Loading...
HomeMy WebLinkAboutHVAC Load CalculationsStephen Blauvelt Florida Room Addition HVAC Load Calculations for Stephen Blauvelt 113 N. Las Olas, Hutchinson Island Ft. Pierce, Florida Prepared By: Residential Energy Calc's Friday, March 16, 2007 Rhvac - Residential $ Light Commercial HVAC Loads Kerr Humphrey Elite Software Development, Inc. Stephen Blauvelt Florida Room. Addition Port Saint Lucie, FL 34983 Page 2 Pro ect Report General Project Information Project Title: Stephen Blauvelt Florida Room Addition Designed By: Larry Rynearson Project Date: Friday, March 16, 2007 Client Name: Stephen Blauvelt Client Address: 113 N. Las Olas, Hutchinson Island Client City: Ft. Pierce, Florida Company Name: Residential Energy Calc's Design Data Reference City: Fort Pierce, Florida Daily Temperature Range: Medium Latitude: 27 Degrees Elevation: 25 ft. Altitude Factor: 0.999 Elevation Sensible Adj. Factor: 1.000 Elevation Total Adj. Factor: 1.000 Elevation Heating Adj. Factor: 1.000 Elevation Heating Adj. Factor: 1.000 Outdoor Outdoor Indoor Indoor Grains Dry Bulb Wet Bulb Rel.Hum Dry Bulb Difference Winter: 42 0 30 72 3 Summer: 90 78 50 75 61 Check Figures Total Building Supply CFM: 321 CFM Per Square ft.: 1.864 Square ft. of Room Area: 172 Square ft. Per Ton: 208 Volume (ft?) of Cond. Space: 1,376 Air Turnover Rate (per hour): 14.0 Building Loads Total Heating Required With Outside Air: 6,299 Btuh 6.299 MBH Total Sensible Gain: 7,426 Btuh 85 % Total Latent Gain: 1,295 Btuh 15 % Total Cooling Required With Outside Air: 8,721 Btuh 0.73 Tons (Based On Sensible + Latent) 0.83 Tons (Based On 75% Sensible Capacity) Notes Calculations are based on 8th edition of ACCA Manual J. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads. Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc. KAri'Humphrey Stephen Blauvelt Florida Room Addition Port Saint Lucie, FL 34983 Page 3 Miscellaneous Report System 1 Fedders.Or Equivalent Outdoor Outdoor Indoor Indoor Grains Input Data Dry Bulb Wet Bulb ReI.Hum Dry$ulb Difference Winter. 42 0 30 72 3.44 Summer: 90 78 50 75 61.09 Duct Sizing Inputs Main Trunk Runouts Calculate: Yes Yes Use Schedule: Yes Yes Roughness Factor. 0.00300 0.01000 Pressure Drop: 0.1000 in.wg./l00 ft. 0.1000 in.wg./l00 ft. Minimum Velocity: 650 ft./min 450 ft./min Maximum Velocity: 900 ft./min 750 ft./min Minimum Height: 0 in. 0 in. Maximum Height: 0 in. 0 in. Outside Air Data Winter Summer Infiltration: 0.410 AC/hr 0.220 AC/hr Above Grade Volume: X 1,376 Cu.ft. X 1,376 Cu.ft. 564 Cu.ft./hr 303 Cu.ft./hr X 0.0167 X 0.0167 Total Building Infiltration: 9 CFM 5 CFM Total Building Ventilation: 23 CFM 23 CFM —System 1--- Infiltration & Ventilation Sensible Gain Multiplier: 16.49 = (1.10 X 0.999 X 15.00 Summer Temp. Difference) Infiltration & Ventilation Latent Gain Multiplier: 41.50 = (0.68 X 0.999 X 61.09 Grains Difference) Infiltration & Ventilation Sensible Loss Multiplier: 32.97 = (1.10 X 0.999 X 30.00 Winter Temp. Difference) Rhvac - Residential & Light Commercial HVAC Loads KenHumphreyStephen Elite Software Development, Inc. Blauvelt Florida Room Addition Port Saint Lucie, FL 34983 Page 4 Load Preview Report Sens Lat Net Sens Win Sum Sys Duct Scope Area Gain Gain Gain Loss CFM CFM CFM Size Building: 0.73 Net Tons, 0.83 Recommended Tons, 208 ft.21Ton, 6.30 MBH Heating 7771 Building 172 7,426 1,295 8,721 6,299 62 321 321 S stem 1: 0.73 Net Tons, 0.83 Recommended Tons, 208 Urron, 6.30 MBH Heating System 1 172 7,426 1,295 8,721 6,299 62 321 321 8x8 Ventilation 378 952 1,330 756 AED Excursion 405 406 Duct Loads 456 135 590 768 Zone 1 _ 172 6,187 209 6,396 4,775 62 321 321 1-Florida Room Addition 172 6,187 209 6,396 4,775 62 321 321 3-6 Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc. Kerr Humphrey Stephen Blauvelt Florida Room Addition Port Saint Lucie, FL 34983 Page 5 Total Building Summary Loads Component Area Sen Lat Sen: s . Total Description Quan x }Loss Gain Gain' Gain 1A-cb-o: Glazing -Single pane, operable window, clear, 48 1,556 0 2,326 2,326 metal frame with break, u-value 1.08 1A-cm-o: Glazing -Single pane, operable window, clear, 42 1,600 0 3,268 3,268 metal frame no break, u-value 1.27 12C-Osm: Wall -Frame, R-13 insulation in 2 x 4 stud 70 241 0 173 173 cavity, no board insulation, siding finish, metal studs 16C-19: Roof/Ceiling-Under attic or knee wall, Vented 172 253 0 337 337 Attic, No Radiant Barrier, White or Light Color Shingles, Any Wood Shake, Light Metal, Tar and Gravel or Membrane, R-19 insulation 22A-ph: Floor -Slab on grade, No edge insulation, no 20 815 0 0 0 insulation below floor, any floor cover, passive, heavy moist soil Subtotals for structure: 4,465 0 6,104 6,104 People: 0 0 0 0 Equipment: 0 0 0 Lighting: 0 0 0 Ductwork: 768 135 456 590 Infiltration: Winter CFM: 9, Summer CFM: 5 310 209 83 292 Ventilation: Winter CFM: 23, Summer CFM: 23 756 952 378 1,330 AED Excursion: 0 0 405 405 Total Building Load Totals: 6,299 1,295 7,426 8,721 Check Figures ;. Total Building Supply CFM: 321 CFM Per Square ft.: 1.864 Square ft. of Room Area: 172 Square ft. Per Ton: 208 Volume (ft) of Cond. Space: 1,376 Air Turnover Rate (per hour): 14.0 Building Loads Total Heating Required With Outside Air: 6,299 Btuh 6.299 MBH Total Sensible Gain: 7,426 Btuh 85 % Total Latent Gain: 1,295 Btuh 15 % Total Cooling Required With Outside Air: 8,721 Btuh 0.73 Tons (Based On Sensible + Latent) 0.83 Tons (Based On 75% Sensible Capacity) Notes Calculations are based on 8th edition of ACCA Manual J. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads. Rhvac -Residential &Light Commercial HVAC Loads Elite Software Development, Inc. Ken Humphrey Stephen Blauvelt Florida Room Addition Port Saint Lucie, FL 34983 r Page 6 System 1 Fedders Or Equivalent Summary Loads Component Area> Sen Lat Sen Total r Descri tion r 4 - '3, _.-y'. " ;Quam"4 Loss _. Gain °, Game Gairi` IA-cb-o: Glazing -Single pane, operable window, clear, 48 1,556 0 2,326 2,326 metal frame with break, u-value 1.08 1A-cm-o: Glazing -Single pane, operable window, clear, 42 1,600 0 3,268 3,268 metal frame no break, u-value 1.27 12C-Osm: Wall -Frame, R-13 insulation in 2 x 4 stud 70 241 0 173 173 cavity, no board insulation, siding finish, metal studs 16C-19: Roof/Ceiling-Under attic or knee wall, Vented 172 253 0 337 337 Attic, No Radiant Barrier, White or Light Color Shingles, Any Wood Shake, Light Metal, Tar and Gravel or Membrane, R-19 insulation 22A-ph: Floor -Slab on grade, No edge insulation, no 20 815 0 0 0 insulation below floor, any floor cover, passive, heavy moist soil Subtotals for structure: 4,465 0 6,104 6,104 People: 0 0 0 0 Equipment: 0 0 0 Lighting: 0 0 0 Ductwork: 768 135 456 590 Infiltration: Winter CFM: 9, Summer CFM: 5 310 209 83 292 Ventilation: Winter CFM: 23, Summer CFM: 23 756 952 378 1,330 AED Excursion: 0 0 405 405 System 1 Fedders Or Equivalent Load Totals: 6,299 1,295 7,426 8,721 Check Figures Supply CFM: 321 CFM Per Square ft.: 1.864 Square ft. of Room Area: 172 Square ft. Per Ton: 208 Volume (ft3) of Cond. Space: 1,376 Air Turnover Rate (per hour): 14.0 System Loads .. Total Heating Required With Outside Air. 6,299 Btuh 6.299 MBH Total Sensible Gain: 7,426 Btuh 85 % Total Latent Gain: 1,296 Btuh 15 % Total Cooling Required With Outside Air: 8,721 Btuh 0.73 Tons (Based On Sensible + Latent) 0.83 Tons (Based On 75% Sensible Capacity) Notes Calculations are based on 8th edition of ACCA Manual J. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads. Rhvac - Residential & Light Commercial HVAC Loads OR Elite Software Development, Inc. Ken Humphrey Stephen Blauvelt Florida Room Addition Port Saint Lucie, FL '34983 ° Page 7 System 1, Zone 1 Summary Loads (Average Load Procedure for Rooms) Component Area _ Sen Lat Sen Total Description Gain `Gain': .Gain 1A-cb-o: Glazing -Single pane, operable window, clear, 48 1,556 0 2,326 2,326 metal frame with break, u-value 1.08 1A-cm-o: Glazing -Single pane, operable window, clear, 42 1,600 0 3,268 3,268 metal frame no break, u-value 1.27 12C-Osm: Wall -Frame, R-13 insulation in 2 x 4 stud 70 241 0 173 173 cavity, no board insulation, siding finish, metal studs 16C-19: Roof/Ceiling-Under attic or knee wall, Vented 172 253 0 337 337 Attic, No Radiant Barrier, White or Light Color Shingles, Any Wood Shake, Light Metal, Tar and Gravel or Membrane, R-19 insulation 22A-ph: Floor -Slab on grade, No edge insulation, no 20 815 0 0 0 insulation below floor, any floor cover, passive, heavy moist soil Subtotals for structure: 4,465 0 6,104 6,104 People: 0 0 0 0 Equipment: 0 0 0 Lighting: 0 0 0 Ductwork: 0 0 0 0 Infiltration: Winter CFM: 9, Summer CFM: 5 310 209 83 292 System 1, Zone 1 Load Totals: 4,775 209 6,187 6,396 Check Figures Supply CFM: 321 CFM Per Square ft.: 1.864 Square ft. of Room Area: 172 Square ft. Per Ton: 313 Volume (ft3) of Cond. Space: 1,376 Air Turnover Rate (per hour): 14.0 Zone•Loads Total Heating Required: 4,775 Btuh 4.775 MBH Total Sensible Gain: 6,187 Btuh 97 % Total Latent Gain: 209 Btuh 3 % Total Cooling Required: 6,396 Btuh 0.53 Tons (Based On Sensible + Latent) 0.55 Tons (Based On 75% Sensible Capacity) Notes Calculations are based on 8th edition of ACCA Manual J. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads. Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc. Ken -Humphrey & Stephen Blauvelt Florida Room Addition Port Saint Lucie, FL 34983 `� Page 8 Detailed Room Loads - Room 1 - Florida Room Addition (Average Load Procedure) General Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 17.2 ft. System Number. 1 Room Width: 10.0 ft. Zone Number: 1 Area: 172.0 sq.ft. Supply Air. 321 CFM Ceiling Height: 8.0 ft. Supply Air Changes: 14.0 AC/hr Volume: 1,376.0 cu.ft. Required Vent.: 0 CFM Number of Registers: 3 Actual Winter Vent.: 23 CFM Runout Air: 107 CFM Percent of Supply.: 7 % Runout Duct Size: 6 in. Actual Summer Vent.: 23 CFM Runout Air Velocity: 544 ft./min. Percent of Supply: 7 % Design Loss: 0.100 in.wg./100 ft. Actual Winter Infil.: 9 CFM Actual Loss: 0.190 in.wg./100 ft. Actual Summer Infil.: 5 CFM Area -U- Htg. Sen Clg Lat Sen IItem Denription -Quantity Value <HTM = Loss - HTM 'Gain` Gain N -Wall-12C-Osm 10 X 8 56 0.115 3.5 193 2.5 0 138 E -Wall-12C-Osm 10 X 8 14 0.115 3.5 48 2.5 0 35 N -GIs-1A-cb-o shgc-0.75 100%S 24 1.080 32.4 778 32.0 0 768 (2) E -GIs-1A-cb-o shgc-0.75 41%S (2) 24 1.080 32.4 778 64.9 0 1,558 E-GIsAA-cm-o shgc-0.75 23%S (2) 42 1.270 38.1 1,600 77.8 0 3,268 UP-Ceil-16C-19 17.2 X 10 172 0.049 1.5 253 2.0 0 337 Floor-22A-ph 20 ft..Per. 20 1.358 40.7 815 0.0 0 0 Subtotals for Structure: 4,465 0 6,104 Infil.: Win.: 9.4, Sum.: 5.0 160 1.938 310 0.519 209 83 Room Totals: 4,775 209 6,187 Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc. Karr Humphrey Stephen Blauvelt Florida Room Addition Port Saint Lucie, FL 34983Page 9 System 1 Room Load Summary Htg Htg Run Run Cig Clg Clg Air, Room Area Sens Nom Duct' Duct Sens Lat Nom - Sys No Name SF Btuh CFM Size Vel Btuh Btuh CFM CFM —Zone 1- 1 Florida Room 172 4,775 62 3-6 544 6,187 209 321 321 Addition Ventilation 756 378 952 AED Excursion 405 Duct Loads 768 456 135 System 1 total 172 6,299 62 7,426 1,295 321 321 System 1 Main Trunk Size: 8x8 in. Velocity: 769 ft./min Loss per 100 ft.: 0.158 in.wg I -Cooling System Summary - Cooling Sensible/Latent Sensible - Latent Total Tons _ Split Btuh Btuh Btuh Net Required: 0.73 85% / 15% 7,426 1,295 8,721 Recommended: 0.83 75% / 25% 7,426 2,475 9,901 Actual: 0.83 75% / 25% 7,500 2,500 10,000 Equipment Data Heating System Cooling System Type: ROOM UNIT ROOM UNIT Model: AE7U10W7E AE7U10W7E Brand: FEDDERS OR EQUIVALENT FEDDERS OR EQUIVALENT Description: HEAT/COOL UNIT HEAT/COOL UNIT Efficiency: 9.4 EER 9.4 EER Sound: Capacity: 8.2K BTU 10K BTU Sensible Capacity: n/a 7,500 Btuh Latent Capacity: n/a 2,500 Btuh