HomeMy WebLinkAboutProduct Review; Kohler Automatic Switch Transfer Switch1 B•1iH 4W 4R19✓ V RYfFY
KOHLER® In T Cb n nrin.Model: RXT
Automatic Transfer Switch
ST. Lucie County, Permlitting 100-400 Amps
09001 Model RXT Automatic Transfer Switch
KOHLER. The Model RXT'automatic transfer switch is designed for use
NATIONALLY REGISTERED only with Kohler® generator Sets equipped With RDC2 or DC2
generator set/transfer switch controls. The transfer switch
operation is controlled by the RDC2/DC2 controller.
Covers have been removed for illustration.
Available Models
• 100, 200, and 400 amp standard and service
entrance models are available.
• 150 and 300 amp service entrance models are also
available.
• Combined interface/load management board is
available on single-phase standard and service
entrance models. (Not available on 3-phase or load
center models.)
• 100 amp standard single-phase models are available.
with or without a 16-space load center. Up to 8
tandem breakers can be used for a total of 24
circuits.
• 100amp standard single phase model with a
12-space load center and a NEMA 1 enclosure is
available as a standalone non -configurable spec
(GM85273-SA,.
• See page 7.for more information.
Standard Features
• Allows utility voltage display on the RDC2/DC2 generator
set/transfer switch controller, available exclusively on Kohler®
residential and light commercial generator sets
•, UL listed
o UL 1008 listed, file #E58962
o Models with load centers use UL 67 listed components
• GSA certification, file # LR58301, is available for:
o Standard ATS without load center (single and three-phase)
o Service entrance ATS 100 and 200 amp models
• Corrosion -resistant NEMA 3R aluminum enclosure
o Padlockable
o Approved for indoor or outdoor installation
o ANSI 49 gray
• NEMA 1 enclosure available on 100 amp load center models
• Contactor electrically and mechanically interlocked
• Double throw inherently interlocked design
• 'Contactor manually operable for maintenance purposes
• Silver alloy main contacts
• Transfer switches are 100% equipment rated and can be
applied at the rated current without derating (non -service
.entrance- models)
• Service entrance models include disconnect circuit breaker
on the utility (normal) source side (80% rated)
• Five-year limited warranty
Standard Interface Board
• Standard interface board connects to the Model RDC2 or
DC2 generator set/transfer switch controller.
• Includes a load control contact that provides a 5 minute time
delay for startup of selected loads after transfer to the
emergency source. Use for large motor loads.
Combined Interface/ Load
Management Board
• Optional combined interface] load management board
replaces the standard interface board and connects to the
Model RDC2 or DC2 generator set/transfer switch controller.
• The combined board is available on single-phase standard
and service entrance models.
(Not available on 3-phase or load center models.)
• The combined board automatically manages up to six
residential loads:
o Up to four customer -supplied power relay modules can
be connected for management of non -essential
secondary loads.
o _ Two HVAC relays are included for control, of two
independent air conditioner loads.
G11-140 (Model RXT Automatic Transfer Switch) 3/20g Pagel
Specifications
Codes and Standards
Standard Interface Board
Controller interface connections
A and B
#20 AWG shielded twisted -pair
Belden 9402 or 8762 or equivalent
Controller interface connections
PWR and COM
#12-20 AWG
(see ATS Installation Manual)
Load control contact rating
10 A @ 250 VAC
Load control connections
#12-18 AWG
Note: For combined interface/load management board
specifications, see page 3.
Environmental Specifications
Operating temperature
- 20°C to 70-C (- 4°F to 158°F)
Storage temperature
- 40°C to 85°C (- 40-F to 185-F)
Humidity
5 to 950% noncondensing
The ATS meets or exceeds the requirements of the following
specifications:
• Underwriters Laboratories UL 1008, Standard for Automatic
Transfer Switches for Use in Emergency Systems, file
# E58962
• Underwriters Laboratories UL 508, Standard for Industrial
Control Equipment
• GSA certification available, file #LR58301(not available for
150, 300; or 400 amp service entrance or 100 amp load
center models). Must be selected when the transfer switch
is ordered.
• NFPA 70, National Electrical Code
• NFPA 110, Emergency and Standby Power Systems
• NEMA Standard 1C10-1993, AC Automatic Transfer
Switches
Cable Sizes
AL/CU UL-Listed Solderless Screw Type Terminals for External Power Connections
Switch
Range of Wire Sizes, Cu/AI
Size,
Normal and Emergency
Load
Neutral
Ground
Amps
Switch
Phases
Standard
1
(1) #14 - 1/0 AWG
(1) #14-1/0 AWG
(5) #12 to 250 KCMIL (Cu) or
(5) #10 to 250 KCMIL (An
12-or 16-
s ace load
P
center
1
(1) #14-1/0 AWG
per customer -supplied
circuit breaker
(26) #4 - 14 AWG or
2 #14 - 1/0 AWG or
()
9 #6 - #14 AWG
( )
(NEMA 1)
(1) #6 - 210 AWG
(4) #14 - 110 AWG
100
16-space
load center
1
(1) #14-1/0 AWG
per customer -supplied
(26) #4 - 14 AWG or
(2) #14 - 1/0 AWG or
(NEMA 3R)
circuit breaker
(1) 2/0 AWG
Service
1
Normal: (1) #12-2/0 AWG
(1) #14-1/0 AWG
(5) #12 to 250 KCMIL (Cu) or
Entrance
Emerg: (1) #14-1/0 AWG
(5) #10 to 250 KCMIL (Al),
3-Phase
3
(1) #14-1/0 AWG
(1) #14 -1/0 AWG
(3) #4 AWG - 600 KCMIL
(4).#14-1/0 AWG
(6) 110 AWG - 250 KCMIL
(9) #14 - #6 AWG
150
Service
1
Normal: (1) #4-300 KCMIL
(1) #6 -250 KCMIL
(5) #12 to 250 KCMIL (Cu)or
200
Entrance
Emerg: (1) #6 - 250 KCMIL
(5) #10 to 250 KCMIL (Al)
200
Standard
1
(1) //6 AWG - 250 KCMIL
(1) #6 - 250 KCMIL
O #12 to 250 KCMIL Cu or
5 ( )
(9) #14 - #4 AWG
3-Phase
3
(5) #10 to 250 KCMIL (AQ
(4) #14 - 1/0 AWG
300
400
Service
Entrance
i
Normal:: (1) #1 - 600 KCMIL
or (2) #1- 250 KCMIL
(2) #6 - 250 KCMIL
(3) #4 AWG - 600 KCMIL
(6) #6 - 3/0 AWG
Emerg: (2) #6 - 250 KCMIL
(6) 1/0 AWG - 250 KCMIL
Standard
1
3-pole
3
(2) #6-250 KCMIL
(2) #6-250 KCMIL
400
208-240 V
(3) #4 AWG -600 KCMIL
(6) #6 - 3/0 AWG
(6)1/0 AWG - 250 KCMIL
3 or 4 le
pole
3
(1) #4-600 KCMIL
(1) #4-600 KCMIL
480V
(2) 1/0-250 KCMIL
(2) 1/0-250KCMIL
Note: Data is subject to change. Refer to the transfer switch dimension drawings and wiring diagrams.for planning and installation.
GII-140(Model RXIAutomaticTransfer Spritch) =Og Paget
Optional Combined Interface/Load Management Board
The RXT transfer switch is available with either a standard
interface board or a combined interface/load management
board. The combined board allows load management as
described below.
Load Management
• The combined load management board disconnects
non -critical loads to prevent generator overload, in
compliance with NEC.
• The combined load management board monitors generator
current and frequency to determine when to add or shed
loads. This monitoring prevents frequency drops that can
damage valuable electronics like computers and televisions.
• Load management allows the use of a smaller generator set.
Operation
• Loads are automatically added or shed based on generator
capacity.
• The load control system uses dynamic logic to prevent
shedding important loads unnecessarily when air
conditioning, refrigerator, or water pump motors start
(patent pending).
• The load management board and generator communicate to
provide smart power management. The time to shed loads
decreases as each load is shed to quickly adapt to critical
power requirements.
• Load shed power level and frequency setpoinis can be
adjusted using a personal computer (laptop) and Kohler®
SiteTech- software, which is only available to Kohler -
authorized distributors and dealers.
Load Shed Specifications
Priority Setting
• Loads are added and shed according to their priority. Load 1
is the top priority, which is added first and shed last. Load 6
is the lowest priority.
Less critical loads can be turned off automatically when
essential appliances are running.
Load priorities are hard -wired at installation.
Viewing Load Shed Outputs with OnCueo
Plus
• Use Kohler's OnCue® Plus Generator Management System
(sold separately) to view load status (On or Oft) for loads
connected to the load shed relays.
• Use OnCueG Plus to remotely monitor when loads are shed
or added.
• The load shed outputs can be labeled in OnCue® Plus.
Current Transformer
• The combined load management board option includes a
400 amp current transfomer (CT) for load monitoring.
• A larger diameter CT is available for applications that require
larger cables:
• A 500 amp CT is available for use with a 60RCL generator.
• See the table below for current transformer specifications
and optional kit numbers.
Connection
Rating
Connection
Pilot Relays*
125VAC, 10 A total (general purpose)
#12-20 AWG
120VAC, 125VA (pilot duty)
HVAC Relays (qty. 2)
125VAC, 10 A (general purpose)
#12-20 AWG
120VAC, 125VA (pilot duty)
RBUS Communication and Power
Use Belden #9402 or equivalent 20 AWG
Connections to the RDC2/DC2
0.5 A @ 12 VDC
shielded, twisted -pair communications
controller
cable #
* Four (4) pilot relays are provided for customer -supplied normally closed load -switching contactors/relays. The combination of four load relay
outputs cannot exceed 10 amps total current draw. Kohler® power relay modules are recommended.
# For long distances, use an equivalent shielded, twisted -pair cable for RBUS connections and individual 12-20 AWG wires (qty. 2) for power
connections.
Current Transformer Specifications
Ratio
Outer Diameter
Inner Diameter
Service Part
(Amps -VAC)
mm fn.)
mm (in.)
Number
Sales Kit Part Number
CTAvailability
400:3
63.5 (2.5)
28.7 (1.13)
GM83929
N/A
Included with combined
board
400:3
111.8 (4.4)
57.2 (2.25)
GM17250
GM17250-KP1-QS
Sold Separately
500:3
171.5 (6.75)
108.0 (4.25)
GM60264
GM17250-KP2-QS
Sold Separately
(use with 60RCL)
G71-140 (Model RXT Automatic Transfer Switch) 3/20g Page 3
Withstand and Close -On Ratings (WCR)
Service Entrance Transfer Switch Ratings
The service entrance transfer switch is factory -equipped with a normal source disconnect circuit breaker.
Suitable for the control of motors, electric discharge lamps, tungsten filament lamps and electric heating equipment where the sum
of motor full -load ampere ratings and the ampere ratings of other loads do not exceed the ampere rating of the switch and the
tungsten load does not exceed 30 percent of switch rating.
Switch Rating, Amps *
WCR, RMS Symmetrical Amps at 240 VAC
100, 150, 200
22,000
300,400
35,000
* Continuous load current not to exceed 80% of switch rating.
Contactor Ratings with Coordinated Circuit Breakers
Single-phase transfer switches are UL listed at 240 VAC maximum. Three-phase transfer switches are rated at 480 VAC
maximum. The following table lists contactor withstand current ratings (WCR) for 100- 400 ampere non -service entrance rated
switches with specific manufacturer's circuit breakers per UL and Canadian safety standards. Suitable for the control of motors,
electric discharge lamps, tungsten filament lamps and electric heating equipment where the sum of motor full -load ampere ratings
and the ampere ratings of other loads do not exceed the ampere rating of the switch and the tungsten load does not exceed 30
percent of switch rating.
The transfer switch is rated for use on a circuit capable of delivering not more than the RMS symmetrical amperes maximum as
shown in the tables below, but no greater than the interrupting capacity of the selected breaker.
WCR
Ratings with Specific Manufacturer's Molded -Case Circuit Breakers
Switch
Number
WCR, RMS
Rating,
Voltage,
of Poles/
Symmetrical
Maximum
Amps
max..
Phases
Amps
Manufacturer
Type or Class
Size, Amps
100
240
2 pole/
1 phase
10,000
Any Breaker *
Any Breaker (0.025 seconds max.)
—
250
240
1 Fn le/
10,000
Any Breaker *
Any Breaker (0.025 seconds max.)
—
FCL
100
JGS, JGH, JGC, JGU, JGX, JBD, JD, HJD, JDC,
250
Eaton
LCL, LCLA
LDC, CLDC, KDB, Im, Him, ImC, LD, CLD,
400
HLD, CHLD
CEDE, HED4, HED6
125
CFD6, FD6A, FXD6, HFD6, HFXD6, HHFD6,
HHFXD6
250
100
200
480
3 pole/
p
4 pole/
3 phase
30,000
ITE/Slemens
CJD6
400
SEL, SEP, THLC1, PE_E, PE_N, PE_H, PE_L
150
THL02
225
General Electric
SFH, SFL, SFP, PE_E, PE_N, PE_H, PE_L
250
SGH, SGL, SGP, FGN, FGH, FGL, FGP, PG_E,
400
PG_N, PG_H, PG_L, PG_P
HG, HJ, HL, HR
150
JJ, JL, JR
250
Schneider
LG, LEI, LL, LR
400
* For higher WCR values, contact the
factory for additional specific breaker ratings.
G11-140(Model RXTAutomatic Transfer Switch) 3/20g Page4
WCR
Ratings with Specific Manufacturer's Molded -Case Circuit Breakers
Switch
Number
WCR, RMS
Rating,
Voltage,
of Poles/
Symmetrical
Maximum
Amps
max.
Phases
Amps
Manufacturer
Type or Class
Size, Amps
ABB
T5, T6
600
CHKD, CKD, DK, HKD, KD, KDB, KDC,
LATRIPAC, LCL
400
Eaton
CHLD, CLD, CLDC, HLD, LD, LDB, LDC
600
HMDL, MDL, NB TRI- PAC
800
General Electric
FGH, FGL, FGN, FGP, SGHA
600
GJD6, HHJD6, HHJXD6, HJD6, HJGA, HJXD6,
JD6, JXD2, JXD6, SGJD6, SHJD6, SJD6, NJGA,
400
300
400
240
2 pole/
1 phase
35,000
Siemens
LJGA
CLD, HHLD, HHLXD, HLD, HLGA, HLXD, LD,
LLGA, LXD, NLGA, SCLD, SHLD, SLD
600
CMD, HLMD, HLMXD, HMD, HMG, HMXD, LMD,
LMG, LMXD, MD, MXD, NMG, SCMD, SHMD,
800
SMD
LA, LC, LE, LH, U, LX, DU
400
Square D
DG, DJ, DL, LC, LE, U, LX, LXI
600
Merlin Gerin
CJ400H, CJ400L, CJ40ON
400
GJ600H,CJ60ON
600
Schneider
LJ, LL, LR
600
General Electric
SEL, SEP, PE_N, PE_H, PE_L
150
240
3 pole/
3 phase
4 pole/
3 phase
65,000
SFL, SFP, PE_N, PE_H, PE_L
250
SGL, SGP
400
SGL, SGP, FGL, FGP
600
HJD, JDC, JGC, JGH, JGU, JGX
250
CHLD4, CLD, HLD4, CLDC, LDC, KDC, HKD,
400
Eaton
CHMDL4, GMDL4
CHLD6, HDL6, CHMDL6, CMDL6, CLDC, CLD6,
600
LDC6,CLDG6
CHMDL8, HMDL8, MDL8, CMDL8
800
CFD6, HFD6, HFXD6, HHFD6, HHFXD6
250
CJD6
400
400
480
3 pole/
3 phase
4 pole/
50,000
ffE/Siemens
CLD6, HHLD6, H14LXD6, HLD6, HLXD6
600
CMD6, MD6, HMD6, HMXD6, MXD6
800
SEL, SEP, PE-N, PE H. PE L
- -
150
SFL, SFP, PE_N, PE_H, PE_L
250
3 phase
SGL, SGP
400
General Electric
FGL, FGP, SGL, SGP, PG H, PG , PG-N,
600
PG_P - -L
HJ, HL, HR
150
JJ, JL, JR
250
Schneider
U. LL, LR
600
MJ
800
100,000
General Electric
PG H, PG_L, PG P
600
G11-140 (Model RXT Automatic Transfer Switch) 3f20g Page 5
Dimensions and Weights
Note: Always use the transfer switch dimension drawing for planning and installation. Weights and dimensions may vary for
different configurations. See the Operation/Installation Manual or your local distributor for dimension drawings.
Transfer switch weights and dimensions shown in the table do not include packaging. To estimate the shipping weight, add 3 kg
(5 lbs.) or 10% (whichever is larger) to the weight shown.
Amps
Description,
Dimensions H x W x D mm in. 't
Shipping
Weight i
k9 (lb.)
Dimension
Drawing
Single phase
623 x 335 x 180 (24.5 x 13.2 x 7.1)
7 (15)
ADV-8688
With 12-space load center (NEMA 1)
610 x 330 x 154 (24.0 x 13.0 x 6.0)
12 (26)
ADV-9186
With 16-space load center (NEMA 1)
610 x 330 x 154 (24.0 x 13.0 x 6.0)
12 (26)
ADV-9187
100
With 16-space load center
614 x 335 x 180 (24.2 x 13.2 x 7.1)
8 (18)
ADV-9188
Three phase
682 x 462 x 228 (26.8 x 18.2 x 9.0)
14 (30)
ADV-8689
Service entrance (ASE)
734 x 416 x 175 (28.9 x 16.4 x 6.9)
10 (22)
ADV-9046
Service entrance (CSE)
754 x 416 x 175 (29.7 x 16.4 x 6.9)
14 (30)
ADV-8797
150
Service entrance (ASE)
734 x 416 x 175 (28.9 x 16.4 x 6.9)
12 (26)
ADV-9046
Service entrance (ASE)
734 x 416 x 175 (28.9 x 16.4 x 6.9)
12 (26)
ADV 9046
Service entrance (CSE)
754 x 416 x 175 (29.7 x 16.4 x 6.9)
16 (36)
ADV-8798
200
Single phase
623 x 335 x 180 (24.5 x 13.2 x 7.1)
7 (15)
ADV-8688
Three phase
682 x 462 x 228 (26.8 x 18.2 x 9.0)
14 (30)
ADV-8689
300
Service entrance
1075 x 559 x 329 (42.3 x 22.0 x 12.9)
46 (101)
ADV-8694
Single phase.
1067 x 559 x 329 (42.0 x 22.0 x 12.9)
55 (120)
ADV-8691
3-Pole1208- 240 volts
1067 x 559 x 329 (42.0 x 22.0 x 12.9)
41 (90)
ADV-8692
400
3-Pole/480 volts
1222 x 610 x 343 (48.1 x 24.0 x 13.5)
59 (130)
ADV-8693
4-Pole
1222 x 610 x 343 (48.1 x 24.0 x 13.5)
59 (130)
ADV-8693
Service entrance
1075 x 559 x 329 (42-3 x 22.0 x 12.9)
46 (101)
ADV-8694
t Depth does not include the padlock hasp on the front of the enclosure.
# Transfer switch weights are approximate and do not include packaging.
Note: Enclosures are type NEMA 3R except as noted.
G71-140 (Model RXT Automatic Transfer Switch) 3120g Pages
Accessories
❑ Auxiliary position -indicating contacts
• One closed on normal position and one closed on emergency
position
• Form C contacts rated 15 A @ 250 VAC
❑ Power relay modules
• 50 amp DPST power relay mounted in a NEMA type 3R
enclosure
• Use up to four modules with the combined interface/load
management board
• UL/cUL listed
• Dimensions: 172 x 233 x 92 mm (6.8 x 9.2 x 3.6 in.)
• For more information, see specification sheet G6-1.43
❑ Status indicator kit for standard interface board
• LEDs indicate normal and emergency source availability
and contactor position
• Mounts on the outside of the RXT enclosure
• View transfer switch status without removing enclosure
cover
• An overhang on the enclosure protects the indicator
panel and ribbon cable opening
• Dimensions: 92 mm x 42 mm (3.62 in. x 1.65 in.)
• Connects to the standard interface board only
• For more information on the status indicator kit, see
specification sheet G11-123
❑ Status indicator kit for combined interface/load
management board
• LEDs indicate normal and emergency source availability
and contactor position
• Dual color LEDs for each load indicate load status
(powered or shed) and flash during atest
• Load shed test button allows the operator to cycle the
load shed relays in order of priority (when generator is in
RUN mode)
• Mounts on the outside of the RXT enclosure
• View transfer switch and load status without removing
enclosure cover
• An overhang on the enclosure protects the indicator
panel and ribbon cable opening
• Dimensions: 183 mm x 42 mm (7.20 in, x 1.65 in.)
• Connects to the combined interface/load management
board only
q. For more information on the status indicator kit, see
specification sheet G11-123
❑ Auxiliary circuit breaker (service entrance models only)
• 15 amp single -pole type QO circuit breaker
• Mounts on a bracket inside the enclosure
Available Models
All Model RXT transfer switches are standard -transition 60 Hz automatic transfer switches. Letters in parentheses refer to,the
model designation code described on the last page.
Am
Description
Connections
Voltages
Poles
Phases
WCR §
RMS Symmetrical Amps
208 (C)
240 (F)
480 (M)
Standard (A)
•
2 (N)
1
10,000
Standard, with 16-space load
center (B) ¶
•
2 (N)
1
10,000
100
Standard, with 12 space
load center"
•
2 (N)
1
10,000
Service entrance (ASE, CSE)
•
2 (N)
1
22,000
Standard, 3-phase (A)
•
•
•
3 m or 4 (V)
3
30,000
150
Service entrance (ASE)
•
2 (N)
1
22,000
Standard (A)
•
2 (N)
1
10,000
200
Service entrance (ASE, CSE)
•
2 (N)
1
22,000
Standard, 3-phase (A)
•
•
•
3 (T) or 4 (V)
3
30,000
300
Service entrance (ASE)
•
2 (N)
1
35,000
Standard (A)
•
2 (N)
1
50,000
400
Service entrance (ASE)
•
2 (N)
1
35,000
Standard, 3-phase (A)
•
•
•
3 (r) or 4 M
3
50,000
§ Withstand and close -on rating. See pages 3-5 for WCR information and specific breaker ratings.
¶ With 16-space load center and NEMA t or NEMA 3R enclosure. Up to 8 tandem breakers can be used, for a maximum of 24 circuits.
*" GM85273-SA with 12-space load center and,NEMA 1 enclosure:
Note: Combined interface board is available on single-phase standard or service entrance models. (Not available on 3-phase or load center models.)
G11-140 (Model RXT Automatic Transfer Switch) 3/20g Page 7
KOHLER® Phone 9 CO., Kohler,Wisconsina9253044 USA
Phone 920-457-444i, Fax 920-459-1'646
For the nearest sales and service outlet in the
US and Canada, phone 1-800-544-2444
KOHLERPower.com
Model Designation
Model Controls Voltage Poles Enclosure Current Rating Connections
Record the transfer switch model designation in the boxes: The transfer switch model designation. defines ratings and
characteristics as explained below.
Sample Model Designation: FW-JFNC-02O0A
Model
RXT Kohler Automatic Transfer Switch
Controls
J: Interface for RDC2/DC2 Controller
(standard or combined interface/load
management)
Voltage/Frequency
C: 208 Volts/60 Hz (3-phase only)
F: 240 Volts/60 Hz
M: 480 Volts/60 Hz (3-phase only)
Number of Poles/Wires
N: ' 2-pole, 3-wire, solid neutral (120/240 V only)
T. 3-pole, 4-wire, solid neutral
V. 4-pole, 4-wire, switched neutral
Availability is subject to change without notice. Kohler Co. reserves the
right to change the design or specifications without notice and without
any obligation or liability whatsoever. Contact your local Kohler®
generator distributor for availability. (9 2014 Kohler co. AN rights reserved.
Gii-M (Model RXTAutomatic Transfer Switch) 3/20g Pages
Enclosure
A: NEMA 1
C: NEMA 3R
* NEMA 1 enclosure is available on 100 amp load center models only.
Current Rating
0100: 100amps 0300: 300 amps
0150: 150 amps 0400: 400 amps-
0200: 200 amps
Connections
A No load center
B: With load center (100 amp single-phase only)
ASE: Service entrance rated'
CSE: Service entrance rated with CSA certification
(100/200 amps only)
DISTRIBUTED BY: