Ref: 3211 Sunrise Blvd, Proposed Change of Use: Existing Abandoned Garage to Storage
Permit #:1912‐0490
Dear Dave,
We received your comments. Please find our responses below:
Comment 1:
ALL WORK TO BE SHOWN. OUTLETS IN A STORAGE BUILDING REQUIRE GFCI
PROTECTION. OUTSIDE LIGHT REQUIRED FOR EGRESS. NO SWITCHES OR
RECEPTACLES PERMITTED IN THE BATHTUB/SHOWER DELINEATION. GROUNDING
ELECTRODE SYSTEM REQUIRED. INSTALLATION TO MATCH PLANS, ALL WORK TO
MEET REQUIRED ELECTRICAL REQUIREMENTS
Response:
All outlets are proposed to be GFCI protection. Outside light proposed. No switches or
receptacles are proposed in the bathtub/shower area. Plan note added for grounding electrode
system.
Comment 2:
PLEASE INCLUDE ON PLANS ALL APPLICABLE BUILDING CODES THIS WORK IS
DESIGNED TO. 107.2 FBC
Response:
Building Codes included. Please see sheet 7 of 7.
Comment 3:
PLEASE INDICATE WIND SPEEDS SPECIFIC TO THIS PROJECT.107.3.5 FBC
Response:
Wind speed is included. For risk category I and St. Lucie County, using Florida Building Code –
Building, Figure 1609.3(3), design wind speed is 145 mph.
Comment 4:
PROVIDE WALL SECTION FOR GARAGE DOOR INFILL. INCLUDE ATTACHMENT
DETAILS FOR FILLED CELL REINFORCEMENT TO EXISTING STRUCTURE. INTERIOR
WALL FINISH AND ATTACHMENT DETAILS. EXTERIOR WALL FINISH.
Response:
Wall section for garage door infill is added. Attachment details, interior and exterior wall finish
are added.
Comment 5:
PROVIDE IN SCOPE WORK METHOD FOR REMOVAL OF GARAGE DOOR. 107.2 FBC
Response:
Revised scope of work with abandoned garage door removal and new wall construction is
attached.