HomeMy WebLinkAboutProduct Approval Code Version 2014
Application Status Approved
Comments E IVSD
Archived
FEB 15 2017
Product Manufacturer Dynamic Metals PERMITTING
Address/Phone/Email 3201 SE Dominica Terace St. Lucie County, FL
Stuart, FL 34997
X772) 872-8030
juan@dynamicmetal.net
Authorized Signature Juan Martinez
juan@dynamicmetal.net
Technical Representative
Address/Phone/Email
Quality Assurance Representative
Address/Phone/Email
Category' Roofing
Subcategory Metal Roofing
Compliance Method Evaluation Report from a Florida Registered Architect or a
Licensed Florida Professional Engineer
Evaluation Report- Hardcopy Received
Florida Engineer or Architect Name who developed Thomas D. Sullivan
the Evaluation Report
Florida License PE-55358
Quality Assurance Entity Keystone Certifications, Inc.
Quality Assurance Contract Expiration Date 12/06/2026
Validated By Charles L. Anderson, PE
Validation Checklist - Hardcopy Received
Certificate of Independence FL21388 RIO COI Letter of Independence -Sullivan,pd
Referenced Standard and Year(of Standard) Standard Year
UL580 2006
Equivalence of Product Standards
Certified By
Sections from the Code
Product Approval Method Method 1 Option D
FL# Model, Number or Name Description
4"" 1388.1 1" Nailstrip-24 Ga Steel Galvalume 1" Nailstrip, 24 Ga Steel Galvalume non-structural
roof panel
Limits of Use Installation Instructions
Approved for use in HVHZ: No FL21388 RO II_D_ynamic 1.0 24 gage steel.pdf
Approved for use outside HVHZ: Yes Verified By: Thomas D. Sullivan 55358
Impact Resistant: N/A Created by Independent Third Party: Yes
Design Pressure: +N/A/-206 Evaluation Reports
Other: Fasteners at 6" OC and 6" from ends. Uplift FL21388_RO A 1.0 24 gage steel.pd�
DP equals 206 psf(includes FS=2) Created by Independent Third Party: Yes
21388.2 1-1/2" Nailstrip-.032 Aluminum 1-1/2" Nailstrip, .032 Aluminum non-structural roof
panel
Limits of Use Installation,Instructions
Approved for use in HVHZ: No FL21388 RO 11-1.5 nailstrip 032 Aliuminum SS.pdf
Approved for use outside HVHZ: Yes Verified By: Thomas D. Sullivan 55358
Impact Resistant: N/A Created by Independent Third Party: Yes
Design Pressure: +N/A/-337 Evaluation Reports
#t Other: Fasteners 6" OC and 6" from ends FL21388 RO AE_1.5 nailstrip 032 Aliuminum SS.pdf
4 Created by. Independent Third Party: Yes
21388.3 1-1/2" Nailstrip-24 Ga Steel 1-1/2" Nailstrip, 24 Ga Steel non-structural roof
panel
«` Limits of Use Installation Instructions
.h Approved for use in HVHZ: No FL21388_R0 II_1.5 Nailstrip 24 gage steel SS.Ddf
Approved for use outside HVHZ: Yes Verified By: Thomas D. Sullivan 55358
r" R; Impact Resistant: N/A Created by Independent Third Party: Yes
Design Pressure: +N/A/-307 Evaluation Reports
Other: Fasteners 6" OC and 6" from ends FL21388_90AE_1.5 Nailstrip 24 gage steel SS.pdf
Created by Independent Third Party: Yes
21388.4 1-3/4"Snaplock-.032 Aluminum 1-3/4" Snaplock-.032 Aluminum non-structural roof
IN- panel
Limits of Use Installation Instructions
, Approved for use in HVHZ: No FL21388 RO 13_1.75 Snaplock 032 Alum SS.pdf
t4 - Approved for use outside HVHZ: Yes Verified By: Thomas D. Sullivan 55358
Impact Resistant: N/A Created by Independent Third Party: Yes
Design Pressure: +N/A/-191 Evaluation Reports
x.
a Other:Field Installation Uplift DP: clips at 16" OC FL21388 RO AE 1.75 Snaplock 032 Alum SS.pdf
and 4"from ends.equals 146 psf(includes FS=2); Created by Independent Third Party: Yes
Corner Installation Uplift DP: clips at 8" OC and 4"
t from ends equals 191 psf(includes FS=2)
' %
- ` 21388.5 1-3/4" Snaplock-24 Ga Steel 1-3/4" Snaplock, 24 Ga Steel non-structural roof
panel
* � Limits of Use Installation Instructions
} �
Approved for use in HVHZ: No FL21388 RO II_1.75 Snaplock 24 Gage SS.pdf
Approved for use outside HVHZ: Yes Verified By: Thomas D. Sullivan 55358
«�r Impact Resistant: N/A Created by Independent Third Party: Yes
Design Pressure: +N?A/-243 Evaluation Reports
` Other: Field Installation Uplift DP: Clips at 16" OC, FL21388 RO AE_1.75 Snaplock 24 Gage SS.pdf
sd r
equals -176 psf(includes FS=2); Corner Installation Created by Independent Third Party: Yes
ro x } ,E Uplift DP: Clips at 8" OC, equals 243 psf(includes
QXT
21388.6 5v Crimp-.032 Aluminum 5V Crimp, .032 Aluminum non-structural roof panel
Ii
a Limits of Use Installation Instructions
' Approved for use in HVHZ: No FL21388_R(OII_5V Crimp 032 Alum SS.pdf
a
Approved for use outside HVHZ: Yes Verified By: Thomas D. Sullivan 55358
Impact Resistant: N/A Created by Independent Third Party: Yes
Design Pressure: +N/A/-183 Evaluation Reports
Other: Fasteners at 12" OC and 6" from ends. Uplift FL21388 RO AE 5V Crimp 032 Alum SS. df_
DP of 183 psf (includes FS=2) -.- Created by Independent Third Partv: Yes.
r
JB&B ENGINEERING, LLC
DYNAMIC METALS; LLCCONSULTING ENGINEERS
5203 Silver Charm. Terrace
3201 SE Dominica Terrace Wesley Chapel, FL 33644
Stuart, Florida 34997 Phone (813)646-1323
Email TSullivaneng®gmail.cam
FL Certiftcate of Authorization.#30903
DYNAMIC " NAMSTRIP"
Drawings
-� 16"
2/4
Panel Profile
16"o.c.
'Abod neck
Integral Snap Lock
(rr ,15i
C•, --' s-`-- - =_- Panciip Screws
o dot-"
• s�°OOMAXIMUM DESIGN UPLIFT PRESSURE=206.0 PSF
pe
p •o o o•o° ��`�o ANCHORS TO BE SPACED 6" FROM ENDS & 6" O.C.
O
o°°��Ci Nis •••'rl�p®
0 o Client Name:DYNAMIC METALS, LLC
to ° 2 0 ® Project Name:DYNAMIC NAIL 1.0" STRIP 24 go STEEL
o //yy '�
THOMe+� LLNAI T. E OCOMPU� E�/y Tr
FLORIDA BUILDING CODE 5TH ED. (2014) Project Address: FLORIDA PRODUCT APPROVAL
39 o W
�Bd ••,� Q V,o 6•� oJ� N0.216-1062 DATE: 10-29-2016
0
°a;ooD�NAU
Jf 30tl1.90
JB&B Engineering Consultants, LLC
5203 Silver Charm Terrace
Wesley Chapel, FL 335-44
Phone: 813-545-1323
Email:TSullivanengfcimail.com
Florida Certificate of Authorization#30903
Product Evaluation Report
Dynamic 1.0" Nail Strip 24 gage Steel
Non-HVHZ
1.0 Product Manufacturer: Dynamic Metals, LLC
3201 SE Dominica Terrace
Stuart, FL 34997
2.0 Code edition: Florida Building Code 5th edition (2014)-Building Volume-Non-HVHZ
Sections 1504.3.2 and 1504.7
3.0 Evaluation Method: Engineering Evaluation (method 1 D) in accordance with 61 G20-3.005 F.A.C.
4.0 Product Category: Roofing
4.1 Product Sub-Category: Metal Roofing
5.0 Product Description:
5.1 General Description: Dynamic 10' nailstrip 24 gage steel non structural roof deck
5.2 Fy=50 ksi
5.3 Panel Thickness:20Gage(0,0276")minimum coated thickness
5.4 Corrosion Resistance to comply with Florida Building Code 51h ed. (2014), section 1507.4.3
5.5 Width: 15"maximum coverage
5.6 Rib Height: 1.0"major rib height @ 15"o.c.
6.0 Panel Fastener:#10 x V pancake head fastener through the nail strip 6"from ends and 6" o.c. with
an integral male/female integral snaplock with adhesive.Corrosion resistance per Florida Building Code
51h edition(2014), sections 1506.6 and 1507.4.4
6.1 Substrate Description: 1 layer of 30#organic felt paper over minimum 7./16" OSB(or 15/32"
4=ply APA plywood)over,2x SYP rafters spaced no more than 24"o.c. Substrate must meet all
applicable requirements and be designed with the Florida Building Code 5'h edition (2014)
6.2 Design Uplift Pressures:
Field Installation 412.0 psf/2=206.0 psf(Fasteners spaced 6"ox.And 6"from ends)
7.0 Code Testing Performance Requirements:
7.1 UL 580-0.6-Test-for Uplift Resistance of Roof Assemblies
7.2 UL 1897-04-Uplift Test for Roof Covering'Systems
8.0 Performance Test Results Summary:
8.1 Architectural Testing, Inc.West Palm Beach, FL(TST 1527), Report#G1195.06-450-44
8.1.1 Signed/Sealed by Charles Anderson, P.E. on October 2131, 2016
8.1.2 UL580-06/UL 1897-04 Field Installation (7412.0:0 psf)
9.0 Installation Instructions:
9.1 Per manufacturer's installation instructions and fastening patterns described herein
paUe 1 2
JB&B Engineering Consultants, LLC
5203 Silver Charm Terrace
Wesley Chapel, FL 33544
Phone: 813-545-1323
Email:TSullivaneng(ammail.com
Florida Certificate of Authorization#30903
10.0 Design Procedure: Based on the dimensions of the structure,appropriate wind loads are determined
using Chapter 16 of the Florida Building Code 2014 for roof cladding wind loads. These component wind
loads for roof cladding are compared to the allowable design pressures listed herein. The design
professional shall select the the appropriate erection details to reference in his drawings for proper fastener
attachment to his/her structure and analyze the panel fasteners for pullout and pullover. Support framing
must be in compliance with Florida Building Code 2014 chapter 22 for steel, chapter 23 for wood and
chapter 16 for structural loading.
11.0 Limits and Conditions of Use:
11.1 Maximurn allowable design pressures listed in this report
11.2 Fire classification has not been considered and is outside the scope of this report
11.3 Panels were not evaluated structurally to resist shear diaphragm, axial, transverse or
racking loads
11.4 Alternate conditions not specifically addressed by this approval shall be designed by a
registered Florida Professional Engineer or Architect
11.5 The structural adequacy of the substrate bearing the wind loads superimposed by this
product are the responsibility of others
11.6 Underlayment shall comply with the Florida Building Code 5th edition (2014)
11.7 Minimum slope shall comply with the Florida Building Code 5th edition (2014, including
section 1507.4.2 and in accordance with the manufacturers recommendations. For
slopes less than 3:12, lap sealant must be used in the panel side laps
12.0 Quality Assurance Entity: The manufacturer has established compliance of roof panel products in
Accordance with the Florida Building Code and Rule 61 G20-3.005(3)for manufacturing under a quality
assuranceprogram audited by an approved quality assurance agency.
13.0 Certificate of Independence: Pursuant to the requirements of 61620-3 F.A.G, I hereby certify that
this Florida Professional Engineer, performing this evaluation, does not have nor will acquire an interest in
any company manufacturing or distributing products for which the report is being,issued.This is also to
certify that this Florida Professional Engineer, does not have,nor will acquire a financial interest in any
other entity involved in the approval process of this product.
14.0 Certification: in the professional opinion of this evaluating engineer the aforementioned product,
meets the requirements of the Florida Building Code 2014 (5th edition), specifically sections 1504.3.2 and
1504.7 for use in non-HVHZ,when utilized within the limits of use noted herein.
'.Oq%00©1Opp8°
IS D.S�j°°o
l_e ° C E IV
° m
T s D. m
FLS •5358 •'��o
� T o
0
Jo
.806 ONAI_F�L.aoo°
'tF5in7a'�
Page22
J
Cerf lixite ofAuthorizatron No.29824
Raw rdad( 17520 Edinburgh Drive I'O"X R"EEM A E".4'K
Tampa,FL 33647
{813}480.3421
TECHNICAL 'ER'4RCES,
EVALUATION REPORT FLORiD9?i°BUiLDINC,CODE 5r"EDn10N(2014)
Manufacturer: ALPHA PROTECH ENGINEERED PRODUC*j.'*C. Issued June 22,2015
301 South Blanchard Street
Valdosta,GA 31601 a ' "
(229)2421931
htta l/www alahanrotech corn `
Manufacturing Locations: Valdosta,GA 1 207
Quality AssurancRAQCO,Inc.(QUA1990) . PERMlTT!!
e:
St:°Lucie County,FL
3f
SCOPE
'. Category: Roofing
Subcategory: Underlayments
Code Sections: 15072.3,1607.3.3,1507.5.3,1547.7.3,1507.8.3, �t
Properties: Physical properties 4
REFERENCES
Enth Report No. L Sfandan9 Year
PRI Construction Matedals Technologies(TST5878) AEP-017-02-01 ASTM D 226 2006
ASTM D 4869 2005el
RADCO,Inc(TST'19B7) RAD-5212 AC 188 2012
Rarntech Laboratories,Inc.W6127) 13075-04-08 r AC 188 2012
PRODUCT DESCRIPTION
REX'm SynFelt A mechanically attached,Woven polypropylene undadayr�iient(nominal weightµ2,56
lbM00f 2)used an alternative to'ASTM D 226,Typ -,!.:and Type 11 roofing undedayments,
REXtrenie A mechanically attached,woven polypropylene ujf4drlayment(nominal weight=2.87
W10011?)used an alternative to ASTM D 226,Type;and Type 11 roofing undedayments
TECHNOply A mechanically attached,woven polypropylene uridedayment(nominal weight=2.05
Ib110011x)used an alternative to ASTM D 226,Type[and Type If roofing underlayments .
TECHNO SS A mechanically attached,woven polypropylene udd'edayment(nominal weight=2.00
Ib1100ttx)used an alternative to ASTM D 226,Type I and Type 11 and ASTM D 4869,
Type 11 and IV roofing underlayments
AFPLtcAmox INSTRUCTIONS
Deck Type: The roof deck shall be constructed of closely fisted,solid sheathing for new or existing
construction. Sheathing-shall be installed in'aroordance with FBC requirements. Roof
decks shall have no more than 119"gap at abuttting:joints.
Min.slope: 2:12.For slopes.less than 4:12,the undedaymegt must be haff4apped a full 24"over the
i
underlying course.
.Attachment method: Undedayment shall be attached in aceordanderwrth the FBC and manufacturer's
Installation Instructions. At minimum,mechanically fastened with ruin.12 ga.corrosion
resistant ring shank nail with min.14nch diameter:corrosion resistant round cap to a min.
3/44nch penetration, 8" o.c. at side and end laps and 24" o.c in a staggered pattern
along the center lines printed on the sheet.The;side laps shall be a minimum 3"wide
APT15601.1 FL12642-R4 Page 1 of 2
This evaluation report is provided for State of Florida product approval under Rule 61q20-3. The manufacturer shalt notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty,installation,recommended use,or other product attributes that are not
specifically addressed herein.
r?ka
t�
j
1•t
CREEK ALPHA PROTECH ENGINEERED PRODUCTS,INC.
Underlayments
TIrCHmcAL Swnms,LLC
and minimum 6"wide at the end laps. The underl anent is installed starting at the eave,
with the length of the roll parallel to the-eave with:the.printed side facing up. All side laps
shall be installed to shed water from the deck. `. ..
Allowable roof coverings: Asphalt shingles,slate shingles, clay and concrete tiles,metal roof panels and shingles,
wood shakes and shingles _
LimrwiON8
1) This evaluation report is not for use In the'HVHZ.
2) Fir:Classification is not within the scope of this evaluation.
3) Wind uplift resistance is not within the scope of this evaluation.
4) Installation of the evaluated product shall comply with this report,the FBC,and the manufacturer's published
application instructions. Where discrepancies exist between these sources,the more restrictive and FBC
compliant installation detail shall prevail.
6) Deck substrates shall be clean,dry, and free'from any..irregularibes and debris. All fasteners in the deck
shall be checked for protrusion and corrected prior to underlayment application.
6) The roof deck shall be constructed of closely fitted sheathing for ne�r+or existing construction. Roof deck
shall be installed in accordance with FBC requirements.
7) Unless otherwise stated,the minimum roof slope shall be in accordance with FBC requirements.
8) All undedayments shall be installed with the roll length parallel to the eave,starting at the eave,and lapped
in success courses installed up the deck In a manner that effectively'sheds water from the deck. End laps
shall be staggered between courses In accordance with the manufacWi'er's application instructions.
9) Contact the manufacturer when installing at temperatures below the minimum application temperature.
10) The underiayment may be used as described in other current.FBC product approval documents.
11) Roof coverings shall not be adhered directly to the underlayment. .fwof coverings shalt be mechanically
fastened through the underlayment to the roof deck. "
12) The underlayment shall be exposed on the roof deck for a maximum 30 days unless otherwise stated,
13) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61G2".
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest, P.E. have demonstrated'compliance with the Florida Building
Code -Edition(2014)as evidenced in the referenced documents submitted by`the named manufacturer.
y14 • •
UM
2 13.55.44
�'."•+;y'' ".i�• :iR;.l..t,:.Y •njj,..b My..+!iaai5si••.a"!,*`?M,:�h:
-0400
OT
Zachary.��� � .. -�'�.R,�,,•;��,�-..: ry R.Priest P.E.
Florida Registration No.74021
Organization No.ANE9641
CERTIFICATION OF INDEPENDENCE a
CREEK Technical Services,LLC does not have,nor wll it acquire,a financial interest in any w mpary'lrlanuhacWring or distributing products underthis
evaluation..
CREEK Technical Services,LLC Is not owned,operated,or controlled by any company manufacturing or distributing products under this evaluation.'
ZacharyR.Priest,P.E.does not have,nor Al! :I
acquire,afinancral interest in any company manufacturing or distributing products under this evaluation.
Zachary R.Priest,P.E.does not have,nor will ecqulre,a financial interest in any other entity lmolvedl r'the approval process of the product.
END OF IRMPORT
APT15001.1 FL12512-R4 Page 2 of 2
This evaltiation report Is provided for State of Florida product approval under Rule 61G2W. The manufacturer shall notify CREEK
Technical Services,IlC of any product changes or quality assurance changes throughniW the duration for which this report is valid.
This evaluation report does not express nor imply warranty,Installation,recommended use,or other product attributes that are not
specifically addressed herein.