HomeMy WebLinkAboutBuilding Plan ReviewST. LUCIE COUNTY - FORT PIERCE
FIRE DISTRICT
P.O.BOX 3030
FT. PIERCE, FL. 34950-3030
TELEPHONE (407)-462-2312
FAX NO. (407)-462-2325
BUILDING PLAN REVIEW
JURISDICTION: ST LUCIE COUNTY
PROJECT NAME: COUNCIL ON CHILD ABUSE
CONTRACTOR: ASSOCOCIATED BUILDERS
ARCHITECT: DONADIO & ASSOC.
BUILDING OWNER: THE EXCHANGE CLUB
BUILDING LOCATION: 3525 W. MIDWAY RD.
OCCUPANCY TYPE: BUSINESS
• GROSS SQ FOOTAGE: 5251 SQ FT.
OCCUPANCY LOAD: 52
CONSTRUCTION TYPE: NFPA # 220 _III_ (200 )
F.P.B. NO: 6497
BUILDING DEPT. NO: 52587
PHONE NO: 335-1990
PHONE NO: (407)-234-4066
REVIEW DATE: 12-28-95
NUMBER OF STORIES: ONE
AUTOMATIC SPKLRS. Yes _No_X_
NET SQ FT: 5251 SQ. FT.
BASED ON: 100 sq ft p/p
SBCCI : _V (Protected)
NEW CONSTRUCTION:_X_ SHELL ONLY:, TENANT IMPROVEMENT:
ADDITION RENOVATION: OTHER:
ALL REVISIONS LISTED MUST BE IN COMPLIANCE BEFORE THE FINAL INSPECTION.
THE FIRE MARSHALL REQUIRES 24 HOUR NOTICE ON ALL INSPECTIONS.
REQUIRED REVISIONS:
1. Doors identified as No. 18, located in the one hour wall shall be a Class B-1 hr.
rated door and jamb assembly, equipped with a self closing device.
2. Insulating material installed in concealed spaces shall have a flame spread rating
of 0 to 25 and a smoke development rating of 450. The flame spread rating do not
apply to facings that are in contact with unexposed surfaces of the ceiling material.
3. When listed smoke detectors are installed in a building not equipped with a fire
alarm system they shall
a. cause a visual and audible signal in a normally occupied area, and
b. Detector trouble conditions shall be indicated visually and audibly in a
normally occupied are shall be identified as air duct detector trouble.
\ REVIEWED BY: DATE: / >