HomeMy WebLinkAboutMain control panel ,Mosquito Control #18, response to commentsSt. Lucie County Mosquito Control
Impoundment # 18
613 N. Causeway Dr.
MAIN CONTROL PANEL
3-POLE, 15A
10kAIC
1-POLE, 20A
10kAIC
MOTOR
STARTER
controls: timeclock, phase -monitor, time -delay, GFl receptacle
3-POLE, 90A
10kAIC MOTOR
1-POLE, 20A controls
10kAIC
3-POLE, 90A
10kAIC
STARTER
timeclock, phase -monitor, time -delay, GFI receptacle
MOTOR
STARTER
Richmond Electric, Inc.
3086 Enterprise Road
Ft. Pierce, FL 34982
(772) 461-1951
chris@richmondelectricinc.com
(3) rx 12 AWG cu
(1) # 12 AWG cu ground
(3) # 4 AWG cu
(1) # 6 A WG cu ground
(3) # 4 AWG cu
(1) d 6 AWG cu ground
Replace (2) existing 20HP motor control panels with (1) larger control panel. (supplied by SLC)
Reuse existing OCP, motor starters, timeclocks, phase monitors, etc.
Existing meter and service lateral to FPL to remain. No changes.
Existing underground conduits to aerator and pump station to remain. No changes.
Existing branch circuit wiring to aerator and pump station to remain. No changes.
3 phase
2 HP
230v
3 phase
20 HP
230v
3 phase
20 HP
230v