HomeMy WebLinkAboutMANJCalculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Sep-22 09:06:28
Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1
...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N
1329Job:Load Short Form Sep 21, 2020Date:House Vicki Lynne NisaBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Martire Residence, Groza Builders, IncFor:
10210 Carlton Rd, Ft Pierce, FL 34987
Design Information
InfiltrationClgHtg
Blower doorMethod9041Outside db (°F)
3 (partial) / 1Shielding / stories7570Inside db (°F)
50 Pa / 0 cfmPressure / AVF1529Design TD (°F)
L-Daily range
5030Inside humidity (%)
572Moisture difference (gr/lb)
HEATING EQUIPMENT COOLING EQUIPMENT
Make Make Lennox
Trade Trade LENNOX
Model Cond 14ACXS030-230A**
AHRI ref Coil CBA27UHE-030-230*++TDR
AHRI ref 10259390
Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW6.7 Sensible cooling Btuh20020
Heating output Btuh22789 Latent cooling Btuh8580
Temperature rise °F22 Total cooling Btuh28600
Actual air flow cfm953 Actual air flow cfm953
Air flow factor cfm/Btuh0.043 Air flow factor cfm/Btuh0.053
Static pressure in H2O0.70 Static pressure in H2O0.70
Space thermostat Load sensible heat ratio 0.74
ROOM NAME Area Htg load Clg load Htg AVF Clg AVF
(ft²)(Btuh)(Btuh)(cfm)(cfm)
Laundry 53 1627 1014 71 54
Pantry 20 319 87 14 5
Foyer 63 1049 360 46 19
Master Bedroom 247 3624 2456 158 131
M Bath 125 1006 445 44 24
WIC 88 1634 502 71 27
GR/Kit/DR 749 5555 7862 242 419
Bath 2 58 538 198 23 11
Bed 3 137 1383 1604 60 85
WIC 3 30 885 257 38 14
WIC 4 33 477 153 21 8
Hall 47 0 0 0 0
Bed 2 149 1458 1565 63 83
Bed 4 160 2356 1396 102 74
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Sep-22 09:06:28
Right-Suite® Universal 2019 19.0.20 RSU27054 Page 2
...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N
House d 1957 21911 17899 953 953
Other equip loads 1819 966
Equip. @ 0.95 RSM 17997
Latent cooling 6588
TOTALS 1957 23730 24584 953 953
2020-Sep-22 09:06:28
Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1
...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N
1329Job:Building Analysis Sep 21, 2020Date:House Vicki Lynne NisaBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Martire Residence, Groza Builders, IncFor:
10210 Carlton Rd, Ft Pierce, FL 34987
Design Conditions
Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US
1529Design TD (°F)ft26Elevation:
5030Relative humidity (%)°N28Latitude:
Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating
Infiltration:9041Dry bulb (°F)
Blower doorMethod)L(15-Daily range (°F)
3 (partial) / 1Shielding / stories77-Wet bulb (°F)
50 Pa / 0 cfmPressure / AVF7.515.0Wind speed (mph)
Heating
Walls
Glazing
Other
Ceilings
Floors
Infiltration
Ducts
Ventilation
% of loadBtuhBtuh/ft²Component
19.646522.6Walls
4.610899.3Glazing
0.61403.7Doors
13.131051.6Ceilings
27.765783.43.4Floors
11.827931.7Infiltration
15.03555Ducts
00Piping
00Humidification
7.71819Ventilation0Adjustments
100.023730Total
Cooling
Walls
Glazing
Other
Ceilings
Infiltration Ducts
Internal Gains
Ventilation
% of loadBtuhBtuh/ft²Component
15.128511.6Walls
10.8204217.4Glazing
0.71413.7Doors
12.723921.2Ceilings
000Floors
4.48320.5Infiltration
12.72392Ducts
5.1966Ventilation
38.47250Internal gains
00Blower
0Adjustments
100.018865Total
Latent Cooling Load = 6588 Btuh
Overall U-value = 0.209 Btuh/ft²-°F
Data entries checked.
2020-Sep-22 09:06:28
Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1
...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N
1329Job:Component Constructions Sep 21, 2020Date:House Vicki Lynne NisaBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Martire Residence, Groza Builders, IncFor:
10210 Carlton Rd, Ft Pierce, FL 34987
Design Conditions
Location: CoolingHeatingIndoor:
7570Indoor temperature (°F)St Lucie Co Intl, FL, US
1529Design TD (°F)ft26Elevation:
5030Relative humidity (%)°N28Latitude:
Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating
Infiltration:9041Dry bulb (°F)
Blower doorMethod)L(15-Daily range (°F)
3 (partial) / 1Shielding / stories77-Wet bulb (°F)
50 Pa / 0 cfmPressure / AVF7.515.0Wind speed (mph)
Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr
BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft²
Walls
Block R-9 Wall: Blk Wall, Stuc Ext, 8" Thk, R-9 Foam Fill, 1/2" Gyp Bd 8772.589.00.089340n 5611.65
7771.6512152.589.00.089471e
2351.653672.589.00.089142s
7811.6512222.589.00.089474w
621.65982.589.00.08938nw
24171.6537782.589.00.0891466all
Partitions
Frm Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16"
OC Stud
4341.468742.9411.00.101298
Windows
Impact: Impact; NFRC rated (SHGC=0.22); 50% blinds 45°, medium;
50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang
(5.2 ft window ht, 1 ft sep.); 6.9 ft head ht
1187.591459.2800.32016n
35923.01459.2800.32016e
52923.02139.2800.32023e
2249.742139.2800.32023s
35923.01459.2800.32016w
158917.18619.2800.32093all
Impact, TEMP, OBSC: Impact, TEMP, OBSC; NFRC rated (SHGC=0.22);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (0.8 ft window ht, 1 ft sep.); 6.9 ft head ht
4823.0199.2800.3202w
Impact: Impact; NFRC rated (SHGC=0.22); 50% blinds 45°, medium;
50% outdoor insect screen; foreground = green grass (0.23); 15 ft
overhang (5.2 ft window ht, 1 ft sep.); 6.9 ft head ht
40518.02099.2800.32023nw
Doors
Door, wd sc type: Fbrgls Door 753.73743.697.00.12720s
673.73663.697.00.12718w
1413.731403.697.00.12738all
Ceilings
Attic, Metal Roof, R-20 Roof Deck Ins, 1/2" Gyp Bd Int Fnsh 21.00.4051957 23921.2231051.59
2020-Sep-22 09:06:28
Right-Suite® Universal 2019 19.0.20 RSU27054 Page 2
...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N
Floors
On Grade Depth, Tile Flr Fnsh 00657828.700.989229
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Sep-22 09:06:28
Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1
...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N
1329Job:Project Summary Sep 21, 2020Date:House Vicki Lynne NisaBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Martire Residence, Groza Builders, IncFor:10210 Carlton Rd, Ft Pierce, FL 34987
Notes:
Design Information
St Lucie Co Intl, FL, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75
Design TD °F29 Design TD °F15Daily range L
Relative humidity %50Moisture difference gr/lb57
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh18356 Structure Btuh15507
Ducts Btuh3555 Ducts Btuh2392Central vent (57 cfm) 1819 Btuh Central vent (57 cfm) Btuh966
Outside air Outside airHumidification Btuh0 Blower Btuh0
Piping Btuh0Equipment load Btuh23730 Use manufacturer's data n
Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh17997
Method Latent Cooling Equipment Load SizingBlower door
Shielding / stories 3 (partial) / 150 Pa / 0 cfmPressure / AVF Structure Btuh2899
Ducts Btuh1484Central vent (57 cfm) Btuh2205
CoolingHeating Outside air19571957Area (ft²) Equipment latent load Btuh6588
1684216842Volume (ft³)Air changes/hour 0.180.31 Equipment Total Load (Sen+Lat)Btuh24584
Equiv. AVF (cfm) 4988 Req. total capacity at 0.70 SHR ton2.1
Heating Equipment Summary Cooling Equipment Summary
Make Make LennoxTrade Trade LENNOX
Model Cond 14ACXS030-230A**AHRI ref Coil CBA27UHE-030-230*++TDR
AHRI ref 10259390Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW6.7 Sensible cooling Btuh20020Heating output Btuh22789 Latent cooling Btuh8580
Temperature rise °F22 Total cooling Btuh28600Actual air flow cfm953 Actual air flow cfm953
Air flow factor cfm/Btuh0.043 Air flow factor cfm/Btuh0.053Static pressure in H2O0.70 Static pressure in H2O0.70
Space thermostat Load sensible heat ratio 0.74
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Sep-22 09:06:28Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N
1329Job:Right-J® Worksheet Sep 21, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name House Laundry
2 Exposed wall 229.3 ft 21.5 ft
3 Room height 8.6 dft 8.0 heat/coolft
4 Room dimensions ft7.5x7.0
5 Room area 1956.9 ft²52.5 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 356 340 877 561 56 56 144 92
.GG ImpactImpact 0.3200.320 nn 9.289.28 7.597.59 16 0 145 118 0 0 0 0
.WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 510 471 1215 777 60 60 155 99
.GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 16 0 145 359 0 0 0 0
11 GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 23 0 213 529 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 186 142 367 235 0 0 0 0
GG ImpactImpact 0.3200.320 ss 9.289.28 9.749.74 23 19 213 224 0 0 0 0
DD Door, wd sc typeDoor, wd sc type 0.1270.127 ss 3.693.69 3.733.73 20 20 74 75 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 510 474 1222 781 0 0 0 0
GG ImpactImpact 0.3200.320 ww 9.289.28 23.0223.02 16 0 145 359 0 0 0 0
GG Impact, TEMP, OBSC 0.320Impact, TEMP, OBSC 0.320 ww 9.289.28 23.0223.02 2 0 19 48 0 0 0 0
DD Door, wd sc typeDoor, wd sc type 0.1270.127 ww 3.693.69 3.733.73 18 18 66 67 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 nwnw 2.582.58 1.651.65 60 38 98 62 0 0 0 0
GG ImpactImpact 0.3200.320 nwnw 9.289.28 17.9917.99 23 0 209 405 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 298 298 874 434 56 56 165 82
CC Attic, Metal Roof, R 0.405Attic, Metal Roof, R 0.405 --1.591.59 1.221.22 1957 1957 3105 2392 53 53 83 64
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 1957 229 6578 0 53 22 617 0
6 c) AED excursion 0 -18
Envelope loss/gain 15563 7426 1163 319
12 a) Infiltration 2793 832 200 59
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 5 1150 0 0
Appliances/other 6100 500
Subtotal (lines 6 to 13)18356 15507 1363 879
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 18356 15507 1363 879
15 Duct loads 19%15%3555 2392 19%15%264 135
Total room load 21911 17899 1627 1014
Air required (cfm)Air required (cfm)953 953 71 54
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Sep-22 09:06:28Right-Suite® Universal 2019 19.0.20 RSU27054 Page 2...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N
1329Job:Right-J® Worksheet Sep 21, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Pantry Foyer
2 Exposed wall 4.5 ft 12.5 ft
3 Room height 8.0 heat/coolft 9.0 heat/coolft
4 Room dimensions ft4.5x4.5 ft11.5x5.5
5 Room area 20.3 ft²63.3 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3200.320 nn 9.289.28 7.597.59 0 0 0 0 0 0 0 0
.WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 0 0 0 0 0 0 0 0
11 GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 50 29 76 48
GG ImpactImpact 0.3200.320 ss 9.289.28 9.749.74 0 0 0 0 0 0 0 0
DD Door, wd sc typeDoor, wd sc type 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 20 20 74 75
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3200.320 ww 9.289.28 23.0223.02 0 0 0 0 0 0 0 0
GG Impact, TEMP, OBSC 0.320Impact, TEMP, OBSC 0.320 ww 9.289.28 23.0223.02 0 0 0 0 0 0 0 0
DD Door, wd sc typeDoor, wd sc type 0.1270.127 ww 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 nwnw 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3200.320 nwnw 9.289.28 17.9917.99 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 36 36 106 53 63 63 185 92
CC Attic, Metal Roof, R 0.405Attic, Metal Roof, R 0.405 --1.591.59 1.221.22 20 20 32 25 63 63 100 77
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 20 5 129 0 63 13 359 0
6 c) AED excursion -2 -6
Envelope loss/gain 267 76 794 286
12 a) Infiltration 0 0 85 25
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)267 76 879 312
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 267 76 879 312
15 Duct loads 19%15%52 12 19%15%170 48
Total room load 319 87 1049 360
Air required (cfm)Air required (cfm)14 5 46 19
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Sep-22 09:06:28Right-Suite® Universal 2019 19.0.20 RSU27054 Page 3...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N
1329Job:Right-J® Worksheet Sep 21, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Master Bedroom M Bath
2 Exposed wall 39.5 ft 10.0 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft14.5x17.0 ft10.0x12.5
5 Room area 246.5 ft²125.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3200.320 nn 9.289.28 7.597.59 0 0 0 0 0 0 0 0
.WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 64 64 165 105 0 0 0 0
.GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 0 0 0 0 0 0 0 0
11 GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 136 113 291 186 0 0 0 0
GG ImpactImpact 0.3200.320 ss 9.289.28 9.749.74 23 19 213 224 0 0 0 0
DD Door, wd sc typeDoor, wd sc type 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 116 116 299 191 80 78 201 128
GG ImpactImpact 0.3200.320 ww 9.289.28 23.0223.02 0 0 0 0 0 0 0 0
GG Impact, TEMP, OBSC 0.320Impact, TEMP, OBSC 0.320 ww 9.289.28 23.0223.02 0 0 0 0 2 0 19 48
DD Door, wd sc typeDoor, wd sc type 0.1270.127 ww 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 nwnw 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3200.320 nwnw 9.289.28 17.9917.99 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Metal Roof, R 0.405Attic, Metal Roof, R 0.405 --1.591.59 1.221.22 247 247 391 301 125 125 198 153
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 247 40 1133 0 125 10 287 0
6 c) AED excursion -42 16
Envelope loss/gain 2492 966 705 345
12 a) Infiltration 544 162 138 41
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 1000 0
Subtotal (lines 6 to 13)3036 2128 843 386
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 3036 2128 843 386
15 Duct loads 19%15%588 328 19%15%163 59
Total room load 3624 2456 1006 445
Air required (cfm)Air required (cfm)158 131 44 24
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Sep-22 09:06:28Right-Suite® Universal 2019 19.0.20 RSU27054 Page 4...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N
1329Job:Right-J® Worksheet Sep 21, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name WIC GR/Kit/DR
2 Exposed wall 19.5 ft 47.8 ft
3 Room height 8.0 heat/coolft 9.5 heat/coolft
4 Room dimensions ft7.0x12.5 ft749.4x1.0
5 Room area 87.5 ft²749.4 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 100 100 258 165 0 0 0 0
.GG ImpactImpact 0.3200.320 nn 9.289.28 7.597.59 0 0 0 0 0 0 0 0
.WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 190 167 430 275
.GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 0 0 0 0 0 0 0 0
11 GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 0 0 0 0 23 0 213 529
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3200.320 ss 9.289.28 9.749.74 0 0 0 0 0 0 0 0
DD Door, wd sc typeDoor, wd sc type 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 56 56 144 92 62 44 113 72
GG ImpactImpact 0.3200.320 ww 9.289.28 23.0223.02 0 0 0 0 0 0 0 0
GG Impact, TEMP, OBSC 0.320Impact, TEMP, OBSC 0.320 ww 9.289.28 23.0223.02 0 0 0 0 0 0 0 0
DD Door, wd sc typeDoor, wd sc type 0.1270.127 ww 3.693.69 3.733.73 0 0 0 0 18 18 66 67
WW Block R-9 WallBlock R-9 Wall 0.0890.089 nwnw 2.582.58 1.651.65 0 0 0 0 60 38 98 62
GG ImpactImpact 0.3200.320 nwnw 9.289.28 17.9917.99 0 0 0 0 23 0 209 405
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 143 143 419 208
CC Attic, Metal Roof, R 0.405Attic, Metal Roof, R 0.405 --1.591.59 1.221.22 88 88 139 107 749 749 1189 916
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 88 20 559 0 749 48 1372 0
6 c) AED excursion -9 -139
Envelope loss/gain 1100 355 4109 2395
12 a) Infiltration 269 80 538 160
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 5 1150
Appliances/other 0 3100
Subtotal (lines 6 to 13)1369 435 4646 6806
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 8 6
14 Subtotal 1369 435 4654 6811
15 Duct loads 19%15%265 67 19%15%901 1050
Total room load 1634 502 5555 7862
Air required (cfm)Air required (cfm)71 27 242 419
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Sep-22 09:06:28Right-Suite® Universal 2019 19.0.20 RSU27054 Page 5...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N
1329Job:Right-J® Worksheet Sep 21, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Bath 2 Bed 3
2 Exposed wall 5.5 ft 13.0 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft5.5x10.5 ft13.0x10.5
5 Room area 57.8 ft²136.5 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3200.320 nn 9.289.28 7.597.59 0 0 0 0 0 0 0 0
.WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 0 0 0 0 0 0 0 0
11 GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3200.320 ss 9.289.28 9.749.74 0 0 0 0 0 0 0 0
DD Door, wd sc typeDoor, wd sc type 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 44 44 113 73 104 88 228 146
GG ImpactImpact 0.3200.320 ww 9.289.28 23.0223.02 0 0 0 0 16 0 145 359
GG Impact, TEMP, OBSC 0.320Impact, TEMP, OBSC 0.320 ww 9.289.28 23.0223.02 0 0 0 0 0 0 0 0
DD Door, wd sc typeDoor, wd sc type 0.1270.127 ww 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 nwnw 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3200.320 nwnw 9.289.28 17.9917.99 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Metal Roof, R 0.405Attic, Metal Roof, R 0.405 --1.591.59 1.221.22 58 58 92 71 137 137 217 167
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 58 6 158 0 137 13 373 0
6 c) AED excursion -3 152
Envelope loss/gain 363 140 962 823
12 a) Infiltration 76 23 179 53
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 500
Subtotal (lines 6 to 13)438 162 1141 1376
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 12 9 18 13
14 Subtotal 451 171 1159 1390
15 Duct loads 19%15%87 26 19%15%224 214
Total room load 538 198 1383 1604
Air required (cfm)Air required (cfm)23 11 60 85
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Sep-22 09:06:28Right-Suite® Universal 2019 19.0.20 RSU27054 Page 6...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N
1329Job:Right-J® Worksheet Sep 21, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name WIC 3 WIC 4
2 Exposed wall 11.0 ft 5.5 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft6.0x5.0 ft6.0x5.5
5 Room area 30.0 ft²33.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 40 40 103 66 44 44 113 73
.GG ImpactImpact 0.3200.320 nn 9.289.28 7.597.59 0 0 0 0 0 0 0 0
.WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 0 0 0 0 0 0 0 0
11 GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3200.320 ss 9.289.28 9.749.74 0 0 0 0 0 0 0 0
DD Door, wd sc typeDoor, wd sc type 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 48 48 124 79 0 0 0 0
GG ImpactImpact 0.3200.320 ww 9.289.28 23.0223.02 0 0 0 0 0 0 0 0
GG Impact, TEMP, OBSC 0.320Impact, TEMP, OBSC 0.320 ww 9.289.28 23.0223.02 0 0 0 0 0 0 0 0
DD Door, wd sc typeDoor, wd sc type 0.1270.127 ww 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 nwnw 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3200.320 nwnw 9.289.28 17.9917.99 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Metal Roof, R 0.405Attic, Metal Roof, R 0.405 --1.591.59 1.221.22 30 30 48 37 33 33 52 40
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 30 11 315 0 33 6 158 0
6 c) AED excursion -5 -3
Envelope loss/gain 590 177 323 110
12 a) Infiltration 152 45 76 23
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)741 222 399 133
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 741 222 399 133
15 Duct loads 19%15%144 34 19%15%77 20
Total room load 885 257 477 153
Air required (cfm)Air required (cfm)38 14 21 8
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Sep-22 09:06:28Right-Suite® Universal 2019 19.0.20 RSU27054 Page 7...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N
1329Job:Right-J® Worksheet Sep 21, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Hall Bed 2
2 Exposed wall 0 ft 13.5 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft13.5x3.5 ft13.5x11.0
5 Room area 47.3 ft²148.5 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0
.GG ImpactImpact 0.3200.320 nn 9.289.28 7.597.59 0 0 0 0 0 0 0 0
.WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 108 92 238 152
.GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 0 0 0 0 16 0 145 359
11 GG ImpactImpact 0.3200.320 ee 9.289.28 23.0223.02 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3200.320 ss 9.289.28 9.749.74 0 0 0 0 0 0 0 0
DD Door, wd sc typeDoor, wd sc type 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3200.320 ww 9.289.28 23.0223.02 0 0 0 0 0 0 0 0
GG Impact, TEMP, OBSC 0.320Impact, TEMP, OBSC 0.320 ww 9.289.28 23.0223.02 0 0 0 0 0 0 0 0
DD Door, wd sc typeDoor, wd sc type 0.1270.127 ww 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Block R-9 WallBlock R-9 Wall 0.0890.089 nwnw 2.582.58 1.651.65 0 0 0 0 0 0 0 0
GG ImpactImpact 0.3200.320 nwnw 9.289.28 17.9917.99 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Metal Roof, R 0.405Attic, Metal Roof, R 0.405 --1.591.59 1.221.22 47 47 75 58 149 149 236 181
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 47 0 0 0 149 14 387 0
6 c) AED excursion -1 85
Envelope loss/gain 75 57 1006 778
12 a) Infiltration 0 0 186 55
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 500
Subtotal (lines 6 to 13)75 57 1192 1333
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution -75 -57 30 22
14 Subtotal 0 0 1221 1356
15 Duct loads 19%15%0 0 19%15%237 209
Total room load 0 0 1458 1565
Air required (cfm)Air required (cfm)0 0 63 83
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Sep-22 09:06:28Right-Suite® Universal 2019 19.0.20 RSU27054 Page 8...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N
1329Job:Right-J® Worksheet Sep 21, 2020Date:House Vicki Lynne NisaBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Bed 4
2 Exposed wall 25.5 ft
3 Room height 8.0 heat/coolft
4 Room dimensions ft11.0x14.5
5 Room area 159.5 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area Load
number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 W Block R-9 Wall 0.089 n 2.58 1.65 116 100 259 165
.G Impact 0.320 n 9.28 7.59 16 0 145 118
.W Block R-9 Wall 0.089 e 2.58 1.65 88 88 227 145
.G Impact 0.320 e 9.28 23.02 0 0 0 0
11 G Impact 0.320 e 9.28 23.02 0 0 0 0
W Block R-9 Wall 0.089 s 2.58 1.65 0 0 0 0
G Impact 0.320 s 9.28 9.74 0 0 0 0
D Door, wd sc type 0.127 s 3.69 3.73 0 0 0 0
W Block R-9 Wall 0.089 w 2.58 1.65 0 0 0 0
G Impact 0.320 w 9.28 23.02 0 0 0 0
G Impact, TEMP, OBSC 0.320 w 9.28 23.02 0 0 0 0
D Door, wd sc type 0.127 w 3.69 3.73 0 0 0 0
W Block R-9 Wall 0.089 nw 2.58 1.65 0 0 0 0
G Impact 0.320 nw 9.28 17.99 0 0 0 0
P Frm Wall, 1/2" Gyp B 0.101 -2.94 1.46 0 0 0 0
C Attic, Metal Roof, R 0.405 -1.59 1.22 160 160 253 195
F On Grade Depth, Tile 0.989 -28.68 0.00 160 26 731 0
6 c) AED excursion -25
Envelope loss/gain 1615 599
12 a) Infiltration 351 105
b) Room ventilation 0 0
13 Internal gains: Occupants @ 230 0 0
Appliances/other 500
Subtotal (lines 6 to 13)1966 1204
Less external load 0 0
Less transfer 0 0
Redistribution 8 6
14 Subtotal 1974 1210
15 Duct loads 19%15%382 187
Total room load 2356 1396
Air required (cfm)102 74
2020-Sep-22 09:06:29
Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1
...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N
1329Job:Duct System Summary Sep 21, 2020Date:House Vicki Lynne NisaBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Martire Residence, Groza Builders, IncFor:
10210 Carlton Rd, Ft Pierce, FL 34987
CoolingHeating
External static pressure in H2O0.70in H2O0.70
Pressure losses in H2O0in H2O0
Available static pressure in H2O0.70in H2O0.70
Supply / return available pressure 0.448 / 0.252 in H2O in H2O0.448 / 0.252
Lowest friction rate in/100ft0.127in/100ft0.127
Actual air flow cfm953cfm953
Total effective length (TEL) ft552
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv
Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk
st3300.046.7VlFx0x04.00.1291328538hBath 2
st3300.048.0VlFx0x06.00.129100761565cBed 2
st3300.043.2VlFx0x06.00.131102721604cBed 3
st3300.051.6VlFx0x07.00.127891232356hBed 4
st2205.029.9VlFx0x05.00.19123551049hFoyer
st1200.026.4VlFx0x07.00.198126721965cGR/Kit/DR
st1200.026.2VlFx0x07.00.198126721965cGR/Kit/DR-A
st1200.026.6VlFx0x07.00.198126721965cGR/Kit/DR-B
st1200.026.2VlFx0x07.00.198126721965cGR/Kit/DR-C
105.013.6VlFx0x05.00.37865851627hLaundry
st2205.024.8VlFx0x04.00.19528531006hM Bath
st2205.034.8VlFx0x06.00.18778951812hMaster Bedroom
st2205.025.4VlFx0x06.00.19478951812hMaster Bedroom-A
100.08.4VlFx0x04.00.413617319hPantry
st2205.028.2VlFx0x06.00.19232851634hWIC
st3300.050.9VlFx0x04.00.1281646885hWIC 3
st3300.053.1VlFx0x04.00.1271025477hWIC 4
Supply Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
st3 Peak AVF 370 330 0.127 472 12.0 0x0 VinlFlx st1
st1 Peak AVF 660 833 0.127 596 16.0 0x0 VinlFlx
st2 Peak AVF 382 240 0.187 700 10.0 0x0 VinlFlx
2020-Sep-22 09:06:29
Right-Suite® Universal 2019 19.0.20 RSU27054 Page 2
...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N
Return Branch Detail Table
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk
rb4 0x 760 100 196.6 0.128 374 7.0 x0 0 VlFx rt1
rb2 0x 1480 99 198.2 0.127 424 8.0 x0 0 VlFx rt1
rb3 0x 1180 119 196.9 0.128 445 7.0 x0 0 VlFx rt1
rb1 0x 5270 637 198.6 0.127 596 14.0 x0 0 VlFx rt1
rb5 0x 2740 189 74.0 0.341 503 10.0 x0 0 VlFx
Return Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
rt1 Peak AVF 869 955 0.127 540 18.0 0x0 VinlFlx
2020-Sep-22 09:06:29
Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1
...uments\Wrightsoft HVAC\10210 Carlton Rd GBI.rup Calc = MJ8 Front Door faces: N
1329Job:Manual S Compliance Report Sep 21, 2020Date:House Vicki Lynne NisaBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Martire Residence, Groza Builders, IncFor:
10210 Carlton Rd, Ft Pierce, FL 34987
Cooling Equipment
Design Conditions
°F76.1Entering coil DB:Btuh18865Sensible gain:°F90.4Outdoor design DB:
°F64.0Entering coil WB:Btuh6588Latent gain:°F77.4Outdoor design WB:
Btuh25452Total gain:°F75.0Indoor design DB:
cfm953Estimated airflow:%50Indoor RH:
Manufacturer's Performance Data at Actual Design Conditions
Split ACEquipment type:
14ACXS030-230A**+CBA27UHE-030-230*++TDRModel:LennoxManufacturer:
cfm953Actual airflow:
% of load106Btuh20020Sensible capacity:
% of load130Btuh8580Latent capacity:
%70SHR:% of load112Btuh28600Total capacity:
Heating Equipment
Design Conditions
°F68.1Entering coil DB:Btuh23730Heat loss:°F41.0Outdoor design DB:
°F70.0Indoor design DB:
Manufacturer's Performance Data at Actual Design Conditions
Elec stripEquipment type:
Model:Manufacturer:
cfm953Actual airflow:
°F50Temp. rise:% of load96kW6.7Output capacity:
Meets all requirements of ACCA Manual S.
Job #: 1329
Performed by Vicki Lynne Nisa for:
Martire Residence
10210 Carlton Rd
Ft Pierce, FL 34987
Air Calcs, LLC
7550 Hidden Hammock Ln
Vero Beach, FL 32966
Phone: 772.800.8413
vickilynne@aircalcs.com
Scale: 1 : 248
Page 1
Right-Suite® Universal 2019
19.0.20 RSU27054
2020-Sep-22 09:07:09
...ft HVAC\10210 Carlton Rd GBI.rup
N
Level 1
Garage/Workshop
Laundry
Pantry
Foyer
Master Bedroom
M Bath
WIC
GR/Kit/DR
Bath 2
Bed 3
WIC 3
WIC 4
Hall
Bed 2
Bed 4
10 x 10
126 cfm 10 x 10
126 cfm
10 x 10
126 cfm
10 x 10
126 cfm
8 x 8
95 cfm
8 x 4
46 cfm
8 x 4
25 cfm
8 x 8
95 cfm
12 x 8
123 cfm
10 x 6
85 cfm
8 x 4
28 cfm
10 x 6
55 cfm
6 x 6
53 cfm 8 x 4
17 cfm
10 x 6
85 cfm
10 x 6
100 cfm
10 x 6
102 cfm
12 x 12
148 cfm
12 x 12
119 cfm
12 x 12
274 cfm
30 x 18
637 cfm
12 x 12
100 cfm
5 "
6 "
4 "
6 "
6 "
10 "
18 "
14 "
7 "
8 "
7 "
10 "
7 "
16 "
7 "
7 "
4 "
5 "
4 "
12 "
6 "
7 "
6 "
4 "
4 "
7 "