Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAboutEnergy Calculation Form & Manual J's 4
j OFFICE USE ONLY:
DATE FILED: PERMIT#
jREVISION FEE: RECEIPT#
PLANNING&DEVELOP
j BUILDING&CODE REGUL I
2300 VIRGINI E
FORT PIERCE,F 3
(772)462.
APPLICATION FOR BUILDI R IS
PROJECT INFORM 0
LOCATION/SITE
ADDRESS:
Pa ry—
DETAILED DESCRIPTION OF PROJECT
REVISIONS:
P e rrm i i q l 0 3 -
CONTRACTOR INFORMATION:
STATE of FL REG./CERT.#: C-C---,C- 1 S 1,-7 H 5 �3 ST. LUCIE CO CERT.#:
BUSINESS NAME: . 1N,-I-H 5::L_ �(�, ^ w nCf e ; )U r(711�sLj
QUALIFIERS NAME: e
ADDRESS: Oc2l C CN-r- ff c�r• 3�U'
CITY: N DY C r0 STATE: GA ZIP: 3©©l)
PHONE(DAYTIME): 3 a, I a-7 0• U LP -.-)-C) FAX: K-413c,
OWNER/BUILDER INFORMATION:
NAME: Vq-T H F L - yva C,,)
ADDRESS: 3Qej I &c�Oerncrs LC e C -.
CITY: N(',(-n STATE: C.,/-/-� ZIP: -�OCFI r
PHONE(DAYTIME: ?�, ) , (j . �Q tp a q FAX:
ARCHITECT/ENGINEER INFORMATION:
NAME: y l V-Ne;n 1_ 1C U l P
ADDRESS: --3 (3 0 PY OC&?) Gk-P-) Ayt'-",
CITY: �\,M�,}-e7 STATE: -1 ZIP: 1 C�(�
PHONE(DAYTIME): a ) S U 00 FAX: ,I'
SLCCC: 9123109
Revised 06/30/17
FORM R405-2017
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: Lot 10 1612 A RHG-S Builder Name: WADE JOURNEY HOMES
Street: 6504 Santa Clara Blvd Permit Office: ST LUCIE
City,State,Zip: Fort Pierce,FL, Permit Number:
Owner: WADE JOURNEY Jurisdiction: 661000
Design Location: FL,ST_LUCIE_CO_INTL County: St.Lucie(Florida Climate Zone 2)
1. New construction or existing New(From Plans) 9. Wall Types(1464.0 sqft.) Insulation Area
2. Single family or multiple family Single-family a.Frame-Wood,Exterior R=13.0 1172.00 ft2
b.Frame-Wood,Adjacent R=13.0 292.00 ft2
3. Number of units,if multiple family 1 c.N/A R= ft2
4. Number of Bedrooms 4 d.N/A R= ft2
5. Is this a worst case? No 10.Ceiling Types (1603.0 sqft.) Insulation Area a.Under Attic(Vented) R=30.0 1603.00 ft2
6. Conditioned floor area above grade(ft2) 1603 b.N/A R= ft2
Conditioned floor area below grade(ft2) 0 c.N/A R= ft2
11.Ducts R ft2
7. Windows(111.0 sqft.) Description Area a.Sup:Attic,Ret:Main,AH:Main 6 320.6
a. U-Factor: Dbl,U=0.35 111.00 ft2
SHGC: SHGC=0.29
b. U-Factor: N/A ft2 12.Cooling systems kBtu/hr . Efficiency
SHGC: a.Central Unit 22.2 SEER:14.50
c. U-Factor: N/A ft2
SHGC, 13.Heating systems kBtu/hr Efficiency
d. U-Factor: N/A ft2 a.Electric Heat Pump 22.2 HSPF:8.20
SHGC:
Area Weighted Average Overhang Depth: 1.000 ft.
Area Weighted Average SHGC: 0.290 14.Hot water systems
a.Electric Cap:50 gallons
8. Floor Types (i603.0 sqft.) Insulation Area
EF:0.920
a.Slab-On-Grade Edge Insulation R=0.0 1603.00 ft2 b. Conservation features
b.N/A R= ft2 None
c.N/A R= ft2 15.Credits Pstat
Glass/Floor Area: 0.069 Total Proposed Modified Loads: 47.38 PASS
Total Baseline Loads: 49.20
I hereby certify that the plans and specifications covered by Review of the plans and 0X 114E ST,gp�
this calculation are in compliance with the Florida Energy specifications covered by this
Code. calculation indicates compliance
with the Florida Energy Code.
PREPARED BY: .4M2j�" 1i-9M Before construction is completed ��
DATE: - 8/_1712020 __ _ _ this building will be inspected for i - a
compliance with Section 553.908
I hereby certify that this buildi , s designed, is in complian Florida Statutes.
with the Florida Energy Co !2
CODS
OWNER/AGENT: BUILDING OFFICIAL:
DATE: DATE:
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory-sealed in accordance with R403.3.2.1.
- Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires
an envelope leakage test report with envelope leakage no greater than 7.00 ACH50(R402.4.1.2).
- Compliance with a proposed duct leakage Qn requires a Duct Leakage Test Report confirming duct leakage to outdoors,tested
in accordance with ANSI/RESNET/ICC 380,is not greater than 0.080 Qn for whole house.
I
5/14/2020 2:22 PM EnergyGaugeO USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software �� Page 1 of 4
i
I
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
PROJECT
Title: Lot 10 1612 A RHG-S Bedrooms: 4 Address Type: Street Address
Building Type: User Conditioned Area: 1603 Lot# ' 10
Owner Name: WADE JOURNEY Total Stories: 1 Block/Subdivision: LAKEWOOD PARK
#of Units: 1 Worst Case: No PlatBook:
Builder Name: WADE JOURNEY Rotate Angle: 0 Street: 6504 Santa Clara Blvd
Permit Office: ST LUCIE Cross Ventilation: No County: St.Lucie
Jurisdiction: 661000 Whole House Fan: No City,State,Zip: Fort Pierce,
Family Type: Single-family FL,
New/Existing: New(From Plans)
Comment:
CLIMATE
Design Temp Int Design Temp Heating Design Daily Temp
V/ Design Location TMY Site 97.5% 2.5% Winter Summer Degree Days Moisture Range
FL,ST_LUCIE_CO_INTL FL_VERO_BEACH_MUNI 39 90 70 75 299 58 Medium
I
BLOCKS
Number Name Area Volume
1 Block1 1603 12824
SPACES
Number Name Area Volume Kitchen Occupants Bedrooms InfilID Finished Cooled Heated
1 Main 1603 12824 Yes 5 4 1 Yes Yes Yes
FLOORS
# Floor Type Space Perimeter ' R-Value Area Tile Wood Carpet
1 Slab-On-Grade Edge Insulatio Main 146.5 ft 1603 ft2 __-- 0.29 0 0.71
ROOF
/ Roof Gable Roof Rad Solar SA Emitt Emitt Deck Pitch
V # Type Materials Area Area Color Barr Absor. Tested Tested Insul. (deg)
1 Gable or Shed Composition shingles 1736 ft2 334 ft2 Medium N 0.7 N 0.7 No 0 22.6
/ ATTIC
V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC
1 Full attic Vented 300 1603 ft2 N N
CEILING
# Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type
1 Under Attic(Vented) Main 30 Blown 1603 ft2 0.1 Wood
i
I
5/14/2020 2:22 PM EnergyGauge®USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 2 of 4
I
I
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
j WALLS
Adjacent Space Cavity Width Height Sheathing Framing Solar Below
9 Ornt To Wall Type
1 N Exterior Frame-Wood Main 13 38 6 8 0 308.0 ft2 0 0.25 0.6 0
2 E Exterior Frame-Wood Main 13 36 6 8 0 292.0 ft2 0 0.25 0.6 0
3 S Exterior Frame-Wood Main 13 18 6 8 0 148.0 ft2 0 0.25 0.6 0
4 W Exterior Frame-Wood Main 13 53 0 8 0 424.0 ftZ 0 0.25 0.6 0
5 - Garage Frame-Wood Main 13 36 6 8 0 292.0 ft2 0 0.25 0.6 0
I
DOORS
# Omt Door Type Space Storms U-Value Width Height Area
Ft In Ft In
1 N Wood Main None .39 2 7 6 7 17 ftZ
2 S Insulated Main None .39 3 6 7 19.8 ft2
3 - Wood Main None .39 2 10 6 10 19.4 ft2
I
WINDOWS
Orientation shown is the entered,Proposed orientation.
Wall Overhang
V # Ornt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation Int Shade Screening
1 N 1 Vinyl Low-E Double Yes 0.35 0.29 N 6.0 ft2 1 ft 0 in 1 ft 0 in Drapes/blinds None
2 N 1 Vinyl Low-E Double Yes 0.35 0.29 N 30.0 ft2 1 ft 0 in 1 ft 0 in Drapes/blinds None
3 E 2 Vinyl Low-E Double Yes 0.35 0.29 N 30.0 ft2 1 ft 0 in 1 ft 0 in Drapes/blinds None
4 S 3 Vinyl Low-E Double Yes 0.35 0.29 N 15.0 ft2 1 ft 0 in 1 ft 0 in Drapes/blinds None
5 W 4 Vinyl Low-E Double Yes 0.35 0.29 N 30.0 ft2 1 ft 0 in 1 ft 0 in Drapes/blinds None
I
GARAGE
# Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation
1 387 ft2 387 ft2 64 ft 8 ft 1
INFILTRATION
# Scope Method SLA CFM 50 ELA EgLA ACH ACH 50
1 Wholehouse Proposed ACH(50) .000356 1496.1 82.14 154.47 .1233 7
HEATING SYSTEM
# System Type Subtype Speed Efficiency Capacity Block Ducts
1 Electric Heat Pump/ Split Singl HSPF:8.2 22.2 kBtu/hr 1 sys#1
I
COOLING SYSTEM
# System Type Subtype Subtype Efficiency Capacity Air Flow SHR Block Ducts
1 Central Unit/ Split, Singl SEER:14.522.2 kBtu/hr 666 cfm 0.75 1 sys#1
5/14/2020 2:22 PM EnergyGauge®USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 3 of 4
i
I
i
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
HOT WATER SYSTEM
# System Type 'SubType Location EF Cap Use SetPnt Conservation
1 Electric None Garage 0.92 50 gal 60.9 gal 120 deg None
SOLAR HOT WATER SYSTEM
FSEC Collector Storage
Cert # Company Name System Model# Collector Model# Area Volume FEF
None None ftZ
I
DUCTS
----Supply---- ----Return---- Air CFM 25 CFM25 HVAC#
# Location R-Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool
j 1 Attic 6 320.6 ft Main 80.15 ft Proposed Qn Main ---cfm 48.1 cfm 0.08 0.50 1 1
TEMPERATURES
Programable Thermostat:Y Ceiling Fans:
CoolingJan Feb Mar Apr May X Jun X Jul rj Aug Se Oct Nov Dec
Heatin Jan H
Feb HX
Mar Apr May Jun Jul AuSep Oct Nov HDec
Ventin Jan Feb Mar [X]Apr May Jun Jul Aug Se Oct H
Nov Dec
Thermostat Schedule: HERS 2006 Reference Hours
Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12
Cooling(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80
PM 80 80 78 78 78 78 78 78 78 78 78 78
Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78
PM 78 78 78 78 78 78 78 78 78 78 78 78
Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
MASS
Mass Type Area Thickness Furniture Fraction Space
Default 8 Ibs/s .ft. 0 ftZ 0 ft 0.3 Main
I
I
5/14/2020 2:22 PM EnergyGauge®USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 4 of 4
I
i
Florida Building Code, Energy Conservation, 6th Edition (2017)
Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods
ADDRESS: 6504 Santa Clara Blvd Permit Number:
Fort Pierce,FL,
MANDATORY REQUIREMENTS See individual code sections for full details.
I
SECTION R401 GENERAL
0 R401.3 EnergyPerformance Level EPL display card(Mandatory)The The building official shall require that an energy performance level EPL display
(EPL) P Y ( rY1• 9 q 9Y P (EPL) P Y
card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy.Florida law(Section
553.9085,Florida Statutes)requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold
residential buildings.The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a
9 P Y 9 9Y P P
dwelling unit.The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and
specifications submitted to demonstrate code compliance for the building.A copy of the EPL display card can be found in Appendix RD.
R402.4 Air leakage(Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
R402.4.1 Building thermal enveldlitim building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2.
The sealing methods between dissimilar materials shall allow for differential expansion and contraction.
0 R402.4.1.1 InstallationThe components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with
the manufacturer's instructions and the criteria listed in Table R402.4.1.1,as applicable to the method of construction.Where required by the
code official,an approved third party shall inspect all components and verify compliance.
i
0 R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2,and three air changes per hour in Climate Zones 3 through 8.Testing shall be conducted in
accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g.(50 pascals).Testing shall be conducted by either
individuals as defined in Section 553.993(5)or(7),Florida Statutes,or individuals licensed as set forth in Section 489.105(3)(f),(g)or(i)or
an approved third party.A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official.Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions,alterations,renovations,or repairs,of the building thermal envelope of existing
buildings in which the new construction is less than 85 percent of the building thermal envelope.
During testing:
1.Exterior windows and doors,fireplace and stove doors shall be closed,but not sealed,beyond the intended weatherstripping or
other infiltration control measures.
2.Dampers including exhaust,intake,makeup air,backdraft and flue dampers shall be closed,but not sealed beyond intended
infiltration control measures.
3.Interior doors,if installed at the time of the test,shall be open.
4.Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5.Heating and cooling systems,if installed at the time of the test,shall be turned off.
6.Supply and return registers,if installed at the time of the test,shall be fully open.
❑ R402.4.2 Fireplaces. New wood-burning fireplaces shall have tight-fitting flue dampers or doors,and outdoor combustion air.Where using
tight-fitting doors on factory-built fireplaces listed and labeled in accordance with UL 127,the doors shall be tested and listed for the
fireplace.Where using tight-fitting doors on masonry fireplaces,the doors shall be listed and labeled in accordance with UL 907.
R402.4.3 Fenestration air Ieakagdi indows,skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per
square foot(1.5 Us/m2),and swinging doors no more than 0.5 cfm per square foot(2.6 Us/m2),when tested according to NFRC 400 or
AAMA/WDMA/CSA 101/I.S.2/A440 by an accredited,independent laboratory and listed and labeled by the manufacturer.
Exception: Site-built windows,skylights and doors.
I
I
5/14/2020 2:23 PM EnergyGauge®USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 1 of 5
j
i
MANDATORY REQUIREMENTS - (Continued)
R402.4.4 Rooms containing fuel-burning appliances. In Climate Zones 3 through 8,where open combustion air ducts provide combustion air to open
combustion fuel burning appliances,the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a
room,isolated from inside the thermal envelope.Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table
R402.1.2,where the walls,floors and ceilings shall meet not less than the basement wall R-value requirement.The door into the room shall be fully
gasketed and any water lines and ducts in the room insulated in accordance with Section R403.The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside.
2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code,Residential.
R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between
spaces.All recessed luminaires shall be IC-rated and labeled as having an air leakage rate not more than
conditioned and unconditionedg g
P
2.0 cfm(0.944 Us)when tested in accordance with ASTM E283 at a 1.57 psf(75 Pa)pressure differential.All recessed luminaires shall be
sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
SECTION R403 SYSTEMS
R403.1 Controls.
❑ R403.1.1 Thermostat provision(Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
i
❑ R403.1.3 Heat pump supplementary heat(Mandatory). Heat pumps having supplementary electric-resistance heat shall have controls
that,except during defrost,prevent supplemental heat operation when the heat pump compressor can meet the heating load.
❑ R403.3.2 Sealing(Mandatory) All ducts,air handlers,filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts or plenum chambers,shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5)or
(7),Florida Statutes,or individuals licensed as set forth in Section 489.105(3)(f),(g)or(i),Florida Statutes,to be"substantially leak free"in
accordance with Section R403.3.3.
I "
❑ R403.3.2.1 Sealed air handier. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of
the design airflow rate when tested in accordance with ASHRAE 193.
❑ R403.3.3 Duct testing(Mandatory).Ducts shall be pressure tested to determine air leakage by one of the following methods:
1. Rough-in test:Total leakage shall be measured with a pressure differential of 0.1 inch w.g.(25 Pa)across the system,including the manuft
air handler enclosure if installed at the time of the test.All registers shall be taped or otherwise sealed during the test.
2. Postconstruction test:Total leakage shall be measured with a pressure differential of 0.1 inch w.g.(25 Pa)across the
entire system,including the manufacturer's air handler enclosure.Registers shall be taped or otherwise sealed during the
test.
Exceptions:
1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building
thermal envelope.
2. Duct testing is not mandatory for buildings complying by Section 405 of this code.
A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.
❑R403.3.5 Building cavities(Mandatory). Building framing cavities shall not be used as ducts or plenums.
0 R403.4 Mechanical system piping insulation(Mandatory). Mechanical system piping capable of carrying fluids above 105°F(41°C)or
below 55°F(13°C)shall be insulated to a minimum of R-3.
❑ R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage,including that caused
by sunlight,moisture,equipment maintenance and wind,and shall provide shielding from solar radiation that can cause degradation of the
material.Adhesive tape shall not be permitted.
❑ R403.5.1 Heated water circulation and temperature maintenance systems(Mandatory)Heated water circulation systems shall be in
accordance with Section R403.5.1.1.Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2.
Automatic controls,temperature sensors and pumps shall be accessible.Manual controls shall be readily accessible.
R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump.The system return pipe
❑ shall be a dedicated return pipe or a cold water supply pipe.Gravity and thermosiphon circulation systems shall be prohibited.
Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the
occupancy.The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and
when there is no demand for hot water.
I
❑ R403.5.1.2 Heat trace systems.Electric heat trace systems shall comply with IEEE 515.1 or UL 515.Controls for such systems shall
automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the
times when heated water is used in the occupancy.
5/14/2020 2:23 PM EnergyGauge®USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 2 of 5
i
MANDATORY REQUIREMENTS - (Continued)
R403.5.5 Heat traps(Mandatory). Storage water heaters notequipped with inte integral heat traps and having vertical pipe risers shall have
P ( ry)• 99 P 9 P�p
heat traps installed on both the inlets and outlets.External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3%inches(89 mm)in the hot water distribution line and cold water line located as close as possible
to the storage tank.
R403.5.6 Water heater efficiencies(Mandatory).
O R403.5.6.1.1 Automatic controls. Service water-heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use.The minimum temperature setting
range shall be from 100°F to 140°F(38°C to 60oC).
R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to
electric service systems to be turned off.A separate valve shall be provided to permit the energy supplied to the main burner(s)of
combustion types of service water-heating systems to be turned off.
0 R403.5.6.2 Water-heating equipment. Water-heating equipment installed in residential units shall meet the minimum efficiencies of Table
C404.2 in Chapter 4 of the Florida Building Code,Energy Conservation,Commercial Provisions,for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate
water-heating category.Solar water heaters shall meet the criteria of Section R403.5.6.2.1.
aR403.5.6.2.1 Solar water-heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system.The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
i
Certified Solar Systems.Solar collectors shall be tested in accordance with ISO Standard 9806,Test Methods for Solar Collectors,
and SRCC Standard TM-1,Solar Domestic Hot Water System and Component Test Protocol.Collectors in installed solar
water-heating systems should meet the following criteria:
1. Be installed with atilt angle between 10 degrees and 40 degrees of the horizontal;and
2. Be installed at an orientation within 45 degrees of true south.
0 R403.6 Mechanical ventilation(Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code,Residential,or Florida Building Code,Mechanical,as applicable,or with other approved means of ventilation
. including:Natural,Infiltration or Mechanical means.Outdoor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
0 R403.6.1 Whole-house mechanical ventilation system fan efficacy.When installed to function as a whole-house mechanical
ventilation system,fans shall meet the efficacy requirements of Table R403.6.1.
Exception: Where whole-house mechanical ventilation fans are integral to tested and listed HVAC equipment,they shall be
powered by an electronically commutated motor.
0 R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation
shall meet the following criteria:
1. The design air change per hour minimums for residential buildings in ASHRAE 62.2,Ventilation for Acceptable
Indoor Air Quality,shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawlspaces,attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed space(s),then the walls of the space(s)from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19,space permitting,or R-10
otherwise. i
R403.7 Heating and cooling equipment(Mandatory).
O R403.7.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the
equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies,
based on building loads for the directional orientation of the building.The manufacturer and model number of the outdoor and indoor
units(if split system)shall be submitted along with the sensible and total cooling capacities at the design conditions described in
Section R302.1.This Code does not allow designer safety factors,provisions for future expansion or other factors that affect
equipment sizing.System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as
standard kitchen and bathroom exhaust systems.New or replacement heating and cooling equipment shall have an efficiency rating
equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed.
TABLE R403.6.1
WHOLE-HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY
FAN LOCATION AIRFLOW RATE MINIMUM MINIMUM EFFICACY a AIRFLOW RATE MAXIMU
(CFM) (CFM/WATT) (CFM)
Range hoods Any 2.8 cfm/watt Any
In-line fan Any 2.8 cfm/watt Any
Bathroom,utility room 10 1.4 cfm/watt <90
Bathroom,utility room 90 2.8 cfm/watt Any
For SI:1 cfm=28.3 L/min. a. When tested in accordance with HVI Standard 916
5/14/2020 2:23 PM EnergyGauge®USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 3 of 5
I
j
MANDATORY REQUIREMENTS - (Continued)
❑ R403.7.1.1 Cooling equipment ca aci Cooling only equipment shall be selected so that its total capacity is not less than
9capacity. 9 YP Y
the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section
403.7,or the closest available size provided by the manufacturer's product lines.The corresponding latent capacity of the equipment shall
not be less than the calculated latent load.
The published value for AHRI total capacity is a nominal,rating-test value and shall not be used for equipment sizing.Manufacturer's
expanded performance data shall be used to select cooling-only equipment.This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation(or entering water temperature for water-source equipment),the blower CFM provided by the expanded
performance data,the design value for entering wet-bulb temperature and the design value for entering dry-bulb temperature.
Design values for entering wet-bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s)is installed in an unconditioned space.
Exceptions:
1. Attached single-and multiple-family residential equipment sizing may be selected so that its cooling capacity is less than the
calculated total sensible load but not less than 80 percent of that load.
2.
When signed and sealed by a Florida-registered engineer,in attached single-and multiple-family units,the capacity of
equipment may be sized in accordance with good design practice.
R403.7.1.2 Heating equipment capacity.
❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1,and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1.
O R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
I
R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis,such as anticipated additional loads caused by major entertainment events,shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
El and
Systems serving multiple dwelling units(Mandatory). Systems serving multiple dwelling units shall comply with Sections C403
and C404 of the IECC—Commercial Provisions in lieu of Section R403.
I
i
a R403.9 Snow melt and ice system controls(Mandatory) Snow-and ice-melting systems,supplied through energy service to the building,
shall include automatic controls capable of shutting off the system when the pavement temperature is above 50oF(10°C),and no
precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40oF(4.WC).
❑ R403.10 Pools and permanent spa energy consumption(Mandatory). The energy consumption of pools and permanent spas shall
be in accordance with Sections R403.10.1 through R403.10.5.
❑ R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on-off switch that is an
integral part of the heater mounted on the exterior of the heater,or external to and within 3 feet(914 mm)of the heater.Operation of
such switch shall not change the setting of the heater thermostat.Such switches shall be in addition to a circuit breaker for the
power to the heater.Gas-fired heaters shall not be equipped with continuously burning ignition pilots.
❑ R403.10.2 Time switches.Time switches or other control methods that can automatically turn off and on according to a preset schedule
shall be installed for heaters and pump motors.Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operation.
2. Pumps that operate solar-and waste-heat-recovery pool heating systems.
3. Where pumps are powered exclusively from on-site renewable generation.
❑ R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor-retardant cover on or at
the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Where more than 70 percent of the energy for heating,computed over an operation season,is from site-recovered
energy,such as from a heat pump or solar energy source,covers or other vapor-retardant means shall not be required.
R403.10.4 Gas-and oil-fired pool and spa heaters. All gas-and oil-fired pool and spa heaters shall have a minimum thermal
❑ efficiency of 82 percent for heaters manufactured on or after April 16,2013,when tested in accordance with ANSI Z 21.56.Pool
heaters fired by natural or LP gas shall not have continuously burning pilot lights.
5/14/2020 2:23 PM EnergyGauge®USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 4 of 5
I
I
aR403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with
AHRI 1160,Table 2,Standard Rating Conditions-Low Air Temperature.A test report from an independent laboratory is required to
verify procedure compliance.Geothermal swimming pool heat pumps are not required to meet this standard.
0 R403.11 Portable spas(Mandato%e energy consumption of electric-powered portable spas shall be controlled by the
requirements of APSP-14.
SECTION R404
ELECTRICAL POWER AND LIGHTING SYSTEMS
F I R404.1 Lighting equipment(Mandatory). Not less than 75 percent of the lamps in permanently installed lighting fixtures shall be
high-efficacy lamps or not less than 75 percent of the permanently installed lighting fixtures shall contain only high-efficacy lamps.
Exception:Low-voltage lighting.
R404.1.1 Lighting equipment(Mandatory)Fuel gas lighting systems shall not have continuously burning pilot lights.
I
I
i
I
5/14/2020 2:23 PM EnergyGaugeO USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 5 of 5
i
I
2017 EPL DISPLAY CARD
i
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX*= 96
The lower the Energy Performance Index, the more efficient the home.
1. New home or, addition 1. New(From Plans) 12. Ducts, location&insulation level
a)Supply ducts R 6.0
2.Single-family or multiple-family 2. Single-family b)Return ducts R 6.0
c)AHU location Main
3. No.of units(if multiple-family) 3. 1
4. Number of bedrooms 4. 4 13. Cooling system: Capacity 22.2
a)Split system SEER 14.5
5. Is this a worst case?(yes/no) 5. No b)Single package SEER
I c)Ground/water source SEER/COP
6.Conditioned floor area(sq.ft.) 6. 1603 d)Room unit/PTAC EER
e)Other
7.Windows,type and area
a)U-factor:(weighted average) 7a. 0.350
b)Solar Heat Gain Coefficient(SHGC) 7b. 0.290 14. Heating system: Capacity 22.2
c)Area 7c. 111.0 a)Split system heat pump HSPF 8.2
b)Single package heat pump HSPF
8.Skylights c)Electric resistance COP
a)U-factor:(weighted average) 8a. NA d)Gas furnace, natural gas AFUE
b)Solar Heat Gain Coefficient(SHGC) 8b. NA e)Gas furnace, LPG AFUE
f)Other
9. Floor type, insulation level:
a)Slab-on-grade(R-value) 9a. 0.0
b)Wood, raised(R-value) 9b. 15.Water heating system
c)Concrete, raised(R-value) 9c. a) Electric resistance EF 0.92
b)Gas fired, natural gas EF
10.Wall type and insulation: c)Gas fired, LPG EF
A. Exterior: d)Solar system with tank EF
1.Wood frame(Insulation R-value) 10A1. 13.0 e) Dedicated heat pump with tank EF
2. Masonry(Insulation R-value) 10A2. 0 Heat recovery unit HeatRec%
B.Adjacent: g)Other
1.Wood frame(Insulation R-value) 10131. 13.0
2. Masonry(Insulation R-value) 10132.
16. HVAC credits claimed(Performance Method)
11. Ceiling type and insulation level a)Ceiling fans
a)Under attic 11 a. 30.0 b)Cross ventilation No
b)Single assembly 11 b. c)Whole house fan No
c) Knee walls/skylight walls 11 c. d)Multizone cooling credit
d) Radiant barrier installed 11d. No e)Multizone heating credit
f)Programmable thermostat Yes
*Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
I certify that this home has complied with the Florida Building Code, Energy Conservation,through the above energy
saving features which will be installed(or exceeded)in this home before final inspection.Otherwise, a new EPL
display card will be completed ed on installed code compliant ures.
Builder Signature: de Date:
Address of New Home: 6504 Santa Clara Blvd City/FL Zip: Fort Pierce, FL
5/14/2020 2:23:24 PM EnergyGauge®USA 6.0.04(Rev.1)-FlaRes2017 FBC 6th Edition(2017)Compliant Software Page 1 of 1
i
i
2017 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: Lot 10 1612 A RHG-S Builder Name: WADE JOURNEY
Street: 6504 Santa Clara Blvd Permit Office: ST LUCIE
City,State,Zip: Fort Pierce,FL, Permit Number:661000 Y
U
Owner: WADE JOURNEY Jurisdiction: W
x
Design Location: FL,ST_LUCIE_CO_INTL U
COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA
General A continuous air barrier shall be installed in the building envelope. Air-permeable insulation shall
The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material.
requirements Breaks or joints in the air barrier shall be sealed.
Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with the The insulation in any dropped ceiling/soffit
insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier.
Access openings,drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
Walls
The junction of the foundation and sill plate shall be sealed. Cavities within comers and headers of frame walls
The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity with
sealed. a material having a thermal resistance of R-3 per
Knee walls shall be sealed. inch minimum.
Exterior thermal envelope insulation for framed walls
shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows,skylights The space between window/door jambs and framing,and
and doors skylights and framing shall be sealed.
Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated.
Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to
(including insulation. maintain permanent contact with the underside of
above-garage subfloor decking,or floor framing cavity insulation
and cantilevered shall be permitted to be in contact with the top side
floors) of sheathing,or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation,insulation
a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace
Shafts,penetrations Duct shafts,utility penetrations,and flue shafts opening to
exterior or unconditioned space shall be sealed.
Batts in narrow cavities shall be cut to fit,or narrow
Narrow cavities cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
Garage separation Air sealing shall be provided between the garage and conditioned spat s.
Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building
shall be sealed to the drywall. thermal envelope shall be air tight and IC rated.
Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls,or insulation that on
installation readily conforms to available space shall
extend behind piping and wiring.
Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall
on exterior wall tubs shall separate them from the showers and tubs. be insulated.
Electrical/phone box or The air barrier shall be installed behind electrical or communication
exterior walls boxes or air-sealed boxes shall be installed.
HVAC register boots HVAC register boots that penetrate building thermal envelope shall
be sealed to the sub-floor or drywall.
Concealed When required to be sealed,concealed fire sprinklers shall only be
sprinklers sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
between fires rinkler cover Nates and walls or ceilin s.
a.In addition,inspection of log walls shall be in accordance with the provisions of]CC-400.
5/14/2020 2:23 PM EnergyGauge®USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 1 of 1
i
I
I
i
I
ProjePt Summary Job: Lot101612ARHG-S
ct- - wrightsoft® ry Date: 05/14/2020
House By- DSILIIe
One Stop Cooling and Heating Plan: RHG
7225 Sandscove Court,winter Park,FL 32792 Phone:(407)629-6920 Fax.(407)629-9307 Web:wAw0neStopCooling.com License:CAC032444
Project • •
For. WADE JOURNEY
6504 Santa Clara Blvd,Fort Pierce,FL
Notes:
Design Information
Weather: St Lucie Co Intl,FL,US
Winter Design Conditions Summer Design Conditions
Outside db 41 °F Outside db 90 °F
Inside db 68 °F Inside db 74 'F
Design TD 27 °F Design TD 16 'F
Daily range L
Relative humidity 50 %
Moisture difference 59 gdlb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 14740 Btuh Structure 12244 Btuh
Duds 1474 Btuh Ducts 2871 Btuh
Central vent(0 cfm) 0 Btuh Central vent(0 cfrn) 0 Btuh
(none) (none)
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 16214 Btuh Use manufacturers data n
Rate/swing multiplier 0.95
Infiltration Equipment sensible load 14420 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 1 (Average) Structure 3309 Btuh
Ducts 672 Btuh
Central vent(0 cfm) 0 Btuh
Heatingg Cooling (none)
Area(fn 1662 1662 Equipment latent load 3981 Btuh
Volume(fP) 13292 13292
Air changes/hour 0.59 0.26 Equipment Total Load(Sen+Lat) 18401 Btuh
Equiv AVF(cfm) 131 58 Req.total capacity at 0.75 SHR 1.6 ton
Heating Equipment Summary. Cooling Equipment Summary
Make Carrier Make Carrier
Trade Trade
Model CH14NB02400GOA0 Cond CH14NB02400GOA0
AHRI ref 9162301 Coil FB4CNP025L
AHRI ref 9162301
Efficiency 8.2 HSPF Efficiency 11.5 EER,14.5 SEER
Heating input Sensible cooling 16650 Btuh
Heating output 22200 Btuh @ 47°F Latent cooling 5550 Btuh
Temperature rise 0 °F Total cooling 22200 Btuh
Actual airflow 0 cfm Actual airflow 740 cfm
Airflowfactor 0 cfmBtuh Airflowfactor 0.049 cfmBtuh
Static pressure 0 in H2O Static pressure 0.50 in H2O
Space thermostat Load sensible heat ratio 0.79
Capacity balance point=33°F
Backup:
Input=13 kW, Output=43537 Btuh,100 AFUE
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
wrightsoft- 2020-May-1413:5327
Right-Suite®Universal2019 19.0.19 RSU76793 Page 1
ACCA...Lot 101612 ARHG-StLot 101612 ARHG-S.rup Calc=MJ8 Front Doorfaoes:S
1
°
Lot 10
wrightsoft° Right-JO Worksheet Job: OW1412612ARHG-S
I House date: 5/14/2020
By DS1L M
i
One Stop Cooling and Heating Plan: RHG
7225 Sandscove Court,Winter Park,FL 32792 Phone:(407)629-6920 Fax:(407)629-9307 Web:wwwOneStopCooling.com License:CAC032444
1 Room name House KIT
2 Eposed wall 146.5 ft 9.5 It
3 Room height 8.0 it d 8.0 It heat/cool
4 Room dimensions 1.0 x 155.6 ft
5 Room area 1661.5 Itz 155.6 W
Ty Constudion U-value Or HTM Area (fF) Load Area (ilk Load
number (Btrhd2--°F) (Btihffl) or perimeter (ft) (Btah) or perimeter (ft) (Btrh)
Heat Cod Gross N/P/S Heat Cod Gross N/P/S Heat Cool
6 W 12C-0 sv 0.091 ne 2.46 2.30 292 262 644 603 0 0 0 0
4A572ov .- 0.320- ne. _ .8.64.- 17.32._ _ 30 0 259 520 0 0 _ 0 0
IW - 12C-0sw 0.091 se 2.46 2.30 148 113 277 259 0 0 0 0
4A5-2ov 0.3201 se 8.64 16A3 15 2 130 246 0 0 0 0
11 11DO 0.3901 se 10.53 11.82 20 20 215 241 0 0 0 0
W 12C-0sw 0.091 sN 2A6 2.30 424 394 968 907 0 0 0 0
_�G 4A5-2ov_ __ _ 0.320 sw- _ 8.64 16A3 _30._ _ _4 259 493 0 _ -._ 0 0_ __ 0
W 12C-0sw 0.091 nw 2.46 2.30 308 253 622 583 76 70 172 161
4A5-2ov 0.320 nw 8.64 17.32 6 0 52 104 6 0 52 104
4A5.2ov 0.320 nw 8.64 17.32 30 0 259 520 0 0 0 0
11DO 0.390 nw 10.53 11.82 19 19 200 224 0_ 0 0 0
q 12C-0sw 0.091 - 2.46 1.40 292 273 670 382 0 0 0 0
_ -__-D 11DO__ - 0,390 .n 10.53 _. 11.82 .._ _ 19 - 19 203_. _ _228 _ 0 0 rt _ . 0 0.
C--. - 16E730ad. _ _, .0.032- -0 86.. _ 1.72 ._ _-1662 _ -_ 1662 _ _... 1436 ._ 2860_- 156._ 156 134 _268
F 22A-tpm_,._ _. 1.180 _ 31.86. 0.00 1662. 147 4667 _ 0 ,_ _156_ __ 10_ 303 - - _ 0
6 c)AED exarsion 186 -28
Envelopeloss/gain 10860 8356 661 505
12 a) Infilbaton 3880 1038 252 67
b) Room ventilation 0 0 0 0
13 Internal gains'. Occupants @ 230 5 1150 0 0
Applianceslother 1700 1200
Subtotal(lines 6to13) 14740 12244 913 1772
Lesse)demalload 0 0 0 0
Lesstransfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 14740 12244 913 1772
15 Dudloads 10% 23% 1474 2871 10% 23% 91 415
Total room load 16214 15115 10G4 2188
Air required(dm) 0 740 0 107
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
wrigtitsoTt° 2020-May-1413:53:27
Right-Suile@ Universal 2019 19.0.19 RSU16793 Page 1
Lot 101612 ARHG-S\Lot 101612 ARHG-S.rup Calc=MJB Front Door faces:S
I
I
l
- -wrightsoft° Right-J®Worksheet Job: Lot 10 1612 A MG-S
House Date: 05/14/2020
By DS/LM
One Stop Cooling and Heating Plan: RHG
7225 Sandscove Court,Winter Park,FL 32792 Phone:(407)629-6920 Fax:(407)629-9307 Web:vwvwOneStopCooling.com License:CAC032444
1 Room name FOY MBA
2 Exposed wall 4.5 ft 0 ft
3 Room height 8.0 ft heat/cool 8.0 ft heaUcool
4 .Room dimensions 1.0 x 91.5 ft 6.0 x 11.5 ft
5 Room area 91.5 R2 69.0 ft
TY Construction U-value Or HTM Area OF) Load Area (ftF) Load
number (BtuhAR-°F) (BtuW or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross NIP/S Heat Cool Gross N/P/S Heat Cool
6 W 12C-Osw 0 091 ne 2.46 2.30 0 0 0 _ 0. 0 0 0 0
4A5-2ov._ _. __ 0.320 .ne. ---8.64 117.32, _ _,.0 0 _ _ -.0- -.. --0...--_._- 0 _ 0 _ 0 _. .0.
W 12C-0sw 0.091 se 2.46 2.30 36 16 38 36 0 0 0 0
4A5-2ov 0.320 se 8.64 16.43 0 0 0 0 0 0 0 0
11 11DO 0.390 se 1.0.53 11.82 20 20 215 241 0 0 0 0
�1l 12C-0sw 0.091 sw 2.46 2.30 0 0 0 0 0 0 0 0
G.0S2ov _ _. 0.320 sw . _ 8.64 16.43 0___. _ 0_..- 0 .- 0-,_. . ._..0- _.0 .. _ 0 _ 0
W 12C-0sw 0.091 nw 2.46 2.30 0 0 0 0 0 0 0 0
4A5-2ov 0.320 nw 8.64 17.32 0 0 0 0 0 0 0 0
4A5.2ov 0.320 nw 8.64 17.32 0 0 0 0 0 0 0 0
_. 11D0-. _-..-_ 0.390 nw__ „_.10;53 11.82 -0 0 0 0....- 0-
12C-Osw- 0.091 ,- 2.46 1.40 120 120 295 168 6 0 0 0
. 11.DO- 0.390 _n _._.10.53_ _.11.82 _. 0 ,. _-. 0 _ _. 0 ..- 0 .__.. _0 . . . 0-
C __ 16B 30ad _ .... 0.032 . __0.86 . 1.72 _-_....92_..._. _ 92 . _.. ....79. ... 158_.._ _ 69.- 69 _ 80 119
F.-_ 22A,tpm.. .. _.. _ _- 1.180_ -_ _31,86 _0.00 92 _ ._ 5 _143 - 0 _.. _.69. 0. 0. _. _._0
6 c)AED excursion -29 -5
Envelope loss(gain 770 574 60 113
12 a) Infiltration 119 32 0 0
b) Room ventilation 0 0 0 0
13 Internal gains., Occupants@ 230 0 0 0 0
Appliances(other 0 0
Subtotal(lines 6 to 13) 890 606. 60 113
Less etemalload 0 0 0 0
Lesstransfer 0 0 0 0
Redistribution -890 -606 90 127
14 Subtotal 0 0 150 240
15 Ductloads 110% 23% 0 0 10% 23% 15 56
Total room load 0 0 165 217
Air required(clm) 0 0 0 15
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
w_ vightsort- 2020-May-1413:53:27
- �- Right Suite@ Universal 2019 19.0.19 RSU16793 Page 2
Lot 10-1612 ARHG-Slot 10 1612 ARHG-S.rup Calc=MJ8 Front Door faces:S
i
-wrightsoft` Right-J®Worksheet Job:Date: 51 0511 412 0 2 Lot1 RHG-S
i 2020 0
House B}r DS„LI
One Stop Cooling and Heating Plan: RHG
7225 Sandscove Court,Winter Park,FL 32792 Phone:(407)629-6920 Fax(407)629-9307 Web:www.OneStopCooling.com License:CAC032444
1 Room name MBED LAUN
2 Exposed wall 11.5 ft 0 It
3 Room height 8.0 ft heat/cool 8.0 ft heaU000l
4 Room dimensions 14.0 x 11.5 ft 7.0 x 4.0 ft
5 Room area 161.0 fl2 28.0 T
Ty Construction U-value Or HTM Area (11F) Load Area (T) Load
number (BtuW--T) (B or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cod Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 W 12C-O w - 0.091 ne 2.46 2.30 92 77 189 177 0 0 0 0
_G 4AS2ov__._ 0.320 ne 8.64 17.32 15 0 130 260_ ._ - 0 0 0 0
W 12C-09w 0.091 se 2.46 2.30 0 0 0 0 0 0 0 0
Ej 4A5-2ov 0.320 se 8.64 16.43 0 0 0 0 0 0 0 0
11 11 DO 0.390 se 10.53 11.82 0 0 0 0 0 0 0 0
W 12C-Osw 6.091 sw 2.46 2.30 0 0 0 0 0 0 0 0
4AS2ov ___. 0.320 sw. _ 8.64 - . 16.43 _0 0 _ 0 0 0 0. 0_ 0.
W 12C-Osw 0.091 nw 2.46 2.30 0 0 0 0 0 0 0 0
4AS2ov 0.320 nw 8.64 17.32 0 0 0 0 0 0 0 0
t-G
4AS2ov 0.320 nw 8.64 17.32 0 0 0 0 0 0 0 0
11D0_ 0 0 0 0 - 0 _ 0
_ _-0.390 nw 10.53 11.82 _- 0 0
q 12C-Osw 0.091 2.46, 1 A0 0 0 0 0 0 0 0 0
-D 11DO 0.390 n 10.53 11.82 0 0 0 0_ 0 0 0, 0
C 166-30ad 0.032 0.86 1.72 161 161 139 277 28 28 24 4.8
F 22A-tpm _1.180 31.86, 0.00 _ 161 - 12 366 - 0 _ 28- 0. 0 _ _ 0
6 c)AED excursion -26 -25
Envelope loss/gain 824 689 24 23
12 a) Irfiiltration 305 81 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 2 460 0 0
Applianoesrother 0 500
Subtotal(lines 6 to 13) 1129 1230 24 523
Less extemalload 0 0 0 0
Lesstransfer 0 0 0 0
Redistribution 18 25 24 523
14 Subtotal 1147 1255 0 0
15 Ductloads 1 10% 23% 115 294 10% 23% 0 0
Total room load 1262 1550 0 0
Air required(dm) I 1 0 76 0 0
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
_ fi.F- wrigF�tsoTt^ 2020-May-1413:53:27
- -•• Right-Suite®Universal 2019 19.0.19 RSU16793 Page 3
ACC` ...Lot 101612 ARHG-Slot 10 1612 ARHG-S.rup Calc=MJ8 Front Door faces:S
i
wrightsoft° Right-J®Worksheet Job: Lot101612ARHG-S
House Date: 05/14/2020
BL Ds/LM
One Stop Cooling and Heating Pan: RHG
7225 Sandscove Court,Winter Park,FL 32792 Phone:(407)629-6920 Fax(407)629-9307 Web:vmw.OneStopCooling.com License:CAC032444
1 Room name PAN BA2
2 E>posed wall 4.5 ft 6.0 ft
3 Room height 8.0 ft heaUceol 8.0 ft heat/cool
4 Room dimensions 1.0 x 19A ft 10.0 x 6.0 ft
5 Room area 19.4 fF 60.0 fF
Ty Construction U-value Or HTM Area (W) Load Area (IF) Load
number (Btuh/W--°F) (Btuh/IF) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cod Gross N/P/S Heat Cool
6 W 12C-Osw 0.091 ne 2.46 2.30 0 0 0 0 0 0 0 0
I-G 4A5-2ov 0.320 ne ,_ 8.64 17.32_ 0 0 0 -__ .0_-_ 0 0 0 0
I W - 12C-Osw 0.091 se 2.46 2.30 0 0 0 0 0 0 0 0
4AS2ov 0.320 se 8.64 16.43 0 0 0 0 0 0 0 0
11 11DO 0.390 se 10.53 11.82 0 0 0 0 0 0 0 0
W 12C-Osw- 0.091 sw 2.46 2.30 0 0 0 0 48 48 118 111
4A5-2ov_ _. 0.320 sw 8.64 16.43 _ 0 __ 0 _ _ 0 _ _ _0_. _ _ 0 __ 0 _0 _ 0
W 12C-Osw 0.091 nw 2A6 2.30 36 36 88 83 0 0 0 0
4A5-20
v 0.320 n v 8.64 17.32 0 0 0 0 0 0 0 0
4A5-20v 0.320 nw 8.64 17.32 0 0 0 0 0 0 0 0
---.. 11D0, 0,390 nw, . 10.53 . 11.82-. _ 0 0 0 0 ..- 0 0- - _ 0 _ - .. 0
1-0
12C-Osw 0.091 - 2.46 1.40 0 0 0 0 0 0 0 0
11 DO - _ 0.390 _n 10.53, 11.82 _ .0 _ _ 0 0 0 0 0 __ 0._ - - 0
C_. 1613-30ad 0.032_ - 0.86 1.72 - 19_ 19 17 _ _ 33. - 60- _ 60 52 _103
F.. 22A-tpm.._ ..1.180,. - _ .31.86 , .0.00_ 19 5 143 0 - _60- _._ .-6. --. 191 0
6 c)AED excursion -7 -12
Envelope loss/gain 249 109 361 202
12 a) Infiltration 119 32 159 43
b) Room ventilation 0 0 0 0
13 Intemal gains: Occupants@ 230 0 0 0 0
Appliancesrother 0 0
Subtotal(lines6 b:)13) 368 141 520 245
Less exdemalload 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 232 158
14 Subtotal 368 141 752 403
15 Ductloads 10% 23% 37 33 10% 23% 75 94
Total room load 405 175 827 497
Air required(dm) 0 9 0 24
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
F wr27
...... oiFt° 2020-May-1413:age4
--••-°-• -•�•••^---•n••-• Right-Suite®Universal 201919.0.19RSU16793 Page4
...Lot 101612 ARHG-StLot 10 1612 ARHG-S.ru Calc=MJ8 Front Door faces:S
i
i
1-wrightsoft° Right-J®Worksheet Job:��: si 05/ 16121la/2020 LotRHG-S
i House 2o2o
gy: DSILM
One Stop Cooling and Heating Plan: RHG
7225 Sandscove Court,Winter Park,FL 32792 Phone:(407)629-6920 Fax(407)629-9307 Web:vmwOneStopCooling.com License:CAC032444
1 Room name BED 2 BED 3
2 Exposed wall 27.0 ft 10.5 ft
3 Room height 8.0 ft heaUmol 8.0 It heat/oocl
4 Roomdimensions 14.0 x 11.0 ft 14.0 x 10.5 It
5 Room area 154.0 fF 147.0 ft=
Ty Construction U-value Or HTM Area (fF) Load Area (ft) Load
number (BthAF-°F) (BtrhAF) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross NIPS Heat Cool Gross N/P/S Heat Cool
6 W 12C-0sw 0.091 ne 2.46 2.30 16 16 39 37 0 0 0 0
4A5-2. 0.320 ne 8.64 17.32 0 0 0 0 _0 _ 0 0 0
W 12C-0sw 0.091 se 2.46 2.30 112 97 238 223 0 0 0 0
4A5-2ov 0.320 se 8.64 16.43 15 2 130 246 0 0 0 0
11 11D0 0.390 se 10.53 11.82 0 0 0_ 0 0 0 0 0
12C-0sw 0.091 sw 2.46 2.30 88 88 216 203 84 69 170 159
t _G 4A5-2ov_.. _ _ '0.320 sw_ _ _ 8.64 _16.43- 0 0 -0 -- _ 0 - __ __15_ _ 2 130 246
W 12C-Osw 0.091 nw 2.46 2.30 0 0 0 0 0 0 0 0
L: 4A5-2ov 0.320 nw 8.64 17.32 0 0 0 0 0 0 0 0
G 4A5-2ov 0.320 nw 8.64 17.32 0 0 0 0 0 0 0 0
11 DO 0.390 nw - 10.53 _ 11.82 - 0 0-_ _ 0, 0 0_ 0 0 0
R 12C-Osw 0.091 - 2.46 1 A 0 0 0 0 0 0 0 0
11DO 0.390 _n 10.53 11.82 0,_ _ 0 _.- -_0 . _ 0 0 0 01. _ _ ,._ 0
C,_ _ 16B-30ad. _ 0.032 0.86_ _ 1.72 154_ 154 _ 133 _. 265 _ _ -147.._ 147 127 _ _ 253
F 22A-tpm _ 1.180__- 31.86 _0.00- . _-154 27 .860 0 147 11 _M5 ,. -6
6 c)AED a)mrsion 64 71
Envelope loWgain 1617 1038 761 730
12 a) Infiltration 715 191 278 74
b) Room ventilation 0 0 0 0
13 Intemalgains: Occupants@ 230 1 230 1 230
Applianoes/other 0 0
Subtotal(lines 6 to 13) 2332 1460 1039 1034
Less extemal load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 503 342 218 194
14 Subtotal 2835 1802 1256 1228
15 Ductloads 10% 23% 283 422 10% 23% 126 288
FITotal room load 3118 2224 1382 1516
Air required(dm) 0 109 0 74
I
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
I�.F- wrGgF�tsoft- 2020-May-1413:53:27
ACCP. - Right-Suite®Universal 201919.0.19 RSU16793 Page 5
Lot 10 1612 ARHG-StLot 10 1612 ARHG-S.rup Calc=MJ8 Front Door faces:S
I
-wrightsoft' Right-JO Worksheet Job: Lot10 1612 A RHG-S
House Date: 05/14/2020
Efv RHG
One Stop Cooling and Heating Pfan: HG
7225 Sandscove Court,Winter Park,FL 32792 Phone:(407)629-6920 Fax:(407)629-9307 Web:vmwOneStopCooling.00m License:CAC032444
1 Room name MWIC BED 4
2 E>q>osed wall 18.5 ft 10.5 it
3 Room height 8.0 ft heattcool 8.0 ft heat/cool
4 Room dimensions 6.0 x 12.5 it 1.0 x 138.5 it
5 Room area 75.0 W 138.5 fF
Ty Construction U-value Or HTM Area (fF) Load Area (fF) Load
number (BtuhAF-°F) (BtuhAF) or perimeter (ft) (Stuh) or perimeter (it) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 W 12C-0sw 0.091 ne 2.46 2.30 100 100 246 230 84 69 170 159'
.4A572ov 0.320 ne _-.. 8.64 _ 17.32 ,. 0 0 0 -.0 - 15 0 130 260
W 12C-0sw 0.091 se 2.46 2.30 0 0 0 0 0 0 0 0
4A5-2ov 0.320 se 8.64 16.43 0 0 0 0 0 0 0 0
11 11 DO 0.390 se 10.53 11.82 0 0 0 0 0 0 0 0
W 12C-0sw 0.091 sv 2.46 2.30 0 0 0- 0 - . - 0.- _ 0. - - ..0 _ 0
.4A572ov. _ _ _ 0.320 s6v _ 8.64.- -_ 16.43 0 _ 0 __0 _ 0 _-. __0 0 -. _ _--0 - _0
W 12C-Osw 0.091 nw 2.46 2.30 48 48 118 111 0 0 0 0
4A5-2ov 0.320 nw 8.64 17.32 0 0 0 0 0 0 0 0
4A5-2ov 0.320 nw 8.64 17.32 0 0 0 0 0 0 0 0
11 DO 0.390 n_w _ 10.53 _ _11.82 0 0 0 0 0 0 0 0
12C-Osw 0.091 2.46 1.40 0 0 0 0 128 128 314 179
1100 __. 0.390 _n_ .._ 10.53 _ - 11.82. _ 0_.- _ 0 0 _ _ -0 -_ .. _ 0• -- -0
C 16B-30ad 0.032 0.86 1.72 75 75 65 129 139 139 0.00 120 238
F__ 22A-ipm.. ._ 1.180-_ -.. 31.8t , _. .
_ 75 19. _. 589 _ 0 .. - __139. _-__ 11. __- 335 D.
6 c)AED excursion -27 -20
Envelope loss/gain 1018 442 1068 816
12 a) Infiltration 490 131 278 74
b) Room ventilation 0 0 0 0
13 Intemal gains. Occupants@ 230 0 0 1 230
Applianoes/other 0 0
Subtotal(lines 6 to 13) 1508 574 1346 1120
Less extemal load 0 0 0 0
Lesstransfer 0 0 0 0
Redistribution 0 0 146 632
14 Subtotal 1508 574 1492 1753
15 Ductloads 1 10% 23% 151 134 10% 23% 149 411
Total room load 1659 708 1641 2164
Airrequired(cfm) 0 35 0 106
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
�� wri-gF�ts_o_Tt•° 2020-May-1413:53:27
Right-Suite@ Universal 2019 19.0.19 RSU16793 Page 6
Lot 10 1612 ARHG MS\Lot 101612 ARHG-S.rup Calc=MJ8 Front Door faces:S
Job: Lot 10 1612 A RHG-S
wrightsoft° Right-J®Worksheet
Date: 0511412020
gy: DS/LM
One Stop Cooling and Heating Pfan: RHG
7225 Sandscove Court,Winter Park,FL 32792 Phone:(407)629-6920 Fax(407)629-9307 Web:w,wxOneStopCooling.com License:CAC032444
1 Room name AM FLEX
2 Exposed wall 0 ft 10.5 ft
3 Room height 8.0 ft heat/000l 8.0 ft heat/cool
4 Room dimensions 4.0 x 3.0 ft 14.0 x 10.5 ft
5 Room area 12.0 ft' 147.0 ft
Ty Construction U-value Or HTM Area (W) Load Area (ft') Load
number (Btuhff--°F) (BtuhM or perimeter (ft) (Btuh) I or perimeter (ft) (Btuh)
Heat Cool Gross NIPS Heat Cool Gross N/P/S Heat Cool
6 W 12C-0sw 6.091 ne 2.46 2.30 0 0 0 0 0 0 0 0
4A5-2ov. 0.320 ne 8.64 17.32 0 0-- _ .- 0 0 0 - 0 0 0
W 12C-Osw 0.091 se 2.46 2.30 0 0 0 0 0 0 0 0
4A5-2ov 0.320 se 8.64 16.43 0 0 0 0 0 0 0 0
11 D 11DO 0.390 se 10.53 11.82 0 0 0 0 0 0 0 0
- -
W, __ 12C-0sw _ - 0.091 sw 2.46 2.30 0 0 _ 0_ _ 0 84 69 170 159
I G 4A572ov 0.320 sw 8.64 _.16.43_. __-0._ 0- ._ 0 0_ 15. - 2 .130 -_.. 246
W 12C-0sw 0.091 nw 2.46 2.30 0 0 0 0 0 0 0 0
4A5.2ov 0.320 nw 8.64 17.32 0 0 0 0 0 0 0 0
tG 4A5-2ov, 0.320 nw 8.64 17.32 0 0 0 0 0 0 0 0
11 DO _ 0.390 nw _ 10.53 11.82 _ 0 0 0 0 ... -0 0 0 _ _ -0
0
R 12C-0sw 0.091 - 2.46 1A0 32 32 79 45 6 0 0 0
_ D. 11DO- -_ - - - -. .- 0.390_ n ._ 10.531,. 11.82- 0 . 0- 0 _..0 .. -0 __0
C 16B-30ad _ _ _0.032 _ 0.86 1.72 12_ _ 12 _ _„ 10. 21 147 147 127 _ - 253
F 22A-tpm _ _ .1.180 31.86, `- 0.00 - 12 ._ 0- 0 - -0 _ 147, 11- _ 335 0
6 c)AED excursion -3 82
Envelope loss/gain 89 63 761 740
12 a) Infiltration 0 0 278 74
b) Room ventilation 0 0 0 0
13 Intemal gains: Occupants @ 230 0 0 0 0
Appliances/other 1 0 0
Subtotal(lines 6 to 13) 89 63 1039 815
Less ertemalload 0 0 0 0
Lesstransfer 0 0 0 0
Redistribution -89 -03 63 89
14 Subtotal 0 0 1102 903
15 Ductloads 10% 23% 0 0 10% 23% 110 212
Total room load 0 0 1212 1115
Air required(clm) 0 0 0 55
I
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
wrigf�t_soft^ 2020-May-1413:53:27
Right-Suite®Universal 201919.0.19 RSU16793 Page 7
Lot 10-1612 ARHG-SYLot 10 1612 ARHG-S rup Calc=MJ8 Front Door faces:S
i
' -wrightsoft' Right-J®Worksheet Job: Lot 10 1612 A RHG-S
House Date: 05/14/2020
By DS1LM
One Stop Cooling and Heating Plan: RHG
7225 Sandsceve Court,Wnter Park,FL 32792 Phone:(407)629-6920 Fax:(407)629-9.307 Web:www.OneStopCooling.com License:CAC032444
1 Room name GREAT
2 E�Wsed wall 33.5 It 0 ft
3 Room height 8.0 ft heaf/cool 8.0 It heat(cool
4 Room dimensions 18.5 x 15.0 ft 1.0 x 126.0 ft
5 Room area 277.5 ft2 126.0 fF
Ty Conduction U-value Or HTM Area (W) Load Area (W) Load
number (BtuhiW--°F) (Btu or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 V- 12C-Osw 0.091 ne 2.46 2.30 0 0 0 0 -0 -6 0 0
'__._G.4A5.2ov_-_ .- .. _ 0.320 ne_ _8.64., _ 17.32.. - :. -0,_. 0 . _. __0 - 0: .0- _0 0 ---.0
W - 12C-Osw 0.091 se 2.46 2.30 0 0 0 0 0 0 0 0
EG 4A5-2ov 0.320 se 8.64 16A3 0 0 0 0 0 0 0 0
11 D 11DO 0.390 se 10.53 11.82 0 0 0 0 0 0 0 0
WI -- 12C-Osw 0.091 sw 2.46 2.30 120 120 295 276 0 0 0 0
�~_-G 4A5-2ov�------- ___0.320 sw 8.64_ _.16A3 _ _O _ _._ 0_. _--,.0 _. _.0- _ ._0_ 0•, ..__ 0
W 12C-09w 0.091 nw 2.46 2.30 148 99 243 228 0 0 0 0
4A5-2ov, 0.320 nw 8.64 17.32 0 0 0 0 0 0 0 0
4A5-2ov 0.320 nw 8.64 17.32 30 0 259 520 0 0 0 0
_ - 1.1_DO___._._._. _. _ _. . .0.390-nw, _._10, 3 -._- 11.82 _ 200 -.- 224.-, 0_ _._.._0 0 g.
R 12C-Osw' 0.661 2.46 1.40 b 0 0 0 12 -7 -18 -10
11 DO--:__ - _ .= . 0:390 n _. 10.53 __...11.82 0 0 ., _' ,. 0 19_ _..19 _=-.___203- ____228
• 0 _ _.__ .
C __ _ -161330ad _0.032 =- ......0.86. .._.1_72 _,.278 ._.. _ 278__..,- 2401._. -_.478_._ .._126. _ -.._126__ _109 - -217
_1.180 __ . _.. 1.86- _...0.00_. __.. .278_. 34 ,-._1067 _ _ _0 m_ _126.. _ 0 0 0
6 c)AED excursion 171 -20
n '
Envelopeloss/gain 2304 1897 294 415
12 a) Infiltration 887 237 0 0
b) Room ventilation 0 0 0 0
13 Internal gains. Occupants@ 230 0 0 0 0
Appliances/other 0 0
Subtotal(lines 6 to 13) 3192 2134 294 415
Less external load. 0 0 0 0
Lesstransfer 0 0 0 0
Redistribution 27 38 -294 -415
14 Subtotal 3219 2172 0 0
15 Dudloads 10% 23% 322 509 10% 23% 0 0
Total room load 3540 26821 0 0
Air required(dm) 1 0 131 0 0
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
_ -+}t wrightsoft� Right-Suite®Universal 2019 19.0.19 RSU16793 2020.May 141 Page 8
'��...Lot 101612 ARHG-S\Lot 101612 ARHG-S.rup Calc=MJ8 Front Door faces:S 9
' Job: Lot 101612 A MG-S
ft r �+- wrightsoo Duct System Summary pate: 05/1412020
House EIT. DS1LM
One Stop Cooling and Heating Plan: MG
7225 Sandscove Court,Winter Park,FL 32792 Phone:(407)629-6920 Fax(407)629-9307 Web:wwwOneStopCooling.00m License:CAC032444
Project • •
For: WADE JOURNEY
6504 Santa Clara Blvd,Fort Pierce,FL
Heating Cooling
External static pressure 0 in H2O 0.50 in H2O
Pressure losses 0.16 in H2O 0.16 in H2O
Available static pressure -0.2 in H2O 0.34 in H2O
Supply/return available pressure 0.080/-0.080 in H2O 0.170/0.170 in H2O
Lowest friction rate -0.12 in/100ft 0.250 in/100ft
Actual airflow 0 cfm 740 dim
Total effective length(TEL) 136 ft
SupplyDetail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv
Name (Btuh) (cfm) (cfm) FIR (in) (in) Mati Ln(ft) Ln(ft) Trunk
BA2 c 497 0 24 0.287 4.0 Ox0 VIFx 18.3 100.0 st1
BED c 2224 0 109 0.287 6.0 Ox0 VIFx 23.6 95.0 st1
BEDS c 1516 0 74 0.283 6.0 Ox0 VIFx 20.1 100.0 st1
BED4 c 2164 0 106 0.283 6.0 Ox 0 VIFx 19.9 100.0 st1
FLEX c 1115 0 55 0.279 5.0 Ox0 VIFx 21.9 100.0 st2
GRE/U c 1341 0 66 0.295 5.0 Ox 0 VIFx 20.4 95.0 st2
GREAT-A c 1341 0 66 0.273 5.0 Ox0 VIFx 29.5 95.0 st2
KIT c 2188 0 107 0.277 6.0 NO VIFx 28.0 95.0 st2
MBA c 297 0 15 0.279 4.0 Ox 0 VIFx 22.1 100.0 st2
MBED c 1550 0 76 0.289 6.0 Ox 0 VIFx 22.7 95.0 st2
MwC c 708 0 35 0.254 4.0 Ox 0 VIFx 34.0 100.0 st2
PM c 175 0 9 0.250 4.0 Ox 0 VIFx 36.2 100.0 s12
SupplyDetail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk
st1 PeakAVF 0 313 0.283 575 10.0 .0 x 0 VinlFlx
st2 PeakAVF 0 427 0.250 543 12.0 0 x 0 VinlFlx
WrAg171�OTt 2020-May-1413:53:28
�� _ e Right-SuileC�Universal 2019 19.0.19 RSU16793 Page 1
AM ...Lot 101612 ARHG-StLct 10 1612 ARHG-S.rup Calc=MJ8 Front Door faces:S
Return Branch Detail TAble
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
j Name Size(in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening(in) Matl Trunk
rbl Ox 0 0 740 0 0 0 0 Ox 0 VIFx
WtTiMgI7t5Oft'° 2020.May-1413:53:28
AL- ,,, _, „. Right-SuiteO Universal 201919.0.19RSU16793 Paget
/1CCA ...Lot 101612 ARHG-S\Lot 101612 ARHG-S.rup Calc=MJ8 Front Door faces:S
Static Pressure Friction Rate Job: Lot101612ARHG-S
-�- wrightsoW ressure an on Date: 05114/2020
House 13T. DS1LM
One Stop Cooling and Heating Plan: RHG
I
7225 SandsoDve Court,Winter Park,FL 32792 Phone:(407)629-6920 Fax(407)629-9307 Web:www.OneStopGooling.com License:CAC032444
Project • •
For: WADE JOURNEY
6504 Santa Clara Blvd,Fort Pierce,FL
Available
Heating Cooling
(in H2O) (in H2O)
External static pressure 0 0.50
Pressure losses
Coil 0 0
Heat exchanger 0 0
Supply diffusers 0.03 0.03
Return grilles 0.03 0.03
Filter 0.10 0.10
Humidifier 0 0
Balancing damper 0 0
Other device 0 0
Available static pressure -0.2 0.34
• Length
Supply Return
(ft) (ft)
Measured length of run-out 22 0
Measured length of trunk 15 0
Equivalent length of fittings 100 0
Total length 136 0
Total effective length 136
Friction
Heating Cooling
(in/10011t) (in/100ft)
Supply Ducts -0.118 <0.06 0.250 >0.18
Return Ducts -0.118 <0.06 0.250 >0.18
Fitting Equivalent LengthDetails
Supply 4X=35,11 A=20,11 G=5,11 G=5,1 A=35:Total EL=100
Return TotalEL=0
wrightsoft- 2020-May-14 13:53:28
Right-Suite®Universal2019 19.0.19 RSU16793 Page 1
ACCP. ...Lot 10 1612 ARHG-S\Lot 10 1612 ARHG-S.rup Cale=MJ8 Front Door faces:S
I
i
i
N
I
I
i
i
I
I
WWI 1
r i Cz 9 cfm
PAN Bx4
10x6
107 cfm
MWIc
GREAT _ I x4
5 i 'V 35.Bz
u16 ost 10xfi I '6 �, ;
ficflli--�•\ -n6'6cftm-�� � � - � ,� .o�
EF1=50 CFM Fan
EF2=80 CFM Fan _ I� 4"
EF3=110 CFM Fan
EFL1=50 CFM Fan 5" 5 " 4 r -gi
EFL2=80 CFM Fan I cMBA 61, EFL1 ViR
EFL3=110 CFM Fan
\
FLEX_ 5°� .-' v-
VTR=Vent to Roof FB31 I 9 76 cfm
VTW=Vent to Wall w q 10x6 24x 4
DV=Dryer Vent S10z61
RV=Range Vent
— — =Lineset Chase 12 �jppc cfm - 24x4
Condensate ���� 8x4 DV VTR
�T =Thermostat 18/8 iI Dx6
SRB=Small Reduction Box 74 cfm
LRB=Large Reduction Box i r
FB8=Feld Built Box we-1:20rw 14s
4x a�A 6 1UOXC6im ®SEERH.P.
\`
24
EFI VTR �— ffrLES) RREA�ER
i ui -f LRB 1 u eox --
BA2 _.
24ad c t 4"
di >Czrr..r FOY -
6 24x4 - Y
5: GAR
j' L RAGE OCCF
)IIppi' I 91 14:CKNE?PREVE
=BED 1IIz6cf
I
I
Job M Lot 101612 A RHG-S One Stop Cooling and Heating Scale:1:80
Performed by DS/LM for: Page 1
WADE JOURNEY 7225 Sandscove Court fagh1 . .e@ Universal 2019
6504 Santa Clara Blvd Winter Park,FL 32792 20-lVl9 R413:55:
i 2020-May-1413:55:24
Fort Pierce,FL Phone:(407)629-6920 Fax:(407)629-9307 FIG-S\Lot 10 1612 A RHG-S.rup
www.OneStopCooling.com