Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-22 09:06:28 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1 ...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N 1329Job:Load Short Form Sep 21, 2020Date:House Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Martire Residence, Groza Builders, IncFor: 10210 Carlton Rd, Ft Pierce, FL 34987 Design Information InfiltrationClgHtg Blower doorMethod9041Outside db (°F) 3 (partial) / 1Shielding / stories7570Inside db (°F) 50 Pa / 0 cfmPressure / AVF1529Design TD (°F) L-Daily range 5030Inside humidity (%) 572Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond 14ACXS030-230A** AHRI ref Coil CBA27UHE-030-230*++TDR AHRI ref 10259390 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW6.7 Sensible cooling Btuh20020 Heating output Btuh22789 Latent cooling Btuh8580 Temperature rise °F22 Total cooling Btuh28600 Actual air flow cfm953 Actual air flow cfm953 Air flow factor cfm/Btuh0.043 Air flow factor cfm/Btuh0.053 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.74 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Laundry 53 1627 1014 71 54 Pantry 20 319 87 14 5 Foyer 63 1049 360 46 19 Master Bedroom 247 3624 2456 158 131 M Bath 125 1006 445 44 24 WIC 88 1634 502 71 27 GR/Kit/DR 749 5555 7862 242 419 Bath 2 58 538 198 23 11 Bed 3 137 1383 1604 60 85 WIC 3 30 885 257 38 14 WIC 4 33 477 153 21 8 Hall 47 0 0 0 0 Bed 2 149 1458 1565 63 83 Bed 4 160 2356 1396 102 74 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-22 09:06:28 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 2 ...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N House d 1957 21911 17899 953 953 Other equip loads 1819 966 Equip. @ 0.95 RSM 17997 Latent cooling 6588 TOTALS 1957 23730 24584 953 953 2020-Sep-22 09:06:28 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1 ...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N 1329Job:Building Analysis Sep 21, 2020Date:House Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Martire Residence, Groza Builders, IncFor: 10210 Carlton Rd, Ft Pierce, FL 34987 Design Conditions Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) Blower doorMethod)L(15-Daily range (°F) 3 (partial) / 1Shielding / stories77-Wet bulb (°F) 50 Pa / 0 cfmPressure / AVF7.515.0Wind speed (mph) Heating Walls Glazing Other Ceilings Floors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 19.646522.6Walls 4.610899.3Glazing 0.61403.7Doors 13.131051.6Ceilings 27.765783.43.4Floors 11.827931.7Infiltration 15.03555Ducts 00Piping 00Humidification 7.71819Ventilation0Adjustments 100.023730Total Cooling Walls Glazing Other Ceilings Infiltration Ducts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 15.128511.6Walls 10.8204217.4Glazing 0.71413.7Doors 12.723921.2Ceilings 000Floors 4.48320.5Infiltration 12.72392Ducts 5.1966Ventilation 38.47250Internal gains 00Blower 0Adjustments 100.018865Total Latent Cooling Load = 6588 Btuh Overall U-value = 0.209 Btuh/ft²-°F Data entries checked. 2020-Sep-22 09:06:28 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1 ...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N 1329Job:Component Constructions Sep 21, 2020Date:House Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Martire Residence, Groza Builders, IncFor: 10210 Carlton Rd, Ft Pierce, FL 34987 Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) Blower doorMethod)L(15-Daily range (°F) 3 (partial) / 1Shielding / stories77-Wet bulb (°F) 50 Pa / 0 cfmPressure / AVF7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Block R-9 Wall: Blk Wall, Stuc Ext, 8" Thk, R-9 Foam Fill, 1/2" Gyp Bd 8772.589.00.089340n 5611.65 7771.6512152.589.00.089471e 2351.653672.589.00.089142s 7811.6512222.589.00.089474w 621.65982.589.00.08938nw 24171.6537782.589.00.0891466all Partitions Frm Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16" OC Stud 4341.468742.9411.00.101298 Windows Impact: Impact; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.9 ft head ht 1187.591459.2800.32016n 35923.01459.2800.32016e 52923.02139.2800.32023e 2249.742139.2800.32023s 35923.01459.2800.32016w 158917.18619.2800.32093all Impact, TEMP, OBSC: Impact, TEMP, OBSC; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (0.8 ft window ht, 1 ft sep.); 6.9 ft head ht 4823.0199.2800.3202w Impact: Impact; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 15 ft overhang (5.2 ft window ht, 1 ft sep.); 6.9 ft head ht 40518.02099.2800.32023nw Doors Door, wd sc type: Fbrgls Door 753.73743.697.00.12720s 673.73663.697.00.12718w 1413.731403.697.00.12738all Ceilings Attic, Metal Roof, R-20 Roof Deck Ins, 1/2" Gyp Bd Int Fnsh 21.00.4051957 23921.2231051.59 2020-Sep-22 09:06:28 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 2 ...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N Floors On Grade Depth, Tile Flr Fnsh 00657828.700.989229 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-22 09:06:28 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1 ...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N 1329Job:Project Summary Sep 21, 2020Date:House Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Martire Residence, Groza Builders, IncFor:10210 Carlton Rd, Ft Pierce, FL 34987 Notes: Design Information St Lucie Co Intl, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F29 Design TD °F15Daily range L Relative humidity %50Moisture difference gr/lb57 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh18356 Structure Btuh15507 Ducts Btuh3555 Ducts Btuh2392Central vent (57 cfm) 1819 Btuh Central vent (57 cfm) Btuh966 Outside air Outside airHumidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh23730 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh17997 Method Latent Cooling Equipment Load SizingBlower door Shielding / stories 3 (partial) / 150 Pa / 0 cfmPressure / AVF Structure Btuh2899 Ducts Btuh1484Central vent (57 cfm) Btuh2205 CoolingHeating Outside air19571957Area (ft²) Equipment latent load Btuh6588 1684216842Volume (ft³)Air changes/hour 0.180.31 Equipment Total Load (Sen+Lat)Btuh24584 Equiv. AVF (cfm) 4988 Req. total capacity at 0.70 SHR ton2.1 Heating Equipment Summary Cooling Equipment Summary Make Make LennoxTrade Trade LENNOX Model Cond 14ACXS030-230A**AHRI ref Coil CBA27UHE-030-230*++TDR AHRI ref 10259390Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW6.7 Sensible cooling Btuh20020Heating output Btuh22789 Latent cooling Btuh8580 Temperature rise °F22 Total cooling Btuh28600Actual air flow cfm953 Actual air flow cfm953 Air flow factor cfm/Btuh0.043 Air flow factor cfm/Btuh0.053Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.74 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-22 09:06:28Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N 1329Job:Right-J® Worksheet Sep 21, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name House Laundry 2 Exposed wall 229.3 ft 21.5 ft 3 Room height 8.6 dft 8.0 heat/coolft 4 Room dimensions ft7.5x7.0 5 Room area 1956.9 ft²52.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 356 340 877 561 56 56 144 92 .GG ImpactImpact 0.3200.320 nn 9.289.28 7.597.59 16 0 145 118 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 510 471 1215 777 60 60 155 99 .GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 16 0 145 359 0 0 0 0 11 GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 23 0 213 529 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 186 142 367 235 0 0 0 0 GG ImpactImpact 0.3200.320 ss 9.289.28 9.749.74 23 19 213 224 0 0 0 0 DD Door, wd sc typeDoor, wd sc type 0.1270.127 ss 3.693.69 3.733.73 20 20 74 75 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 510 474 1222 781 0 0 0 0 GG ImpactImpact 0.3200.320 ww 9.289.28 23.0223.02 16 0 145 359 0 0 0 0 GG Impact, TEMP, OBSC 0.320Impact, TEMP, OBSC 0.320 ww 9.289.28 23.0223.02 2 0 19 48 0 0 0 0 DD Door, wd sc typeDoor, wd sc type 0.1270.127 ww 3.693.69 3.733.73 18 18 66 67 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nwnw 2.582.58 1.651.65 60 38 98 62 0 0 0 0 GG ImpactImpact 0.3200.320 nwnw 9.289.28 17.9917.99 23 0 209 405 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 298 298 874 434 56 56 165 82 CC Attic, Metal Roof, R 0.405Attic, Metal Roof, R 0.405 --1.591.59 1.221.22 1957 1957 3105 2392 53 53 83 64 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 1957 229 6578 0 53 22 617 0 6 c) AED excursion 0 -18 Envelope loss/gain 15563 7426 1163 319 12 a) Infiltration 2793 832 200 59 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 5 1150 0 0 Appliances/other 6100 500 Subtotal (lines 6 to 13)18356 15507 1363 879 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 18356 15507 1363 879 15 Duct loads 19%15%3555 2392 19%15%264 135 Total room load 21911 17899 1627 1014 Air required (cfm)Air required (cfm)953 953 71 54 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-22 09:06:28Right-Suite® Universal 2019 19.0.20 RSU27054 Page 2...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N 1329Job:Right-J® Worksheet Sep 21, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Pantry Foyer 2 Exposed wall 4.5 ft 12.5 ft 3 Room height 8.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft4.5x4.5 ft11.5x5.5 5 Room area 20.3 ft²63.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.3200.320 nn 9.289.28 7.597.59 0 0 0 0 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 0 0 0 0 0 0 0 0 11 GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 50 29 76 48 GG ImpactImpact 0.3200.320 ss 9.289.28 9.749.74 0 0 0 0 0 0 0 0 DD Door, wd sc typeDoor, wd sc type 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 20 20 74 75 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3200.320 ww 9.289.28 23.0223.02 0 0 0 0 0 0 0 0 GG Impact, TEMP, OBSC 0.320Impact, TEMP, OBSC 0.320 ww 9.289.28 23.0223.02 0 0 0 0 0 0 0 0 DD Door, wd sc typeDoor, wd sc type 0.1270.127 ww 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nwnw 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3200.320 nwnw 9.289.28 17.9917.99 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 36 36 106 53 63 63 185 92 CC Attic, Metal Roof, R 0.405Attic, Metal Roof, R 0.405 --1.591.59 1.221.22 20 20 32 25 63 63 100 77 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 20 5 129 0 63 13 359 0 6 c) AED excursion -2 -6 Envelope loss/gain 267 76 794 286 12 a) Infiltration 0 0 85 25 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)267 76 879 312 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 267 76 879 312 15 Duct loads 19%15%52 12 19%15%170 48 Total room load 319 87 1049 360 Air required (cfm)Air required (cfm)14 5 46 19 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-22 09:06:28Right-Suite® Universal 2019 19.0.20 RSU27054 Page 3...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N 1329Job:Right-J® Worksheet Sep 21, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Master Bedroom M Bath 2 Exposed wall 39.5 ft 10.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft14.5x17.0 ft10.0x12.5 5 Room area 246.5 ft²125.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.3200.320 nn 9.289.28 7.597.59 0 0 0 0 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 64 64 165 105 0 0 0 0 .GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 0 0 0 0 0 0 0 0 11 GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 136 113 291 186 0 0 0 0 GG ImpactImpact 0.3200.320 ss 9.289.28 9.749.74 23 19 213 224 0 0 0 0 DD Door, wd sc typeDoor, wd sc type 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 116 116 299 191 80 78 201 128 GG ImpactImpact 0.3200.320 ww 9.289.28 23.0223.02 0 0 0 0 0 0 0 0 GG Impact, TEMP, OBSC 0.320Impact, TEMP, OBSC 0.320 ww 9.289.28 23.0223.02 0 0 0 0 2 0 19 48 DD Door, wd sc typeDoor, wd sc type 0.1270.127 ww 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nwnw 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3200.320 nwnw 9.289.28 17.9917.99 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Metal Roof, R 0.405Attic, Metal Roof, R 0.405 --1.591.59 1.221.22 247 247 391 301 125 125 198 153 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 247 40 1133 0 125 10 287 0 6 c) AED excursion -42 16 Envelope loss/gain 2492 966 705 345 12 a) Infiltration 544 162 138 41 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 1000 0 Subtotal (lines 6 to 13)3036 2128 843 386 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 3036 2128 843 386 15 Duct loads 19%15%588 328 19%15%163 59 Total room load 3624 2456 1006 445 Air required (cfm)Air required (cfm)158 131 44 24 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-22 09:06:28Right-Suite® Universal 2019 19.0.20 RSU27054 Page 4...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N 1329Job:Right-J® Worksheet Sep 21, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name WIC GR/Kit/DR 2 Exposed wall 19.5 ft 47.8 ft 3 Room height 8.0 heat/coolft 9.5 heat/coolft 4 Room dimensions ft7.0x12.5 ft749.4x1.0 5 Room area 87.5 ft²749.4 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 100 100 258 165 0 0 0 0 .GG ImpactImpact 0.3200.320 nn 9.289.28 7.597.59 0 0 0 0 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 190 167 430 275 .GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 0 0 0 0 0 0 0 0 11 GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 0 0 0 0 23 0 213 529 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3200.320 ss 9.289.28 9.749.74 0 0 0 0 0 0 0 0 DD Door, wd sc typeDoor, wd sc type 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 56 56 144 92 62 44 113 72 GG ImpactImpact 0.3200.320 ww 9.289.28 23.0223.02 0 0 0 0 0 0 0 0 GG Impact, TEMP, OBSC 0.320Impact, TEMP, OBSC 0.320 ww 9.289.28 23.0223.02 0 0 0 0 0 0 0 0 DD Door, wd sc typeDoor, wd sc type 0.1270.127 ww 3.693.69 3.733.73 0 0 0 0 18 18 66 67 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nwnw 2.582.58 1.651.65 0 0 0 0 60 38 98 62 GG ImpactImpact 0.3200.320 nwnw 9.289.28 17.9917.99 0 0 0 0 23 0 209 405 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 143 143 419 208 CC Attic, Metal Roof, R 0.405Attic, Metal Roof, R 0.405 --1.591.59 1.221.22 88 88 139 107 749 749 1189 916 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 88 20 559 0 749 48 1372 0 6 c) AED excursion -9 -139 Envelope loss/gain 1100 355 4109 2395 12 a) Infiltration 269 80 538 160 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 5 1150 Appliances/other 0 3100 Subtotal (lines 6 to 13)1369 435 4646 6806 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 8 6 14 Subtotal 1369 435 4654 6811 15 Duct loads 19%15%265 67 19%15%901 1050 Total room load 1634 502 5555 7862 Air required (cfm)Air required (cfm)71 27 242 419 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-22 09:06:28Right-Suite® Universal 2019 19.0.20 RSU27054 Page 5...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N 1329Job:Right-J® Worksheet Sep 21, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bath 2 Bed 3 2 Exposed wall 5.5 ft 13.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft5.5x10.5 ft13.0x10.5 5 Room area 57.8 ft²136.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.3200.320 nn 9.289.28 7.597.59 0 0 0 0 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 0 0 0 0 0 0 0 0 11 GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3200.320 ss 9.289.28 9.749.74 0 0 0 0 0 0 0 0 DD Door, wd sc typeDoor, wd sc type 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 44 44 113 73 104 88 228 146 GG ImpactImpact 0.3200.320 ww 9.289.28 23.0223.02 0 0 0 0 16 0 145 359 GG Impact, TEMP, OBSC 0.320Impact, TEMP, OBSC 0.320 ww 9.289.28 23.0223.02 0 0 0 0 0 0 0 0 DD Door, wd sc typeDoor, wd sc type 0.1270.127 ww 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nwnw 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3200.320 nwnw 9.289.28 17.9917.99 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Metal Roof, R 0.405Attic, Metal Roof, R 0.405 --1.591.59 1.221.22 58 58 92 71 137 137 217 167 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 58 6 158 0 137 13 373 0 6 c) AED excursion -3 152 Envelope loss/gain 363 140 962 823 12 a) Infiltration 76 23 179 53 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 500 Subtotal (lines 6 to 13)438 162 1141 1376 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 12 9 18 13 14 Subtotal 451 171 1159 1390 15 Duct loads 19%15%87 26 19%15%224 214 Total room load 538 198 1383 1604 Air required (cfm)Air required (cfm)23 11 60 85 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-22 09:06:28Right-Suite® Universal 2019 19.0.20 RSU27054 Page 6...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N 1329Job:Right-J® Worksheet Sep 21, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name WIC 3 WIC 4 2 Exposed wall 11.0 ft 5.5 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft6.0x5.0 ft6.0x5.5 5 Room area 30.0 ft²33.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 40 40 103 66 44 44 113 73 .GG ImpactImpact 0.3200.320 nn 9.289.28 7.597.59 0 0 0 0 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 0 0 0 0 0 0 0 0 11 GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3200.320 ss 9.289.28 9.749.74 0 0 0 0 0 0 0 0 DD Door, wd sc typeDoor, wd sc type 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 48 48 124 79 0 0 0 0 GG ImpactImpact 0.3200.320 ww 9.289.28 23.0223.02 0 0 0 0 0 0 0 0 GG Impact, TEMP, OBSC 0.320Impact, TEMP, OBSC 0.320 ww 9.289.28 23.0223.02 0 0 0 0 0 0 0 0 DD Door, wd sc typeDoor, wd sc type 0.1270.127 ww 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nwnw 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3200.320 nwnw 9.289.28 17.9917.99 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Metal Roof, R 0.405Attic, Metal Roof, R 0.405 --1.591.59 1.221.22 30 30 48 37 33 33 52 40 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 30 11 315 0 33 6 158 0 6 c) AED excursion -5 -3 Envelope loss/gain 590 177 323 110 12 a) Infiltration 152 45 76 23 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)741 222 399 133 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 741 222 399 133 15 Duct loads 19%15%144 34 19%15%77 20 Total room load 885 257 477 153 Air required (cfm)Air required (cfm)38 14 21 8 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-22 09:06:28Right-Suite® Universal 2019 19.0.20 RSU27054 Page 7...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N 1329Job:Right-J® Worksheet Sep 21, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Hall Bed 2 2 Exposed wall 0 ft 13.5 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft13.5x3.5 ft13.5x11.0 5 Room area 47.3 ft²148.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.3200.320 nn 9.289.28 7.597.59 0 0 0 0 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 108 92 238 152 .GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 0 0 0 0 16 0 145 359 11 GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3200.320 ss 9.289.28 9.749.74 0 0 0 0 0 0 0 0 DD Door, wd sc typeDoor, wd sc type 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3200.320 ww 9.289.28 23.0223.02 0 0 0 0 0 0 0 0 GG Impact, TEMP, OBSC 0.320Impact, TEMP, OBSC 0.320 ww 9.289.28 23.0223.02 0 0 0 0 0 0 0 0 DD Door, wd sc typeDoor, wd sc type 0.1270.127 ww 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nwnw 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3200.320 nwnw 9.289.28 17.9917.99 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Metal Roof, R 0.405Attic, Metal Roof, R 0.405 --1.591.59 1.221.22 47 47 75 58 149 149 236 181 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 47 0 0 0 149 14 387 0 6 c) AED excursion -1 85 Envelope loss/gain 75 57 1006 778 12 a) Infiltration 0 0 186 55 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 500 Subtotal (lines 6 to 13)75 57 1192 1333 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -75 -57 30 22 14 Subtotal 0 0 1221 1356 15 Duct loads 19%15%0 0 19%15%237 209 Total room load 0 0 1458 1565 Air required (cfm)Air required (cfm)0 0 63 83 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-22 09:06:28Right-Suite® Universal 2019 19.0.20 RSU27054 Page 8...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N 1329Job:Right-J® Worksheet Sep 21, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bed 4 2 Exposed wall 25.5 ft 3 Room height 8.0 heat/coolft 4 Room dimensions ft11.0x14.5 5 Room area 159.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W Block R-9 Wall 0.089 n 2.58 1.65 116 100 259 165 .G Impact 0.320 n 9.28 7.59 16 0 145 118 .W Block R-9 Wall 0.089 e 2.58 1.65 88 88 227 145 .G Impact 0.320 e 9.28 23.02 0 0 0 0 11 G Impact 0.320 e 9.28 23.02 0 0 0 0 W Block R-9 Wall 0.089 s 2.58 1.65 0 0 0 0 G Impact 0.320 s 9.28 9.74 0 0 0 0 D Door, wd sc type 0.127 s 3.69 3.73 0 0 0 0 W Block R-9 Wall 0.089 w 2.58 1.65 0 0 0 0 G Impact 0.320 w 9.28 23.02 0 0 0 0 G Impact, TEMP, OBSC 0.320 w 9.28 23.02 0 0 0 0 D Door, wd sc type 0.127 w 3.69 3.73 0 0 0 0 W Block R-9 Wall 0.089 nw 2.58 1.65 0 0 0 0 G Impact 0.320 nw 9.28 17.99 0 0 0 0 P Frm Wall, 1/2" Gyp B 0.101 -2.94 1.46 0 0 0 0 C Attic, Metal Roof, R 0.405 -1.59 1.22 160 160 253 195 F On Grade Depth, Tile 0.989 -28.68 0.00 160 26 731 0 6 c) AED excursion -25 Envelope loss/gain 1615 599 12 a) Infiltration 351 105 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 0 0 Appliances/other 500 Subtotal (lines 6 to 13)1966 1204 Less external load 0 0 Less transfer 0 0 Redistribution 8 6 14 Subtotal 1974 1210 15 Duct loads 19%15%382 187 Total room load 2356 1396 Air required (cfm)102 74 2020-Sep-22 09:06:29 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1 ...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N 1329Job:Duct System Summary Sep 21, 2020Date:House Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Martire Residence, Groza Builders, IncFor: 10210 Carlton Rd, Ft Pierce, FL 34987 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0in H2O0 Available static pressure in H2O0.70in H2O0.70 Supply / return available pressure 0.448 / 0.252 in H2O in H2O0.448 / 0.252 Lowest friction rate in/100ft0.127in/100ft0.127 Actual air flow cfm953cfm953 Total effective length (TEL) ft552 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st3300.046.7VlFx0x04.00.1291328538hBath 2 st3300.048.0VlFx0x06.00.129100761565cBed 2 st3300.043.2VlFx0x06.00.131102721604cBed 3 st3300.051.6VlFx0x07.00.127891232356hBed 4 st2205.029.9VlFx0x05.00.19123551049hFoyer st1200.026.4VlFx0x07.00.198126721965cGR/Kit/DR st1200.026.2VlFx0x07.00.198126721965cGR/Kit/DR-A st1200.026.6VlFx0x07.00.198126721965cGR/Kit/DR-B st1200.026.2VlFx0x07.00.198126721965cGR/Kit/DR-C 105.013.6VlFx0x05.00.37865851627hLaundry st2205.024.8VlFx0x04.00.19528531006hM Bath st2205.034.8VlFx0x06.00.18778951812hMaster Bedroom st2205.025.4VlFx0x06.00.19478951812hMaster Bedroom-A 100.08.4VlFx0x04.00.413617319hPantry st2205.028.2VlFx0x06.00.19232851634hWIC st3300.050.9VlFx0x04.00.1281646885hWIC 3 st3300.053.1VlFx0x04.00.1271025477hWIC 4 Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st3 Peak AVF 370 330 0.127 472 12.0 0x0 VinlFlx st1 st1 Peak AVF 660 833 0.127 596 16.0 0x0 VinlFlx st2 Peak AVF 382 240 0.187 700 10.0 0x0 VinlFlx 2020-Sep-22 09:06:29 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 2 ...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb4 0x 760 100 196.6 0.128 374 7.0 x0 0 VlFx rt1 rb2 0x 1480 99 198.2 0.127 424 8.0 x0 0 VlFx rt1 rb3 0x 1180 119 196.9 0.128 445 7.0 x0 0 VlFx rt1 rb1 0x 5270 637 198.6 0.127 596 14.0 x0 0 VlFx rt1 rb5 0x 2740 189 74.0 0.341 503 10.0 x0 0 VlFx Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 869 955 0.127 540 18.0 0x0 VinlFlx 2020-Sep-22 09:06:29 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1 ...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N 1329Job:Manual S Compliance Report Sep 21, 2020Date:House Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Martire Residence, Groza Builders, IncFor: 10210 Carlton Rd, Ft Pierce, FL 34987 Cooling Equipment Design Conditions °F76.1Entering coil DB:Btuh18865Sensible gain:°F90.4Outdoor design DB: °F64.0Entering coil WB:Btuh6588Latent gain:°F77.4Outdoor design WB: Btuh25452Total gain:°F75.0Indoor design DB: cfm953Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: 14ACXS030-230A**+CBA27UHE-030-230*++TDRModel:LennoxManufacturer: cfm953Actual airflow: % of load106Btuh20020Sensible capacity: % of load130Btuh8580Latent capacity: %70SHR:% of load112Btuh28600Total capacity: Heating Equipment Design Conditions °F68.1Entering coil DB:Btuh23730Heat loss:°F41.0Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Elec stripEquipment type: Model:Manufacturer: cfm953Actual airflow: °F50Temp. rise:% of load96kW6.7Output capacity: Meets all requirements of ACCA Manual S. Job #: 1329 Performed by Vicki Lynne Nisa for: Martire Residence 10210 Carlton Rd Ft Pierce, FL 34987 Air Calcs, LLC 7550 Hidden Hammock Ln Vero Beach, FL 32966 Phone: 772.800.8413 vickilynne@aircalcs.com Scale: 1 : 248 Page 1 Right-Suite® Universal 2019 19.0.20 RSU27054 2020-Sep-22 09:07:09 ...ft HVAC\10210 Carlton Rd GBI.rup N Level 1 Garage/Workshop Laundry Pantry Foyer Master Bedroom M Bath WIC GR/Kit/DR Bath 2 Bed 3 WIC 3 WIC 4 Hall Bed 2 Bed 4 10 x 10 126 cfm 10 x 10 126 cfm 10 x 10 126 cfm 10 x 10 126 cfm 8 x 8 95 cfm 8 x 4 46 cfm 8 x 4 25 cfm 8 x 8 95 cfm 12 x 8 123 cfm 10 x 6 85 cfm 8 x 4 28 cfm 10 x 6 55 cfm 6 x 6 53 cfm 8 x 4 17 cfm 10 x 6 85 cfm 10 x 6 100 cfm 10 x 6 102 cfm 12 x 12 148 cfm 12 x 12 119 cfm 12 x 12 274 cfm 30 x 18 637 cfm 12 x 12 100 cfm 5 " 6 " 4 " 6 " 6 " 10 " 18 " 14 " 7 " 8 " 7 " 10 " 7 " 16 " 7 " 7 " 4 " 5 " 4 " 12 " 6 " 7 " 6 " 4 " 4 " 7 "