HomeMy WebLinkAboutElectrical PlansEXIST. UTILITYPAD-MTD XFMR208Y/120V 3PH 4W300KVA 4.01%Z~20.8KA AFCEXIST. ENCLOSEDGENERATORCUMMINS DQHAB300KW/375KVA208Y/120V 3PH1041 FLA, ~10.4KA AFCEXIST. METERAND CT CABINET(HARDEES)EXIST.CONCRETESLABEXIST. MDP(HARDEES,INTERIOR)800A MLOEXIST. METER ANDCT CABINET (LOVES)12PB AND/OR CONDUITBODIES (QTY AS REQ'D,SIZED PER NEC)NEW HARDEESEM DISC SW400A 3P HDNEMA 3R DISCSW, FUSED AT400A, CLASS L~9.4KA AFCEXIST. 1200A STANDBYFEEDER: 4-3"C EACH WITH4-350KCMIL CU AND 3/0 BJ CU*EXIST 1200ABKR, SQ DPOWERPACTEXIST. 1600ALOVES SERVICEEXIST. 800A HARDEESSERVICE: 4-3"C EACHWITH 4-4/0 AL** CONTRACTOR SHALLVERIFY EXIST SERVICE ANDFEEDER CONDUCTORS ANDEXIST CONDITIONSNG5EXIST 4"CONC CURB67EXIST. MDP(LOVES)1600A MLO**N.O.NG8MAX UTILITY PEAK DEMANDS AS OF AUG 2020:222KVA, 617A - UTILITY XFMR154KVA, 428A - LOVES SERVICE62KVA, 172A - HARDEES SERVICEEXIST. ATS(LOVES)399NEW TAP FEEDER:2-2"C EACH WITH 4-3/0 AND1-3/0G (THWN-2 Cu CABLES)NEW STANBY FEEDER (HARDEES):2-2"C EACH WITH 4-3/0 AND 1-3/0G(THWN-2 Cu CABLES)NEW ATS(HARDEES)4-POLE~14.2KA AFC11NGN1212EXIST. 800A MDP FEEDER:3-3"C EACH WITH4-400KCMIL AL, 4/0G AL*ISOLATE EM NEUTRALFROM GROUNDBOND NORMALNEUTRAL TO GROUNDCONFIRMEXIST MBJPROVIDE 3/4"C. WITH 2#12CONDUCTORS FOR START/STOPSIGNAL FROM NEW ATS.4QTY OF TICK MARKS INDICATEQTY OF CONDUITS (TYP.) KEYED NOTES1.PROVIDE NEW AND REPLACE LUGS AS REQUIRED TOACCOMMODATE NEW TAP FEEDER ON SOURCE 2(EMERGENCY) INCOMING POWER CONNECTIONS.2.PROVIDE NEW PLAQUE ON EXTERIOR OF GENERATORENCLOSURE, NEAR GENERATOR BREAKER, WHICHREADS "GENERATOR PROVIDES BACKUP POWER TOMULTIPLE AUTOMATIC TRANSFER SWITCHES".3.PROVIDE NEW PLAQUES ON FRONT EXTERIOR ANDSIDE EXTERIOR OF EXISTING ATS WHICH READS"WARNING: EMERGENCY FEEDER TAP INSIDE".4.INTERCEPT EXISTING GENERATOR START/STOPSIGNAL CONDUCTORS AT EXISTING ATS. CONNECTNEW ATS GENERATOR START/STOP CONDUCTORSSUCH THAT THE ENGINE START CONTACTS FOR BOTHATS'S (LOVES AND HARDEES) ARE IN PARALLEL WITHEACH OTHER.5.CONFIRM EXIST GENERATOR NEUTRAL IS NOTBONDED TO GROUND AT GENERATOR.6.DEMO 800A FUSED MAIN SERVICE DISCONNECTSWITCH (HARDEES). PRESERVE FEEDERS ANDGROUNDING ELECTRODE CABLES FORRE-CONNECTION TO NEW ATS IN SAME LOCATION.7.1600A, 3-POLE, 208Y/120V, 3PH, 4W, SLAB-MOUNTED,NEMA 3R ENCL, SERVICE ENTRANCE RATED ATS.OVERCURRENT PROTECTION PROVIDED FOR NORMALSOURCE ONLY; EMERGENCY SOURCE CONNECTED TO2000A MOLDED CASE SWITCH W/O TRIP UNIT. EATONPOWER-FRAME TYPE ATS #ATVIMGC31600BRU.8.ATS ENCLOSURE REMOVABLE SIDE PANELS FORACCESSING CABLE CONNECTIONS.9.EXISTING GROUNDING ELECTRODE SYSTEM TOREMAIN (TYP).10.UNKNOWN EXISTING PIPING STUB UP. DO NOT MOUNTDISCONNECT DIRECTLY ABOVE STUB UP.11.800A, 4-POLE ATS, 208Y/120V 3PH 4W, SERVICEENTRANCE RATED WITH 800A TRIP SERVICEENTRANCE BREAKER, MOLDED CASE SWITCH FORGENERATOR, NEMA 3R ENCL. INSTALL AT SAMELOCATION AS HARDEES DISCONNECT SWITCH.PROVIDE SPECIAL LUGS AS REQUIRED TOACCOMMODATE EXISTING ALUMINUM CONDUCTORS.BASIS OF DESIGN: MOLDED CASE TYPE TRANSFERSWITCH, EATON HMDL.12.ENLARGED GROUNDING CONDUCTOR PROVIDED INTHIS FEEDER TO FUNCTION AS A GROUNDINGELECTRODE BONDING JUMPER FOR THE TWOSERVICES LOCATED ON THE SAME MULTi-TENANTBUILDING.#EXIST.GENERATOREXIST.XFMRLOVESHARDEESEXIST. METERAND CT CABINET(HARDEES)EXIST. METERAND CT CABINET(LOVES)EXIST. ATS(LOVES)EXIST. MDP(LOVES)EXIST. GASSERVICE10HARDEES EMDISC SWWOMENSRESTROOMAPPROX. 8'CLG HTMENSRESTROOMAPPROX. 8'CLG HTCOOLERFRZ/COOLERFRZ/COOLEREXIST. MDP(HARDESS)RETAILAPPROX. 10'CLG HTSTORAGENO CLGSTORAGENO CLGSTORAGEAPPROX. 8'CLGKITCHENAPPROX. 8'CLGRETAILAPPROX. 10'CLG HTSHOWERSELEC RMLB FITTINGSAT WALLPENETRATIONLB FITTINGSAT WALLPENETRATIONPROVIDE CONC PAD FORNEW ATS. TOTAL SIZE OFCONCRETE PAD UNDER ATSSHALL EXTEND BEYOND ATSOUTSIDE DIMENSIONSAPPROX. 2" EACH WAY(30"Wx22"Dx4"H FOR BASISOF DESIGN SWITCH)FEEDER ROUTEDABOVE CLGHARDEESEXIST. METERAND CT CABINET(HARDEES)DEMO EXIST. 800AMAIN DISC. (HARDEES)EXIST. RECEPTACLE,DOOR BELL BUTTON, ANDEM LIGHT FIXTUREADJACENT TO DOORJAMB TO REMAIN.DEMO EXIST. CONC.CURB AS REQ'D TOACCOMMODATENEW PADHARDEES STANDBY POWER FORT PIERCE, FLORIDA 34945 200 SOUTH KINGS HIGHWAY8/21/2020 PERMIT SETABBREVIATIONSAAMPEREAFCAVAILABLE FAULT CURRENTAFFABOVE FINISHED FLOORALALUMINUMATSAUTOMATIC TRANSFER SWITCHAWGAMERICAN WIRE GAUGEBKRBREAKERCCONDUITCKTCIRCUITCLGCEILINGCOORD COORDINATECuCOPPERDISCDISCONNECTEBJEQUIPMENT BONDING JUMPEREGCEQUIPMENT GROUNDING CONDUCTOREMEMERGENCYEMTELECTRICAL METAL TUBINGENCLENCLOSURE, ENCLOSEDEXISTEXISTINGG, GNDGROUNDGECGROUNDING ELECTRODE CONDUCTORHDHEAVY DUTYIMCINTERMEDIATE METAL CONDUITJBJUNCTION BOXKVAKILO-VOLT AMPEREKWKILO-WATTLFMCLIQUIDTIGHT FLEXIBLE METAL CONDUITMBJMAIN BONDING JUMPERMCBMAIN CIRCUIT BREAKERMINMINIMUMMLOMAIN LUGS ONLYMTDMOUNTEDNNEUTRALN.O.NORMALLY OPENNECNATIONAL ELECTRICAL CODENFNON-FUSEDNTSNOT TO SCALEOEMORIGINAL EQUIPMENT MANUFACTURERPPOLEPH, ØPHASEPNLPANELPRIPRIMARYQTYQUANTITYRGSRIGID GALVANIZED STEELRMCRIGID METAL CONDUITSECSECONDARYSWSWITCHTYPTYPICALUG UNDERGROUNDUNOUNLESS NOTED OTHERWISEVVOLTVAVOLT-AMPEREVACVOLTS ALTERNATING CURRENTWWIRE OR WATTW/WITHWPWEATHERPROOFXFMRTRANSFORMERTHE FOLLOWING NOTES ARE APPLICABLE TO ALL ELECTRICAL SHEETS.1.ALL WORK SHALL COMPLY WITH THE REQUIREMENTS OF TEH LOCAL AUTHORITYHAVING JURISDICTION AND THE APPLICABLE CODES, INCLUDING:1.1.2017 FLORIDA BUILDING CODE (6TH EDITION)1.2.2014 NATIONAL ELECTRICAL CODE (NFPA 70)1.3.2013 NATIONAL FIRE ALARM AND SIGNALING CODE (NFPA 72)2.ALL MATERIALS PROVIDED SHALL BE NEW AND UNUSED (UNLESS FURNISHED BYTHE OWNER), LISTED UNDER AN UL CATEGORY, AND SHALL BE A PRODUCT OF AMANUFACTURER REGULARLY ENGAGED IN PRODUCING SUCH EQUIPMENT ANDMATERIALS FOR AT LEAST FIVE YEARS.3.UPON COMPLETION OF INSTALLATION , CONTRACTOR SHALL SCHEDULE ADEMONSTRATION IN THE PRESENCE OF THE OWNER TO CONFIRM THE FOLLOWING:3.1.AUTOMATIC START OF GENERATOR UPON ATS LOSS OF NORMAL POWER(SIMULATED BY OPENING SERVICE ENTRANCE BREAKER ON ATS).3.2.AUTOMATIC TRANSFER TO EMERGENCY POWER.3.3.AUTOMATIC RE-TRANSFER BACK TO NORMAL POWER AFTER DETECTION OFACCEPTABLE NORMAL VOLTAGE PLUS 15 MINUTE DELAY (PROGRAMMABLE).3.4.AUTOMATIC GENERATOR SHUTDOWN AFTER 10 MINUTE COOL DOWN(PROGRAMMABLE; SHALL BE SET TO COMPLY WITH EXISTING GENERATORMANUFACTURER RECOMMENDATION).4.PENETRATIONS OF NEMA 3R ENCLOSURES SHALL BE WATERTIGHT.5.INTERIOR CONDUIT SHALL BE EMT, IMC, OR RMC. EXTERIOR CONDUIT SHALL BERMC.6.CONTRACTOR SHALL VERIFY LOCATIONS OF EXISTING EQUIPMENT AND UTILITIESBEFORE COMMENCING WORK.7.ALL MATERIALS PROVIDED SHALL BE NEW AND UNUSED, LISTED UNDER AN ULCATEGORY, AND SHALL BE A PRODUCT OF A MANUFACTURER REGULARLYENGAGED IN PRODUCING SUCH EQUIPMENT AND MATERIALS FOR AT LEAST FIVEYEARS.8.ALL NEW CONDUCTORS SHALL BE 600V RATED, WITH THWN-2 INSULATION. PROVIDESTRANDED COPPER CONDUCTORS, EXCEPT NO. 12 MAY BE SOLID COPPER. MIN.CONDUCTOR SIZE IS NO. 12 AWG.9.ALL EQUIPMENT ENCLOSURES, RACEWAY SYSTEMS, ETC., SHALL BE GROUNDED.10.PATCH NEW AND EXISTING CONSTRUCTION AT ALL OPENINGS CUT (OR DAMAGED)FOR INSTALLATION OF NEW ELECTRICAL WORK. ADDITIONALLY, PATCH NEW ANDEXISTING CONSTRUCTION (TO MATCH ORIGINAL CONDITIONS) AT ALL REMAININGOPENINGS CAUSED BY THE REMOVAL OR RELOCATION OF EXISTING WORK.11.SEAL ALL PENETRATIONS THROUGH FIRE RATED ASSEMBLIES WITH FIRE-STOPPINGMATERIAL AS MANUFACTURED BY 3M, DOW CORNING, CHASE TECHNOLOGY,TREMCO, THOMAS AND BETTS, OR 0.Z. GEDNEY. FIRE-STOPPING METHOD SHALL BEUL APPROVED FOR THE INTENDED ASSEMBLY, AND ACCEPTABLE TO THE LOCALAUTHORITY HAVING JURISDICTION. ALL MATERIALS SHALL BE INSTALLED PERMANUFACTURER'S RECOMMENDATIONS.12.ENGRAVED PLASTIC NAMEPLATES SHALL BE PROVIDED FOR ATS, DISCONNECTSWITCH, AND EXISTING ITEMS AS NOTED.13.UNLESS SPECIFIED BY GOVERNING AUTHORITY HAVING JURISDICTION, POWERWIRING SHALL BE COLOR CODED AS FOLLOWS:A.FOR 208Y/120V, 3-PHASE, 4-WIRE SYSTEMS:PHASE A = BLACKPHASE B = REDPHASE C = BLUENEUTRAL = WHITEGROUND = GREEN14.CONDUIT FITTINGS SHALL BE ZINC PLATED STEEL. EMT FITTINGS SHALL BECONCRETE TIGHT, SET SCREW TYPE.15.PROVIDE CONDUIT BUSHINGS AT TERMINATION POINT OF ALL CONDUIT.GRAPHIC SCALEGENERAL ELECTRICAL NOTES AND SPECS