Loading...
HomeMy WebLinkAboutO'Quinn signed print A-5Ceramic Tile Shall be installed in accordance with ANSI A108.1, A108.4, A108.5 A108.6, A108.11, A118.1, A118.3, A136.1, & A137.1. Fiber mat reinforced backer shall be used behind wall applied ceramic tiles in the tub and shower areas and conform to ASTM C1325. Per Durock, cement board exceeds ASTM 01325. Gypsum Note Gypsum board shall conform to ASTM C22, C475, C514, C1002, C1047 C1177, C1178, 01278, C1396, or C1658 and installed per FBC residential code. Per USG, Wallboard conforms to C1396. Gypsum Board & Gypsum Panel Products Gypsum board and gypsum panel products shall be applied at right angles or parallel to framing members. All edges and ends of gypsum board and gypsum panel products shall occur on framing members, except those edges and ends that are perpendicular to the framing members. Interior gypsum board shall not be installed where it is directly exposed to weather or to water. Wall and ceiling gypsum board shall be fastened with screws spaced at 12"o,c. Screws for attaching gypsum board and gypsum panel products to wood framing shall be Type W or Type S in accordance with ASTM C1002 andshall penetrate thewood not less than 5/8" inch (15.9mm) Gypsum board and Gypsum panel products shall be attached to cold formed steel framing less than 0.033" (1mm) thick shall be Type S in accordance with ASTM C1002 or bugle head style in accordance with ASTM C1513 and shall penetrate the steel not less than 3/8" to 0.112" 0 mm to 3mm) thick shall be in accordance with ASTM 0954 or bugle head style in accordance with ASTM 1513. Screws for attaching gypsum board or gypsum panel products to structural insulated panles shall penetrate the wood structural panle facing not less than 7/16"o.c. (11.1 mm). Gypsum board used as the base orbacker for adhesive application of ceramic tile or other required nonabsorbent finish material shall conform to ASTM C1396, C1178, C1278. Use of water resistant gypsum backing board shall be permitted on ceilings. Water resistant gypsum board shall not be installed over a Class 1 or Class 2 vapor retarder in a shower or tub compartment. Cut or exposed edges, including those at wall intersections, shall be sealed as recommended by the manufactuer. Water resistant gypsum backing board shall not be used where there will be direct exposure to water, or areas subject to continuous high humidity. Cold Formed Steel Note Cold formed steel framing supporting gypsum board and gypsum panel products shall be not less than 1 1/4" (32mm) wide in the least dimension. Non Load bearing cold formed steel framing shall comply with AISI S220 and ASTM C645, Section 10. Load bearing cold formed steel framing shall comply with AISI 5200 and ASTM C955, Section 8. Wood Framing Note Wood framing supporting gypsum board and gypsum panel products shall be not less than 2" (51 mm) nominal thickness in th least dimension except that wood furring strips not less than 1 " by 2" (25mm x 51 mm) nominal dimension shall be permitted to be used over solid backing or framing spaced not more than 24 `o.c. (610mm) Wire Lath Attachment Over wood framing the paper backed wire lath shall be installed over one layer of approved plastic house wrap. Lath shall be attached horizontal framing members with 1.5" roofing nails and to vertical wood framing members with 6d common nails or 1 roofing nails driven to penetration of not less then 3/4" of an inch, or 1 wire staples driven flush with the plaster base. Staples shall have crowns not less than 3/4" and shall engage not less than three strands of lath and penetrate the wood framing members not less than 3/4if. The fasteners must penetrate the wood framing members not less than 3/4. Fasteners shall be 7" o.c. max. EXTERIOR CEILING & SOFFIT NOTE 7/8" Stucco finish over 3/8" high ribbed galv. wire lath fastened to framing members with No. 11 guage nails with 1 3/4"embed. with 3/8- dia. head 6""o.c. max. edges to be tied and nailed at 9""o.c. Install one layer of 15# felt to framing prior to installing ribbed lath INTERIOR WALL FRAMING NOTE Interior non bearing walls to be 2 x 4 studs 24"o.c. Spruce, Pine, Fir (SPF) #3 Grade lumber or better or metal studs (25 Ga.) Crimper may be used in lieu of screws. BUCK ATTACHMENT NOTES AT DOORS USE P.T. PINE OR SPRUCE AND ATTACH TO BLOCK WITH 1/4"" DIA. TAPCONS INTO C.B.S. SET AT 6" FROM CORNERS AND AT 12"o.c. MAX. AT WINDOWS USE P.T. PINE OR SPRUCE AND ATTACH BUCKS TO BLOCK WITH 8d CASED HARD COIL NAILS OR ""T" NAILS" 4" FROM ENDS AND 12"o.c. USE WOOD SHIMS MINIMUM DURING DOOR INSTALLATION THRESHOLD NOTE At egress door (see floor plan) the max. hgth. of the threshold shall be 1 /2" STRUCTURAL NOTES: All reinforcing steel shall be high strength billet steel and shall conform to ASTM A-615 grade 60 specifications. Lap continuous reinforcing 48 bar diameters or 30" in beams and in slabs. Lap bottom steel over supports and top steel at midspan. Hook discontinuous ends of all top bars. Reinforcing steel shall have a minimum of 1 " concrete cover, or as follows: BOTTOM TOP SIDES Beams: 1 1/2- 1 1/2" 1 1/2" Slab on Grade: 1 1/2- 1 Structural Poured: 3/4" 3/4`" _ Poured Walls:_ _ 3/4" Slabs exposed to the weather 3/4" 1" _ Reinforcing steel shall be detailed and fabricated in accordance with the "Manual of Standard Practice of Detailing Reinforcing Concrete Structures" and the current "ACI Building Code 318" All structural steel shall conform to current ASTM Specification A-36 All wood in contact with masonry shall be pressure treated or approved seperating material. All dimensions shall be verified in field by the contractor. If there are any discrepancies the Architect or Engineer shall be notified before proceeding. No slump over 5" shall be permitted for any structural concrete without the Architect or Engineer approval. All Design and Construction shall be inaccordance with the current American Concrete Institute (ACI). and the American Institute of Steel Construction (AISC), The Florida Building Code and all applicable local codes. Structural Concrete shall attain a minimum ultimate compressive strength (Fc') in 28 days as follows: Column Footing and Wall Footing: 3000 p.s.i. Column and walls from foundation to roof: see column schedule. All other concrete: 3000 p.s.i. Footing sizes and reinforcing are based on allowable soil bearing capacity of 2000 p.s.i. All footings shall bear in virgin soil. If this is not the case, the Architect or Engineer shall be notified before proceeding with the work. Timber (Heavy Timber Construction) (a) Truss manufacturer shall submit a signed and sealed shop drawings by a registered Engineer. (b) Wood rafters to have a Stress Grade of Fb=1200 p.s.i. (c) Roof members should be secured to the beams or other structural components with hurricane anchors for wind uplift. All wood members shall have a minimum fiber stress in bending of 1200 p.s.i. with 1/360 max. deflection. All bolted connections shall be 1/2" Cadmium plated or better. Lag bolts to be used only in shear connections with minimum 4" threaded penetration past steel plate. Lag bolted conditions shall be drill tapped no larger than the internal thread diameter and shall not be hammer driven. Under Girder Trusses provide equal number of studs as girder plys at frame bearing locations GENERAL REQUIREMENTS All work to be as per the current edition of the Florida Building Code and meet or exceed all applicable local requirements. General contractor is responsible for all labor, materials, utilities, testing, waste removal, storage, securing of site, accomodation, transport/freight, and all other cost related to the completion of this project., unless explicitly identified here. Owner is responsible for all municipal related charges such as impact fees, and water connection, except building permit fees, which are to be included in the construction bid. General contractor to check all drawings for errors and ommissions and bring them to the attention of the architect prior to starting any work, or ordering any materials of the respective division of work. If such errors and ommissions are not reported in writingto the architect, any resulting damages or costs shall be born entirely by the general contractor. Architect is not responsible for the contractors method or means of construction. General contractor is to keep the site in a clean and safe state through out the course of construction. On building turnover, general contractor to clean all surfaces so as to be free of dust, grease, stains, scuffs, etc. Unless otherwise noted, the installation of specified hardware shall conform to the manufacturers instructions and standard practice. All plans and drawings are not considered complete until they have been reviewed and approved by the St. Lucie County Building Department and the building permit has been issued. SHEATHING NAILING NOTES Nailing Pattern Zone 1: 8d at 6"o.c. field & 4"o.c. edges Zone 2: 8d at 4"o.c. edges & field Zone 3: 8d at 4-o.c. edges & field Pneumatic Nails Pneumatic or mechanicaly driven nails will be accepted under the following conditions: Min. nails size 8d or larger ring shank with Min. shank diameter: .113 Min. Length: 2" Min. Head Diameter: .280 Full Round Min. Ring Diameter .012 over shank dia. Min. 16 to 20 Rings per Inch Note Gun nails shall be permitted as an acceptable fastener from any manufacturer Wood screws meeting the same size requirement may be used in lieu of nails without comment Nailin-a Schedule ROOF & FLOOR DIAGRAM Use sheathing with #8 gun nails at 6"o.c. at supported panel edges and #8 gun nails at 6"o.c. at intermediate supports. ROOF SHEATHING TO GABLE END FRAME Use #8 gun nails at 4o.c. EXTERIOR SHEATHING Use #8 gun nails at 4"o.c. at panel edges and #8 gun nails at 4"o.c. at panel top and bottom and 6"o.c. in field 0 0 GENERAL ROOFING NOTES Roofing to be composed of and attached to pre manufactured wood trusses as follows: Felt underlayment (min. ASTM 0 226 Type II) with 4"" min. side and end laps, fasten with coorosion resistant annular ring shank nails at 6o.c. in laps and in staggered rows spaced 12""o.c. in field. If roof pitch is < 4/12 install (2) layers 15# felt. If roof pitch is 4/12 or greater, install (1) layer 30# felt. 5/8" c.d.x. sheathing or equal installed with staggered joints & GI clips, nailed to trusses with 8d corrosion resistant annular ring shank nails spaced max. 6"o.c. throughout, except max. 4"o.c. at gable ends. All roof trusses are to be pre -manufactured assemblies provided by a licensed wood truss fabricator with seperate drawings and data prepared for actual project conditions by a Florida registered professional engineer certified for truss design. Any deviation from the proposed plans as shown regarding placement or bearing shall be brought to the attention of the truss engineer prior to fabrication of the trusses. The truss manufacturer's certified layout shall govern after fabrication. The handling, erection, and fixing of wood trusses shall be in accordance with the specifications contained on the certified mfgr's. drawings and data. All engineered headers and truss hangers to be provided by the truss manufacturer. Splitting or cracking of structural components due to installation of hardware is not permitted. Unless otherwise noted, the installation of specified hardware shall conform to the truss manufacturers installation instructions and standard practice. 8" x 16" C.M.U. WITH CELLS FILLED WITH GROUT & (1) #5 VERT. i..'. DOWEL J J Q X Lu P.T. 2 x 6 AT (3) SIDES OF &A OPENING, FASTEN TO BLOCK AS NOTED. 1/2" x 6"" REDHEADS WITH MIN. a 2" x 1/8"WASHER 12" FROM ENDS 0 AND 16-o.c. MAX. Cr 00 DOOR HEAD 0 1/4" x 2 3/4" TAPCONS STAGGERED 24"o.c. Garage Door Buck Detail Bottom Cord of Truss 2 x 4 top plate 1/2- gyp. d.w. 2 x 4 studs 24-o.c. No. 3 Stud Grade 2 x 4 p.t. sill plate wood base Cased Hard Coil Nails 12"o.c. max. 0.00'-1�-F.F.E. Concrete Foundation Interior Wail Section corner bars at beam (outside only) (2) corner bars at footing (min.) - vert. dowel lapped with wall reinforcing, all laps 30' (min.) in grout filled cell Corner Reinforcing Detail 3/8" continuous bead of caulk (back bedding) behind - buck to prevent liquid passage set flange in continuous bead of caulk across the entire face of buck stucco finish Jt Approval perimeter caulk CBS 0 1/4" max, struct. shim Attach p.t. bucks Min. 1 1/4" embedment o caulk 12""o.c. w C Manufacturer at windows and min. Typ. Alum, window Q�.E jamb or sliding glass d d': 1 1/2""embedment at doorjamb oN - NOTE: Method of attachment and 4 ° d d sl. gl. doors waterproofing procedures are the M =14 �oo.= same at poured concrete sill. . . • . LL oou,E � Coat Bucks with Protecto LWM200 Waterproofing ° co co N U N d 1/2"" drywall S.H. Windows ; m ocn U o PGT Industries R20 Spray Cl) n m +/- 50.0 ° Foam Insu r' M . T.O.B. into concrete AT7/101-04L U � Q stucco finish Jt Approval perimeter caulk O 0 1/4" max, struct. shim Attach p.t. bucks Building Rated with 8d coil nails at caulk 12""o.c. Model Number Manufacturer attach as per Typ. Alum, window manufacturers jamb or sliding glass product approvals doorjamb T o0 Co NOTE: Method of attachment and Gunable sealants shall comply with waterproofing procedures are the ASTM C 920 Class 25 grade or same at poured concrete sill. greater for proper joint expansion LL and contraction Coat Bucks with Protecto LWM200 Waterproofing after they have been installed and Chaulked Head: 12" max. from corners & 30"o.c, max. Jambs: Window &. Door Flashing Detail at CBS Wall Includes Buck Attachment Method Alum, window frame 3/8" continuous bead of caulk (back bedding) behind shim to prevent liquid passage 1/4" struct. shi set flange in continuous bead of caulk across the entire face of buck perimeter caulk stucco finish all corner bars to be the same size, number, and spacing as horizontial bars in footing, beams, and walls corrosive resistant Tapcon concrete srews installed as specified in window manufacturers product approval window sill ° d Protecto LWM200 precast Coating on Outside face conc. sill and Janbs of Openings all Sides min. 8' Gunable sealants shall comply with ASTM C 920 Class 25 grade or greater for proper joint expansion and contraction Typical Precast Conc. Sill Detail Coat Bucks with Protecto LWM200 Waterproofing after they have been installed and Chaulked 2`" dia. Pipe Set balla from app Galv. Cc (4) 1/4" Tapcons ^- L, Cap Jnc. t•ounclatlon 1/2- d.wJ 1 x 4 p.t. Firestop Two Course Perimeter Beam with (1) #5 Rebar in each course, Filled with Grout 1 x 2 p.t. furring strips 24 o.c.--\ with R4.1 Foil insulation 1/2" d. #5 vert. rebar in grout filled cell See Floor Plan for Locations CL J 0 F.F.E. 0.00' -�--- �---- 4 2500# Fibermix Conc. on .006 Vapor Bearier on - Clean, Compacted, Termite Treated Fill (2) #5 Rebar V-4" 5V Roof Panels over 30# Felt on 19/32"c.d.x. plywood fastened as per nailing schedule Pre Engineered Wood Roof Trusses 24"o.c. Shop Drawings by Others See Connector /- Schedule 12 Galv. Drip Edge a 5 over 1 x 3 p.t. V-6- 8 x '-6" 2 x 6 Cedar Fascia Board Stucco Soffit Over High Ribbed Wire Lath Install one layer of 15# felt to framing prior to installing wire lath 8x 16x8 CMU Typ. Light Textured Stucco Finish #5 Vert. Rebar with 10"" Hook and 30" Lap. Tie to Vert. Rebar In Cells (1) #5 Rebar W co o +-J U c0 0- I 06 N i +J C uJ E Grade �° cc colN T Typical Wall Section PRODUCT APPROVAL Approval O 0 Glass Building Rated Product Rated W Product Model Number Manufacturer U) M Attachment Method LO N �... Number dam' T o0 Co C Type M Design Pressures Design Pressures Q LL LC) co W Head: 12" max. from corners & 30"o.c, max. Jambs: CD I FL: 239.7 S.H. Windows SH -5500 Singlehung PGT Industries Impact 12" max. from corners & 17.7"' max. 5'" each side of meeting rail. Use 1/4"" Tapcon with 1 1/4' embedment +33.5 -44.8 +/- 50.0 Q r' M W into concrete U � Q > U Head and Sill: 6"max, from corners & 15"o.c. max. at (U FL: 243.5 Picture Windows PW -5520 Singlehung PGT Industries Impact Jambs. Use 1/4'" Tapcon with 1 1/4'" embedment +33.5 -44.8 +/- 50.0 into concrete Glazed 6" from corners and 3"& 7"each side of center at head & FL#: 17184.2 Swing Doors Fiberglass Plastpro Impact sill and 6"from corners & 14 1/4""max. o.c. at jambs. +33.5 -36.3 +/-50.0 Door 1/4" tapcon screws with 1 1/4" embed. into conc. Fiberglass Plastpro Impact 6"" from corners & 14""o.c. at jambs, head, sill. 1/4"" tapcon + 65.0 -70.0 (Inswing) FL#: 17184.5 Swing Doors Door screws with 1 1/4" embed. into conc. +33.5 -36.3 +/- 65.0 (Outswing) FL#: 5678.28 Overhead Door Grand Harbour Clopay I m pact Flag Bracket Angle (3) total 5/16"" x 1 5/8"" lag screws. (7) total +27.9 '31.2 + 37.0 -41.0 Series Bracket T-0" height (1) 5/16" x 1 5/8"" lag screws per bracket. Approval Building Rated Product Rated Product Model Number Manufacturer Attachment Method Number Design Pressures Design Pressures FL: 17443.1 Roofing#9-15 5V Crimp JA Taylor Roofing x 1" coorosion resistant screw with sealing washer at each rib 12"o.c. in field and 6""o.c. along perimeter. -45.0 -69.25 FL: 9777.7 Roofing Weatherlock Owens Corning Direct attachment to plywood deck -45.0 -142.5 (Optional) Aerosmith Fastening Systems, SurePin 2"long, .30 Head Dia., .145 Shank FL: 12098.1 Siding Lap Siding Nichiha dia. Direct to CBS, Face Nail 16""o.c. -45.0 -78.3 U O 0 ~ W �_ ' s.. 0 3 ® U) M tV 00 LO N �... W dam' T o0 Co C Z M 0 ® Q LL LC) co W U L CD I LD n Lo 00 ® -J Li Q r' M W U � Q > U (U W M Q) ®n O 0 ~ W �_ ' s.. 0 U ~ M M Lt') LO N r y U o ` r i o T o0 Co C o Z 0 ® Q W U r, OO T J drawn s.l. checked s.l. date 11/7/2020 scale as noted job number 20011 sheet A-5 O W �_ ' s.. 0 U - LL Z > W O C 0 U W � J -J 0 (n U drawn s.l. checked s.l. date 11/7/2020 scale as noted job number 20011 sheet A-5