLAN SEAT THERAPY LINES RETURN LINES to Spa Construction. #3BARS ® REBOUND 16. NI Pool and Spa Heaters shall be equipped with an On/Off Switch mounted for 12" O.C.E.W. (2) 8"0 ANTI -VORTEX easy access to allow the Heater to be Shut Off without adjusting the Thermostat DRAINS SEPARATED BY 3' settings and to allow restarting without relighting the Pilot Light. 17. WARNINGI To empty the Pool for any reason, the Hydrostatic Uplift Pressure must SPA STRUCTURAL DETAILS be eliminated. The Owner must consult a Contractor experienced in eliminating Uplift Pressure. I FILTER SYSTEM 1 MAIN DRAIN LINE 2 SKIMMER LINE 3 WASTE LINE 4 RETURN LINE 5 PRESSURE CLEANING UNE (OPTIONAL) A HAIR & UNIT STRAINER B RECIRCULATION PUMP C FILTER D IN -UNE CHLORINATOR (OPTIONAL) E HEATER (OPTIONAL) SPILLWAY PER CONTRACTORS POOL KIM PLAN 6x6 GLASS -BLOCK MOUNTED IN 2,500 psi CEMENT (IF SPECIFIED) -'-'-#3 REEAR O.C.E.W. RAISED SPA DETAIL ST. #3 BARS 0 6" O.C. EACH WAY 6" WALL - THICKNESS MARBLE— PLASTER FINISH TYPICAL WALL AND FLOOR WITH/N ANGLE OF REPOSE TILES SWIM -OUT DETAIL DECK OVER POUR OR 8 I BRICK COPING WATER UNE TILES i 174° COVER ALL BARSNOTE #5) ALTERNATE BEAM FINISH DETAIL 7ii,. NEW OR 1-#3 BAR CONT. IN 5' THICK BOND BEAM CONTRACTOR MUST PLACE ALL STEEL IN THE POOL WALL AT NO MORE THAN 6" ON CENTER IN BOTH DIRECTIONS IN THIS CRITICAL AREA. ALSO THE POOL SHELL WALL SHALL BE CONSTRUCTED TO 6" THICKNE'. THE STEEL MAT AND THICKER SHELL WALL SHALL EXTEND ALONG THE CRITICAL AREA AND TO A POINT WHICH IS GREATER THAN THE MINIMUM REQUIRED AS DETERMINED BY THE 1 ON 1 + 1 METHOD. � 1101.-03 r� Tvfsfox ro 11 nTTT.TIM -n, D FOR C iXP.LLA_�CE P95ANS ANI) PTT011 T NfUST BE KEPT OR NO ML"LCi::,)N Ni ILL BE NL -I DE. PLAN EXPIRES 1 YEAR FROM THE SIGNATURE DATE OR THE EFFECTIVE DATE OF A MAJOR FLORIDA BUILDING CODE CHANGE WHICHEVER IS SOONER OCT 12 2016 OR H. SHEPARN, P.E. P.A. LRE# 1933 2431 Aloma Ave. Ste 124 Winter Park, FL 32792 Office: (407) 275-1099 Fax: (407) 275-1015 LADDERS AW TO BE CROSS BRACED PER MANUFACTURERS SPECS S.S. LADDER , ea DECK SUP RESISTANT I W p . 4'-0' SWITCH -- CTION rFDECK y DISC. 12V WEDGE JOINTS AS REQUIRED TREAD SURFACE ANCHOR ADDTRONAL CONCRETE IRUBBER AS REQUIRED FOR 3" MIN. TO 6" MAX STURDY INSTALLATION BETWEEN TREAD#8 AND POOL WALL BARE, SOLID, COPPER CONDUCTOR TO SHELL REINFORCING TYPICAL LADDER DETAIL L /-#8 AWG COPPER WIRE TIME TO SERVICE CLOCK SPST TOGGLES I W p . 4'-0' SWITCH -- CTION rFDECK y DISC. 12V go' OL(+ -TRANS. T 712V/4DOW ART. 680 OF THE 1t' LATEST ADAPTED NEC. UIT MAX. POOL LIGHT W/ LOW WATER CUT-OFF OR 120 V.A.C. W/ GFI PER NEC. ELECTRICAL DIAGRAM THESE PLANS AND ALL PROPOSED WORK ARE SUBJECT TO ANY CORRECTIONS REQUIRED BY FIELD INSPECTORS THAT MAY BE NECESSARTIN ORDER, TO COMPLY WITH ALL APPLICABLE CODES. "4� AMERICAN POOLS 8 SPAS 7320 Narcoosee Rd Orlando FL 32822 (407) 847-9322 CPCO57251 Swimming Pool Specification For: 2506 TAMARIND DR FORT PIERCE FL Scale: None Rev 10 — 06/30/15 T 6. Refer to Contractor's Plan on file with the Building Department for Details on Turndown Location. 7. If the Base of the Turndown does not extend into the Old (Existing) Ground, a 4"0 CONCRETE DECK TURNDOWN Pilaster will be required every 5'-0" that will be either 2'-0" into the Ground or to 6" into the Indigenous Material, Whichever is Deeper, The Pilaster will have a #3 Rebar tied into the #5 Rebar in the base of the Vertical Pour. PROPOSED CONCRETE FINISHED DECK 8. A Deck Turndown is NOT intended to be a substitute for a Retaining Wall. If the GRADE Vertical Dimension from the Top of the Concrete Deck to the Old (Existing) Ground "' reaches 42" for a 12" Turndown, 48" for a 18" Turndown, for more than 20% of Tj_ _ _ _ - the Turndown Length or the Finished Grade Slope exceeds (steeper than) 4' Horizontally and 1' Vertically, a Turndown should not be used. 9, For a Paver Deck, if the Vertical Dimension from the Top of the Deck to the Old (Existing) Ground reaches 30.0" for a 12" Turndown, 36.0" for a 18" Turndown, for NO FOOTER more than 20% of the Turndown Length or the Finished Grade Slope exceeds (steeper than) 4' Horizontally and 1' Vertically, a Turndown shall not be used. 10. A Screen Enclosure is not to be installed on top of any of the depicted PROPOSED Turndowns. FINISHED GRADE r FOOTER NOTES 1. If a Screen Enclosure is to be installed, the Swimming Pool Contractor must Coordinate Design and Construction of any required Footer with the Screen Contractor. Specific Details for Footer to be Provided by the screen Enclosure Engineer, 2. Footer shall bear on Rock, Sand or Structurally Sound Soils (>1,500 PSF) that shall be compacted to provide Optimum Bearing Capacity and prevent Settling or Shifting. 3. Concrete shall have a 28 Day Compressive Strength of 2,500 PSI with Fiber Mesh or 6x6 -10x10 W.W. Mesh. 4. (3) #3 Rebars is Equivalent to (1) #5 Rebar. 5. A Footer may be installed with a Brick Paver Pool Deck If required by the Jurisdiction or at the Option of the Contractor and may be placed over the Top of the Footer or Abutting the Side of the Footer. PROPOSED FINISHED GRADE T -- 3 BAR CONTINUOUS v COMPACTED PAVER BRICK PAVER BRICK PAVER BASE MATERIAL POOL DECK 1-#5 BAR VERTICALLY POOL DECK AT 36 ON CENTER ' A = 12" to 18" ! B = Y4 x A (9" to 13.5') PAVER SECURED TO TOP OF TURNDOWN BY PAVER COMPACTED SUBGRADE PROPOSED FINISHED INDUSTRY STANDARDS r.', GRADE (COMPACTED) 1-#5 BAR CONTINOUS m 4 MIN. SEE PAVER DECK --I1 TURNDOWN DETAIL FOR INFORMATION 8"'�I NOT SHOWN 4"0 CONCRETE PILASTER � II I AT 5'-0" ON CENTER WITH io �j rEEXISTING 1-#3 BAR VERTICALLY �, I PAVER DECK TURNDOWN PROPOSED CONCRETE FlNISHED POOL DECK Gn RADE e... l.. T� TTLjT 8" I 1-#5 BAR CONTINUOUS 8" x 8" FOOTER w 4 CONCRETECONCRETE �^ ' POOL DECK PROPOSED FINISHED POOL DECK GRADE 24 T N Y' ✓ 12"2-#5 BARS 2-#5 BARS CONTINUOUS 12" CONTINUOUS 8" x 12" FOOTER 12" x 12" FOOTER WER BRICK PAVER CK '-2-#5 BARS 12" CONTINUOUS 12" x 12" FOOTER V PAVER DECK FINISHED GRADE PROPOSED POOL DECK FINISHED GRADE n i TTTZ 700 —I 8" 1-#5 BAR CONTINUOUS 8" x 8" FOOTER W/ PAVER DECK OCT 12 201612 2016 BRICK PAVER IPOOL DECK - - - - - - - nw— 6 112 2-#5 BARS OO FI R Ei�# RkS 19 3 P.E. P.A. CONTINUOUS v FL PE Ave.Ste Aloma e. Ste 124 2" FOOTER Winter Park, FL 32792 Office: (407) 275-1099 R DECK Fax: (407) 275-1015 ALTERNATE PAVER ON TURNDOWN DRAINAGE SWALE� 1-#3 BAR CONTINUOUS 1-#5 BAR VERTICALLY AT 36" ON CENTER a 1-#5 BAR CONTINUOUS n BRICK PAVER A = 12" to 16" 8 = Y4 x A (9" to 13.5") POOL DECK s' ' r 1 COMPACTED PAVER BASE MATERIAL I p• COMPACTED SUBGRADE ALTERNATE -PAVER LOCATION AMERICAN POOLS & SPAS 7320 Narcoosee Rd Orlando FL 32822 (407) 847-9322 CPC057251 Swimming Poo/ Specification For: 2506 TAMARIND DR FORT PIERCE FL Scale: None Rev 10 - 06/30/15 T TURNDOWN NOTES 1-#3 BAR CONTINUOUS 1. Detail is based on NO surcharge behind the Turndown and the Ground away from CONCRETE COMPACTED POOL DECK SUBGRADE 1-#5 BAR VERTICALLY AT 36" ON CENTER the Turndown is Level (>4 to 1). Turndown may abut Ribbon Footer and be tied into Footer if Appropriate, with #3 Rebar. PROPOSED FINISHED 2. Turndown shall bear on Rock, Clean Sand or Structurally Sound Soils (>1,500 PST) ;. GRADE (COMPACTED) that shall be compacted to provide Optimum Bearing Capacity and prevent Settling 1-#5 BAR CONTINUOUS z or Shifting, 4 MIN. 3. All Reinforcing Steel is to Conform to ASTM 615, Grade 40. 8"'I'1' _ ( —,1 4*0 CONCRETE PILASTER f'-- 4. Concrete shall contain Fiber Mesh and have a 28 Day Compressive Strength of AT 5'-0" ON CENTER WI EXISTING 2,500 PSI. 1-#3 BAR VERTICALLY GRADE AN 5. All Construction to Conform to Florida Building Code, 5th Edition, 2014, FBC z Building and FBC Residential. 6. Refer to Contractor's Plan on file with the Building Department for Details on Turndown Location. 7. If the Base of the Turndown does not extend into the Old (Existing) Ground, a 4"0 CONCRETE DECK TURNDOWN Pilaster will be required every 5'-0" that will be either 2'-0" into the Ground or to 6" into the Indigenous Material, Whichever is Deeper, The Pilaster will have a #3 Rebar tied into the #5 Rebar in the base of the Vertical Pour. PROPOSED CONCRETE FINISHED DECK 8. A Deck Turndown is NOT intended to be a substitute for a Retaining Wall. If the GRADE Vertical Dimension from the Top of the Concrete Deck to the Old (Existing) Ground "' reaches 42" for a 12" Turndown, 48" for a 18" Turndown, for more than 20% of Tj_ _ _ _ - the Turndown Length or the Finished Grade Slope exceeds (steeper than) 4' Horizontally and 1' Vertically, a Turndown should not be used. 9, For a Paver Deck, if the Vertical Dimension from the Top of the Deck to the Old (Existing) Ground reaches 30.0" for a 12" Turndown, 36.0" for a 18" Turndown, for NO FOOTER more than 20% of the Turndown Length or the Finished Grade Slope exceeds (steeper than) 4' Horizontally and 1' Vertically, a Turndown shall not be used. 10. A Screen Enclosure is not to be installed on top of any of the depicted PROPOSED Turndowns. FINISHED GRADE r FOOTER NOTES 1. If a Screen Enclosure is to be installed, the Swimming Pool Contractor must Coordinate Design and Construction of any required Footer with the Screen Contractor. Specific Details for Footer to be Provided by the screen Enclosure Engineer, 2. Footer shall bear on Rock, Sand or Structurally Sound Soils (>1,500 PSF) that shall be compacted to provide Optimum Bearing Capacity and prevent Settling or Shifting. 3. Concrete shall have a 28 Day Compressive Strength of 2,500 PSI with Fiber Mesh or 6x6 -10x10 W.W. Mesh. 4. (3) #3 Rebars is Equivalent to (1) #5 Rebar. 5. A Footer may be installed with a Brick Paver Pool Deck If required by the Jurisdiction or at the Option of the Contractor and may be placed over the Top of the Footer or Abutting the Side of the Footer. PROPOSED FINISHED GRADE T -- 3 BAR CONTINUOUS v COMPACTED PAVER BRICK PAVER BRICK PAVER BASE MATERIAL POOL DECK 1-#5 BAR VERTICALLY POOL DECK AT 36 ON CENTER ' A = 12" to 18" ! B = Y4 x A (9" to 13.5') PAVER SECURED TO TOP OF TURNDOWN BY PAVER COMPACTED SUBGRADE PROPOSED FINISHED INDUSTRY STANDARDS r.', GRADE (COMPACTED) 1-#5 BAR CONTINOUS m 4 MIN. SEE PAVER DECK --I1 TURNDOWN DETAIL FOR INFORMATION 8"'�I NOT SHOWN 4"0 CONCRETE PILASTER � II I AT 5'-0" ON CENTER WITH io �j rEEXISTING 1-#3 BAR VERTICALLY �, I PAVER DECK TURNDOWN PROPOSED CONCRETE FlNISHED POOL DECK Gn RADE e... l.. T� TTLjT 8" I 1-#5 BAR CONTINUOUS 8" x 8" FOOTER w 4 CONCRETECONCRETE �^ ' POOL DECK PROPOSED FINISHED POOL DECK GRADE 24 T N Y' ✓ 12"2-#5 BARS 2-#5 BARS CONTINUOUS 12" CONTINUOUS 8" x 12" FOOTER 12" x 12" FOOTER WER BRICK PAVER CK '-2-#5 BARS 12" CONTINUOUS 12" x 12" FOOTER V PAVER DECK FINISHED GRADE PROPOSED POOL DECK FINISHED GRADE n i TTTZ 700 —I 8" 1-#5 BAR CONTINUOUS 8" x 8" FOOTER W/ PAVER DECK OCT 12 201612 2016 BRICK PAVER IPOOL DECK - - - - - - - nw— 6 112 2-#5 BARS OO FI R Ei�# RkS 19 3 P.E. P.A. CONTINUOUS v FL PE Ave.Ste Aloma e. Ste 124 2" FOOTER Winter Park, FL 32792 Office: (407) 275-1099 R DECK Fax: (407) 275-1015 ALTERNATE PAVER ON TURNDOWN DRAINAGE SWALE� 1-#3 BAR CONTINUOUS 1-#5 BAR VERTICALLY AT 36" ON CENTER a 1-#5 BAR CONTINUOUS n BRICK PAVER A = 12" to 16" 8 = Y4 x A (9" to 13.5") POOL DECK s' ' r 1 COMPACTED PAVER BASE MATERIAL I p• COMPACTED SUBGRADE ALTERNATE -PAVER LOCATION AMERICAN POOLS & SPAS 7320 Narcoosee Rd Orlando FL 32822 (407) 847-9322 CPC057251 Swimming Poo/ Specification For: 2506 TAMARIND DR FORT PIERCE FL Scale: None Rev 10 - 06/30/15 T MAP " ' FOOTEF: TDH POOL SPECS 249SF J0z71AISTORY m w w JOB# HO-STU-16142 DECK PATTERN: N/A SKIMMER COLOR: WHITE ---- COPING: NIA SKIMMER LID: WHITE BRANCH: 3" TERMITE BOND COMPANY: N/A PHONE NUMBER: 000-000-0000 ORIGDRAWOATE: 10AM016 CREATED: BRIAN WHISNER E+: BRIANWHISNER®amerl—000ls.com J N ' POOL PERIMETER: 82 LF REVISION AI DATE: CREATED: BRIAN WHISNER CHANGES: NIA BEAM PMP011DjryyL pC/O�/N�CR�Li�/E�y DB:K TRUNK: 2.5" REVISION RA DATE: CREATED: BRIAN WHISNER CHANGES: NIA 1 FlNISHED BARRIERS POOL AREA: 403 SF REVISION #,A DATE: CREATED: BRIAN WHISNER CHANGES: NIA /1GA11r GWE RETURN. VAr REVISION ## DATE: CREATED: BRIAN WHISNER REVISION #9 DATE: CREATED: BRIAN WHISNER CHANGES: NIA CHANGES: NIA ALARMS -BATTERY: 7 WINDOWAND DOOR OWNER TO INSTALL FENCING: NIA 0 H� • POOL STEPS: 34 LF 1 p •, 4D 33+ FLOAT SALES CON@ULTANT: AL TEL: AYAE9322 CONSTRUCTION SUPER: CRAIG TEL: E-: Wamsricana ob.com E.: REWINDS DR ANCHOR 7 _ _ TOTAL P/D AREA: 908 SF 8• 1-#5 BAR CONIINOUS DECK PERIMETER: 61 LF POOL SPECIFICATIONS X TOTAL DECK AREA: 505 SF POOL SHAPE: CUSTOM POOL TYPE: GUNITE POOL GAL: 13565 LN POOL SIZE: 15X30 POOL DEPTH: 3'6' o ° Z ' TER 8 x 8" FOO LANAI AREA: 467 SF TILE TYPE: 6"X6" PUMP ONE: PENTAIR SUPERFLO VS PUMPA W ACRYLIC AREA: 972 SF FILTER ONE: PENTAIR C*C 1503E FILTERTER TWO: NIA Q CHILD FENCE: 75 LF SANITIZERONE: IC40 SANITIZER TWO: NIA r POOL HEATER: NIA DECK DRAIN: 59 LF MAIN DRAINS: PENTAIR STARGUARD SKIMMER: Yes RETURN LINES: 3 POOL CLEANER: NIA VAC LINE: Yes EXTRA SUCTION: NIA CONTROLS: SIEMENS POOL LIGHT: WHITE LED EXTRA STEPS: NIA EXTRA BENCH: NIA SUNSHELF: YES POOL SLOPE DETAIL 4.67 TO 1 SLOPE —14' ROPE AND 36'4.1 RETURNS /3-T EXISTING LANAI " ' w> . m Vy -- 249SF m w w DECK PATTERN: N/A SKIMMER COLOR: WHITE ---- COPING: NIA SKIMMER LID: WHITE f J TERMITE BOND COMPANY: N/A PHONE NUMBER: 000-000-0000 PAVER BORDER: NIA SPECIAL: NIA , J N ' 18" TO 24" FROM POOL BEAM 3'D COPING FOOTER TYPE ACRYLIC: YES PAVER: NIA DESCRIPTION: N/A ACRYLIC: YES PAVER: NIA DESCRIPTION: 8X8 DESCRIPTION: NIA 1 BARRIERS 6'D 6 1 CHILD FENCE: 75 LF VAr I POOL LIGHT ALARMS -BATTERY: 7 WINDOWAND DOOR OWNER TO INSTALL FENCING: NIA 0 \ ALARMS -HARD WIRED: NIA APS TO INSTALL FENCING: N/A 1 p FLOAT ANCHOR c ------------------------- 9� EXISTING LANAI 218SF n HO-STU-16142 Q NO SPA 0 -- - - - - -- DECKDRAIN ----- NO SCREEN CHILD FENCE COLOR SELECTIONS EQUIPOTENTVL BONDING GRID POOL INTERIOR: WET EDGE PEARL SUPREME TEAL TILE SELECTION: SCPINPT TRIDENT TURQUOISE CHILD FENCE #8 BARE, SOLID COPPER DECK PATTERN: N/A SKIMMER COLOR: WHITE ---- COPING: NIA SKIMMER LID: WHITE CONDUCTOR ATTACHED TO TERMITE BOND COMPANY: N/A PHONE NUMBER: 000-000-0000 PAVER BORDER: NIA SPECIAL: NIA THE SHELL N FOUR PLACES 18" TO 24" FROM POOL BEAM DECK COPING FOOTER TYPE ACRYLIC: YES PAVER: NIA DESCRIPTION: N/A ACRYLIC: YES PAVER: NIA DESCRIPTION: 8X8 DESCRIPTION: NIA BARRIERS 6'D CHILD FENCE: 75 LF EXISTING FENCE)Meets COGe): NIA POOL LIGHT ALARMS -BATTERY: 7 WINDOWAND DOOR OWNER TO INSTALL FENCING: NIA 0 \ ALARMS -HARD WIRED: NIA APS TO INSTALL FENCING: N/A 0 -- - - - - -- DECKDRAIN ----- NO SCREEN CHILD FENCE OPTIONS OPTION: ROPE AND FLOAT ANCHORS OPTION: ALARM OPTION: _ OPTION: OPTION: _ OPTION: LIGHT SWITCH OPTION: _ OPTION: LOCATIONTBO AT a CCESS PRESITE7 AMERICAN POOLS & SPAS 7320 Narcoossee Rd. Orlando, FL 32822 Office: 407-847-8322 Fax: BUYER NAME(S): TERRY+ FERNANDASTURGELL E-MAIL: N/A ADDRESS: 2506 TAMARIND DRIVE CITY: FORT PIERCE STATE: FL ZIP CODE: 34949 SCALE: 1/8" = WIFE CELL: 7723264143 HUSBAND CELL: 772-018.4844 SUBDIVISION: FT. PIERCE SHORES LOT #: 3 PLAT BOOK: 9 PAGES #: 19 COUNTY: ST. LUCIE COUNTY COLOR SELECTIONS POOL INTERIOR: WET EDGE PEARL SUPREME TEAL TILE SELECTION: SCPINPT TRIDENT TURQUOISE SPA INTERIOR: NIA TILE GROUT: WHITE DECK COLOR: BOMBAY STEP TILE: 3X3 DECK PATTERN: N/A SKIMMER COLOR: WHITE ---- COPING: NIA SKIMMER LID: WHITE COPING GROUT: NIA DRAIN AND FITTINGS: WHITE PAVER BORDER: NIA SPECIAL: NIA OPTIONS OPTION: ROPE AND FLOAT ANCHORS OPTION: ALARM OPTION: _ OPTION: OPTION: _ OPTION: LIGHT SWITCH OPTION: _ OPTION: LOCATIONTBO AT a CCESS PRESITE7 AMERICAN POOLS & SPAS 7320 Narcoossee Rd. Orlando, FL 32822 Office: 407-847-8322 Fax: BUYER NAME(S): TERRY+ FERNANDASTURGELL E-MAIL: N/A ADDRESS: 2506 TAMARIND DRIVE CITY: FORT PIERCE STATE: FL ZIP CODE: 34949 SCALE: 1/8" = WIFE CELL: 7723264143 HUSBAND CELL: 772-018.4844 SUBDIVISION: FT. PIERCE SHORES LOT #: 3 PLAT BOOK: 9 PAGES #: 19 COUNTY: ST. LUCIE COUNTY Swimming Pool Energy Efficiency Compliance Information Note: These Requirements apply ONLY to the Filtration Pump ANSI 1 ASPC / ICC -15 2011 Flow Calculations: Pool water volume 13565 1360 = 38 gpm - this is the calculated flow rate Note: for pools under 13,000 gels. the calculated flow rate or 36 gpm whichever is greater = the filtration flow rate Note: Is there an Auxiliary load on the filtration pump? FX Yes ❑ No If so, what is the calculated auxilliary flow rate 36 gpm Flow rate (low speed) 35 gpm @ 1725 rpm Minimum suction side pipe size @ 6 fps 1.5 in. Minimum suction side branch pipe size @ 6 fps Minimum return side pipe size @ 6 fps 1.5 in. Minimum return side branch pipe size @ 6 fps Determine Filter Size: .09 = 1.8 (Lengm d Sud Pipe) Filter Factors (GPM/SF): 7 Cartridge (0.375) ❑ D E (2.0) ❑ $and (15) 1.5 in. 1.5 in. Filter Size: O (Ri�aSa) = 9,) PENTAIR C+C 150SF (FrterMalm aiM Mode ) Pump Controls: Filtration pump has no auxiliary load- standard time clock ❑ Filtration pump with auxiliary load -Control model for low speed default within 24 hrs Heater Model: XX (Make,Model and Size) Gas Heater Efficiency Rating XX (No Pilot Light) Heater Pump Efficiency C.O.P XX SUPERFLO VS ANSI 5 & ANSI 7 Compliance Work Sheet Determine Simplified TDH: Distance ce from pool to pump in feet: 20 2' Friction loss (in suction pipe) in 2.5 Inch pipe par 18 @ 103 gPg = 3. Friction loss (in return pipe) in 2 inch pipe per 1 It. @ 103 gpm Determine Simplified TDH (CONTINUED): 4. 20 x .09 = 1.8 (Lengm d Sud Pipe) (Ft of heedn B ar APS tmH Bud. Pipe) s. 20 x .16 = 3.2 (LwO d Remm Reel rR d headm fi Of Pipe) (TDH Rehm P01 .09 (from pipe flowlfriction loss chart) • 16 (from pipe flow/(fiction loss chart) TDH in Piping: 5 Filter I Heater loss in TDH 7 All other losses 21 Total Dynamic Head (TDH): 33+ Determine Pipe Sizes: Branch Piping to be 3 inch to keep velocity @ 6 fps max. at 103 gpm System Flow Rate. Trunk, Skimmer 8 Suction Piping to be 2.5 inch to keep velocity @NO fps max. at 103 gpm System Flow Rate. Return Piping to be 2 inch to keep velocity @ fps max. at 103 gpm System Flow Rate. Pump Selection. as Listed on Curve A or C (circle one) Filtration Pump PENTAIRSUPERFLO] Maximum Flow Rate 103 gpm Determine the Number and Type of Required In -Floor Suction Outlets: Check all that apply. ® O 3A0 O 2 PENTAIR SG 3�� o � Main Drain Cover PENTAIR STARGUARD (Make aM V0 M) suction outlets @ 144 gpm max. now auction outlets @ gpm max. flow channel drain @ gpm w/ ports 'NOTE: FIELD TDH MUST BE EQUAL TO OR HIGHER THAN THE CALCULATED TDH. Flow and Friction Loss Per Foot Total Head In Feet Conversion Chart velod -Fed PH Serand 0 2 Inches Mercury (Vacuum Gauge) 1 4 1 6 8 1 10 1 12 1 14 1 18 1 16 26 pm 035 0 OA 2.3 4.5 6.8 9.0 1 113 1 13:8 1 15.8 181 20.3 227 pm 0.10' 1 2.3 4.6 68 9.1 11A 13.6 r 15.9 1 18,1 2M 22.7 or eachor each pump 2 4.6 68 9.1 11.4 13.7 15.9 182 T 20.4 22.7 25A Total Dynamic Head (TDH) 3 89 92 11.5 13.7 16.0 18.2 20.8 228 25.0 273 of the new or replacement pump. 4 92 115 13.8 18.0 183 20.5 228 25.1 27.3 288 5 11.5 138 191 18.3 208 228 281 21.4 28.6 31S 6 13.9 16.1 18.4 25.6 22.9 252 27.4 29.7 31.9 342 7 162 18.4 20.7 23.0 25.2 27.5 29.7 1 320 343 36S 8 105 20.7 23.0 25.3 27.5 29.8 32,0 34.3 366 388 9 20.8 1 23.1 25.3 27.6 29.8 32.1 34.3 36.6 1 38.8 1 41.1 10 23.1 25.4 1 27.6 1 29S 321 1 34A 35.7 38.9 41.2 1 43.4 11 25A 27.7 29.9 322 34.5 1 36.7 38.0 412 43.5 45.8 12 27.7 30.0 322 34S 368 1 39.0 41.3 43S 45.8 48.1 N 13 30.0 32.3 34.6 36.8 39.1 413 43.6 45.9 4B.1 50.4 14 32.3 318 36.9 39.1 41A 43.6 45.9 482 53A 52.7 75 31.8 38.9 302 47.1 43.7 45.9 IBR 50.5 52.7 55.0 16 37,0 39.2 41.5 43.7 46A4643 50.5 528 35A 57.3 5 11 393 41.5 43.8 46.1 46.3 50.6 52.8 55.1 57.4 59.6 18 41.6 43.8 46.1 494 50.6 529 55.1 57.4 59.7 61$ 19 43.9 482 404 507 529 552 574 59.7 820 642 _ 20 462 48.5 50.7 53.0 St2 57.5 59:8 82.0 64.3 66.5 a 21 463 50.8 53.0 553 57.6 598 62.1 643 SGS 88.9 22 50.8 53.1 1 $53 578 598 62.1 64,4 666 68.9 71.2 23 53.1 86.4 1 57.7 59A 622 64A 86:1 69A 712 73.5 24 55.4 57.7 1 60.0 62.2 64.5 65.7 69.0 71.3 135 75.8 25 57.8 60.0 1 62.3 64.5 668 W.1 718 73.6 758 78.1 26 60.1 623 64.6 86.8 69.1 71A 73,6 75.9 78,1 80.4 27 62.4 64.6 66.9 092 71A 787 75:9 702 805 82.7 28 84.7 88.9 692 71.5 73.7 76.0 782 B0.5 B28 06.0 29 67.0 693 71.5 738 78.0 78.3 Bob 828 85.1 87.3 30 69.3 71.6 738 781 783 80.8 829 85.1 87A 89.6 31 71.6 73.9 701 78A 80.7 82.9 852 87.4 89.7 92.0 32 73.9 762 78.4 60.7 83.0 852 01:6 89.7 92.0 943 33 762 78.5 80.7 83.0 85.3 87.5 098 82.0 81.3 98.6 34 78.5 808 83.1 85.3 87.6 898 92.1 AA 98.6 98.9 35 80.9 33.1 85A 878 89.9 922 944 %.7 988 1012 'NOTE: FIELD TDH MUST BE EQUAL TO OR HIGHER THAN THE CALCULATED TDH. Flow and Friction Loss Per Foot Schedule 40 PVC Pipe velod -Fed PH Serand Pbasie9 6fps 8fps 10 fps 1' 16 gi Me 21 Spn 023' 26 pm 035 1.S 37 jPM OA6 W 9P. 0.14' 62 tipm 0.21' Y 62. ox 82 gqn 010' 103 Wn 0.16 257 88 gPFn IN 117gpm 0.09 146 girm 0.13' Y 138 opm 004' 1B1 gpm OOT 227 pm 0.10' 4' 234 0.03' 313 gpm 0.05' 392 pm 0.0T B' 534 002' 712 gpm O.IXY TDH Calculation Options or eachor each pump Check one. Simplified Total Dynamic Head (STDH) Complete STDH Worksheet - FIII In all blanks. Total Dynamic Head (TDH) Complete Program or other talcs. Fill in required blanks on worksheet & attach calculations. Maximum Flow Capacity of the new or replacement pump. owner Date spam gnaeim CoMM*m Cert No. p,p TdOPNOM No. Al Scale: None