Duro-Last Roofing, Inc. Evaluation Report D9750.05.08-1110
525 Morley Drive
Saginaw, MI 48601
(800) 248-0280
FL1559-R13
Date of Issuance: 05/22/2008
Revision 10: 10/17/2018
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code. The product described herein has been evaluated for
compliance with the 6eh Edition (2017) Florida Building Code sections noted herein.
DESCRIPTION: Duro-Last Single Ply Roof Systems
LABELING: Labeling shall be in accordance with the requirements of the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. of any changes to the
product(s), the Quality Assurance or the production facility location(s). MEMO ETC, LLC requires a complete review of
this Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "NEMO ETC, LLC Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 5, plus a 44-page Appendix.
Prepared by:
jJJTEn", ---
Robert J.M. Nieminen, P.E.
'-;F.^.;_�•��= The facsimile seal appearing was authorized by Robert
Florida Registration No. 59166, Florida DCA ANE1983
'w� �4" ''����` �i' Nieminen, P.E. on 10/17/2019. This does not serve as an
� .;u,,,,,,;,;�.�
electronically signed document.
CERTIFICATION OF INDEPENDENCE:
1. NEMO ETC, LLC does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. NEMO ETC, LLC is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
©2019 NEMO ETC, LLC
ONEMO I etc.
ROOFING SYSTEMS EVALUATION:
Product Category: Roofing
Sub -Category: Single Ply Roof Systems
Compliance Statement: Duro-Last Single Ply Roof Systems, as produced by the Duro-Last Roofing, Inc., have
demonstrated compliance with the following sections of the 6th Edition (2017) Florida Building Code through
testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and
Limitations / Conditions of Use set forth herein.
Section
1504.3.1
1504.3.1
1504.7
1507.13.2
1523.6.2
Entity
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST11294)
ERD (TST6049)
ERD (TST6049)
FM Approvals (TST1867)
FM Approvals (TST1867)
FM Approvals (TST1867)
FM Approvals (TST1867)
FM Approvals (TST1867)
FM Approvals (TST1867)
FM Approvals (TST1867)
FM Approvals (TST1867)
FM Approvals (TST1867)
FM Approvals (TST1867)
FM Approvals (TST1867)
FM Approvals (TST1867)
FM Approvals (TST1867)
FM Approvals (TST1867)
NEMO ETC, LLC
Certificate of Authorization #32455
Property
Wind
Wind
Impact
Physical Properties
Wind
Examination
FM 4474
FM 4474
FM 4474
FM 4474
FM 4474
Physical Properties
F M 4474
FM 4474
FM 4474
FM 4474
Physical Properties
FM 4474
FM 4474
FM 4474
FM 4474
FM 4474
FM 4474
Physical Properties
FM 4474
Tensile Adhesion
Tensile Adhesion
FM 4470
FM 4470
FM 4470
F M 4470
FM 4470
FM 4470
Standard
FM 4474
UL 1897
FM 4470
ASTM D4434
TAS 114
Reference
02733.01.05-1
02737.03.05-1
02743.04.06-R1
02744.05.06
D6760.08.07
02750.02.08
P12200.10.08
02762.03.05-R2
D35320
D42320.08.12
D35210.08.11-R1
D41660SC
D43030SC
D42390.10.12
D42320.11.12
D41660.11.12-R1
SFS-SC10010.02.16-R1
DL-SC13445.02.17
14325.07.17-3
ICP-SC15630.09.17
ICP-SC16225.09.17
2M4A8.AM
3Y5A6.AM
4D6A4.AM
1X2A7.AM
3005604
3008342
FM 4470
3009502
FM 4470/4474
3012321
FM 4470
30IS444
FM 4470/4474
3014692
FM 4470/4474
3023458
FM 4470/4474
3026128
FM 4470/4474
3026508
FM 4470/4474
3030225
6T" EDITION
(2017) FBC NON-HVHZ EVALUATION
Duro-Last Single Ply Roof Systems
Year
2011
2012
2012
2012
2011
Date
01/21/2005
03/21/2005
06/13/2006
05/17/2006
08/01/2007
02/04/2008
10/14/2008
04/01/2010
04/20/2011
08/31/2012
09/17/2012
09/27/2012
09/28/2012
10/03/2012
11/30/2012
12/12/2012
07/06/2016
02/17/2017
07/20/2017
09/06/2017
09/06/2017
03/05/1987
03/10/1995
08/09/1999
08/09/1999
03/13/2000
10/19/2000
12/21/2000
07/29/2002
07/11/2003
08/05/2003
07/18/2006
08/04/2006
05/03/2007
06/18/2007
Evaluation Report D9750.05.08-1110
FL1559-R13
Revision 10: 10/17/2019
Page 2 of 5
ONEMOjetc.
Knfty
Examination
Reference
Date
FM Approvals (TST1867)
FM 4470/4474
3033314
08/26/2008
FM Approvals (TST1867)
FM 4470/4474
3032172
06/12/2009
FM Approvals (TST1867)
FM 4470/4474
3041535
06/08/2011
FM Approvals (TST1867)
FM 4470/4474
3040346
07/06/2011
FM Approvals (TST1867)
FM 4470/4474
3040741
10/17/2011
FM Approvals (TST1867)
FM 4470/4474
3047477
10/03/2012
FM Approvals (TST1867)
FM 4470/4474
3044466
11/07/2012
FM Approvals (TST1867)
FM 4470/4474
3056207
02/09/2016
FM Approvals (TST1867)
FM 4470/4474
3059661
09/21/2018
FM Approvals (TST1867)
FM 4470/4474
PR451159
05/09/2019
NEMO (TST11294)
FM 4474
2a-DL-19-LSWUS-01.A
06/27/2019
PRI(TST5878)
FM 4474
DLRI-013-02-01
08/28/2012
PRI(TST5878)
FM 4474
DLRI-014-02-01
08/28/2012
PRI(TST5878)
FM 4474
DLRI-029-02-01
10/25/2012
PRI(TST5878)
FM 4474
DLRI-070-02-01
07/30/2014
PRI(TST5878)
FM 4474
DLRI-073-02-02
11/18/2014
PRI(TST5878)
ASTM D4434
DLRI-080-02-01
08/03/2016
PRI (TST5878)
Small -Scale Criticality
DLRI-021-02-01.15
05/09/2019
PRI(TST5878)
FM 4474
DLRI-133-02-01
05/09/2019
PRI(TST5878)
FM 4474
DLRI-133-02-02
09/06/2019
UL(TST1740)
UL1897
TGIK.R10128
03/25/2002
UL, LLC. (QUA9625)
Quality Control
Service Confirmation
04/12/2019
4. '•••DESCRIPTION:
This Evaluation Report covers Duro-Last Single Ply Roof Systems installed in accordance with Duro-Last published
installation instructions and the Limitations / Conditions of Use herein.
4.1 Duro-Last roof cover is a nominal 40-mil (1.0 mm), 50-mil (1.3 mm) or 60-mil (1.5-mm) thick thermoplastic (PVC)
roof covering having an 18 x 14 polyester fabric reinforcement composed of 840 x 1000 denier threads.
4.2 Duro-Last EV roof cover is a nominal 50-mil (1.3 mm) or 60-mil (1.5-mm) thick thermoplastic (PVC/KEE) roof
covering having an 18 x 9 polyester fabric reinforcement with weft insertion, composed of 840 x 1000 denier
threads.
4.3 Duro-Tuff roof cover is a nominal 50-mil (1.3 mm) or 60-mil (1.5-mm) thick thermoplastic (PVC) roof covering
having an 18 x 9 polyester fabric reinforcement composed of 840 x 1000 denier threads.
4.4 Duro-Fleece roof cover is a nominal 50-mil (1.3 mm) or 60-mil (1.5-mm) thick thermoplastic (PVC) roof covering
having an 18 x 9 polyester fabric reinforcement composed of 840 x 1000 denier threads and a polyester fleece
backing.
4.5 Duro-Fleece Plus roof cover is a nominal 50-mil (1.3 mm) or 60-mil (1.5-mm) thick thermoplastic (PVC) roof
covering having an 18 x 14 polyester fabric reinforcement composed of 840 x 1000 denier threads and a polyester
fleece backing.
NEMO ETC, LLC Evaluation Report 139750.05.08-1110
Certificate of Authorization #32455 6i" EDITION (2017) FBC NON-HVHZ EVALUATION FL1559-1113
Duro-Last Single Ply Roof Systems Revision 10: 10/17/2019
Page 3 of 5
01
MEMO I etc.
5.1 This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nieminen, P.E. are, in any way, the Designer
of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting
or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Refer to a current Approved Roofing Materials Directory for fire ratings of this product.
5.4 For steel deck installations, foam plastic insulation shall be separated from the building interior in accordance with
FBC 2603.4 unless the exceptions stated in FBC 2603.4.1 and 2603.6 apply.
5.5 The roof system evaluation herein pertains to above -deck roof components. Roof decks and structural members
shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load
resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation.
5.6 For recover installations, the existing roof shall be examined in accordance with FBC 1511.
5.7 For mechanically attached insulation or membrane or strip -bonded insulation, the maximum design pressure for
the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC Chapter
16. Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the
elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29,
Roofing Application Standard RAS 117 and Roofing Application Standard RAS 137. Assemblies marked with an
asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016)
for Zone 2/3 enhancements.
5.8 For assemblies with all components fully bonded in place, the maximum design pressure for the selected assembly
shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16. No rational analysis
is permitted for these systems.
5.9 For mechanically attached insulation or membrane over existing roof decks, fasteners shall be tested in the existing
deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the
minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-1 or Testing
Application Standard TAS 105.
5.10 For bonded insulation or membrane over existing substrates in a re -roof (tear off) or recover installation, the
existing deck or existing roof surface shall be examined for compatibility with the adhesive to be installed. If any
surface conditions exist that bring system performance into question, field uplift testing in accordance with
ANSI/SPRI IA-1, ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124 shall
be conducted on mock-ups of the proposed new roof assembly.
5.11 For bonded insulation or membrane over existing substrates in a recover installation, the existing roof system shall
be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having
Jurisdiction, as documented through field uplift testing in accordance with ASTM E907, FM Loss Prevention Data
Sheet 1-52 or Testing Application Standard TAS 124.
5.12 Metal edge attachment (except gutters), shall be designed and installed for wind loads in accordance with FBC
Chapter 16 and tested for resistance in accordance with ANSI/SPRI ES-1 or Roofing Application Standard RAS 111,
except the basic wind speed shall be determined from FBC Figure 1609.3(1), 1609.3(2) or 1609.3(3).
5.13 All products in the roof assembly shall have quality assurance in accordance with FAC Rule 61G20-3. For non-
Duro-Last components listed within wind uplift rated assemblies in Appendix 1, refer to the Product Approval of
the component manufacturer.
NEMO ETC, LLC Evaluation Report D9750.05.08-R10
Certificate of Authorization #32455 GTH EDITION (2017) FBC NON-HVHZ EVALUATION FL1559-1113
Duro-Last Single Ply Roof Systems Revision 10: 10/17/2019
Page 4 of 5
ONEMOIetc.
6.1 Duro-Last Single Ply Roof Systems shall be installed in accordance with Duro-Last Roofing, Inc. published
installation instructions, subject to the Limitations / Conditions of Use noted herein.
6.2 System attachment requirements for wind load resistance are set forth in Appendix 1. "MDP" = Maximum Design
Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate
passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to FBC
1609 for determination of design wind loads.
6.2 For mechanically fastened membrane systems (Type D) over profiled steel deck, membrane shall be installed
running perpendicular to steel deck flutes.
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation
of this product.
Contact the named QA entity for manufacturing facilities covered by F.A.C. Rule 61G20-3 QA requirements.
UL, LLC. — QUA9625; (414) 248-6409; karen.buchmann@us.ul.com
- THE 44-PAGES THAT FOLLOW FORM PART OF THIS EVALUATION REPORT -
NEMO ETC, LLC Evaluation Report 139750.05.08-1110
Certificate of Authorization #32455 6T" EDITION (2017) FBC NON-HVHZ EVALUATION F1.1559-1113
Duro-Last Single Ply Roof Systems Revision 10: 10/17/2019
Page 5 of 5
ONEMOjetc.
APPENDIX
1: ATTACHMENT REQUIREMENTS
FOR WIND UPLIFT RESISTANCE
TABLE
DECK
APPLICATION
TYPE
DESCRIPTION
PAGE
1A
Wood
New, Reroof (Tear -Off) or Recover
C-1
Mech. Attached Insulation, Bonded Roof Cover
4
1B
Wood
New, Reroof (Tear -Off) or Recover
C-2
Mechanically Attached Insulation, Plate -Bonded Roof Cover
5-6
1C
Wood
New, Reroof (Tear -Off) or Recover
D-1
Prelim. Attached Insulation, Mech. Attached Roof Cover
6-7
2A
Steel
New or Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
8
2B
Steel or Structural Concrete
New, Reroof (Tear -Off) or Recover
B
Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover
9
2C
Steel or Structural Concrete
New, Reroof (Tear -Off) or Recover
C-1
Mech. Attached Insulation, Bonded Roof Cover
10-12
2D
Steel
New, Reroof (Tear -Off) or Recover
C-2
Mechanically Attached Insulation, Plate -Bonded Roof Cover
13-17
2E
Steel
New, Reroof (Tear -Off) or Recover
D-1
Prelim. Attached Insulation, Mech. Attached Roof Cover
18-19
2F
Steel
New or Reroof (Tear -Off)
D-2
Thermal Barrier, Vapor Barrier, Prelim. Attached Insulation, Mech. Attached Roof Cover
20
3A
Structural Concrete
New or Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
21-24
3B
Structural Concrete
New, Reroof (Tear -Off) or Recover
C-2
Mechanically Attached Insulation, Plate -Bonded Roof Cover
25-28
3C
Structural Concrete
New, Reroof (Tear -Off) or Recover
D
Prelim. Attached Insulation, Mech, Attached Roof Cover
28
3D
Structural Concrete
New, Reroof (Tear -Off)
F
Non -Insulated, Bonded Roof Cover
29
4A
Lightweight concrete / steel
New or Reroof (Tear -Off)
A-1
LWC to Steel Deck, Bonded Insulation, Bonded Roof Cover
30
4B
Lightweight concrete /
New or Reroof (Tear -Off)
A-1
LWC to Structural Concrete Deck, Bonded Insulation, Bonded Roof Cover
30-32
4C
Lightweight concrete / steel
New or Reroof (Tear -Off)
E-2
LWC to Steel Deck, Mechanically Attached Base Sheet, Bonded Roof Cover
33
4D
Lightweight concrete / steel
New or Reroof (Tear -Off)
F
LWC to Steel Deck, Bonded Roof Cover
33
4E
Lightweight concrete /
New or Reroof (Tear -Off)
F
LWC to Structural Concrete Deck / Bonded Roof Cover
33
5A
Cementitious wood fiber
Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
34
5B
Cementitious wood fiber
New, Reroof (Tear -Off) or Recover
D-1
Prelim. Attached Insulation, Mech. Attached Roof Cover
34
5C
Cementitious wood fiber
New, Reroof (Tear -Off) or Recover
E-1
Non -insulated, Mech. Attached Roof Cover
34
6A
Gypsum
Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
35
6B
Gypsum
Reroof (Tear -Off) or Recover
D-1
Prelim. Attached Insulation, Mech. Attached Roof Cover
35
7A
Various
Recover
A-1
Bonded Insulation, Bonded Roof Cover
36-39
7B
Steel
Recover
C-2
Mechanically Attached Insulation, Plate -Bonded Roof Cover
40-42
7C
Steel
Recover
D-1
Insulated. Mechanicallv Attached Roof Cover
43
7D Cementitious wood fiber Recover E-1 Non -insulated, Mech. Attached Roof Cover 44
7E Various Recover F Non -Insulated, Bonded Roof Cover 44
The following notes apply to the systems outlined herein:
The roof system evaluation herein pertains to above -deck roof components. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction.
Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation.
Unless otherwise noted, fasteners and stress plates for insulation attachment shall be as follows. Fasteners shall be of sufficient length for the following engagements:
➢ Wood Deck: Duro-Last #14 HD Fasteners and Duro-Last 3-inch Metal Plates. Min. Y.-inch plywood penetration or minimum 1-inch wood plank embedment.
➢ Steel Deck: Duro-Last #14 HD or #15 Extra Heavy Duty Drill Point Fasteners and Duro-Last 3-inch Metal Plates. Minimum %-inch steel penetration, engage the top flute of the steel deck.
➢ Structural Concrete: Duro-Last #14 HD Fasteners, Duro-Last Concrete Screws or Duro-Last Fluted Concrete Nails and Duro-Last 3-inch Metal Plates. Minimum 1-inch embedment. Fasteners installed with a pilot
hole in accordance with the fastener manufacturer's published installation instructions.
Unless otherwise noted, insulation may be any one layer or combination of polyisocyanurate, polystyrene, fiberboard, perlite and/or gypsum -based insulation board that meets the CIA requirements of F.A.C. Rule
61G20-3 and is documented as meeting FBC 1505.1 and, for foam plastic, FBC Chapter 26, when installed with the roof cover.
NEMO ETC, LLC
Certificate of Authorization #32455
©2019 NEMO ETC, LLC
6- EDITION (2017) FBC NON-HVHZ EVALUATION
Duro-Last Single Ply Roof Systems; (800) 248-0280
Evaluation Report D9750.05.08-1110 for FL3559-1313
Revision 10: 10/17/2019
Appendix 1, Page 1 of 44
OMEMO I etc.
4. Minimum 200 psi, minimum 2-inch thick lightweight insulating concrete may be substituted for rigid insulation board for System Type C-2 (plate bonded roof cover) or Type D-1 (mechanically attached roof cover),
whereby the membrane fasteners are installed through the LWIC to engage the structural steel or concrete deck. The structural deck shall be of equal or greater type, thickness and strength to the steel and concrete
deck listings. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the roof deck shall be documented through
proper codified and/or FBC Approval documentation.
5. Preliminary insulation attachment for System Type D-1: Unless otherwise noted, refer to Section 2.2.10.1.3 of FM Loss Prevention Data Sheet 1-29 (January 2016)
6. Unless otherwise noted, insulation adhesive application rates are as follows. Ribbon or bead width is at the time of application; the ribbons/beads shall expand as noted in the manufacturer's published instructions.
➢ Ashland Pliodeck: Continuous''/: to Y.-inch wide ribbons, 12-inch o.c. Ribbons for subsequent layer(s) shall be run perpendicular to those for the underlying layer.
➢ Duro-Grip Board -Max: Continuous 3-inch ribbons, 12-inch o.c.
➢ Duro-Grip CR-20: Continuous 2%to 3%:-inch ribbons, 12-inch o.c.
➢ Duro-Grip Insta-Stik: Continuous Y. to 1-inch wide ribbons, 12-inch o.c.
➢ Duro-Grip OlyBond 500: Continuous Y. to 1-inch wide ribbons, 12-inch o.c. using PaceCart, SpotShot or Cansiter.
➢ Duro-Grip WeatherTite One Step Adhesive (WT OSA): Continuous 0.25 to 0.5-inch wide ribbons, 12-inch o.c.
➢ Hot asphalt: Full mopping, 25-30 Ibs/square.
➢ OMG OlyBond Classic: Continuous %-inch ribbons, 12-inch o.c. or full -coverage
➢ Trufast Roofing Adhesive: Continuous % to 1-inch wide ribbons, 12-inch o.c.
➢ Note: When multiple loyers(s) of insulation and/or coverboard are installed in ribbon -applied adhesive, boards shall be staggered from layer -to -foyer.
➢ Note: The maximum edge distance from the adhesive ribbon to the edge of the insulation board shall be not less than one-half the specified ribbons spacing.
7. Unless otherwise noted, all insulations are flat stock or taper board of the minimum thickness noted. Tapered polyisocyanurate at the following thickness limitations maybe substituted with the following Maximum
Design Pressure (MDP) limitations. In no case shall these values be used to 'increase' the MDP listings in the tables; rather if MDP listing below meets or exceeds that listed fora particular system in the tables, then the
thinner board listed below may be used as a drop -in for the equivalent thicker material listed in the table:
➢ Duro-Grip CR-20: MDP = -117.5 psf (Min. 1.0-inch thick)
➢ Duro-Grip OlyBond 500: MDP = -315.0 psf (Min. 0.5-inch thick H-Shield, Duro-Guard ISO II-H, ENRGY 3 or Duro-Guard ISO II-G)
➢ Duro-Grip OlyBond 500: MDP = -487.5 psf (Min. 0.5-inch thick ACFoam II or Duro-Guard ISO II -A)
➢ Duro-Grip WeatherTite One Step Adhesive (WT OSA): MDP -157.5 psf (Min. 0.5-inch thick)
8. Bonded polyisocyanurate insulation boards shall be maximum 4 x 4 ft.
9. For mechanically attached components or partially bonded insulation, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC
Chapter 16, and Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss Prevention
Data Sheet 1-29, Roofing Application Standard RAS 117 and Roofing Application Standard RAS 137. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data
Sheet 1-29 (January 2016) for Zone 2/3 enhancements.
10. For assemblies with all components fully bonded in place, the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16, and no
rational analysis is permitted.
11. For mechanically attached components over existing decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the minimum
requirements for the system. Testing shall be in accordance with ANSI/SPRI FX-1 or Testing Application Standard TAS 105.
12. For existing substrates in a bonded recover or re -roof installation, the existing roof surface or existing roof deck shall be examined for compatibility and bond performance with the selected adhesive, and the existing
roof system (for recover) shall be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having Jurisdiction, as documented through field uplift testing in accordance with
ANSI/SPRI IA-1, ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124.
13. For System Type D-1, steel deck applications, the roof membrane shall be run with its length perpendicular to the steel deck flutes.
14. For Structural Concrete Deck or Recover Applications using System Type C-2 (Plate Bonded Roof Cover) or Type D-1 (Mechanically Attached Roof Cover), the insulation is optional. Alternatively, Dens Deck, Dens Deck
Prime, SECUROCK Gypsum -Fiber Roof Board, SECUROCK Glass -Mat Roof Board, Duro-Bluer", Duro-Weave'", Duro-Last Geotextile Slip Sheet, Duro-Fold'" or Ultra -Fold" TPM may be used as a separation layer. Board
NEMO ETC, LLC Evaluation Report D9750.05.08-1110 for FL1559-R13
. Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
02019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 2 of 44
ONEMOjetc.
products should be preliminarily attached prior to roof cover installation. The existing roof system shall be suitable for a recover application. The separator component shall be documented as meeting FBC 1505.1 and,
for foam plastic, FBC Chapter 26, when installed with the roof cover in Recover applications.
15. Lightweight Insulating Concrete (LWC) shall be cast in accordance with FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction. For systems where specific LWC is referenced, refer to current LWC
Product Approval for specific deck construction and limitations. Unless otherwise noted, for systems where specific LWC is not referenced, the minimum design mix shall be 300 psi. In all cases, the minimum top -coat
thickness is 2-inches. For LWC over structural concrete, reference is made to FBC Section 1917.4.1, Point 1. For "pre-existent" LWC references, listings were established through testing over lightweight concrete cast
using only foaming agent (ASTM C896), water and Portland cement (ASTM C150), with no proprietary additives, in accordance with procedures adopted by Miami -Dade BCCO (FBC CER1592). Unless otherwise noted,
use of these listings in new construction or re -roof (tear -off) applications is at the discretion of the Designer of Record and Authority Having Jurisdiction.
16. For adhered membrane systems, side laps shall be minimum 3-inch wide sealed with min.1.5-inch heat weld. Membrane adhesive application rates are as follows:
MEMBRANE
•.ROOF
ADHESIVE
COVER I ADHESIVE COMBINATIONS
APPLICATION
RATE
Duro-Last
Duro-Last SB I
Contact
1.5 gal/sq./surface
Duro-Last, Duro-Last EV or Duro-Tuff
Duro-Last SB IV
Contact
1.67 gal/sq./surface
Duro-Last
Duro-Last WB I
Contact
0.5 gal/sq./surface
Duro-Last, Duro-Last EV or Duro-Tuff
Duro-Last WB II
Substrate only
0.7 gal/sq.
Duro-Fleece or Duro-Fleece Plus
Duro-Last WB 11
Substrate only
1.0 gal/sq.
Duro-Fleece or Duro-Fleece Plus
Duro-Fleece Adhesive
Substrate only
Continuous''/< -inch wide ribbons, 6-inch o.c.
Duro-Fleece or Duro-Fleece Plus
Duro-Fleece CR-20 Membrane Adhesive
Substrate only
Splatter -applied, full coverage per Duro-Last instructions
Duro-Fleece or Duro-Fleece Plus
Trufast Roofing Adhesive
Substrate only
Continuous'/< to 1-inch wide ribbons, 4-inch o.c., resulting in full -coverage
17. Vapor barrier options for use over structural concrete deck followed by adhesive -applied insulation carry the following Maximum Design Pressure (MDP) limitations. The lesser of the MOP listings below vs. those in
Table 3A applies.
Option #
Primer
VAPOR 13ARRIER •• .NCRETE DEcK; FOLLOWED B
MDR
(psf)
Vapor Barrier
Insulation Adhesive
Type
Application
VB-1.
ASTM D41
Duro-Last Torch Down Vapor Barrier
torch -applied
Board -Max, 12-inch o.c.
-37.5
VB-2.
ASTM D41
Duro-Last Torch Down Vapor Barrier
torch -applied
OlyBond 500, 12-inch o.c.
-382.5
VB-3.
ASTM D41
Duro-Last Torch Down Vapor Barrier
torch -applied
Trufast Roofing Adhesive, 12-inch o.c.
-180.0
VB-4.
ASTM D41
Duro-Last Torch Down Vapor Barrier
torch -applied
WeatherTite One Step Adhesive, 12-inch o.c.
-270.0
VB-5.
Duro-Last VB Primer
Duro-Last Vapor Barrier
self -adhering
Board -Max, 12-inch o.c.
-37.5
VB-6.
Duro-Last VB Primer
Duro-Last Vapor Barrier
self -adhering
OlyBond 500, 12-inch o.c.
-187.5
VB-7.
Duro-Last VB Primer
Duro-Last Vapor Barrier
self -adhering
Trufast Roofing Adhesive, 12-inch o.c.
-390.0
VB-8.
Duro-Last VB Primer
Duro-Last Vapor Barrier
self -adhering
WeatherTite One Step Adhesive, 12-inch o.c.
-172.5
18. "MDP" = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads. Refer to FBC 1609 for determination of design wind pressures.
NEMO ETC, LLC Evaluation Report D9750.05.08-R10 for FL3559-R33
Certificate of Authorization #32455 6-EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 3 of 44
NNEMOjetc.
TABLE 1A: ....REROOF (TEAR -OFF) OR RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
Top Insulation Layer
No Deck (Note 1)
Base Insulation Layer
Roof Cover (Note 16)
MDP (psf)
Type Fasteners Attach
W 1
Min. 2-inch T&G lumber or min. '/<-
(Optional) One or more
Min. 0.25-inch Dens Deck or Dens Deck
Note 2
1 per 2.67 ft2
Duro-Last / SB 1 or WB II
-30.0*
inch exterior grade plywood
layers, any combination
Prime
W 2
Min. 2-inch T&G lumber or min. ''/e-
(Optional) One or more
Min. Yz-inch Dens Deck or Dens Deck
Note 2
1 per 3.2 ft2
Duro-Last / SB I or WB II
-30.0*
inch exterior grade plywood
layers, any combination
Prime
W 3
Min. 2-inch T&G lumber or min. '/<-
(Optional) One or more
Min. 5/8-inch Dens Deck or Dens Deck
Note 2
1 per 4 ft2
Duro-Last / SB I or WB II
30.0*
inch exterior grade plywood
layers, any combination
Prime
W 4
Min. 2-inch T&G lumber or min. '/<-
(Optional) One or more
Min. 1.5-inch ACFoam 11, Duro-Guard
Note 2
1 per 2 ft2
Duro-Last / WB 1
-45.0*
inch exterior grade plywood
layers, any combination
ISO II -A
Min. 2-inch T&G lumber or min. '/<-
(Optional) One or more
Min. 1.5-inch ACFoam 11, Duro-Guard
W 5.
inch exterior grade plywood
layers, any combination
ISO II -A or ACFoam 111, Duro-Guard 150
Note 2
1 per 4 ft2
Duro-Last / SB 1
-45.0*
III -A
W 6
Min. 2-inch T&G lumber or min. '/<-
(Optional) One or more
Min. 1.5-inch ACFoam III, Duro-Guard
Note 2
1 per 4 ft2
Duro-Last / WB 1
-45.0*
inch exterior grade plywood
layers, any combination
ISO III -A
W 7
Min. 2-inch T&G lumber or min. Y4-
(Optional) One or more
Min. 0.25-inch Dens Deck or Dens Deck
Note 2
1 per 2 ft2
Duro-Last / 513 1 or WB II
-45.0*
inch exterior grade plywood
layers, any combination
Prime
NEMO ETC, LLC
. Certificate of Authorization #32455
©2019 NEMO ETC, LLC
6- EDITION (2017) FBC NON-HVHZ EVALUATION
Duro-Last Single Ply Roof Systems; (800) 248-0280
Evaluation Report D9750.05.08-1110 for FL1559-1113
Revision 10: 10/17/2019
Appendix 1, Page 4 of 44
ONEMOjetc.
TABLE 1B: ....REROOF (TEAR -OFF) OR RECOVER
PLATE-BONDEDSYSTEM TYPE C-2: MECHANICALLY ATTACHED INSULATION, ROOF COVER
System Deck Insulation Layer Attach MDP
Roof Cover / Attach
No. (Note 1) (Note 14) Fasteners Density (Psf)
RHINOBOND INDUCTION WELD:
Duro-Last #14 HD
Duro-Last (min. 60 mil), Duro-Last EV
Min. 19/32-inch
(Optional) One or more
with RHINOBOND
Fasteners 12-inch o.c. in rows spaced 72-inch o.c. positioned atop wood
(min. 50 mil) or Duro-Tuff (min. 80-mil)
W-8.
plywood at max.
layers, any combination;
Insulation Plate
trusses; minimum 0.9-inch fastener embedment into trusses
induction welded to RHINOBOND
-37.5
24-inch spans
preliminarily attached
(PVC)
Insulation Plate (PVC) using
RHINOBOND Installation Tool
Duro-Last #14 HD
Duro-Last (min. 60 mil), Duro-Last EV
Min. 19/32-inch
(Optional) One or more
with RHINOBOND
Fasteners 18-inch o.c. in rows spaced 48-inch o.c. positioned atop wood
(min. 50 mil) or Duro-Tuff (min. 80-mil)
W-9.
plywood at max.
layers, any combination;
Insulation Plate
trusses; minimum 0.9-inch fastener embedment into trusses
induction welded to RHINOBOND
-37.5
24-inch spans
preliminarily attached
(PVC;
Insulation Plate (PVC) using
RHINOBOND Installation Tool
Duro-Last #14 HD
Duro-Last (min. 60 mil) , Duro-Last EV
Min. 19/32-inch
(Optional) One or more
with RHINOBOND
Fasteners 12-inch o.c. in rows spaced 48-inch o.c. positioned atop wood
(min. 50 mil) or Duro-Tuff (min. 80-mil)
W-10.
plywood at max.
P Y
layers, an combination;
Y Y
Insulation Plate
trusses; minimum 0.9-inch fastener embedment into trusses
induction welded to RHINOBOND
-52.5
24-inch spans
preliminarily attached
Insulation Plate (PVC) using
RHINOBOND Installation Tool
Duro-Last #14 HD
Duro-Last (min. 60 mill, Duro-Last EV
Min. 19/32-inch
(Optional) One or more
with RHINOBOND
Fasteners 6-inch o.c. in rows spaced 96-inch o.c. positioned atop wood trusses;
(min. 50 mil) or Duro-Tuff (min. 80-mil)
W-11.
plywood at max.
layers, any combination;
Insulation Plate
minimum 0.9-inch fastener embedment into trusses
induction welded to RHINOBOND
-60.0
24-inch spans
preliminarily attached
Insulation Plate (PVC) using
RHINOBOND Installation Tool
1 per 2.67 ftz
�z' zs• za•--za- i,-
(12 parts per 4Dur
O O OO
#14 HD
x 8 ft bird;
m
Duro-Last (min. 40 mil), Duro-Tuff
Min. 19/32-inch
One or more layers, any
with
with RHINOBOND
Fasteners
(min. 50 mil) or Duro-Last EV (min. 50-
W-12.
plywood at max.
combination; min. 1.5-
InsulationPlate
Insulation Plate
engage wood
OO o0 OO pop
mil) induction welded to RHINOBOND
-60.0
24-inch spans
inch, min. 16 psi
(PVC)
trusses,
Insulation Plate (PVC) using
minimum 0.9-
RHINOBOND Installation Tool
inch
O O O O
embedment)
NEMO ETC, LLC Evaluation Report D9750.05.08-R10 for FL3559-1113
Certificate of Authorization #32455 6-EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
02019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 5 of 44
ONEMOjetc.
System
No.
Deck
(Note 1)
TABLE 1B: .. •.. .. RECOVER
PLATE-BONDEDSYSTEM TYPE C-2: MECHANICALLY ATTACHED INSULATION, ROOF
Insulation Layer Attach
(Note 14) Fasteners Density
Roof Cover /Attach
MDP
(psf)
1per2ft2
12•-- 24- 24• 24• 12•
(16 parts per 4
O O O O
Duro-Last #14 HD
x 8 ft brd;
Duro-Last (min. 40 mil), Duro-Tuff
Min. 19/32-inch
One or more layers, any
with RHINOBOND
Fasteners
O O O O
(min. 50 mil) or Duro-Last EV (min. 50-
W-13.
plywood at max.
combination; min. 1.5-
Insulation Plate
engage wood
ti
mil) induction welded to RHINOBOND
-90.0
24-inch spans
inch, min. 16 psi
(PVC)
trusses,
O O 0 O
Insulation Plate (PVC) using
minimum 0.9-
N
RHINOBOND Installation Tool
inch
embedment)
O O O a
1C: WOOD DECKS - NEW CONSTRUCTION, REROOF (TEAR -OFF) OR RECOVER
INSULATION,TABLE
SYSTEM TYPE D-1: PRELIMINARILY ATTACHED ROOF COVER
Insulation (Note 14) Roof Cover
System Deck (Note 1)
Attach
MDP
No. Type
Membrane
Fasteners
Attach
(psf)
(Note 5)
STANDARD LAP SYSTEMS:
Min. 19/32-inch APA
0.5-inch Duro-Guard EPS Fan Fold and/or min.
Duro-Last #15 Extra Heavy Duty
W-14.
rated CDX plywood at
1-inch Duro-Guard 150 II-H, Duro-Guard ISO II-
Prelim.
Duro-Last,
Drill Point Fasteners and Duro-
Standard Lao System fastened 12-inch o.c.
-30.0
max. 32-inch spans
G, Duro-Guard ISO II -A, Duro-Guard ISO III-H or
attached
min. 40-mil
Last Poly -Plates or Duro-Last
within 6-inch wide tabs spaced 58-inch o.c.
Duro-Guard ISO III -A
Cleat Plates
Min. 19/32-inch APA
0.5-inch Duro-Guard EPS Fan Fold and/or min.
Duro-Last #15 Extra Heavy Duty
Standard Lao System fastened 12-inch o.c.
W-15.
rated CDX plywood at
1-inch Duro-Guard ISO II-H, Duro-Guard ISO II-
Prelim.
Duro-Last EV,
Drill Point Fasteners and Duro-
within inch wide laps spaced 54-inch o.c.
30.0
G, Duro-Guard 150 II -A, Duro-Guard ISO III-H or
attached
min. 50-mil
Last Poly -Plates or Duro-Last
max. 32-inch spans
Duro-Guard I5O III -A
Cleat Plates
Lap sealed with 1.5-inch heat weld
Min. 19/32-inch APA
0.5-inch Duro-Guard EPS Fan Fold and/or min.
Duro-Last #15 Extra Heavy Duty
Standard Lao System fastened 12-inch o.c.
W-16.
rated CDX plywood at
1-inch Duro-Guard ISO II-H, Duro-Guard ISO II-
Prelim.
Duro-Tuff,
Drill Point Fasteners Duro-Last
within 6-inch wide laps spaced 54-inch o.c.
-30.0
max. 32-inch spans
G, Duro-Guard ISO II -A, Duro-Guard ISO III-H or
attached
min. 50-mil
Cleat Plates
Lap sealed with 1.5-inch heat weld
Duro-Guard ISO 111-A
Min. 19/32-inch APA
0.5-inch Duro-Guard EPS Fan Fold and/or min.
Duro-Last #15 Extra Heavy Duty
Standard Lao System fastened 6-inch o.c.
W-17.
rated CDX plywood at
1-inch Duro-Guard ISO II-H, Duro-Guard ISO 11-
Prelim.
Duro-Last EV,
Drill Point Fasteners and Duro-
within 6-inch wide laps spaced inch
37.5
max. 32-inch spans
G, Duro-Guard ISO II -A, Duro-Guard ISO III-H or
attached
min. 50-mil
Last Poly -Plates or Duro-Last
o.c. Lap sealed with 1.5-inch heaatt weld
Duro-Guard ISO III -A
Cleat Plates
Min. 19/32-inch APA
0.5-inch Duro-Guard EPS Fan Fold and/or min.
Duro-Last #15 Extra Heavy Duty
Standard Lap System fastened 6-inch o.c.
W-18.
rated CDX plywood at
1-inch Duro-Guard ISO II-H, Duro-Guard 150 II-
Prelim.
Duro-Tuff,
Drill Point Fasteners and Duro-
within 6-inch wide laps spaced 114-inch
-37.5
max. 32-inch spans
G, Duro-Guard ISO II -A, Duro-Guard ISO III-H or
attached
min. 50-mil
Last Cleat Plates
o.c. Lap sealed with 1.5-inch heat weld
Duro-Guard ISO III -A
NEMO ETC, LLC Evaluation Report D9750.05.08-1110 for FL1559-1113
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 MEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 6 of 44
ONEMOjetc.
1C: WOOD DECKS - NEW CONSTRUCTION, REROOF [TEAR�OFF) OR RECOVER
I
ATTACHEDTABLE
SYSTEM TYPE D-1: PRELIMINARILY ATTACHED INSULATION, MECHANICALLY ROOF COVER
Insulation (Note 14)
Roof Cover
System
Deck (Note 1)
Attach
MDP
No.
Type
Membrane
Fasteners
Attach
(psf)
(Note 5)
Min. 19/32-inch plywood
Prelim.
Duro-Last,
Duro-Last #15 Extra Heavy Duty
Standard Lap System fastened 6-inch o.c.
W 19.
at max. 24-inch spans
(Optional) One or more layers, any combination
attached
min. 40 mil
Drill Point Fasteners and Duro-
within 6-inch wide tabs spaced 57-inch o.c.
-52.5
Last 2.4-inch Barbed Metal Plate
Screws located 2.7-inches from tab edge
Min. 19/32-inch APA
0.5-inch Duro-Guard EPS Fan Fold and/or min.
Duro-Last #15 Extra Heavy Duty
W-20.
rated CDX plywood at
1-inch Duro-Guard 150 II-H, Duro-Guard 150 II-
Prelim.
Duro-Last,
Drill Point Fasteners and Duro-
Standard Lap System fastened 6-inch o.c.
-52.5
max. 32-inch spans
G, Duro-Guard ISO II -A, Duro-Guard ISO III-H or
attached
min. 40-mil
Last Poly -Plates or Duro-Last
within 6-inch wide tabs spaced 58-inch o.c.
Duro-Guard ISO III -A
Cleat Plates
Min. 19/32-inch APA
0.5-inch Duro-Guard EPS Fan Fold and/or min.
Duro-Last #15 Extra Heavy Duty
Standard Lap System fastened 6-inch o.c.
W-21.
rated CDX plywood at
1-inch Duro-Guard ISO II-H, Duro-Guard ISO II-
Prelim.
Duro-Last EV,
Drill Point Fasteners and Duro-
within inch wide laps spaced 54 inch o.c.
52.5
max. 32-inch spans
G, Duro-Guard ISO II -A, Duro-Guard ISO III-H or
attached
min. 50-mil
Last Poly -Plates or Duro-Last
Lap sealed with 1.5-inch heat weld
Duro-Guard ISO III -A
Cleat Plates
Min. 19/32-inch APA
0.5-inch Duro-Guard EP5 Fan Fold and/or min.
Duro-Last #15 Extra Heavy Duty
Standard Lao System fastened 6-inch o.c.
W-22.
rated CDX plywood at
1-inch Duro-Guard ISO II-H, Duro-Guard ISO II-
Prelim.
Duro-Tuff,
Drill Point Fasteners and Duro-
within 6-inch wide laps spaced 54-inch o.c.
-52.5
max. 32-inch spans
G, Duro-Guard ISO II -A, Duro-Guard I50 III-H or
,
attached
.
min50-mil
Last Cleat Plates
Lap sealed with 1.5-inch heat weld
Duro-Guard ISO III -A
DURO-ROOF LAP SYSTEMS: -
Min. 19/32-inch plywood
Prelim.
Duro-Last,
Duro-Last #14 HD Fasteners with
Duro-Roof Lap System fastened 6-inch o.c.
W 23.
at max. 24-inch spans
(Optional) One or more layers, any combination
attached
min. 40 mil
Duro-Last 3-inch Metal Plates
within 6-inch wide tabs spaced 57-inch o.c.
-52.5
Tab Sealer 4725 at max. 60 ft2/gal.
Nominal 1 x 6 —inch T&G
One or more layers, any combination, min. 1.5-
Prelim.
Duro-Last
Duro-Last #15 Extra Heavy Duty
Duro-Roof Lao System fastened 6-inch o.c.
W-24.
board decking attached
inch
Attached
min. 40 mil,
Drill Point Fasteners with OMG 2-
within 6-inch wide tabs spaced 25-inch o.c.
-97.5
per FBC Section 2322.2.2
3/8" Eyehook Plates
Tab Sealer 4725 at max. 60 ft2/gal.
NEMO ETC, LLC Evaluation Report D9750.05.08-1110 for FL1559-1133
Certificate of Authorization #32455 6- EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
02019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 7 of 44
NNEMOjetc.
TABLE 2A: STEEL DECKS - NEW CONSTRUCTION OR REROOF
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System Deck Base Insulation Layer 77 Top Insulation Layer MDP
I
(Note 1) Type Attach (Notes 6 & 7)
Type Attach (Notes 6 & 7)
Roof Cover (Note 16)
(Psf)
BAREBACK MEMBRANE APPLICATIONS:
22 ga., Type B,
Min. 1.5-inch Duro-Guard ISO II-H
WT OSA, 12-inch o.c. (every-
Min. 0.25-inch DEXcell FA Glass Mat
WT OSA
Duro-Last, Duro-Last EV
-75.0
Grade 60 steel
other deck flange)
Roof Board
or Duro-Tuff / SB IV
S-2.
22 ga., Type B,
Min. 1.5-inch Duro-Guard ISO II-H
WT OSA, 12-inch o.c. (every-
(Optional) Additional layers) base
WT OSA
Duro-Last, Duro-Last EV
-82.5
Grade 60 steel
other deck flange)
insulation
or Duro-Tuff / SB IV
S-3.
22 ga., Type B,
Min. 1.5-inch Duro-Guard ISO II-H
WT OSA, 12-inch o.c. (every-
Min. 0.25-inch DEXcell FA Glass Mat
WT OSA
Duro-Last, Duro-Last EV
-75.0
Grade 60 steel
other deck flange)
Roof Board
or Duro-Tuff/ WB II
S-4.
22 ga., Type B,
Min. 1.5-inch Duro-Guard I50 II-H
WT OSA, 12-inch o.c. (every-
(Optional) Additional layer(s) base
WT OSA
Duro-Last, Duro-Last EV
82.5
Grade 60 steel
other deck flange)
insulation
or Duro-Tuff / WB II
DURO-FLEECE OR DURO-FLEECE PLUS MEMBRANE APPLICATIONS:
5-5.
22 ga., Type B,
Min. 1.5-inch Duro-Guard 150 II-H
WT OSA, 12-inch o.c. (every-
Min. 0.25-inch DEXcell FA Glass Mat
WT OSA
Duro-Fleece CR-20
-75.0
Grade 60 steel
other deck flange)
Roof Board
(splatter applied)
S-6.
22 ga., Type B,
Min. 1.5-inch Duro-Guard ISO II-H
WT OSA, 12-inch o.c. (every-
(Optional) Additional layer(s) base
WT OSA
Duro-Fleece CR-20
82.5
Grade 60 steel
other deck flange)
g)
insulation
(splatter applied)
S 7'
22 ga., Type B,
Min. 1.5-inch Duro-Guard I50 II-H
WT OSA, 12-inch o.c. (every-
Min. 0.25-inch DEXcell FA Glass Mat
WT OSA
Duro-Fleece or Duro-
75.0
Grade 60 steel
other deck flange)
Roof Board
Fleece Plus / WB II
S 8.
22 ga., Type B,
Min. 1.5-inch Duro-Guard ISO II-H
WT OSA, 12-inch o.c. (every-
(Optional) Additional layer(s) base
WT OSA
Duro-Fleece or Duro-
82.5
Grade 60 steel
other deck flange)
insulation
Fleece Plus / WB II
NEMO ETC, LLC
Certificate of Authorization #32455
• ©2019 NEMO ETC, LLC
6TH EDITION (2017) FBC NON-HVHZ EVALUATION
Duro-Last Single Ply Roof Systems; (800) 248-0280
Evaluation Report D9750.05.08-R10 for FL1559-R13
Revision 10: 10/17/2019
Appendix 1, Page 8 of 44
ONEMOjetc.
TABLE 2B: STEEL OR •.. OR RECOVER
SYSTEIVITYPEB: MECHANICALLY ATTACHED.BASE INSULATION, BONDED TOP INSPLATION, BON DED ROOF -COVER
System Deck Base Insulation Layer Top Insulation Layer MDP
No.
(Note 1) Type Fasteners Attach
Type Attach (Notes 6 & 7)
Roof Cover (Note 16)
(psf)
BAREBACK MEMBRANE APPLICATIONS: -
Min. 22 ga., Type B,
Min. 2-inch ACFoam II, Duro-Guard
Min. 0.25-inch SECUROCK
Hot asphalt or Board -Max,
Duro-Last, Duro-Last
S-9.
Grade 33 steel or
150 II -A, H-Shield, Duro-Guard 150 II-
Note 2
1 per 4 ft2
CR-20, Insta-Stik or Trufast
EV or Duro-Tuff / SB IV
-37.5*
structural concrete
H, ENRGY 3 or Duro-Guard 150 II-G
Gypsum -Fiber Roof Board
Roofing Adhesive
or WB II
Min. 22 ga., Type B,
Min. 2-inch ACFoam II, Duro-Guard
Min. 0.25-inch SECUROCK
Hot asphalt or Board -Max,
Duro-Last, Duro-Last
S-10.
Grade 33 steel or
ISO II -A, H-Shield, Duro-Guard ISO II-
Note 2
1 per 2.67 ft2
CR-20, Insta-Stik or Trufast
EV or Duro-Tuff / 5B IV
-45.0*
structural concrete
H, ENRGY 3 or Duro-Guard ISO II-G
Gypsum -Fiber Roof Board
Roofing Adhesive
or WB II
Min. 22 ga., Type B,
Min. 2-inch ACFoam 11, Duro-Guard
Min. 0.25-inch SECUROCK
Hot asphalt or Board -Max,
Duro-Last, Duro-Last
S-11.
Grade 33 steel or
150 II -A, H-Shield, Duro-Guard 150 II-
Note 2
1 per 1.33 ft2
CR-20, Insta-Stik or Trufast
EV or Duro-Tuff / SB IV
-60.0
structural concrete
H, ENRGY 3 or Duro-Guard ISO II-G
Gypsum -Fiber Roof Board
Roofing Adhesive, 6-inch o.c.
or WB 11
DURO-FLEECE OR DURO-FLEECE PLUS MEMBRANE APPLICATIONS: -
Min. 22 ga., Type B,
Min. 2-inch ACFoam II, Duro-Guard
Hot asphalt or Board -Max,
Duro-Fleece or Duro-
5-12.
Grade 33 steel or
ISO II -A, H-Shield, Duro-Guard 150 II-
Note 2
1 per 4 ft2
Min. 0.25-inch SECUROCK
CR-20, Insta-Stik or Trufast
Fleece Plus / Duro-
-37.5*
structural concrete
H, ENRGY 3 or Duro-Guard ISO II-G
Gypsum -Fiber Roof Board
Roofing Adhesive, 6-inch o.c.
Fleece CR-20 (splatter
applied) or WB II
Min. 22 ga., Type B,
Min. 2-inch ACFoam II, Duro-Guard
Hot asphalt or Board -Max,
Duro-Fleece or Duro-
S-13.
Grade 33 steel or
ISO II -A, H-Shield, Duro-Guard ISO 11-
Note 2
1 per 2.67 ft2
Min. 0.25-inch SECUROCK
CR-20, Insta-Stik or Trufast
Fleece Plus / Duro-
-45.0*
structural concrete
H, ENRGY 3 or Duro-Guard ISO II-G
Gypsum -Fiber Roof Board
Roofing Adhesive, 6-inch o.c.
Fleece CR-20 (splatter
applied) or WB 11
Min. 22 ga., Type B,
Min. 2-inch ACFoam II, Duro-Guard
Hot asphalt or Board -Max,
Duro-Fleece or Duro-
5-14.
Grade 33 steel or
ISO II -A, H-Shield, Duro-Guard ISO II-
Note 2
1 per 1.33 ft2
Min. 0.25-inch SECUROCK
CR-20, Insta-Stik or Trufast
Fleece Plus / Duro-
-60.0
structural concrete
H, ENRGY 3 or Duro-Guard ISO II-G
Gypsum -Fiber Roof Board
Roofing Adhesive, 6-inch o.c.
Fleece CR-20 (splatter
applied) or WB II
MEMO ETC, LLC Evaluation Report D9750.05.08-1110 for FL1559-R33
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 9 of 44
OMEMO I etc.
TABLE 2C: STEEL . • • .. .. RECOVER
BONDED ---SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, ROOF COVER
System
Deck (Note 1) Base Insulation Layer
F
Top Insulation Layer
Roof Cover (Note 16)
MDP
I Type Fasteners Attach
No.I
(psf)
DURO-LAST MEMBRANE APPLICATIONS:
5-15.
Min. 22 ga., Type B, Grade 33
(Optional) One or more layers, any
Min. 0.25-inch Dens Deck or Dens Deck Prime
Note 2
1 pert .67
Duro-Last / SB I or WB II
30.0*
steel or structural concrete
combination
ft
Min. 22 ga., Type B, Grade 33
(Optional) One or more layers, any
1 per 2.67
Duro-Last, Duro-Last EV
S-16.
steel or structural concrete
combination
Min. 0.25-inch Dens Deck Prime
Note 2
ft2
or Duro-Tuff / SB IV or
-30.0*
WB II
S-17.
Min. 22 ga., Type B, Grade 33
(Optional) One or more layers, any
Min. A -inch Dens Deck or Dens Deck Prime
Note 2
1 per 3.2
Duro-Last / SB I or WB II
-30.0*
steel or structural concrete
combination
ft2
Min. 22 ga., Type B, Grade 33
(Optional) One or more layers, any
1 per 3.2
Duro-Last, Duro-Last EV
5-18.
steel or structural concrete
combination
Min. %-inch Dens Deck or Dens Deck Prime
Note 2
ft2
or Duro-Tuff / SB IV or
-30.0*
WB II
Min. 22 ga., Type B, Grade 33
(Optional) One or more layers, any
5-19.
steel or structural concrete
combination
Min. 5/8-inch Dens Deck or Dens Deck Prime
Note 2
1 per 4 ft2
Duro-Last / SB I or WB 11
-30.0*
Min. 22 ga., Type B, Grade 33
(Optional) One or more layers, any
Duro-Last, Duro-Last EV
5-20.
steel or structural concrete
combination
Min. 5/8-inch Dens Deck or Dens Deck Prime
Note 2
1 per 4 ft 2
or Duro-Tuff / SB IV or
-30.0*
WB II
S-21.
Min. 22 ga., Type B, Grade 33
(Optional) One or more layers, any
Min. 1.0-inch ACFoam 11, Duro-Guard ISO II -A
Note 2
steel or structural concrete
combination
or ACFoam Recover
1 per 2 ft2
Duro-Last / WB II
-37.5*
Min. 22 ga., Type B, Grade 33
(Optional) One or more layers, any
Duro-Last, Duro-Last EV
S 22
steel or structural concrete
combination
Min. 1.0-inch ACFoam 11, Duro-Guard ISO 11-A
Note 2
1 per 2 ft2
or Duro-Tuff / SB IV or
-37.5*
WB II
Min. 22 a., Type B, Grade 33
g yp
(Optional) One or more layers, an
( p ) y y
Min. 0.25-inch SECUROCK Gypsum -Fiber Roof
yp
1 per 2.67
p
Duro-Last, Duro-Last EV
5-23.
steel or structural concrete
combination
Board
Note 2
ft2
or Duro-Tuff / SB IV or
-37.5*
yyg II
Min. 22 ga., Type B, Grade 33
(Optional) One or more layers, any
S 24
steel or structural concrete
combination
Min. 1.5-inch ACFoam 11, Duro-Guard ISO II -A
Note 2
1 per 2 ft2
Duro-Last / WB 1
-45.0*
- 5-25.
Min. 22 ga., Type B, Grade 33
(Optional) One or more layers, any
Min. 1.5-inch ACFoam II, Duro-Guard ISO 11-A
Note 2
1 per 2 ft2
Duro-Last, Duro-Last EV
45.0*
steel or structural concrete
combination
or Duro-Tuff / SB IV
S-26.
Min. 22 ga., Type B, Grade 33
(Optional) One or more layers, any
Min. 2-inch ACFoam II, Duro-Guard ISO II -A or
Note 2
ft2
steel or structural concrete
combination
ACFoam III, Duro-Guard 150 III -A
1 per 4
Duro-Last / SB I
45.0*
Min. 22 ga., Type B, Grade 33
(Optional) One or more layers, any
5 27
steel or structural concrete
combination
Min. 2-inch ACFoam III, Duro-Guard 150 III -A
Note 2
1 per 4 ft2
Duro-Last / WB 1
-45.0*
Min. 22 ga., Type B, Grade 33
One or more layers, any
5 28
steel or structural concrete
combination, min. 1.5-inch thick
Min. 0.25-inch Invinsa Roof Board
Note 2
1 per 2 ft2
Duro-Last / SB IV
-45.0*
Min. 22 ga., Type B, Grade 33
(Optional) One or more layers, any
S 29
steel or structural concrete
combination
Min. 0.25-inch Dens Deck or Dens Deck Prime
Note 2
1 per 2 ft2
Duro-Last / SB I or WB II
-45.0*
NEMO ETC, LLC Evaluation Report D9750.05.08-1110 for F1.3559-1133
Certificate of Authorization #32455 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 10 of 44
ONEMOletc.
TABLE 2C: STEEL . •
.. .. RECOVER
SYSTEM TYPE C-1: MECHANICALLY
ATTACHED INSULATION, BONDED ROOF
System
Top Insulation Layer
MDP
Deck (Note 1)
Base Insulation Layer
Roof Cover (Note 16)
No.
Type
Fasteners
Attach
(psf)
Min. 22 ga., Type B, Grade 33
(Optional) One or more layers, any
Duro-Last, Duro-Last EV
5-30.
Min. 0.25-inch Dens Deck or Dens Deck Prime
Note 2
Z
1 per 2 ft
or Duro-Tuff / SB IV or
-45.0
steel or structural concrete
combination
WB II
5-31.
Min. 22 a., Type B, Grade 33
g yp
(Optional) One or more layers, an
( p ) y y
Min. 0.25-inch SECUROCK Gypsum -Fiber Roof
yp
Note 2
1 per 2 ftZ
Duro-Last, Duro-Last EV
or Duro-Tuff / SB IV or
-45.0`
steel or structural concrete
combination
Board
WB II
5-32.
Min. 22 a., Type B, Grade 33
g yp
(Optional) One or more layers, an
( p ) y y
Min. 5/8-inch SECUROCK Gypsum -Fiber Roof
/ yp
Note 2
1 per 4 ftZ
Duro-Last, Duro-Last EV
or Duro-Tuff / SB IV or
-45.0•
steel or structural concrete
combination
Board
WB II
5-33.
Min. 22 ga., Type B, Grade 33
(Optional) One or more layers, any
Min. 2-inch ACFoam 11, Duro-Guard ISO II -A
Dekfast #15 with Dekfast
1 per 2 ftz
Duro-Last / 5B 1
-60.0
steel or structural concrete
combination
Hex
Min. 22 ga., Type B, Grade 33
One or more layers, any
Min. 0.25-inch SECUROCK Gypsum -Fiber Roof
1 per 1.33
Duro-Last, Duro-Last EV
S-34.
steel or structural concrete
combination, min. 1.5-inch thick
Board
Note 2
ftZ
or Duro-Tuff / SB IV or
-67.5
WB II
Min. 22 ga., Type B, Grade 33
One or more layers, any
Note 2 (#15 Extra Heavy
1 per 1.67
Duro-Last, Duro-Last EV
S-35.
steel or structural concrete
combination, min. 1.5-inch thick
Min. 0.25-inch Dens Deck Prime
Duty only)
ftZ
or Duro-Tuff / SB IV
-67.5
5-36.
Min. 22 ga., Type B, Grade 33
(Optional) One or more layers, any
Min. 0.25-inch Dens Deck
Dekfast #15 with Dekfast
1 per 2 ftZ
Duro-Last / SB I or WB II
-75.0
steel or structural concrete
combination
Hex
Min. 22 ga., Type B, Grade 33
(Optional) One or more layers, any
Min. 15/32-inch APA Rated, Grade B-C
OMG XHD with OMG
5-37.
steel or structural concrete
combination
plywood
Flat Bottom Plates (3-
1 per 2 ftZ
Duro-Last / SB I or WB II
-90.0
inch square metal)
Min. 22 ga., Type B, Grade 33
One or more layers, any
Min. 0.5-inch SECUROCK Gypsum Fiber Roof
Trufast #12 DP with
Duro-Last, Duro-Last EV
5-38.
combination, min. 1.5-inch total
Trufast 3" Metal
Z
1 per 1 ft
or Duro-Tuff / SB IV or
-97.5
steel
thickness
Board
Insulation Plate
WB II
DURO-FLEECE OR DURo-FLEECE PLUS MEMBRANE APPLICATIONS:
Min. 22 ga., Type B, Grade 33
(Optional) One or more layers, any
1 per 2.67
Duro-Fleece or Duro-
S-39.
steel or structural concrete
combination
Min. 0.25-inch Dens Deck Prime
Note 2
ftZ
Fleece Plus / Duro-Fleece
-30.0'
CR-20 (splatter) or WB II
Min. 22 ga., Type B, Grade 33
(Optional) One or more layers, any
1 per 3.2
Duro-Fleece or Duro-
5-40.
steel or structural concrete
combination
Min. Y2-inch Dens Deck or Dens Deck Prime
Note 2
ftZ
Fleece Plus / Duro-Fleece
-30.0•
CR-20 (splatter) or WB II
Min. 22 ga., Type B, Grade 33
(Optional) One or more layers, any
Duro-Fleece or Duro-
5-41.
Min. 5/8-inch Dens Deck or Dens Deck Prime
Note 2
Z
1 per 4 ft
Fleece Plus / Duro-Fleece
R
-30.0
steel or structural concrete
combination
CR-20 (splatter) or WB II
Min. 22 a., Type B, Grade 33
g yp
(Optional) One or more layers, an
( p ) y y
Min. 0.25-inch SECUROCK Gypsum -Fiber Roof
yp
1 per 2.67
p
Duro-Fleece or Duro-
S-42.
steel or structural concrete
combination
Board
Note 2
ftZ
Fleece Plus / Duro-Fleece
-37.5"
CR-20 (splatter) or WB II
NEMO ETC, LLC Evaluation Report D9750.05.08-R10 for FL3559-R33
Certificate of Authorization #32455 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 11 of 44
ONEMOletc.
TABLE 2C: STEEL . •
.. .. RECOVER
TYPE C-1: MECHANICALLY
BONDEDSYSTEM
ATTACHED INSULATION, ROOF COVER
System
Top Insulation Layer
MDP
Deck (Note 1) Base Insulation Layer
Roof Cover (Note 16)
No.
Type Fasteners Attach
(psf)
5-43.
Min. 22 ga., Type B, Grade 33
(Optional) One or more layers, any
Min. 1.0-inch ACFoam II, Duro-Guard 150 II -A
Note 2
1 per 2 ftz
Duro-Fleece or Duro-
-37.5*
steel or structural concrete
combination
Fleece Plus / WB II
Min. 1.5-inch ACFoam 11, Duro-Guard 150 II -A,
Min. 22 ga., Type B. Grade 33
(Optional) One or more layers, any
ACFoam III, Duro-Guard 150 III -A, H-Shield,
Duro-Fleece or Duro-
5-44.
steel or structural concrete
combination
Duro-Guard ISO II-H, ENRGY 3, Duro-Guard
Note 2
1 per 2 ftz
Fleece Plus / WB II
-45.0*
150 II-G or 150 95+ GLISO
5-45.
Min. 22 a., Type B, Grade 33
g YP
(Optional) One or more layers, an
( p ) y y
Min. 0.25-inch SECUROCK Gypsum -Fiber Roof
Yp
Note 2
1 per 2 ftz
Duro-Fleece or Duro-
Fleece Plus / Duro-Fleece
-45.0*
steel or structural concrete
combination
Board
CR-20 (splatter) or WB II
Min. 22 a., Type B, Grade 33
g Yp
(Optional) One or more layers, an
( p ) y y
Min. 5/8-inch SECUROCK Gypsum -Fiber Roof
/ Yp
Duro-Fleece or Duro-
5-46.
Note 2
1 per 4 ftz
Fleece Plus / Duro-Fleece
-45.0*
steel or structural concrete
combination
Board
CR-20 (splatter) or WB 11
5-47.
Min. 22 ga., Type B, Grade 33
(Optional) One or more layers, any
Min. 0.5-inch Dens Deck
Note 2
1 per 2 ftz
Duro-Fleece or Duro-
-45.0*
steel or structural concrete
combination
Fleece Plus / WB II
Min. 22 ga., Type B, Grade 33
(Optional) One or more layers, any
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A,
z
Duro-Fleece or Duro-
5-48.
steel or structural concrete
combination
ACFoam III or 150 95+ GL
Note 2
1 per 2 ft
Fleece Plus / Duro-Fleece
-45.0
Adhesive
Min. 22 ga., Type B, Grade 33
(Optional) One or more layers, any
Duro-Fleece or Duro-
5-49.
steel or structural concrete
combination
Min. 0.5-inch Dens Deck
Note 2
1 per 2 ft z
Fleece Plus / Duro-Fleece
-45.0
Adhesive
Min. 22 ga., Type B, Grade 33
One or more layers, any
Min. 0.25-inch SECUROCK Gypsum -Fiber Roof
1 per 1.33
Duro-Fleece or Duro-
5-50.
steel or structural concrete
combination, min. 1.5-inch thick
Board
Note 2
ftz
Fleece Plus / Duro-Fleece
-67.5
CR-20 (splatter) or WB 11
Min. 22 ga., Type B, Grade 33
One or more layers, any
Note 2 (#15 Extra Heavy
1 per 1.67
Duro-Fleece or Duro-
5-51.
steel or structural concrete
combination, min. 1.5-inch thick
Min. 0.25-inch Dens Deck Prime
Duty only)
ftz
Fleece Plus / Duro-Fleece
-67.5
CR-20 (splatter)
Min. 22 ga., Type B, Grade 33
(Optional) One or more layers, any
1 per 1.33
Duro-Fleece or Duro-
S 52.
steel or structural concrete
combination, min. 1.5-inch thick
Min. 0.25-inch Dens Deck Prime
Note 2
ftz
Fleece Plus / WB 11
67.5
Min. 22 ga., Type B, Grade 33
One or more layers, any
Min. 0.5-inch SECUROCK Gypsum Fiber Roof
Trufast #12 DP with
Duro-Fleece or Duro-
5-53.
combination, min. 1.5-inch total
Trufast 3" Metal
1 per 1 ftz
Fleece Plus / Duro-Fleece
-97.5
steel
thickness
Board
I
I Insulation Plate
CR-20 (splatter) or WB II
NEMO ETC, LLC
Certificate of Authorization #32455
02019 NEMO ETC, LLC
6TH EDITION (2017) FBC NON-HVHZ EVALUATION
Duro-Last Single Ply Roof Systems; (800) 248-0280
Evaluation Report 139750.05.08-1110 for FL1559-1133
Revision 10: 10/17/2019
Appendix 1, Page 12 of 44
ONEMOjetc.
TABLE 21): STEEL DECKS - NEW CONSTRUCTION, .. .. RECOVER
PLATE-BONDEDSYSTEM TYPE C-2: MECHANICALLY ATTACHED INSULATION, ROOF COVER
System Deck Insulation Layer Attach MDP
Roof Cover /Attach
No. (Note i) (Note 14) Fasteners Density (psf)
RHINOBOND INDUCTION WELD:
Min. 22 ga., type
One or more layers, any
Duro-Last #15 Extra Heavy Duty Drill Point
1 per 4 ft z
Duro-Last (min. 40-mil), Duro-Tuff (min. 50-mil) or Duro-
S-54.
B, Grade 33 steel
combination
Fasteners with RHINOBOND Insulation Plate
(2 x 2-ft grid)
Last EV (min. 50-mil) induction welded to RHINOBOND
-37.5
(PVC)
Insulation Plate (PVC) using RHINOBOND Installation Tool
Min. 22 ga., type
One or more layers, any
Duro-Last #15 Extra Heavy Duty Drill Point
1 per 6 ft a
Duro-Last (min. 40-mil), Duro-Tuff (min. 50-mil) or Duro-
5-55.
B, Grade 33 steel
combination
Fasteners with RHINOBOND Insulation Plate
(24 x 36 inch grid pattern)
Last EV (min. 50-mil) induction welded to RHINOBOND
-45.0'
(PVC)
Insulation Plate (PVC) using RHINOBOND Installation Tool
Min. 22 ga., type
One or more layers, any
Duro-Last #15 Extra Heavy Duty Drill Point
1 per 2.29 ftz
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-
5-56.
B Grade 33 steel
combination
Fasteners with RHINOBOND Insulation Plate
(14 parts per 4 x 8 ft board
Tuff (min. 80-mil) induction welded to RHINOBOND
-45.0
(PVC)
in 18 x 18 inch grid pattern)
Insulation Plate (PVC) using RHINOBOND Installation Tool
One or more layers DURO-
1 per 4 ftz
GUARD ISO II -A, DURO-GUARD
(8 parts per 4 x 8 ft board)
Min. 20 ga., Type
ISO II-G, DURO-GUARD ISO II-H,
OMG XHD with RHINOBOND Insulation Plate
parts spaced 24" o.c. in rows spaced
Duro-Last (min. 40-mil), Duro-Tuff (min. 50-mil) or Duro-
5-57.
N, Grade 40 steel
DURO-GUARD ISO III -A or
(PVC)
24"o.c., while maintainingfostener
engagement with the topflange of
Last EV (min. 50-mil) induction welded to RHINOBOND
-52.5
DURO-GUARD ISO III-H• top
the Type Ndeck profile. Every -other
Insulation Plate (PVC) using RHINOBOND Installation Tool
layer min. 1-inch
set of two (2) rows is staggered 8-
inchesfrom the previous set.
Min. 18 ga., type
One or more layers, any
Duro-Last #15 Extra Heavy Duty Drill Point
12-inch o.-in rows spaced
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-
S-58.
B, Grade 33 steel
combination, preliminarily
Fasteners with RHINOBOND Insulation Plate
60-inch o.c.
Tuff (min. 80-mil) induction welded to RHINOBOND
-30.0
attached (Note 5)
(PVC)
Insulation Plate (PVC) using RHINOBOND Installation Tool
Min. 18 ga., type
One or more layers, any
Duro-Last #15 Extra Heavy Duty Drill Point
6-inch o.c. in rows spaced
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-
S-59.
B, Grade 33 steel
combination, preliminarily
Fasteners with RHINOBOND Insulation Plate
120-inch o.c.
Tuff (min. 80-mil) induction welded to RHINOBOND
-45.0
attached (Note 5)
(PVC)
Insulation Plate (PVC) using RHINOBOND Installation Tool
Min. 18 ga., type
One or more layers, any
Duro-Last #15 Extra Heavy Duty Drill Point
12-inch o.-in rows spaced
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-
S-60.
B, Grade 33 steel
combination, preliminarily
Fasteners with RHINOBOND Insulation Plate
48inch o.c.
Tuff (min. 80-mil) induction welded to RHINOBOND
-45.0
attached (Note 5)
(PVC)
Insulation Plate (PVC) using RHINOBOND Installation Tool
Min. ga., type
One or more layers, any
Duro-Last #15 Extra Heavy Duty Drill Point
6-inch o.c. in rows spaced
Duro-Last (min. 40-mil), Duro-Tuff (min. 50-mil) or Duro-
S-61.
B, Grade 33 steel
combination, preliminarily
Fasteners with RHINOBOND Insulation Plate
72-inch o.c.
Last EV (min. 50-mil) induction welded to RHINOBOND
-52.5
attached Note 5
( )
(PVC)
Insulation Plate (PVC) using RHINOBOND Installation Tool
Min. ga., type
One or more layers, any
Duro-Last #15 Extra Heavy Duty Drill Point
6-inch o.c. in rows spaced
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-
S-62.
B, Grade 33 steel
combination, preliminarily
Fasteners with RHINOBOND Insulation Plate
96-inch o.c.
Tuff (min. 80-mil) induction welded to RHINOBOND
-52.5
attached (Note 5)
(PVC)
Insulation Plate (PVC) using RHINOBOND Installation Tool
Min. ga., type
One or more layers, any
Duro-Last #15 Extra Heavy Duty Drill Point
6-inch o.c. in rows spaced
Duro-Last (min. 40-mil), Duro-Tuff (min. 50-mil) or Duro-
S-63.
B, Grade 33 steel
combination, preliminarily
Fasteners with RHINOBOND Insulation Plate
48-inch o.c.
Last EV (min. 50-mil) induction welded to RHINOBOND
-82.5
attached (Note 5)
(PVC)
Insulation Plate (PVC) using RHINOBOND Installation Tool
Min. ga., type
One or more layers, any
Duro-Last #15 Extra Heavy Duty Drill Point
6-inch o.c. in rows spaced
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-
S-64.
B, Grade 33 steel
combination, preliminarily
Fasteners with RHINOBOND Insulation Plate
60-inch o.c.
Tuff (min. 80-mil) induction welded to RHINOBOND
-82.5
attached (Note 5)
(PVC)
Insulation Plate (PVC) using RHINOBOND Installation Tool
NEMO ETC, LLC Evaluation Report D9750.05.08-R10 for FL1559-R33
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 13 of 44
OMEMO I etc.
TABLE 2D: STEEL DECKS - NEW CONSTRUCTION, .. OR RECOVER
PLATE-BONDEDSYSTEM TYPE C-2: MECHANICALLY ATTACHED INSULATION, ROOF COVER
System Deck Insulation Layer
Attach
Roof Cover Attach
MDP
Fasteners
Density
No. (Note 1) (Note 14)
(psf)
Min. 18 ga., type One or more layers, any
Duro-Last #15 Extra Heavy Duty Drill Point
6-inch o.c, in rows spaced
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-
5-65. B Grade 33 steel combination, preliminarily
Fasteners with RHINOBOND Insulation Plate
48-inch o.c.
Tuff (min. 80-mil) induction welded to RHINOBOND
-90.0
attached (Note 5)
(PVC)
Insulation Plate (PVC) using RHINOBOND Installation Tool
ISOWELD INDUCTION WELD:
Min. 22 ga., type
One or more layers, any
SFS Intec Dekfast DF-#15-PH3 with isoweld°
6 ft2 per fastener
Duro-Last (min. 40 mil), Duro-Last EV (min. 50 mil) or Duro-
5-66.
B Grade 40 steel
combination, min. 1.5-inch
Fl-P-6.8-13VC Plates
2 x 3-ft grid, staggered
Tuff (min. 50 mil) induction welded to SFS isoweld° Fl-P-
-37.5
6.8-PVC Plates with SFS isoweld 3000 stand-up tool
Min. 22 ga., type
One or more layers, any
SFS Intec Dekfast DF-#12-PH3 or DF-#15-PH3
6 ft2 per fastener
Duro-Last (min. 40 mil), Duro-Last EV (min. 50 mil) or Duro-
S-67.
B Grade 80 steel
combination, min. 1.5-inch
Fastener with isoweld° Fl-P-6.8-PVC Plates
2 x 3-ft grid, staggered
Tuff (min. 50 mil) induction welded to SFS isoweld° Fl-P-
-37.5
6.8-PVC Plates with 5FS isoweld 3000 stand-up tool
Min. 22 ga., type
One or more layers, any
5FS Intec Dekfast DF-#15-PH3 with isoweld°
4 ftz per fastener
Duro-Last (min. 40 mil), Duro-Last EV (min. 50 mil) or Duro-
S-68.
B Grade 40 steel
combination, min. 1.5-inch
F1-P-6.8-PVC Plates
2 x 2-ft grid, staggered
Tuff (min. 50 mil) induction welded to SF5 isoweld° F1-P-
-52.5
6.8-PVC Plates with SFS isoweld 3000 stand-up tool
Min. 22 ga., type
One or more layers, any
SFS Intec Dekfast DF-#12-PH3 or DF-#15-PH3
4 ft' per fastener
Duro-Last (min. 40 mil), Duro-Last EV (min. 50 mil) or Duro-
S-69.
B, Grade 80 steel
combination, min. 1.5-inch
Fastener with isoweld° Fl-P-6.8-PVC Plates
2 x 2-ft grid, staggered
Tuff (min. 50 mil) induction welded to SFS isoweld° F1-P-
-52.5
6.8-PVC Plates with SFS isoweld 3000 stand-up tool
Min. 22 ga., type
One or more layers, any
SFS Intec Dekfast DF-#15-PH3 with isoweld°
3 ft2 per fastener
Duro-Last (min. 40 mil), Duro-Last EV (min. 50 mil) or Duro-
S-70.
B Grade 40 steel
combination, min. 1.5-inch
F1-P-6.8-PVC Plates
1.5 x 2-ft grid, staggered
Tuff (min. 50 mil) induction welded to SFS isoweld°F1-P-
-82.5
6.8-PVC Plates with SFS isoweld 3000 stand-up tool
Min. 22 ga., type
One or more layers, any
SF5 Intec Dekfast DF-#12-PH3 or DF-#15-PH3
3 ft2 per fastener
Duro-Last (min. 40 mil), Duro-Last EV (min. 50 mil) or Duro-
5-71.
B Grade 80 steel
combination, min. 1.5-inch
Fastener with isoweld° F1-P-6.8-PVC Plates
1.5 x 2-ft grid, staggered
Tuff (min. 50 mil) induction welded to SFS isoweld°F1-P-
-82.5
6.8-PVC Plates with SF5 isoweld 3000 stand-up tool
Min. 22 ga., type
One or more layers, any
SFS Intec Dekfast DF-#15-PH3 with isoweld°
12-inch o.c. in rows spaced
Duro-Last (min. 40 mil), Duro-Last EV (min. 50 mil) or Duro-
5-72.
B, Grade 40 steel
combination, min. 1.5-inch,
Fl-P-6.8-PVC Plates
60-inch o.c.
Tuff (min. 50 mil) induction welded to SFS isoweld° F1-P-
-45.0
preliminarily attached (Note 5)
6.8-PVC Plates with SFS isoweld° 3000 stand-up tool
Min. 22 ga., type
One or more layers, any
SF5 Inter Dekfast DF-#12l-P-
DF-#15tes
12-inch o.-ic. in rows spaced
Duro-Last (min. 40 mil), Duro-Last EV (min. 50 mil) or Duro-
5-73.
B, Grade 80 steel
combination, min. 1.5-inch,
Fastener with isoweld® Fl-P-6.8-PVC Plates
.8
60-inch o.c.
Tuff (min. 50 mil) induction welded to SFS isoweld° F1-P-
-45.0
preliminarily attached (Note 5)
6.8-PVC Plates with SF5 isoweld° 3000 stand-up tool
Min. 22 ga., type
One or more layers, any
SFS Intec Dekfast DF-#15-PH3 with isoweld°
6-inch o.c. in rows spaced
Duro-Last (min. 40 mil), Duro-Last EV (min. 50 mil) or Duro-
S-74.
B, Grade 40 steel
combination, min. 1.5-inch,
Fl-P-6.8-PVC Plates
60-inch o.c.
Tuff (min. 50 mil) induction welded to SFS isoweld® Fl-P-
-90.0
preliminarily attached (Note 5)
6.8-PVC Plates with SFS isoweld° 3000 stand-up tool
Min. 22 ga., type
One or more layers, any
5FS Inter Dekfast DF-#12l-P-
DF-#15tes
6-inch o.c. in rows spaced
Duro-Last (min. 40 mil), Duro-Last EV (min. 50 mil) or Duro-
S-75.
B, Grade 80 steel
combination, min. 1.5-inch,
Fastener with isoweld° Fi-P-6.8-PVC Plates
.8
60-inch D.C.
Tuff (min. 50 mil) induction welded to SFS isoweld® Fl-P-
-90.0
preliminarily attached (Note 5)
6.8-PVC Plates with SFS isoweld° 3000 stand-up tool
TRUFAST INDUCTION WELD:
NEMO ETC, LLC Evaluation Report D9750.05.08-R10 for FL3559-1133
_Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 14 of 44
ONEMOletc.
TABLE 21): STEEL DECKS - NEW CONSTRUCTION, REROOF (TEAR -OFF) OR RECOVER
SYSTEM TYPE C-2: MECHANICALLY ATTACHED INSULATION, PLATE -BONDED ROOF COVER
System
Deck
Insulation Layer Attach
Roof Cover /Attach
MDP
No.
(Note 1)
(Note 14) Fasteners Density
(psf)
Min. 22 ga., type
One or more layers, any
1 per 5.33 ft2
Duro-Last (min. 40 mil), Duro-Last EV (min. 50 mil) or Duro-
5-76.
B, Grade 33 steel
combination, min. 2-inch
Trufast #15 EHD with Trufast PVC IW Plate
(6 parts per 4x8 ft board on
Tuff (min. 50 mil) induction welded to Trufast PVC IW Plates
-45.0'
a 24x36-inch pattern)
with Trufast Induction Welding Tool and Magnets
Min. 2ga., type
One or more layers, anye
1 per 4 ft2
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
S 77
B, Gradd 33 steel
combination, min. 2-inch
Trufast #15 EHD with Trufast PVC IW Plate
(8 parts per 4x8 ft board on
welded to Trufast PVC IW Plates with Trufast Induction
-52.5
a 24x24-inch pattern)
Welding Tool and Magnets
Min. 22 ga., type
One or more layers, any
1 per 4 ft2
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-
S 78
B, Grade 33 steel
combination, min. 2-inch
Trufast #15 EHD with Trufast PVC IW Plate
(8 parts per 4x8 ft board on
Tuff (min. 60 mil) induction welded to Trufast PVC IW Plates
-60.0
a 2424-inch pattern)
with Trufast Induction Welding Tool and Magnets
Min. 22 ga., type
One or more layers, any
1 per 3.2 ft2
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
5 79
B, Grade 33 steel
combination, min. 2-inch
Trufast #15 EHD with Trufast PVC IW Plate
(10 parts per 4x8 ft board
welded to Trufast PVC IW Plates with Trufast Induction
-60.0
on a 24x20-inch pattern)
Welding Tool and Magnets
Min. 22 ga., type
One or more layers, any
1 per 3.2 ft2
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-
5-80.
B, Grade 33 steel
combination, min. 2-inch
Trufast #15 EHD with Trufast PVC IW Plate
(10 parts per 4x8 ft board
Tuff (min. 60 mil) induction welded to Trufast PVC IW Plates
-67.5
on a 24x20-inch pattern)
with Trufast Induction Welding Tool and Magnets
Min. 22 ga., type
One or more layers, any
1 per 2.7 ft2
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
S-81.
B, Grade 33 steel
combination, min. 2-inch
Trufast #15 EHD with Trufast PVC IW Plate
(12 parts per 4x8 ft board
welded to Trufast PVC IW Plates with Trufast Induction
-67.5
per FM LPDS 1-29)
Welding Tool and Magnets
Min. 22 ga., type
One or more layers, any
1 per 2.7 ft2
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-
S-82.
B, Grade 33 steel
combination, min. 2-inch
Trufast #15 EHD with Trufast PVC IW Plate
(12 parts per 4x8 ft board
Tuff (min. 60 mil) induction welded to Trufast PVC IW Plates
-82.5
per FM LPDS 1-29)
with Trufast Induction Welding Tool and Magnets
Min. 22 ga., type
One or more layers, any
1 per 2 ft2
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
5-83.
B Grade 33 steel
combination, min. 2-inch
Trufast #15 EHD with Trufast PVC IW Plate
(16 parts per 4x8 ft board
welded to Trufast PVC IW Plates with Trufast Induction
-90.0
on a 12x24-inch pattern)
Welding Tool and Magnets
Min. 22 ga., type
One or more layers, any
1 per 2 ft2
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-
S-84.
B, Grade 33 steel
combination, min. 2-inch
Trufast #15 EHD with Trufast PVC IW Plate
(16 parts per 4x8 ft board
Tuff (min. 60 mil) induction welded to Trufast PVC IW Plates
-112.5
on a 12x24-inch pattern)
with Trufast Induction Welding Tool and Magnets
Min. 22 ga., type
One or more layers, any
1 per 1.8 ft2
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
5-85.
B, Grade 33 steel
combination, min. 2-inch
Trufast #15 EHD with Trufast PVC IW Plate
(18 parts per 4x8 ft board
welded to Trufast PVC IW Plates with Trufast Induction
-105.0
on an 18x16-inch pattern)
Welding Tool and Magnets
Min. 22 ga., type
One or more layers, any
1 per 1.8 ft2
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-
S-86.
B, Grade 33 steel
combination, min. 2-inch
Trufast #15 EHD with Trufast PVC IW Plate
(18 parts per 4x8 ft board
Tuff (min. 60 mil) induction welded to Trufast PVC IW Plates
-120.0
on an 18x16-inch pattern)
with Trufast Induction Welding Tool and Magnets
Min. 22 ga., type
One or more layers, any
1 per 1.3 ft2
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
S-87.
B, Grade 33 steel
combination, min. 2-inch
Trufast #15 EHD with Trufast PVC IW Plate
(24 parts per 4x8 ft board
welded to Trufast PVC IW Plates with Trufast Induction
-135.0
on a 12x16-inch pattern)
Welding Tool and Magnets
NEMO ETC, LLC Evaluation Report D9750.05.08-R10 for FL1559-R13
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 15 of 44
NNEMOjetc.
TABLE 21): STEEL DECKS - NEW CONSTRUCTION, .. on RECOVER
PLATE-BONDEDSYSTEM TYPE C-2: MECHANICALLY ATTACHED INSULATION, ROOF
System Deck
Insulation Layer Attach
Roof Cover/ Attach
MDP
No. (Note 1)
(Note 14) Fasteners Density
(psf)
Min. ga., type
One or more layers, anye
1 per 1.3 ft2
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-
S 88
B, Grade 33 steel
combination, min. 2-inch
Trufast #15 EHD with Trufast PVC IW Plate
(24 parts per 48 ft board
Tuff (min. 60 mil) induction welded to Trufast PVC IW Plates
-172.5
on a 12x16-inch pattern)
with Trufast Induction Welding Tool and Magnets
Min. ga., type
One or more layers, anye
1 per 1 ft'
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
5 89
B, Grade 33 steel
combination, min. 2-inch
Trufast #15 EHD with Trufast PVC IW Plate
(32 parts per 4x8 ft board
welded to Trufast PVC IW Plates with Trufast Induction
-142.5
per FM LPDS 1-29)
Welding Tool and Magnets
Min. ga., type
One or more layers, anye
1 per 1 ft2
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-
5-90.
B, Grade 33 steel
combination, min. 2-inch
Trufast #15 EHD with Trufast PVC IW Plate
(32 parts per 48 ft board
Tuff (min. 60 mil) induction welded to Trufast PVC IW Plates
-217.5
per FM LPDS 1-29)
with Trufast Induction Welding Tool and Magnets
Min. 22 ga., type
One or more layers, any
12-inch o.c. in rows spaced
Duro-Last (min. 40 mil), Duro-Last EV (min. 50 mil) or Duro-
S-91.
B Grade 33 steel
combination, min. 2-inch,
Trufast #15 EHD with Trufast PVC IW Plate
60-inch o.c.
Tuff (min. 50 mil) induction welded to Trufast PVC IW Plates
-45.0
preliminarily attached
with Trufast Induction Welding Tool and Magnets
Min. ga., type
One or more layers, any
12-inch o.in rows spaced
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
5 92
B, Grade 33 steel
combination, min. 2-inch,
Trufast #15 EHD with Trufast PVC IW Plate
-
48inch o.c.
welded to Trufast PVC IW Plates with Trufast Induction
-52.5
preliminarily attached
Welding Tool and Magnets
Min. 22 ga., type
One or more layers, any
12-inch o.c. in rows spaced
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-
5-93.
B Grade 33 steel
combination, min. 2-inch,
Trufast #15 EHD with Trufast PVC IW Plate
48-inch o.c.
Tuff (min. 60 mil) induction welded to Trufast PVC IW Plates
-60.0
preliminarily attached
with Trufast Induction Welding Tool and Magnets
Min. 22 ga., type
One or more layers, any
12-inch o.c. in rows spaced
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
5-94.
g Grade 33 steel
combination, min. 2-inch
Trufast #15 EHD with Trufast PVC IW Plate
36-inch o.c.
welded to Trufast PVC IW Plates with Trufast Induction
-60.0
Welding Tool and Magnets
Min. 22 ga., type
One or more layers, any
12-inch o.c. in rows spaced
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-
S-95.
B Grade 33 steel
combination, min. 2-inch
Trufast #15 EHD with Trufast PVC IW Plate
36-inch o.c.
Tuff (min. 60 mil) induction welded to Trufast PVC IW Plates
-82.5
with Trufast Induction Welding Tool and Magnets
Min. 22 ga., type
One or more layers, any
6-inch o.c. in rows spaced
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
5-96.
B, Grade 33 steel
combination, min. 2-inch,
Trufast #15 EHD with Trufast PVC IW Plate
72-inch o.c.
welded to Trufast PVC IW Plates with Trufast Induction
-67.5
preliminarily attached
Welding Tool and Magnets
Min. 22 ga., type
One or more layers, any
6-inch o.c. in rows spaced
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-
S 97
B, Grade 33 steel
combination, min. 2-inch,
Trufast #15 EHD with Trufast PVC IW Plate
72-inch o.c.
Tuff (min. 60 mil) induction welded to Trufast PVC IW Plates
-75.0
preliminarily attached
with Trufast Induction Welding Tool and Magnets
Min. 22 ga., type
One or more layers, any
6-inch o.c. in rows spaced
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
S 98
B, Grade 33 steel
combination, min. 2-inch,
Trufast #15 EHD with Trufast PVC IW Plate
60-inch o.c.
welded to Trufast PVC IW Plates with Trufast Induction
-75.0
preliminarily attached
Welding Tool and Magnets
Min. 22 ga., type
One or more layers, any
6-inch o.c. in rows spaced
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-
5 99
B, Grade 33 steel
combination, min. 2-inch,
Trufast #15 EHD with Trufast PVC IW Plate
60-inch o.c.
Tuff (min. 60 mil) induction welded to Trufast PVC IW Plates
-90.0
preliminarily attached
with Trufast Induction Welding Tool and Magnets
NEMO ETC, LLC Evaluation Report D9750.05.08-1110 for FL1559-1113
Certificate of Authorization #32455 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 16 of 44
ONEMOletc.
TABLE 21): STEEL DECKS - NEW CONSTRUCTION, •.. .. RECOVER
PLATE-BONDEDSYSTEM TYPE C-2: MECHANICALLY ATTACHED INSULATION, ROOF COVER
System
Deck
Insulation Layer Attach MDP
Roof Cover /Attach
No.
(Note 1)
(Note 14) Fasteners' Density (psf)
Min. 22 ga., type
One or more layers, any
6-inch o.c. in rows spaced
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
S-300.
8, Grade 33 steel
combination, min. 2-inch,
Trufast #15 EHD with Trufast PVC IW Plate
48-inch o.c.
welded to Trufast PVC IW Plates with Trufast Induction
-90.0
preliminarily attached
Welding Tool and Magnets
Min. 22 ga., type
One or more layers, any
6-inch o.c. in rows spaced
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-
S-101.
B, Grade 33 steel
combination, min. 2-inch,
Trufast #15 EHD with Trufast PVC IW Plate
48-inch o.c.
Tuff (min. 60 mil) induction welded to Trufast PVC IW Plates
-112.5
preliminarily attached
with Trufast Induction Welding Tool and Magnets
Min. 22 ga., type
One or more layers, any
6-inch o.c. in rows spaced
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
5-102.
8 Grade 33 steel
combination, min. 2-inch
Trufast #15 EHD with Trufast PVC IW Plate
36-inch o.c.
welded to Trufast PVC IW Plates with Trufast Induction
-112.5
Welding Tool and Magnets
Min. 22 ga., type
One or more layers, any
6-inch o.c. in rows spaced
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-
5-103.
B, Grade 33 steel
combination, min. 2-inch
Trufast #15 EHD with Trufast PVC IW Plate
36-inch o.c.
Tuff (min. 60 mil) induction welded to Trufast PVC IW Plates
-150.0
with Trufast Induction Welding Tool and Magnets
NEMO ETC, LLC Evaluation Report D9750.05.08-1110 for FL3559-R13
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 17 of 44
NNEMOjetc.
TABLE 2E: STEEL DECKS - NEW CONSTRUCTION, •.. .. RECOVER
ATTACHEDSYSTEM TYPE D-1: PRELIMINARILY INSULATION, MECHANICALLY ATTACHED ROOF
Insulation (Note 14) Roof Cover
System Deck (Note 1) Attach MDP
NO. Type Membrane Fasteners Attach (psf)
(Note 5)
STANDARD LAP SYSTEMS:
Min. 22 ga., Type B, 50
One or more layers, any
Prelim.
Duro-Last EV,
Duro-Last #15 Extra Heavy Duty
Standard Lao System fastened 18-inch o.c. within 6-inch wide
S-104.
ksi steel
combination, min. 1-inch
attach
min. 50-mil
Drill Point Fastener with Duro-
laps spaced 54-inch o.c. Laps sealed with 1.5-inch heat weld.
-30.0
Last Poly -Plate
Min. 22 ga., Type B, 50
One or more layers, any
Prelim.
Duro-Last EV,
Duro-Last #15 Extra Heavy DutyStandard
Lao System fastened 12-inch o.c. within 6-inch wide
5-105.
ksi steel
combination, min. 1-inch
attach
min. 50-mil
Drill Point Fastener with Duro-
laps spaced 54-inch o.c. Laps sealed with 1.5-inch heat weld.
-37.5
Last Cleat Plate
Min. 22 ga., Type B,
One or more layers, any
Prelim.
Duro-Last,
Duro-Last #15 Extra Heavy DutyStandard
Lao System fastened 12-inch o.c. within 5.75-inch wide
S-106.
Grade 33 steel
combination, min. 1.5-inch
attach
min. 40 mil
Drill Point Fastener with Duro-
tabs spaced 120-inch o.c.
-37.5
Last Cleat Plate
Min. 18 ga., Type B,
One or more layers, any
Prelim.
Duro-Last,
Duro-Last #15 Extra Heavy DutyStandard
Lao System fastened 9-inch o.c. within 3-inch wide
5-107.
Grade 33 steel
combination, min. 1.5-inch
attach
min. 40 mil
Drill Point Fastener with Duro-
tabs spaced 60-inch O.C.
-45.0
Last Poly -Plate
Min. 22 ga., Type B, 50
One or more layers, any
Prelim.
Duro-Last EV,
Duro-Last #15 Extra Heavy DutyStandard
Lao System fastened 12-inch o.c. within 6-inch wide
5-108.
ksi steel
combination, min. 1-inch
attach
min. 50-mil
Drill Point Fastener with Duro-
laps spaced 54-inch o.c. Laps sealed with 1.5-inch heat weld.
-45.0
Last Poly -Plate
Min. 22 ga., Type B,
One or more layers, any
Prelim.
Duro-Last EV,
Duro-Last #15 Extra Heavy Duty
Standard Lao System fastened 6-inch o.c. within 6-inch wide
5-109.
Grade 40 steel
combination, min. 1-inch
attach
min. 50-mil
Drill Point Fastener with Duro-
laps spaced 114-inch o.c. Laps sealed with 1.5-inch heat weld.
45.0
Last Poly -Plate
Min. 22 ga., Type B,
One or more layers, any
Prelim.
Duro-Tuff,
Duro-Last #15 Extra Heavy Duty
Standard Lao System fastened 12-inch o.c. within 4-inch wide
S-110.
Grade 33 steel
combination, min. 1.5-inch total
attach
min. 50 mil
Drill Point Fasteners with Duro-
laps spaced 116-inch o.c. Laps sealed with 1.5-inch heat weld.
45.0
thickness, min. 16-psi top layer
Last Cleat Plates
Duro-Last #15 Extra Heavy Duty
S-111.
Min. 22 ga., type B,
One or more layers, any
Prelim.
Duro-Last,
Drill Point Fasteners with Duro-
Standard Lap System fastened 6-inch o.c. within 3-inch wide
Grade 80 steel
combination, min. 1.5-inch
attach
min. 40 mil
Last 2.4-inch Barbed Metal
tabs spaced 84-inch o.c.
60.0
Plates
Min. 22 ga., Type B, 50
One or more layers, any
Prelim.
Duro-Last EV,
Duro-Last #15 Extra Heavy Duty
Standard Lao System fastened 6-inch o.c. within 6-inch wide
S-112.
ksi steel
combination, min. 1-inch
attach
min. 50-mil
Drill Point Fastener with Duro-
laps spaced 54-inch o.c. Laps sealed with 1.5-inch heat weld.
-75.0
Last Cleat Plate
DURO-ROOF LAP SYSTEMS:
Min. 22 ga., Type B,
One or more layers, any
Prelim.
Duro-Last,
Duro-Last #15 Extra Heavy Duty
Duro-Roof Lap System fastened 12-inch o.c. within 5.75-inch
S-113.
Grade 33 steel
combination, min. 1.5-inch
attach
min. 40 mil
Drill Point Fastener with Duro-
wide tabs spaced 120-inch o.c. Tab Sealer 4725 at max. 60
-45.0
Last Cleat Plate
ft2/gal.
Min. 22 ga., type B,
One or more layers, any
Prelim.
Duro-Last,
Duro-Last #15 Extra Heavy Duty
Duro-Roof Lao System fastened 12-inch o.c. within 6-inch wide
5-114.
Grade 80 steel
combination, min. 1.5-inch
attach
min. 40 mil
Drill Point Fasteners with Duro-
tabs spaced 57-inch o.c. Tab Sealer 4725 at max. 60 ft2/gal.
-SZ.S
Last 3-inch Metal Plates
NEMO ETC, LLC
Certificate of Authorization #32455
©2019 NEMO ETC, LLC
6-EDITION (2017) FBC NON-HVHZ EVALUATION
Duro-Last Single Ply Roof Systems; (800) 248-0280
Evaluation Report D9750.05.08-R10 for FL1559-R13
Revision 10: 10/17/2019
Appendix 1, Page 18 of 44
ONEMOjetc.
TABLE 2E: STEEL DECKS - NEW CONSTRUCTION, REROOF (TEAR -OFF) OR RECOVER
SYSTEMTYPED-1: PRELIMINARILY ATTACHED INSULATION, MECHANICALLY ATTACHED ROOF COVER
Insulation (Note 14) Roof Cover
System
Deck (Note 1)
MDP
Attach
No.
Type
Membrane
Fasteners
Attach
(psf)
(Note 5)
Min. 22 ga., type B,
One or more layers, any
Prelim.
Duro-Last,
Duro-Last #15 Extra Heavy Duty
Duro-Roof Lao System fastened 12-inch o.c. within 5.75-inch
5-115.
Drill Point Fastener with Duro-
wide tabs spaced 84-inch o.c. Tab Sealer 4725 at max. 60
-52.5
Grade 80 steel
combination, min. 1.5-inch
attach
min. 40 mil
Last Cleat Plate
ft2/gal.
Min. 22 ga., type B,
One or more layers, any
Prelim.
Duro-Last,
Duro-Last #15 Extra Heavy Duty
Duro-Roof Lao System fastened 12-inch o.c. within 5.75-inch
S-116.
Drill Point Fastener with Duro-
wide tabs spaced 57-inch o.c. Tab Sealer 4725 at max. 60
-67.5
Grade 80 steel
combination, min. 1.5-inch
attach
min. 40 mil
Last Cleat Plate
ft2/gal.
Min. 22 ga., type B,
One or more layers, any
Prelim.
Duro-Last,
Duro-Last #15 Extra Heavy Duty
Duro-RoofLap System fastened 6-inch o.c. within 3-inch wide
S-117.
Grade 80 steel
combination, min. 1.5-inch
attach
min. 40 mil
Drill Point Fastener with Duro-
tabs spaced 60-inch o.c. Tab Sealer 4725 at max. 60 ft2/gal.
-67.5
Last Batten Bar
Min. 22 ga., type B,
One or more layers, any
Prelim.
Duro-Last,
Duro-Last #15 Extra Heavy Duty
Duro-RoofLao System fastened 6-inch o.c. within 6-inch wide
S-118.
Grade 80 steel
combination, min. 1.5-inch
attach
min. 40 mil
Drill Point Fasteners with Duro-
tabs spaced 120-inch o.c. Tab Sealer 4725 at max. 60 ft2/gal.
82.5
Last 3-inch Metal Plates
Min. 22 ga., type B,
One or more layers, any
Prelim.
Duro-Last,
Duro-Last #15 Extra Heavy Duty
Duro-Roof Lao Svstem fastened 6-inch o.c. within 5.75-inch
S-119.
Grade 80 steel
combination, min. 1.5-inch
attach
min. 40 mil
Drill Point Fastener with Duro-
wide tabs spaced 120-inch o.c. Tab Sealer 4725 at max. 60
-82.5
Last Cleat Plate
ft2/gal.
Min. 22 ga., type B,
One or more layers, any
Prelim.
Duro-Last,
Duro-Last #15 Extra Heavy Duty
Duro-Roof Lao System fastened 6-inch o.c. within 5.75-inch
5-120.
Grade 80 steel
combination, min. 1.5-inch
attach
min. 40 mil
Drill Point Fastener with Duro-
wide tabs spaced 84-inch o.c. Tab Sealer 4725 at max. 60
-97.5
Last Cleat Plate
ft2/gal.
Min. 22 ga., type B,
One or more layers, any
Prelim.
Duro-Last,
Duro-Last #15 Extra Heavy Duty
Duro-Roof Lao System fastened 6-inch o.c. within 5.75-inch
S-121.
Grade 80 steel
combination, min. 1.5-inch
attach
min. 40 mil
Drill Point Fastener with Duro-
wide tabs spaced 57-inch o.c. Tab Sealer 4725 at max. 60
-135.0
Last Cleat Plate
ft2/gal.
Min. 22 ga., type B,
One or more layers, any
Prelim.
Duro-Last,
Duro-Last #15 Extra Heavy Duty
Duro-Roof Lao System fastened 6-inch o.c. within 6-inch wide
S-122.
Grade 80 steel
combination, min. 1.5-inch
attach
min. 40 mil
Drill Point Fasteners with OMG
tabs spaced 25-inch o.c. Tab Sealer 4725 at max. 60 ft2/gal.
-142.5
2-3/8" Eyehook Plates
NEMO ETC, LLC Evaluation Report D9750.05.08-1110 for F1.3559-1113
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 19 of 44
OMEMO I etc.
TABLE 2F: STEEL DECKS - NEW CONSTRUCTION .. REROOF
VAPORSYSTEM TYPE D-2: THERMAL BARRIER WITH BARRIER, PRELIMINARILY ATTACHED INSULATION, MECHANICALLY ATTACHED ROOF COVER
System
Deck
Thermal
Vapor
Insulation
Roof Cover
MDP
No.
Note 1
( )
Barrier
Barrier
Slip Sheet
sf
(p )
Base
Top
Attach
Membrane
Fasteners
Attach
(Optional) One or more
(Optional if
Min. 0.25-
layers DURO-GUARD ISO
using base
Duro-Last #14
Min. 22 ga.,
inch Dens
Duro-Last
II -A, DURO-GUARD 150 ll-
layer(s)
Heavy Duty
with Duro-Last
Duro-Last #15 Extra
Standard Lap
Type B,
Deck Prime,
Vapor
G, DURO-GUARD ISO II-H,
insulation) Min.
3-inch Metal
Geotextile
Duro-Last,
Heavy Duty Drill Point
System fastened
5-123.
Grade 40
loose -laid,
Barrier, self-
DURO-GUARD 150 111-A or
0.5-inch DURO-
Platen; 1 per
slip sheet,
min. 40 mil
Fastener with Duro-
12-inch o.c. within
-52.5
steel
adhered or
adhering
DURO-GUARD 150 III-H,
GUARD EPS
5.3 ft ; 6 parts
loose -laid
Last Poly -Plate or
3-inch wide tabs
mech.
DURO-GUARD EPS Type
Type II-C or
Duro-Last Cleat Plate
spaced 60-inch o.c.
attached
II-C or DURO-GUARD EPS
DURO-GUARD
per 4x8 ft
FGF loose -laid
EPS FGF
board
(Optional) One or more
(Optional if
Min. 0.25-
layers DURO-GUARD ISO
using base
Duro-Last #14
Standard Lao
inch Dens
II -A, DURO-GUARD 150 Ik
layer(s)
Heavy Duty
Duro-Last #15 Extra
System fastened
Min. 22 ga.,
Deck Prime,
Duro-Last
G, DURO-GUARD ISO II-H,
insulation) Min.
with Duro-Last
Geotextile
Heavy Duty Drill Point
12-inch o.c. within
5-124.
Type B,
loose -laid,
Vapor
DURO-GUARD ISO III -A or
0.5-inch DURO-
3-inch Metal
slip sheet,
Duro-Tuff,
Fastener with Duro-
6-inch wide laps
-52.5
Grade 40
adhered or
Barrier, self-
DURO-GUARD ISO III-H,
GUARD EPS
Plate n; 1 per
loose -laid
min. 50 mil
Last Poly -Plate or
spaced h o.c.
steel
mech.
adhering
DURO-GUARD EPS Type
Type II-C or
5.3 ft ; 6 parts
Duro-Last Cleat Plate
Side lapss ssealed
sealed
attached
II-C or DURO-GUARD EPS
DURO-GUARD
per 48 ft
with 1.5-inch heat -
FGF loose -laid
EPS FGF
board
weld
NEMO ETC, LLC Evaluation Report D9750.05.08-1110 for FL1559-1113
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 20 of 44
ONEMOletc.
TABLE 3A: STRUCTURAL CONCRETE DECKS � NEW CONSTRUCTION OR REROOF (TEAR -OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
REFER . NOTE 17 FORVAPORBARRIER OPTIONS
System
Deck Base Insulation Layer
Top Insulation Layer
MDP
No.
(Note 1) Type Attach (Notes 6 & 7)
Roof Cover (Note 16)
(psf)
Type Attach (Notes 6 & 7)
DURO-LAST MEMBRANE APPLICATIONS:
C-1.
Min. 2,500 psi
(Optional) Min. 1.5-inch ACFoam 11, Duro-
Ashland Pliodeck
Min. 0.25-inch Dens Deck
Ashland Pliodeck
Duro-Last / WB I
37.5
structural concrete
Guard ISO II -A
C 2
Min. 2,500 psi
Min. 1.5-inch ACFoam 11, Duro-Guard ISO II -A
Ashland Pliodeck
(Optional) Additional layers of base
Ashland Pliodeck
Duro-Last / SB I or WB II-45.0
structural concrete
insulation
C-3.
Min. 2,500 psi
Min. 1.5-inch ACFoam 11, Duro-Guard ISO 11-A
Ashland Pliodeck
(Optional) Additional layers of base
Ashland Pliodeck
Duro-Last, Duro-Last EV or
-45.0
structural concrete
insulation
Duro-Tuff/ SB IV or WB II
C 4
Min. 2,500 psi
Min. 1.5-inch ACFoam 11, Duro-Guard ISO II -A
Ashland Pliodeck
(Optional) Additional layers of base
Ashland Pliodeck
Duro-Last / WB 1
-82.5
structural concrete
insulation
C 5
Min. 2,500 psi
Min. 2-inch ISO 95+ GL
Ashland Pliodeck
Min. 0.25-inch SECUROCK Gypsum-
Ashland Pliodeck
Duro-Last/ WB II
-217.5
structural concrete
Fiber Roof Board
C-6.
Min. 2,500 psi
Min. 2-inch ISO 95+ GL
Ashland Pliodeck
Min. 0.25-inch SECUROCK Gypsum-
Ashland Pliodeck
Duro-Last, Duro-Last EV or
-217.5
structural concrete
Fiber Roof Board
Duro-Tuff / SB IV or WB II
Min. Z,500 psi
Min. 1.5-inch ACFoam 11, Duro-Guard ISO II -A,
Min. 0.25-inch SECUROCK Gypsum-
Duro-Last, Duro-Last EV or
C 7.
structural concrete
H-Shield, Duro-Guard 150 11-H, ENRGY 3 or
Board -Max
Fiber Roof Board
Board -Max
Duro-Tuff / SB IV or WB 11
-247.5
Duro-Guard ISO II-G
C 8
Min. 2,500 psi
Min. 0.75-inch Duro-Guard EPS Type IX
Board -Max
Min. 0.25-inch SECUROCK Gypsum-
Board -Max
Duro-Last, Duro-Last EV or
-247.5
structural concrete
Fiber Roof Board
Duro-Tuff / SB IV or WB 11
C 9
Min. 2,500 psi
Min. 0.75-inch Duro-Guard EPS Type IX
Board -Max
Min. 0.25-inch SECUROCK Gypsum-
Board -Max
Duro-Last, Duro-Last EV or
-255.0
structural concrete
Fiber Roof Board
Duro-Tuff / SB IV or WB II
Min. 2,500 psi
Min. 1.5-inch ACFoam 11, Duro-Guard ISO II -A,
Min. 0.25-inch SECUROCK Gypsum-
Duro-Last, Duro-Last EV or
C-10.
structural concrete
H-Shield, Duro-Guard ISO 11-H, ENRGY 3 or
CR-20
Fiber Roof Board
CR-20
Duro-Tuff / SB IV or WB 11
-247.5
Duro-Guard ISO II-G
C-11.
Min. 2,500 psi
Min. 0.75-inch Duro-Guard EPS Type 11, VIII or
CR-20
Min. 0.25-inch SECUROCK Gypsum-
CR-20
Duro-Last, Duro-Last EV or
-247.5
structural concrete
IX
Fiber Roof Board
Duro-Tuff / SB IV or WB II
C-12.
Min. 2,500 psi
Min. 0.75-inch Duro-Guard EPS Type 11, VIII or
Min. 0.25-inch SECUROCK Gypsum
Duro-Last, Duro-Last EV or
structural concrete
IX
CR-20
Fiber Roof Board
CR-20
Duro-Tuff / SB IV or WB II
255.0
Min. 2,500 psi
(Optional) Min. 1.5-inch ACFoam 11, Duro-
C-13.
structural concrete
Guard ISO II -A
Insta-Stik
Min. 0.25-inch Dens Deck
Insta-Stik
Duro-Last / WB 1
-37.5
C-14.
Min. 2,500 psi
Min. 1.5-inch ACFoam 11, Duro-Guard ISO 11-A
Insta-Stik
(Optional) Additional layers of base
Insta-Stik
Duro-Last / SB I or WB II-45.0
structural concrete
insulation
C-15.
Min. 2,500 psi
Min. 1.5-inch ACFoam 11, Duro-Guard ISO II -A
Insta-Stik
(Optional) Additional layers of base
Insta-Stik
Duro-Last, Duro-Last EV or
-45.0
structural concrete
insulation
Duro-Tuff/SB IV or WB 11
C-16.
Min. 2,500 psi
Min. 1.5-inch ACFoam 11, Duro-Guard ISO 11-A
Insta-Stik
(Optional) Additional layers of base
Insta-Stik
Duro-Last / WB 1
-82.5
structural concrete
insulation
NEMO ETC, LLC Evaluation Report D9750.05.08-R10 for FI.1559-1113
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 21 of 44
ONEMOletc.
CONCRETETABLE 3A: STRUCTURAL . CONSTRUCTION ...... .
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF
REFER . NOTE 17 FOR VAPOR BARRIER OPTIONS
System
Deck
Base Insulation Layer Top Insulation Layer
MDP
No.
(Note 1)
Roof Cover (Note 16)
(psf)
Type
Attach (Notes 6 & 7)
Type
Attach (Notes 6 & 7)
Min. 2,500 psi
Min. 1.5-inch ACFoam II, Duro-Guard 150 II -A,
Min. 0.25-inch SECUROCK Gypsum-
Duro-Last, Duro-Last EV or
C-17.
structural concrete
H-Shield, Duro-Guard ISO II-H, ENRGY 3 or
Insta-Stik
Fiber Roof Board
Insta-Stik
Duro-Tuff/ SB IV or WB II
-247.5
Duro-Guard ISO II-G
C 18
Min. 2,500 psi
Min. 1.5-inch ACFoam 11, Duro-Guard ISO II -A
Hot asphalt
(Optional) Additional layers of base
Hot asphalt
Duro-Last / SB I or WB II
-45.0
structural concrete
insulation
C-19.
Min. 2,500 psi
Min. 1.5-inch ACFoam 11, Duro-Guard ISO II -A
Hot asphalt
(Optional) Additional layers of base
Hot asphalt
Duro-Last, Duro-Last EV or
-45.0
structural concrete
insulation
Duro-Tuff/SB IV or WB II
C-20.
Min. 2,500 psi
Min. 1.5-inch ACFoam II, Duro-Guard ISO 11-A
Hot asphalt
(Optional) Additional layers of base
Hot asphalt
Duro-Last / WB 1
-75.0
structural concrete
insulation
Min. 1.5-inch ACFoam 11, Duro-Guard ISO 11-A,
C-21.
Min. 2,500 psi
H-Shield, Duro-Guard ISO II-H, ENRGY 3 or
Hot asphalt
Min. 0.25-inch SECUROCK Gypsum-
Hot asphalt
Duro-Last, Duro-Last EV or
247.5
structural concrete
Duro-Guard 150 II-G
Fiber Roof Board
Duro-Tuff / SB IV or WB 11
C 22
Min. 2,500 psi
(Optional) Min. 1.5-inch ACFoam 11, Duro-
OlyBond 500
Min. 0.25-inch Dens Deck
OlyBond 500
Duro-Last/ WB 1
-37.5
structural concrete
Guard ISO II -A
C-23.
Min. 2,500 psi
Min. 1.5-inch ACFoam 11, Duro-Guard ISO 11-A
OlyBond 500
(Optional) Additional layers of base
OlyBond 500
Duro-Last / SB I or WB II
-45.0
structural concrete
insulation
C-24.
Min. 2,500 psi
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A
OlyBond 500
(Optional) Additional layers of base
OlyBond 500
Duro-Last, Duro-Last EV or
45.0
structural concrete
insulation
Duro-Tuff/ SB IV or WB 11
C-25.
Min. 2,500 psi
Min. 1.5-inch ACFoam 11, Duro-Guard 150 11-A
OlyBond 500
(Optional) Additional layers of base
OlyBond 500
Duro-Last / WB 1
-82.5
structural concrete
insulation
Min. 2,500 p si
Min. 1.5-inch ACFoam 11, Duro-Guard ISO 11-A,
Min. 0.25-inch SECUROCK Gypsum-
Duro-Last, Duro-Last EV or
C-26.
structural concrete
H-Shield, Duro-Guard ISO 11-H, ENRGY 3 or
OlyBond 500
Fiber Roof Board
OlyBond 500
Duro-Tuff / SB IV or WB II
-247.5
Duro-Guard ISO II-G
C 27
Min. 2,500 psi
Min. 1.5-inch ACFoam 11, Duro-Guard ISO 11-A,
OlyElond Classic, full
Min. 0.25-inch SECUROCK Gypsum-
OlyBond Classic, full
Duro-Last, Duro-Last EV or
structural concrete
H-Shield, Duro-Guard ISO 11-H
coverage
Fiber Roof Board
coverage
Duro-Tuff/ SB IV or WB II
457.5
Min. 2,500 psi
(Optional) Min. 1.5-inch ACFoam 11, Duro-
Trufast Roofing
Trufast Roofing
C-28.
structural concrete
Guard ISO II -A
Adhesive
Min. 0.25-inch Dens Deck
Adhesive
Duro-Last / WB 1
-37.5
C 29
Min. 2,500 psi
Min. 1.5-inch ACFoam 11, Duro-Guard ISO 11-A
Trufast Roofing
(Optional) Additional layers of base
Trufast Roofing
Duro-Last / SB I or WB 11
-45.0
structural concrete
Adhesive
insulation
Adhesive
C-30.
Min. 2,500 psi
Min. 1.5-inch ACFoam 11, Duro-Guard ISO II -A
Trufast Roofing
(Optional) Additional layers of base
Trufast Roofing
Duro-Last / WB I
82.5
structural concrete
Adhesive
insulation
Adhesive
DURO-FLEECE OR DURO-FLEECE PLUS MEMBRANE APPLICATIONS:
C-31.
Min. 2,500 psi
Min. 1.5-inch ACFoam I1, Duro-Guard 150 II -A
Ashland Pliodeck
(Optional) Additional layers of base
Ashland Pliodeck
Duro-Fleece or Duro-Fleece
45.0
structural concrete
insulation
Plus / WB II
C-32.
Min. 2,500 psi
Min. 2-inch ISO 95+ GL
Ashland Pliodeck
Min. 0.25-inch SECUROCK Gypsum-
Ashland Pliodeck
Duro-Fleece or Duro-Fleece
-217.5
structural concrete
Fiber Roof Board
Plus / WB 11
NEMO ETC, LLC
Certificate of Authorization #32455
©2019 NEMO ETC, LLC
6TH EDITION (2017) FBC NON-HVHZ EVALUATION
Duro-Last Single Ply Roof Systems; (800) 248-0280
Evaluation Report D9750.05.08-1310 for FL1559-R13
Revision 10: 10/17/2019
Appendix 1, Page 22 of 44
ONEMOjetc.
TABLE 3A: STRUCTURAL CONCRETE DECKS - NEW CONSTRUCTION REROOF (TEAR -OFF)
SYSTEM TYPE A-1: BONDED BONDED ROOF COVER
REFER . ..VAPOR OPTIONS
System
Deck
Base Insulation Layer Top Insulation Layer
MDP
Roof Cover (Note 16)
Type
Attach (Notes 6 & 7)
Type
Attach (Notes 6 & 7)
No.
(Note 1)
(psf)
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A,
Duro-Fleece or Duro-Fleece
C-33.
Min. 2,500 psi
H-Shield, Duro-Guard 150 II-H, ENRGY 3 or
Board -Max
Min. 0.25-inch SECUROCK Gypsum-
Board -Max
Plus / Duro-Fleece CR-20
-247.5
structural concrete
Fiber Roof Board
Duro-Guard ISO II-G
(splatter) or WB II
Duro-Fleece or Duro-Fleece
C-34.
Min. 2,500 psi
Min. 0.75-inch Duro-Guard EPS Type IX
Board -Max
Min. 0.25-inch SECUROCK Gypsum-
Board -Max
Plus / Duro-Fleece CR-20
-247.5
structural concrete
Fiber Roof Board
(splatter) or WB II
Min. 2,500 psi
Min. 0.25-inch SECUROCK Gypsum-
Duro-Fleece or Duro-Fleece
C-35.
Min. 0.75-inch Duro-Guard EPS Type IX
Board -Max
Board -Max
Plus / Duro-Fleece CR-20
-255.0
structural concrete
Fiber Roof Board
(splatter) or WB II
Min. 1.5-inch ACFoam 11, Duro-Guard ISO II -A,
Duro-Fleece or Duro-Fleece
C-36.
Min. 2,500 psi
H-Shield, Duro-Guard ISO II-H, ENRGY 3 or
CR-20
Min. 0.25-inch SECUROCK Gypsum-
CR-20
Plus / Duro-Fleece CR-20
-247.5
structural concrete
Fiber Roof Board
Duro-Guard ISO II-G
(splatter) or WB II
Min. 2,500 psi
Min. 0.75-inch Duro-Guard EPS Type II, VIII or
Min. 0.25-inch SECUROCK Gypsum-
Duro-Fleece or Duro-Fleece
C-37.
structural concrete
IX
CR-20
Fiber Roof Board
CR-20
Plus / Duro-Fleece CR-20
-247.5
(splatter) or WB II
Min. 2,500 psi
Min. 0.75-inch Duro-Guard EPS Type 11, VIII or
Min. 0.25-inch SECUROCK Gypsum-
Duro-Fleece or Duro-Fleece
C-38.
structural concrete
IX
CR-20
Fiber Roof Board
CR-20
Plus / Duro-Fleece CR-20
-255.0
(splatter) or WB II
C-39.
Min. 2,500 psi
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A
Insta-Stik
(Optional) Additional layers of base
Insta-Stik
Duro-Fleece or Duro-Fleece
-45.0
structural concrete
insulation
Plus / WB 11
Min. 1.5-inch ACFoam 11, Duro-Guard ISO II -A,
Duro-Fleece or Duro-Fleece
C-40.
Min. 2,500 psi
H-Shield, Duro-Guard ISO II-H, ENRGY 3 or
Insta-Stik
Min. 0.25-inch SECUROCK Gypsum-
Insta-Stik
Plus / Duro-Fleece CR-20
-247.5
structural concrete
Duro-Guard ISO 11-G
Fiber Roof Board
(splatter) or WB 11
C-41.
Min. 2,500 psi
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A
Hot asphalt
(Optional) Additional layers of base
Hot asphalt
Duro-Fleece or Duro-Fleece
-45.0
structural concrete
insulation
Plus / WB II
Min. 1.5-inch ACFoam 11, Duro-Guard ISO 11-A,
Duro-Fleece or Duro-Fleece
C 42.
Min. 2,500 psi
H-Shield, Duro-Guard ISO II-H, ENRGY 3 or
Hot asphalt
Min. 0.25-inch SECUROCK Gypsum-
Hot asphalt
Plus / Duro-Fleece CR-20
-247.5
structural concrete
Duro-Guard ISO 11-G
Fiber Roof Board
(splatter) or WB II
C-43.
Min. 2,500 psi
Min. 1.5-inch ACFoam 11, Duro-Guard ISO II -A
OlyBond 500
(Optional) Additional layers of base
OlyBond 500
Duro-Fleece or Duro-Fleece
-45.0
structural concrete
insulation
Plus / WB II
Min. 1.5-inch ACFoam 11, Duro-Guard ISO II -A,
Duro-Fleece or Duro-Fleece
C-44,
Min. 2,500 psi
H-Shield, Duro-Guard ISO 11-H, ENRGY 3 or
OlyBond 500
Min, 0.25-inch SECUROCK Gypsum-
OlyBond 500
Plus / Duro-Fleece CR-20
-247.5
structural concrete
Fiber Roof Board
Duro-Guard ISO II-G
(splatter) or WB II
Min. 2,psi
500 p
Min. 1.5-inch ACFoam 11, Duro-Guard ISO 11-A,
OlyBond Classic, full
Y
Min. 0.25-inch SECUROCK G ypsum-
OlyBond Classic, full
Duro-Fleece or Duro-Fleece
C-45.
structural concrete
H-Shield, Duro-Guard ISO II-H
coverage
Fiber Roof Board
coverage
plus /Duro-Fleece CR-20
-457.5
(splatter) or WB II
NEMO ETC, LLC Evaluation Report D9750.05.O8-R10 for F1.3559-1133
Certificate of Authorization N32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 23 of 44
ONEMOjetc.
TABLE 3A: STRUCTURAL CONCRETE DECKS - NEW CONSTRUCTION OR REROOF
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
REFER To NOTE 17 ..VAPORBARRIER OPTIONS
System
Deck
Base Insulation Layer Top Insulation Layer
MDP
No.
(Note 1)
Roof Cover (Note 16)
(psf)
Type
Attach (Notes 6 & 7)
Type
Attach (Notes 6 & 7)
Min. 2,500 psi
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A,
Trufast Roofing
Min. 0.5-inch Duro-Guard I50 HD -A or
Trufast Roofing
Duro-Fleece or Duro-Fleece
C-46.
structural concrete
ENRGY 3 CGF, Duro-Guard 150 III-G, H-Shield
Adhesive
Duro-Guard ISO HD-H
Adhesive
Plus /Trufast Roofing
-165.0
CG, Duro-Guard ISO III-H
Adhesive, ribbons 4" o.c.
Min. 0.25-inch Dens Deck, Dens Deck
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A,
Prime, DEXcell FA Glass Mat Roof
Duro-Fleece or Duro-Fleece
C 47.
Min. 2,500 psi
ENRGY 3 CGF, Duro-Guard ISO III-G, H-Shield
Trufast Roofing
Board, SECUROCK Gypsum -Fiber Roof
Trufast Roofing
Plus / Trufast Roofing
195.0
structural concrete
CG, Duro-Guard ISO III-H
Adhesive
Board or SECUROCK Glass -Mat Roof
Adhesive
Adhesive, ribbons 4" o.c.
Board or min. 7/16" DEXcell Cement
Roof Board
Min. 2,500 psi
Min. 1.5-inch ACFoam 11, Duro-Guard ISO II -A,
Trufast Roofing
(Optional) Additional layers of base
Trufast Roofing
Duro-Fleece or Duro-Fleece
C-48.
structural concrete
ENRGY 3 CGF, Duro-Guard 150 III-G, H-Shield
Adhesive
insulation
Adhesive
Plus /Trufast Roofing
-345.0
CG, Duro-Guard ISO 111-H
IAdhesive,
ribbons 4" o.c.
NEMO ETC, LLC
Certificate of Authorization #32455
©2019 NEMO ETC, LLC
6T" EDITION (2017) FBC NON-HVHZ EVALUATION
Duro-Last Single Ply Roof Systems; (800) 248-0280
Evaluation Report D9750.05.08-R10 for FL1559-1113
Revision 10: 10/17/2019
Appendix 1, Page 24 of 44
ONEM01letc.
TABLE 3B: STRUCTURAL CONCRETE DECKS - NEW CONSTRUCTION, • .. .. RECOVER
PLATE-BONDEDSYSTEM TYPE C-2: MECHANICALLY ATTACHED INSULATION, ROOF COVER
System Deck Insulation Layer Attach MDP
Roof Cover /Attach
No. (Note 1) (Note 14) Fasteners Density (psf)
RHINOBOND
INDUCTION WELD:
Min. 2,500 psi
One or more layers, any
Duro-Last #14 HD with RHINOBOND
1 per 2.67 ft'
Duro-Last (min. 40-mil), Duro-Tuff (min. 50-mil) or Duro-Last EV
C-49.
structural concrete
combination
Insulation Plate (PVC)
(12 parts per 4 x 8 ft board)
(min. 50-mil) induction welded to RHINOBOND Insulation Plate
-52.5
(PVC) using RHINOBOND Installation Tool
Min. 2,500 psi
One or more layers, any
Duro-Last #14 HD with RHINOBOND
12-inch o.c. in rows spaced
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-Tuff
C-50.
structural concrete
combination, preliminarily
Insulation Plate (PVC)
60-inch o.c.
(min. 80-mil) induction welded to RHINOBOND Insulation Plate
-37.5
attached (Note 5)
(PVC) using RHINOBOND Installation Tool
Min. 2,500 psi
One or more layers, any
Duro-Last #14 HD with RHINOBOND
12-inch o.c. in rows spaced
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-Tuff
C-51.
structural concrete
combination, preliminarily
Insulation Plate (PVC)
48-inch o.c.
(min. 80-mil) induction welded to RHINOBOND Insulation Plate
-37.5
attached (Nate 5)
(PVC) using RHINOBOND Installation Tool
Min. ,
500 psi 2
One or more layers, any
Duro-Last #14 HD with RHINOBOND
6-inch o..
in rows spaced c
Duro-Last (min. 40-mil), Duro-Tuff (min. 50-mil) or Duro-Last EV
C-52.
structural concrete
combination, preliminarilyNote
Insulation Plate (PVC)
..
60-inch oc
(min. 50-mil) induction welded to RHINOBOND Insulation Plate
-45.0
attached 5
( )
(PVC) using RHINOBOND Installation Tool
Min. 2,500 psi
One or more layers, any
Duro-Last #14 HD with RHINOBOND
6-inch o.c. in rows spaced
Duro-Last (min. 40-mil), Duro-Tuff (min. 50-mil) or Duro-Last EV
C-53.
structural concrete
combination, preliminarily
Insulation Plate (PVC)
48-inch o.c.
(min. 50-mil) induction welded to RHINOBOND Insulation Plate
-52.5
attached (Note 5)
(PVC) using RHINOBOND Installation Tool
ISOWELD INDUCTION WELD:
Min. psi
One or more layers, any
SFS Intec Dekfast DF-#14-PH3 or DF-
z
6 ft per fastener
Duro-Last (min. 40 mil), Duro-Last EV (min. 50 mil) or Duro-Tuff
C-54.
U
structural concrete
structural
combination, min. 1.5-inch
#15-PH3 with isoweld° Fl-P-6.8-PVC
2 x 3-ft grid, staggered
(min. 50 mil) induction welded to SFS isoweld° F3-P-6.8-PVC
-37.5
Plates
Plates with SFS isoweld® 3000 stand-up tool
Min. psi
One or more layers, any
SFS Intec Dekfast DF-#14-PH3 or DF-
z
4 ft per fastener
Duro-Last (min. 40 mil), Duro-Last EV (min. 50 mil) or Duro-Tuff
C-55.
structural
structural concrete
u
combination, min. 1.5-inch
#15-PH3 with isoweld° F1-P-6.8-PVC
2 x 2-ft grid, staggered
(min. 50 mil) induction welded to SFS isoweld° Fl-P-6.8-PVC
-52.5
Plates
Plates with SFS isoweld° 3000 stand-up tool
Min. psi
One or more layers, any
SFS Intec Dekfast DF-#14-PH3 or DF-
3 per fastener
Duro-Last (min. 40 mil), Duro-Last EV (min. 50 mil) or Duro-Tuff
C-56.
u
structural concrete
structural
combination, min. 1.5-inch
#15-PH3 with isoweld° Fl-P-6.8-PVC
-
1.5 x 22-ft grid, staggered
(min. 50 mil) induction welded to SFS isoweld° F1-P-6.8-PVC
-82.5
Plates
Plates with SFS isoweld° 3000 stand-up tool
Min. 2,500 psi
One or more layers, any
SFS Intec Dekfast DF-#14-PH3 or DF
12-inch o.c. in rows spaced
p
Duro-Last (min. 40 mil), Duro-Last EV (min. 50 mil) or Duro-Tuff
C-57.
structural concrete
combination, min. 1.5-inch,
#15-PH3 with isoweld° Fl-P-6.8-PVC
60-inch o.c.
(min. 50 mil) induction welded to SFS isoweld° F1-P-6.8-PVC
-45.0
preliminarily attached (Note 5)
Plates
Plates with SFS isoweld® 3000 stand-up tool
Min. 2,500 psi
One or more layers, any
SF5 Intec Dekfast DF-#14-PH3 or DF
6-inch o.c. in rows spaced
Duro-Last (min. 40 mil) induction welded to SFS isoweld° F1-P-
C-58.
structural concrete
combination, min. 1.5-inch,
#15-PH3 with isoweld° F1-P-6.8-PVC
60-inch o.c.
6.8-PVC Plates with SFS isoweld° 3000 stand-up tool
_g0.0
preliminarily attached (Note 5)
Plates
TRUFAST INDUCTION WELD:_ -
Min. 2,500 psi
One or more layers, any
Trufast #14 HD or Trufast Fluted
1 per 5.33 ft'
Duro-Last (min. 40 mil), Duro-Last EV (min. 50 mil) or Duro-Tuff
C-59.
structural concrete
combination, min. 2-inch
Concrete Nail with Trufast PVC IW
(6 parts per 4x8 ft board on
(min. 50 mil) induction welded to Trufast PVC IW Plates with
-45.0*
Plate
a 2436-inch pattern)
Trufast Induction Welding Tool and Magnets
NEMO ETC, LLC Evaluation Report D9750.05.08-R10 for FL3559-Ri3
Certificate of Authorization #32455 6" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 25 of 44
NNEMO I etc.
TABLE 3B: STRUCTURAL
CONCRETE DECKS - NEW CONSTRUCTION, .. .. RECOVER
SYSTEM
TYPE C-2: MECHANICALLY ATTACHED INSULATION, PLATE -BONDED ROOF COVER
System
Deck
Insulation Layer
Attach
Roof Cover /Attach
MDP
No.
(Note 1)
(Note 14)
Fasteners Density
(psf)
Trufast #14 HD or Trufast Fluted
1 per 4 ft'
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
C-60.
Min. 2,500 psi
One or more layers, any
Concrete Nail with Trufast PVC IW
(8 parts per 4x8 ft board on
welded to Trufast PVC IW Plates with Trufast Induction Welding
-52.5
structural concrete
combination, min. 2-inch
Plate
a 24x24-inch pattern)
Tool and Magnets
Trufast #14 HD or Trufast Fluted
1 per 4 ftZ
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-Tuff
C-61.
Min. 2,500 psi
One or more layers, any
Concrete Nail with Trufast PVC IW
(8 parts per 4x8 ft board on
(min. 60 mil) induction welded to Trufast PVC IW Plates with
-60.0
structural concrete
combination, min. 2-inch
Plate
a 24x24-inch pattern)
Trufast Induction Welding Tool and Magnets
Trufast #14 HD or Trufast Fluted
1 per 3.2 ft'
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
C-62.
Min. 2,500 psi
One or more layers, any
Concrete Nail with Trufast PVC IW
(10 parts per 48 ft board
welded to Trufast PVC IW Plates with Trufast Induction Welding
-60.0
structural concrete
combination, min. 2-inch
Plate
on a 2420-inch pattern)
Tool and Magnets
Trufast #14 HD or Trufast Fluted
1 per 3.2 ft'
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-Tuff
C-63.
Min. 2,500 psi
One or more layers, any
Concrete Nail with Trufast PVC IW
(10 parts per 48 ft board
(min. 60 mil) induction welded to Trufast PVC IW Plates with
-67.5
structural concrete
combination, min. 2-inch
Plate
on a 24x20-inch pattern)
Trufast Induction Welding Tool and Magnets
Trufast #14 HD or Trufast Fluted
1 per 2.7 ftZ
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
C-64.
Min. 2,500 psi
One or more layers, any
Concrete Nail with Trufast PVC IW
(12 parts per 4x8 ft board
welded to Trufast PVC IW Plates with Trufast Induction Welding
-67.5
structural concrete
combination, min. 2-inch
Plate
per FM LPDS 1-29)
Tool and Magnets
Trufast #14 HD or Trufast Fluted
1 per 2.7 ftZ
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-Tuff
C-65.
Min. 2,500 psi
One or more layers, any
Concrete Nail with Trufast PVC IW
(12 parts per 4x8 ft board
(min. 60 mil) induction welded to Trufast PVC IW Plates with
-82.5
structural concrete
combination, min. 2-inch
Plate
per FM LPDS 1-29)
Trufast Induction Welding Tool and Magnets
Trufast #14 HD or Trufast Fluted
1 per 2 ft'
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
C-66.
Min. 2,500 psi
One or more layers, any
Concrete Nail with Trufast PVC IW
(16 parts per 4x8 ft board
welded to Trufast PVC IW Plates with Trufast Induction Welding
-90.0
structural concrete
combination, min. 2-inch
Plate
on a 12x24-inch pattern)
Tool and Magnets
Trufast #14 HD or Trufast Fluted
1 per 2 ftZ
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-Tuff
C-67.
Min. 2,500 psi
One or more layers, any
Concrete Nail with Trufast PVC IW
(16 parts per 48 ft board
(min. 60 mil) induction welded to Trufast PVC IW Plates with
-112.5
structural concrete
combination, min. 2-inch
Plate
on a 12x24-inch pattern)
Trufast Induction Welding Tool and Magnets
Min. 2,500 psi
One or more layers, any
Trufast #14 HD or Trufast Fluted
1 per 1.8 ftZ
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
C-68.
structural concrete
combination, min. 2-inch
Concrete Nail with Trufast PVC IW
(18 parts per 48 ft board
welded to Trufast PVC IW Plates with Trufast Induction Welding
-105.0
Plate
on an 18x16-inch pattern)
Tool and Magnets
Trufast #14 HD or Trufast Fluted
1 per 1.8 ft'
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-Tuff
C-69.
Min. 2,500 psi
One or more layers, any
Concrete Nail with Trufast PVC IW
(18 parts per 4x8 ft board
(min. 60 mil) induction welded to Trufast PVC IW Plates with
-120.0
structural concrete
combination, min. 2-inch
Plate
on an 18x16-inch pattern)
Trufast Induction Welding Tool and Magnets
Min. 2,500 psi
One or more layers, any
Trufast #14 HD or Trufast Fluted
1 per 1.3 ftZ
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
C-70.
structural concrete
combination, min. 2-inch
Concrete Nail with Trufast PVC IW
(24 parts per 4x8 ft board
welded to Trufast PVC IW Plates with Trufast Induction Welding
-135.0
Plate
on a 12x16-inch pattern)
Tool and Magnets
Min. 2,500 psi
One or more layers, any
Trufast #14 HD or Trufast Fluted
1 per 1.3 ftZ
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-Tuff
C-71.
structural concrete
combination, min. 2-inch
Concrete Nail with Trufast PVC IW
(24 parts per 48 ft board
(min. 60 mil) induction welded to Trufast PVC IW Plates with
-172.5
Plate
on a 12x16-inch pattern)
I Trufast Induction Welding Tool and Magnets
NEMO ETC, LLC Evaluation Report D9750.05.08-R10 for FL3559-1113
_Certificate of Authorization #32455 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 26 of 44
ONEMOjetc.
TABLE 3B: STRUCTURAL
CONCRETE DECKS - NEW CONSTRUCTION, • .. .. RECOVER
PLATE-BONDEDSYSTEM TYPE C-2: MECHANICALLY ATTACHED INSULATION, ROOF COVER
System
Deck
Insulation Layer
Attach
Roof Cover /Attach
MDP
Fasteners
Density
No.
(Note 1)
(Note 14)
(Psf)
Trufast #14 HD or Trufast Fluted
1 per 1 ft2
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
C 72.
Min. 2,500 psi
One or more layers, any
Concrete Nail with Trufast PVC IW
(32 parts per 4x8 ft board
welded to Trufast PVC IW Plates with Trufast Induction Welding
-142.5
structural concrete
combination, min. 2-inch
Plate
per FM LPDS 1-29)
Tool and Magnets
Trufast #14 HD or Trufast Fluted
1 per 1 ft'
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-Tuff
C-73.
Min. psi
One or more layers, any
Concrete Nail with Trufast PVC IW
(32 parts per 4x8 ft board
(min. 60 mil) induction welded to Trufast PVC IW Plates with
-217.5
u
structural ral concrete
combination, min. 2-inch
Plate
per FM LPDS 1-29)
Trufast Induction Welding Tool and Magnets
Min. 2,500 psi
One or more layers, any
Trufast #14 HD or Trufast Fluted
12-inch o.c. in rows spaced
Duro-Last (min. 40 mil), Duro-Last EV (min. 50 mil) or Duro-Tuff
C-74.
structural concrete
combination, min. 2-inch,
Concrete Nail with Trufast PVC IW
60-inch o.c.
(min. 50 mil) induction welded to Trufast PVC IW Plates with
-45.0
preliminarily attached
Plate
Trufast Induction Welding Tool and Magnets
Min. 2,500 psi
One or more layers, any
Trufast #14 HD or Trufast Fluted
12-inch o.c. in rows spaced
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
C-75.
structural concrete
combination, min. 2-inch,
Concrete Nail with Trufast PVC IW
48-inch o.c.
welded to Trufast PVC IW Plates with Trufast Induction Welding
-52.5
preliminarily attached
Plate
Tool and Magnets
Min. ,
500 psi 2
One or more layers, any
Trufast #14 HD or Trufast Fluted
12-inch o..
in rows spaced c
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-Tuff
C-76.
structural concrete
combination, min. 2-inch,
Concrete Nail with Trufast PVC IW
48-inch o.c.
(min. 60 mil) induction welded to Trufast PVC IW Plates with
-60.0
preliminarily attached
Plate
Trufast Induction Welding Tool and Magnets
Min. 2,500 psi
One or more layers, any
Trufast #14 HD or Trufast Fluted
12-inch o.c. in rows spaced
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
C 77
structural concrete
combination, min. 2-inch
Concrete Nail with Trufast PVC IW
36-inch o.c.
welded to Trufast PVC IW Plates with Trufast Induction Welding
60.0
Plate
Tool and Magnets
Min. 2,500 psi
One or more layers, any
Trufast #14 HD or Trufast Fluted
12-inch o.c. in rows spaced
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-Tuff
C 78.
structural concrete
combination, min. 2-inch
Concrete Nail with Trufast PVC IW
36-inch o.c.
(min. 60 mil) induction welded to Trufast PVC IW Plates with
-82.5
Plate
Trufast Induction Welding Tool and Magnets
Min. 2,500 psi
One or more layers, any
Trufast #14 HD or Trufast Fluted
6-inch o.c. in rows spaced
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
C-79.
structural concrete
combination, min. 2-inch,
Concrete Nail with Trufast PVC IW
72-inch o.c.
welded to Trufast PVC IW Plates with Trufast Induction Welding
-67.5
preliminarily attached
Plate
Tool and Magnets
Min. 2,500 psi
One or more layers, any
Trufast #14 HD or Trufast Fluted
6-inch o..
in rows spaced c
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-Tuff
C-80.
structural concrete
combination, min. 2-inch,
Concrete Nail with Trufast PVC IW
72-inch o.c.
(min. 60 mil) induction welded to Trufast PVC IW Plates with
-75.0
preliminarily attached
Plate
Trufast Induction Welding Tool and Magnets
Min. 2,500 psi
One or more layers, any
Trufast #14 HD or Trufast Fluted
6-inch o..
in rows spaced c
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
C-81.
structural concrete
combination, min. 2-inch,
Concrete Nail with Trufast PVC IW
60-inch o.c.
welded to Trufast PVC IW Plates with Trufast Induction Welding
-75.0
preliminarily attached
Plate
Tool and Magnets
One or more layers, any
Trufast #14 HD or Trufast Fluted
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-Tuff
C-82.
Min. 2,500 psi
combination, min. 2-inch,
Concrete Nail with Trufast PVC IW
6-inch o..
in rows spaced c
(min. 60 mil) induction welded to Trufast PVC IW Plates with
-90.0
structural concrete
preliminarily attached
Plate
60-inch o.c.
Trufast Induction Welding Tool and Magnets
Min. 2,500 psi
One or more layers, any
Trufast #14 HD or Trufast Fluted
6-inch o.c. in rows spaced
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
C-83.
structural concrete
combination, min. 2-inch,
Concrete Nail with Trufast PVC IW
48-inch o.c.
welded to Trufast PVC IW Plates with Trufast Induction Welding
-90.0
preliminarily attached
Plate
Tool and Magnets
NEMO ETC, LLC Evaluation Report D9750.05.08-1310 for FL1559-R13
Certificate of Authorization #32455 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 27 of 44
NNEMOjetc.
TABLE 313: STRUCTURAL
CONCRETE DECKS - NEW CONSTRUCTION, .. OR •
PLATE-BONDEDSYSTEM TYPE C-2: MECHANICALLY ATTACHED INSULATION, ROOF COVER
System
Deck
Insulation Layer
Attach
Roof Cover /Attach
MDP
No.
(Note 1)
(Note 14)
Fasteners Density
(psf)
Min. 2,500 psi
One or more layers, any
Trufast #14 HD or Trufast Fluted
6-inch o.c. in rows spaced
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-Tuff
C-84.
structural concrete
combination, min. 2-inch,
Concrete Nail with Trufast PVC IW
48-inch o.c.
(min. 60 mil) induction welded to Trufast PVC IW Plates with
-112.5
preliminarily attached
Plate
Trufast Induction Welding Tool and Magnets
Min. 2,500 psi
One or more layers, any
Trufast #14 HD or Trufast Fluted
6-inch o.c. in rows spaced
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil) induction
C-85.
structural concrete
combination, min. 2-inch
Concrete Nail with Trufast PVC IW
36-inch o.c.
welded to Trufast PVC IW Plates with Trufast Induction Welding
-112.5
Plate
Tool and Magnets
Min. 2,500 psi
One or more layers, any
Trufast #14 HD or Trufast Fluted
6-inch o.c. in rows spaced
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil) or Duro-Tuff
C 86.
structural concrete
combination, min. 2-inch
Concrete Nail with Trufast PVC IW
36-inch o.c.
(min. 60 mil) induction welded to Trufast PVC IW Plates with
-150.0
Plate
Trufast Induction Welding Tool and Magnets
TABLE 3C: STRUCTURAL CONCRETE DECKS - NEW CONSTRUCTION, REROOF (TEAR -OFF) OR RECOVER
SYSTEM TYPE • • INSULATION,i ROOF COVER
Insulation (Note 14)
Roof Cover
System Deck
Membrane
Fasteners
MDP
Attach (psf)
Attach
No. (Note 1) Type
(Note 5)
STANDARD LAP SYSTEMS:
Min. 2,500 psi
(Optional) One or more
Prelim.
Duro-Last, min. 40
Duro-Last #14 HD Fasteners with
Standard Lap System fastened 9-inch o.c. within 3-inch wide
C 87.
structural concrete
layers, any combination
attached
mil
Duro-Last Cleat Plates
tabs spaced 60-inch o.c.
-37.5
Min. 2,500 psi
(Optional) One or more
Prelim.
Duro-Last, min. 40
Duro-Last Concrete Screws #14 or
Standard Lap System fastened 6-inch o.c. within 3-inch wide
C 88
Duro-Last Concrete Nails with Duro-
-60.0
structural concrete
layers, any combination
attached
mil
tabs spaced 84-inch o.c.
Last 2.4-inch Barbed Metal Plates
DURO-ROOF LAP SYSTEMS:
Min. 2,500 psi
(Optional) One or more
Prelim.
Duro-Last, min. 60
Duro-Last #14 HD Fasteners with
Duro-Roof Lap System fastened 6-inch o.c. within 6-inch wide
C 89.
structural concrete
layers, any combination
attached
mil
Duro-Last Cleat Plates
tabs spaced 120-inch o.c. Tab Sealer 4725 at max. 60 ft2/gal.
37.5
Min. 2,500 psi
(Optional) One or more
Prelim.
Duro-Last, min. 40
Duro-Last Concrete Screws #14 or
Duro-Roof Lap System fastened 12-inch o.c. within 6-inch wide
C-90.
Duro-Last Concrete Nails with Duro-
-52.5
structural concrete
layers, any combination
attached
mil
tabs spaced 57-inch o.c. Tab Sealer 4725 at max. 60 ft2/gal.
Last --inch Metal Plates
Min. 2,500 psi
(Optional) One or more
Prelim.
Duro-Last, min. 40
Duro-Last Concrete Screws #14 or
Duro-Roof Lap System fastened 6-inch o.c. within 3-inch wide
C-91.
Duro-Last Concrete Nails with Duro-
-67.5
structural concrete
layers, any combination
attached
mil
tabs spaced 60-inch o.c. Tab Sealer 4725 at max. 60 ft2/gal.
Last Batten Bar
Min. 2,500 psi
(Optional) One or more
Prelim.
Duro-Last, min. 40
Duro-Last Concrete Screws #14 or
Duro-Roof Lap System fastened 6-inch o.c. within 6-inch wide
C 92
Duro-Last Concrete Nails with Duro-
82 5
structural concrete
layers, any combination
attached
mil,
tabs spaced 120-inch o.c. Tab Sealer 4725 at max. 60 ft2/gal.
Last --inch Metal Plates
Min. 2,500 psi
(Optional) One or more
Prelim.
Duro-Last, min. 40
Duro-Last Concrete Screws #14 or
Duro-Roof Lap System fastened 6-inch o.c. within 6-inch-wide
C 93
structural concrete
layers, any combination
attached
mil
Duro-Last Concrete Nails with OMG 2-
tabs spaced 25-inch o.c. Tab Sealer 4725 at max. 60 ft2/gal.
-142.5
3/8" Eyehook Plates
NEMO ETC, LLC
Certificate of Authorization #32455
©2019 NEMO ETC, LLC
6TM EDITION (2017) FBC NON-HVHZ EVALUATION
Duro-Last Single Ply Roof Systems; (800) 248-0280
Evaluation Report D9750.05.08-1110 for FL1559-1113
Revision 10: 10/17/2019
Appendix 1, Page 28 of 44
ONEMOjetc.
System No.
Deck (Note 1)
Primer
TABLE 3D: STRUCTURAL CONCRETE DECKS -
SYSTEM TYPE F:
Vapor Barrier
NEW CONSTRUCTION .. REROOF
.:... ROOF COVER
Roof Cover (Note 16)
MDP (psf)
C-94.
Structural concrete
None
Duro-Last Vapor Barrier, self -adhering
Duro-Fleece or Duro-Fleece Plus / Duro-Fleece CR-20 (splatter applied)
-502.5
C-95.
Structural concrete
ASTM D41
Duro-Last Torch Down Vapor Barrier, torch -applied
Duro-Fleece or Duro-Fleece Plus / Duro-Fleece CR-20 (splatter applied)
-502.5
C-96.
Structural concrete
None
None
Duro-Fleece or Duro-Fleece Plus / Duro-Fleece WB II Adhesive
-673.0
C-97.
Structural concrete
None
None
Duro-Fleece or Duro-Fleece Plus / Duro-Fleece CR-20 (splatter applied)
-1,025.0
NEMO ETC, LLC Evaluation Report D9750.05.08-R10 for FL3559-1113
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 29 of 44
OMEMO I etc.
TABLE 4A: LIGHTWEIGHT CONCRETE OVER STEEL DECKS - NEW CONSTRUCTION OR REROOF
SYSTEM TYPE A- BONDED INSULATION, BONDED ROOF COVER
Base Insulation Layer Coverboard
System Deck (Note 1) LWC (Note 15) Attach Attach Roof Cover �PD
Type Type
(Notes 6 & 7) (Notes 6 & 7)
PRE-EXISTENT CELLULAR LWC:
BAREBACK MEMBRANE APPLICATIONS:
Min. 22 ga., type
Min. 200 psi, min. 2-inch thick cellular
(Optional) Min. 1.5-inch ACFoam
Ashland
Min. 0.25-inch Dens
Ashland
LWC-1.
BV steel
lightweight insulating concrete
11, Duro-Guard ISO 11-A
Pliodeck
Deck
Pliodeck
Duro-Last / WB 1
-37.5
Min. 22 ga., type
Min. 200 psi, min. 2-inch thick cellular
Min. 1.5-inch ACFoam 11, Duro-
Ashland
(Optional) Additional
Ashland
LWC-2.
BV steel
lightweight insulating concrete
Guard ISO II -A
Pliodeck
layers of base insulation
Pliodeck
Duro-Last / SB I or WB II
-45.0
LWC-3.
Min. 22 ga., type
Min. 200 psi, min. 2-inch thick cellular
Min. 1.5-inch ACFoam 11, Duro-
Ashland
(Optional) Additional
Ashland
Duro-Last, Duro-Last EV or
BV steel
lightweight insulating concrete
Guard ISO 11-A
Pliodeck
layers of base insulation
Pliodeck
Duro-Tuff/ 5B IV or WB II
45.0
Min. 22 ga., type
Min. 200 psi, min. 2-inch thick cellular
(Optional) Min. 1.5-inch ACFoam
Min. 0.25-inch Dens
LWC-4.
BV steel
lightweight insulating concrete
11, Duro-Guard ISO II -A
CR-20
Deck
CR-20
Duro-Last / WB 1
-37.5
Min. 22 ga., type
Min. 200 psi, min. 2-inch thick cellular
Min. 1.5-inch ACFoam 11, Duro-
(Optional) Additional
LWC-5.
BV steel
lightweight insulating concrete
Guard ISO II -A
CR-20
layers of base insulation
CR-20
Duro-Last / SB I or WB 11
-45.0
LWC-6.
Min. 22 ga., type
Min. 200 psi, min. 2-inch thick cellular
Min. 1.5-inch ACFoam II, Duro-
(Optional) Additional
Duro-Last, Duro-Last EV or
BV steel
lightweight insulating concrete
Guard 150 II -A
CR-20
layers of base insulation
CR-20
Duro-Tuff/ SB IV or WB II
45.0
DURo-FLEECE AND DURO-FLEECE PLUS MEMBRANE APPLICATIONS:
LWC-7.
Min. 22 ga., type
Min. 200 psi, min. 2-inch thick cellular
Min. 1.5-inch ACFoam 11, Duro-
Ashland
(Optional) Additional
Ashland
Duro-Fleece or Duro-
BV steel
lightweight insulating concrete
Guard ISO II -A
Pliodeck
layers of base insulation
Pliodeck
Fleece Plus / WB II
45.0
Min. 22 ga., type
Min. 200 psi, min. 2-inch thick cellular
Min. 1.5-inch ACFoam 11, Duro-
(Optional) Additional
Duro-Fleece or Duro-
LWC-8.
BV steel
lightweight insulating concrete
Guard ISO II -A
CR-20
layers of base insulation
CR-20
Fleece Plus / WB II
-45.0
TABLE 4B: LIGHTWEIGHT
CONCRETE OVER STRUCTURAL CONCRETE
DECKS - NEW
CONSTRUCTION OR REROOF
(TEAR -OFF)
SYSTEM TYPE A: BONDED INSULATION,
BONDED ROOF COVER
Base Insulation layer
Coverboard
System
Deck
LWC (Note 15)
Attach
Attach Roof Cover
MDP
No.
(Note 1)
Type
Type
(psf)
(Notes 6 & 7)
(Notes 6 & 7)
PRE-EXISTENT CELLULAR LWC:
BAREBACK MEMBRANE APPLICATIONS:
Min. 200 psi, min. 2-inch thick
Structural
(Optional) Min. 1.5-inch ACFoam 11, Duro-
Ashland
Ashland
LWC-9.
concrete
cellular lightweight insulating
Guard ISO II -A
Pliodeck
Min. 0.25-inch Dens Deck
Pliodeck
Duro-Last / WB 1
-37.5
concrete
Min. 200 psi, min. 2-inch thick
Structural
Ashland
(Optional) Additional
Ashland
LWC-10.
cellular lightweight insulating
Min. 1.5-inch ACFoam 11, Duro-Guard ISO II -A
Duro-Last / SB I or WB-11
-45.0
concrete
Pliodeck
layers of base insulation
Pliodeck
concrete
NEMO ETC, LLC
Certificate of Authorization #32455
©2019 NEMO ETC, LLC
6T" EDITION (2017) FBC NON-HVHZ EVALUATION
Duro-Last Single Ply Roof Systems; (800) I48-0280
Evaluation Report D9750.05.08-1110 for FL3559-R13
Revision 10: 10/17/2019
Appendix 1, Page 30 of 44
System
Deck
LWC (Note 15)
No.
(Note 1)
Min. 200 psi, min. 2-inch thick
Structural
LWC-11.
cellular lightweight insulating
concrete
concrete
Min. 200 psi, min. 2-inch thick
Structural
LWC-12.
cellular lightweight insulating
concrete
concrete
Structural
Min. 200 psi, min. 2-inch thick
LWC-13.
cellular lightweight insulating
concrete
concrete
Min. 200 psi, min. 2-inch thick
Structural
LWC-14.
cellular lightweight insulating
concrete
concrete
DURO-FLEECE AND DURO-FLEECE PLUS MEMBRANE APPLICATIONS:
Min. 200 psi, min. 2-inch thick
Structural
LWC-15.
cellular lightweight insulating
concrete
concrete
Structural
Min. 200 psi, min. 2-inch thick
LWC-16.
cellular lightweight insulating
concrete
concrete
CELCORE(FL2D37):
BAREBACK MEMBRANE APPLICATIONS:
Structural
Min. 200 psi, min. 2-inch thick
LWC-17.
concrete
Celcore Cellular Concrete
Structural
Min. 200 psi, min. 2-inch thick
LWC-18.
concrete
Celcore Cellular Concrete
DURO-FLEECE AND DURO-FLEECE PLUS MEMBRANE APPLICATIONS:
Structural
Min. 200 psi, min. 2-inch thick
LWC-19.
concrete
Celcore Cellular Concrete
ELASTIZELL (FL4994):
BAREBACK MEMBRANE APPLICATIONS:
Structural
Min. 200 psi, min. 2-inch thick
LWC-20.
I
concrete
Elastizell.
Base Insulation Layer Coverboard
Attach Attach
Type (Notes 6 & 7) Type (Notes 6 &
Min. 1.5-inch ACFoam II, Duro-Guard 150 II -A Ashland (Optional) Additional Ashland
Pliodeck layers of base insulation Pliodeck
(Optional) Min. 1.5-inch ACFoam II, Duro-
Guard ISO II -A
CR-20
Min. 0.25-inch Dens Deck
CR-20
(Optional) Additional
Min. 1.5-inch ACFoam II, Duro-Guard 150 II -A
CR-20
CR-20
layers of base insulation
(Optional) Additional
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A
CR-20
CR-20
layers of base insulation
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A Ashland
Pliodeck
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A I CR-20
Min. 1.5-inch ACFoam II, Duro-Guard 150 II -A I CR-20
Min. 1.5-inch ACFoam II, Duro-Guard 150 II -A,
H-Shield, Duro-Guard ISO II-H, ENRGY 3 or CR-20
Duro-Guard ISO II-G
Min. 1.5-inch ACFoam 11, Duro-Guard 150 II -A,
H-Shield, Duro-Guard ISO 11-H, ENRGY 3 or CR-20
Duro-Guard ISO II-G
(Optional) Additional Ashland
layers of base insulation I Pliodeck
(Optional) Additional
layers of base insulation CR-20
(Optional) Additional CR-20
layers of base insulation
Min. 0.25-inch
SECUROCK Gypsum -Fiber CR-20
Roof Board
Min. 0.25-inch
SECUROCK Gypsum -Fiber CR-20
Roof Board
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A I Ashland I (Optional) Additional Ashland
Pliodeck layers of base insulation I Pliodeck
ONEMOletc,
Roof Cover I MDP
(psf)
Duro-Last, Duro-Last EV or
Duro-Tuff / 5B IV or WB II 45.0
Duro-Last / WB 1 1 -37.5
Duro-Last / SB I or WB II 1 -45.0
Duro-Last, Duro-Last EV or
45.0
Duro-Tuff / SB IV or WB II
Duro-Fleece or Duro-
Fleece Plus / WB II 45.0
Duro-Fleece or Duro-
Fleece Plus / Duro-Fleece -45.0
CR-20 (splatter) or WB II
Duro-Last / WB 1 -82.5
Duro-Last, Duro-Last EV or -222 5
Duro-Tuff / SB IV or WB II
Duro-Fleece or Duro-
Fleece Plus / Duro-Fleece 222.5
CR-20 (splatter) or WB II
Duro-Last / WB 1 I -82.5
NEMO ETC, LLC Evaluation Report D9750.05.08-R10 for FL3559-1113
Certificate of Authorization #32455 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 31 of 44
NNEMOjetc.
4B: LIGHTWEIGHT
CONCRETETABLE OVER • rECKS - NEW
CONSTRUCTION OR REROOF (TEAR -OFF)
SYSTEM TYPE A: BONDED INSULATION,BONDED
ROOF COVER
Base Insulation layer
Coverboard
System Deck
LWC (Note 15)
Roof Cover
MDP
Attach
Attach
No. (Note 1)
Type
Type
(psf)
(Notes 6 & 7)
(Notes 6 & 7)
Structural
Min. 200 psi, min. 2-inch thick
Ashland
Min. 0.25-inch
Ashland
Duro-Last, Duro-Last EV or
LWC-21.
Min. 2-inch ISO 95+ GL
SECUROCK Gypsum -Fiber
-105.0
concrete
Elastizell.
Pliodeck
Pliodeck
Duro-Tuff / SB IV or WB II
Roof Board
Ashland
Min. 0.25-inch
Ashland
Structural
Min. 200 psi, min. 2-inch thick
Duro-Last, Duro-Last EV or
LWC-22.
Min. 2-inch ISO 95+ GL
Pliodeck, 6-
SECUROCK Gypsum -Fiber
Pliodeck, 6-inch
-187.5
concrete
Elastizell.
Duro-Tuff / SB IV or WB II
inch o.c.
Roof Board
O.C.
Structural
Min. 200 psi, min. 2-inch thick
(Optional) Additional
LWC-23.
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A
CR-20
CR-20
Duro-Last / WB 1
-82.5
concrete
Elastizell
layers of base insulation
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A,
Min. 0.25-inch
LWC-24.
Structural
Min. 200 psi, min. 2-inch thick
H-Shield, Duro-Guard ISO II-H, ENRGY 3 or
CR-20
SECUROCK Gypsum -Fiber
CR-20
Duro-Last, Duro-Last EV or
-180.0
concrete
Elastizell
Duro-Tuff/ SB IV or WB II
Duro-Guard ISO II-G
Roof Board
DURO-FLEECE AND DURo-FLEECE PLUS MEMBRANE APPLICATIONS:
Structural
Min. 200 psi, min. 2-inch thick
Ashland
Min. 0.25-inch
Ashland
Duro-Fleece or Duro-
LWC-25.
Min. 2-inch ISO 95+ GL
SECUROCK Gypsum -Fiber
Fleece Plus / Duro-Fleece
-105.0
concrete
Elastizell.
Pliodeck
Roof Board
Pliodeck
CR-20 (splatter) or WB II
Structural
Min. 200 psi, min. 2-inch thick
Ashland
Min. 0.25-inch
Ashland
Duro-Fleece or Duro-
LWC-26.
Min. 2-inch ISO 95+ GL
Pliodeck, 6-
SECUROCK Gypsum -Fiber
Pliodeck, 6-inch
Fleece Plus / Duro-Fleece
-187.5
concrete
Elastizell.
inch o.c.
Roof Board
O.C.
CR-20 (splatter) or WB II
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A,
Min. 0.25-inch
Duro-Fleece or Duro-
Structural
Min. 200 psi, min. 2-inch thick
LWC-27.
H-Shield, Duro-Guard ISO II-H, ENRGY 3 or
CR-20
SECUROCK Gypsum -Fiber
CR-20
Fleece Plus / Duro-Fleece
180.0
concrete
Elastizell
Duro-Guard ISO 11-G
Roof Board
CR-20 (splatter) or WB II
MEARLCRETE(FL13492):
BAREBACK MEMBRANE APPLICATIONS:
Structural
Min. 200 psi, min. 2-inch thick
(Optional) Additional
LWC-28.
concrete
Mearlcrete
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A
CR-20
layers of base insulation
CR-20
Duro-Last / WB 1
-82.5
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A,
Min. 0.25-inch
LWC-29.
Structural
Min. 200 psi, min. 2-inch thick
H-Shield, Duro-Guard ISO II-H, ENRGY 3 or
CR-20
SECUROCK Gypsum -Fiber
CR-20
Duro-Last, Duro-Last EV or
-240.0
concrete
Mearlcrete
Duro-Guard ISO II-G
Roof Board
Duro-Tuff / SB IV or WB II
DURo-FLEECE AND DURO-FLEECE PLUS MEMBRANE APPLICATIONS:
StructuralEMea
psi, min. 2-inch thick
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A,
Min. 0.25-inch
Duro-Fleece or Duro-
LWC-30.
H-Shield, Duro-Guard ISO II-H, ENRGY 3 or
CR-20
SECUROCK Gypsum -Fiber
CR-20
Fleece Plus / Duro-Fleece
-240.0
concretete
Duro-Guard ISO II-G
Roof Board
CR-20 (splatter) or WB II
NEMO ETC, LLC Evaluation Report D9750.05.08-1110 for FL1559-R13
Certificate of Authorization #32455 CH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 32 of 44
OMEMO I etc.
TABLE 4C: LIGHTWEIGHT CONCRETE OVER STEEL DECKS - NEW CONSTRUCTION ......
SYSTEM TYPE E-2: MECHANICALLY ATTACHED BASE BONDEDROOF COVER
System1 7- L_ Deck (Note 1) LWC (Note 15) Base Sheet Roof Cover (Note 16) MDP (psf)
No. Type Fasteners Attach
ELASTIZELL (FL4994):
Min. 22 ga., type BV, Grade
Min. 320 psi, min. 2-inch thick
CertainTeed Flexiglas
7.5-inch o.c. at the 3-inch laps and 7.5-
Duro-Fleece or Duro-
Fleece Plus / Duro-
LWC-31.
33 steel at max. 7 ft spans
Elastizell cellular lightweight concrete
Base Sheet, GAFGLAS
Trufast FM-90
inch o.c. in one staggered row in the
Fleece CR-20 (splatter
22.5
cast with Zell Fibers in the mix.
#75
center of the sheet
applied)
Min. 22 ga., type BV, Grade
Min. 380 psi, min. 2-inch thick
CertainTeed Flexiglas
Trufast Twin-
7.5-inch o.c. at the 3-inch laps and 7.5-
Duro-Fleece or Duro-
Fleece Plus / Duro-
LWC-32.
33 steel at max. 7 ft spans
Elastizell cellular lightweight concrete
Base Sheet, GAFGLAS
Loc Nails (min.
inch o.c. in one staggered row in the
Fleece CR-20 (splatter
-37.5
cast with Zell Fibers in the mix.
#75, JM PermaPly 28
1.8-in)
center of the sheet
applied)
Min. 350 psi, min. 2-inch thick
CertainTeed Plexiglas
Trufast Twin-
7.5-inch o.c. at the 3-inch laps and 7.5-
Duro-Fleece or Duro-
LWC-33.
Min. ga., type BV, Grade
Elastizell cellular lightweight concrete
Base SheetGAFGLAS
Loc Nails (min,
inch o.c. in two, equally spaced,
Fleece Plus /Duro
-67.5
33 steelel at max. 7 ftt spans
cast with Zell Fibers in the mix.
,
#75, JM PermaPly 28
1.8-in)
staggered row in the center of the
Fleece CR-20 (splatter
sheet
applied)
TABLE 41): LIGHTWEIGHT CONCRETE OVER STEEL DECKS - NEW CONSTRUCTION OR REROOF (TEAR
-OFF)
SYSTEMTYPEF: NON -INSULATED, BONDED ROOF COVER
System Deck (Note 1) No.
LWC (Note 15)
Roof Cover (Note 16) _FM
DP (psf)
CELCORE(FL2037):
LWC-34.
Min. 22 ga., type BV, Grade 33
Min. 350 psi, min. 2-inch thick Celcore MF Cellular Concrete with Celcore HS Rheology Modifying Admixture,
Duro-Fleece or Duro-Fleece Plus /
steel deck at max. 4 ft spans
with optional 1-inch thick, 1.0 pcf EPS holey board and surfacing of Celcore PVA Curing Compound.
Duro-Fleece Adhesive
37.5
LWC-35.
Min. 22 ga., type BV, Grade 33
Min. 350 psi, min. 2-inch thick Celcore MF Cellular Concrete with Celcore HS Rheology Modifying Admixture,
Duro-Fleece or Duro-Fleece Plus / WB II
-60.0
steel deck at max. 6 ft spans
with optional 1-inch thick, 1.0 pcf EPS holey board and surfacing of Celcore PVA Curing Compound.
ELASTIZELL (FL4994):
LWC-36.
Min. 22 ga., type BV, Grade 33
Min. 350 psi, min. 2-inch thick Elastizell cellular lightweight concrete cast with Zell Fibers in the mix.
Duro-Fleece or Duro-Fleece Plus /
-52.5
steel at max. 7 ft spans
Duro-Fleece CR-20 (splatter applied)
TABLE
4E: LIGHTWEIGHT CONCRETE OVER STRUCTURAL CONCRETE DECKS - NEW CONSTRUCTION OR REROOF
(TEAR -OFF)
SYSTEM TYPE F: NON -INSULATED, BONDED ROOF COVER
System Deck (Note 1)
No.
LWC (Note 15)
Roof Cover (Note i6) TMDP (psf)
CELCORE (FL2037):
LWC-37.
Min. 2,500 psi structural concrete
Min. 350 psi, min. 2-inch thick Celcore MF Cellular Concrete with Celcore HS Rheology Modifying Admixture,
Duro-Fleece or Duro-Fleece Plus /
82.5
with optional 1-inch thick, 1.0 pcf EPS holey board and surfacing of Celcore PVA Curing Compound.
WB II
LWC-38.
Min. 2,500 psi structural concrete
Min. 350 psi, min. 2-inch thick Celcore MF Cellular Concrete with Celcore HS Rheology Modifying Admixture,
Duro-Fleece or Duro-Fleece Plus /
-232.5
with optional 1-inch thick, 1.0 pcf EPS holey board and surfacing of Celcore PVA Curing Compound.
Duro-Fleece Adhesive at 4-inch o.c.
NEMO ETC, LLC Evaluation Report D9750.05.08-R10 for FL1559-1113
Certificate of Authorization #32455 6-EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEW ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 33 of 44
OMEMO I etc,
System
Deck
Base Insulation Layer
Top Insulation Layer
No.
)
(Notes 1 & 12)
Type
Attach
Type Attach (Notes 6 & 7)
Roof Cover (Note 16) MDP (psf)
CWF-1.
Existing min. 2.5-inch Tectum
Min. 0.25-inch SECUROCK
Insta-Stik, 6-
None
N/A
Duro-Last, Duro-Last EV or Duro-Tuff / SB
Plank or Tectum LS Plank
Gypsum -Fiber Roof Board
inch o.c.
-150.0
IV or WB II
CWF-2.
Existing min. 2.5-inch Tectum
Min. 0.25-inch SECUROCK
Insta-Stik, 6-
None
N/A
Duro-Fleece or Duro-Fleece Plus / Duro-
Plank or Tectum LS Plank
Gypsum -Fiber Roof Board
inch o.c.
I
I
-150.0
I Fleece CR-20 (splatter) or WB II
TABLE 5B: CEMENTITIOUS
WOOD FIBER rCONSTRUCTION,••• • OR RECOVER
SYSTEM TYPE r
r INSULATION,r ROOF COVER
Insulation (Note 14)
Roof Cover
System
Deck (Note 1)
Attach
M DP
No.
Type
Membrane
Fasteners
Attach (psf)
(Note 5)
Min. 3-inch One or more layers, any
Prelim.
Duro-Last, min.
Duro-Last Auger Fastener (min. 2-inch
Standard Lao System fastened 6-inch o.c. within 6-inch wide
CWF-3.
Tectum I combination, min. 1.5-inch
attach
40-mil
embedment) with 2" Auger Plate
tabs spaced 57-inch o.c. 45.0
Min. 3-inch One or more layers, any
Prelim.
Duro-Last, min.
Duro-Last Auger Fastener (min. 2-inch
Duro-Roof Lao System fastened 6-inch o.c. within 6-inch wide
CWF-4.
Tectum I combination, min. 1.5-inch
attach
40-mil
embedment) with 2" Auger Plate
tabs spaced 57-inch o.c. Tab Sealer 4725 at max. 60 ft2/gal 52.5
TABLE 5C: CEMENTITIOUS WOOD FIBER rCONSTRUCTION,••• • OR RECOVER
SYSTEM TYPE E-1: • r MECHANICALLY ATTACHED ROOF COVER
Roof Cover
System
Deck (Note 1)
MDP
Fasteners
No.
Membrane
Attach
(psf)
Type
ENERFOAM Installation
CWF-5.
Min. 2-inch
Duro-Last,
Duro-Last Auger Fastener (min. 2-
N/ A
Standard Lao System fastened 6-inch o.c. at 3-inch wide
Tectum I
min. 40-mil
inch embedment)
tabs spaced 60-inch o.c.
30.0
Duro-Last Auger Fastener (min. 2-
7/16-inch diameter x 2.5-inch deep pilot holt filled with
CWF-6.
Min. 3-inch
Duro-Last,
inch embedment) with 2" Auger
Dupont ENERFOAM followed by fastener installation within
Standard Lao System fastened 6-inch o.c. at 3-inch wide
-37.5
Tectum I
min. 40-mil
Plate and Dupont ENERFOAMT1
20-40 seconds after dispensing the foam
tabs spaced 60-inch o.c.
NEMO ETC, LLC Evaluation Report D9750.05.08-R10 for FL3559-Ri3
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 34 of 44
NNEMOjetc.
TABLE 6A: GYPSUM DECKS - REROOF (TEAR -OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF
Base Insulation Layer Top Insulation Layer
System Deck (Notes 1 & 12) Attach Attach Roof Cover (Note 16)
�
PD
Type Type
(Notes 6 & 7) (Notes 6 & 7)
BAREBACK MEMBRANE APPLICATIONS: -
G-1.
Existing poured gypsum
(Optional) Min. 1.5-inch ACFoam II,
CR-20
Min. 0.25-inch Dens Deck
CR-20
Duro-Last / WB 1
-37.5
or gypsum plank
Duro-Guard ISO II -A
G 2
Existing poured gypsum
Min. 1.5-inch ACFoam 11, Duro-Guard
CR-20
(Optional) Additional layers of base insulation
CR-20
Duro-Last / SB I or WB II
-45.0
or gypsum plank
15011-A
G-3.
Existing poured gypsum
Min. 1.5-inch ACFoam 11, Duro-Guard
CR-20
(Optional) Additional layers of base insulation
CR-20
Duro-Last, Duro-Last EV or
-45.0
or gypsum plank
ISO II -A
Duro-Tuff / SB IV or WB II
G-4.
Existing poured gypsum
Min. 1.5-inch ACFoam 11, Duro-Guard
CR-20
(Optional) Additional layers of base insulation
CR-20
Duro-Last / WB 1
-82.5
or gypsum plank
150 II -A
Existing poured gypsum
Min. 1.5-inch ACFoam 11, Duro-Guard
Duro-Last, Duro-Last EV or
G-5.
or gypsum plank
ISO II -A, H-Shield, Duro-Guard ISO 11-H,
CR-20
Min. 0.25-inch SECUROCK Gypsum -Fiber Roof Board
CR-20
Duro-Tuff / SB IV or WB II
-247.5
ENRGY 3 or Duro-Guard ISO II-G
DURO-FLEECE OR DURO-FLEECE PLUS MEMBRANE APPLICATIONS:
G-6.
Existing poured gypsum
Min. 1.5-inch ACFoam II, Duro-Guard
CR-20
(Optional) Additional layers of base insulation
CR-20
Duro-Fleece or Duro-Fleece
-45.0
or gypsum plank
ISO II -A
Plus / WB II
Existing poured gypsum
Min. 1.5-inch ACFoam 11, Duro-Guard
Duro-Fleece or Duro-Fleece
G 7.
or gypsum plank
150 II -A, H-Shield, Duro-Guard ISO II-H,
CR-20
Min. 0.25-inch SECUROCK Gypsum -Fiber Roof Board
CR-20
Plus / Duro-Fleece CR-20
-247.5
ENRGY 3 or Duro-Guard ISO II-G
(splatter) or WB 11
Existing poured gypsum
Min. 1.5-inch ACFoam II, Duro-Guard
Trufast
Min. 0.5-inch Duro-Guard ISO HD -A or Duro-Guard ISO
Trufast
Duro-Fleece or Duro-Fleece
G-8.
or gypsum plank
ISO II -A, ENRGY 3 CGF, Duro-Guard ISO
Roofing
HD-H
Roofing
Plus / Trufast Roofing
-165.0
III-G, H-Shield CG, Duro-Guard ISO III-H
Adhesive
Adhesive
Adhesive, ribbons 4" o.c.
Min. 1.5-inch ACFoam II, Duro-Guard
Trufast
Min. 0.25-inch Dens Deck, Dens Deck Prime, DEXcell FA
Trufast
Duro-Fleece or Duro-Fleece
G 9
Existing
g poured gypsum
ISO II -A, ENRGY 3 CGF, Duro-Guard ISO
Roofing
Glass Mat Roof Board, SECUROCK Gypsum -Fiber Roof
Roofing
Plus /Trufast Roofing
-195.0
or gypsum plank
III-G, H-Shield CIS, Duro-Guard ISO III-H
Adhesive
Board or SECUROCK Glass -Mat Roof Board or min.
Adhesive
Adhesive, ribbons 4" o.c.
7/16" DEXcell Cement Roof Board
Existing poured gypsum
Min. 1.5-inch ACFoam II, Duro-Guard
Trufast
Trufast
Duro-Fleece or Duro-Fleece
G-10.
or gypsum plank
ISO II -A, ENRGY 3 CGF, Duro-Guard ISO
Roofing
(Optional) Additional layers of base insulation
Roofing
Plus / Trufast Roofing
-217.5
III-G, H-Shield CIS, Duro-Guard ISO III-H
Adhesive
Adhesive
Adhesive, ribbons 4" o.c.
TABLE 6B: GYPSUM DECKS - •• • OR RECOVER
SYSTEM TYPE • • INSULATION,• ROOF COVER
System Deck Insulation Roof Cover
No.
(Note 1) Type
Attach
Membrane
Fasteners (Note 11)
MDP (psf)
Attach
G-11.
Existing poured gypsum One or more layers,
Prelim.
Duro-Last, min. 40 mil,
Duro-Last Auger Fastener
Standard Lao System fastened 6-inch o.c. within 6-inch wide -45.0
or gypsum plank any combination
Attached
with 2" Auger Plate
tabs spaced 57-inch o.c.
G-12.
Existing poured gypsum One or more layers,
Prelim.
Duro-Last, min. 40 mil,
Duro-Last Auger Fastener
Duro-Roof Lao System fastened 6-inch o.c. within 6-inch wide -60.0
or gypsum plank any combination
attached
with 2" Auger Plate
tabs spaced 57-inch o.c. Tab Sealer 4725 at max. 60 ft2/gal
NEMO ETC, LLC Evaluation Report D9750.05.08-R10 for FL1559-R33
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 35 of 44
ONEMOjetc.
TABLEM RECOVER APPLICATIONS
SYSTEM TYPE A: BONDED INSULATION, BONDED ROOF
Base Insulation Layer
Top Insulation Layer
System
Substrate
MDP
Type
Attach
No.
(Notes 1 & 12)
Attach Roof Cover (Note 16)
Type (psf)
(Notes 6 & 7)
(Notes 6 & 7)
BAREBACK MEMBRANE APPLICATIONS:
R-1.
Existing asphaltic BUR or mineral
(Optional) Min. 1.5-inch ACFoam II, Duro-
Ashland Pliodeck,
Ashland Pliodeck,
surface cap sheet
Guard ISO II -A
6-inch o.c
Min. 0.25-inch Dens Deck
6-inch o.c
Duro-Last / WB I
37.5
R 2
Existing asphaltic BUR or mineral
Min. 1.5-inch ACFoam 11, Duro-Guard 150 II -A
Ashland Pliodeck,
(Optional) Additional layers
Ashland Pliodeck,
Duro-Last / SB I or WB II
-45.0
surface cap sheet
6-inch o.c
of base insulation
6-inch o.c
R-3.
Existing asphaltic BUR or mineral
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A
Ashland Pliodeck,
(Optional) Additional layers
Ashland Pliodeck,
Duro-Last, Duro-Last EV or
45.0
surface cap sheet
6-inch o.c
of base insulation
6-inch o.c
Duro-Tuff / 5B IV or WB II
R 4
Existing asphaltic BUR or mineral
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A
Ashland Pliodeck,
(Optional) Additional layers
Ashland Pliodeck,
Duro-Last / WB 1
-82.5
surface cap sheet
6-inch o.c
of base insulation
6-inch o.c
R-5.
Existing asphaltic BUR or mineral
Min. 2-inch ISO 95+ GL
Ashland Pliodeck,
Min. 0.25-inch SECUROCK
Ashland Pliodeck,
Duro-Last, Duro-Last EV or
surface cap sheet
6-inch o.c.
Gypsum -Fiber Roof Board
6-inch o.c.
Duro-Tuff / SB IV or WB II
172.5
Existing asphaltic BUR or mineral
(Optional) Min. 1.5-inch ACFoam II, Duro-
R-6.
surface cap sheet
Guard ISO II -A
Board -Max
Min. 0.25-inch Dens Deck
Board -Max
Duro-Last / WB I
-37.5
R 7
Existing asphaltic BUR or mineral
Min. 1.5-inch ACFoam I1, Duro-Guard ISO II -A
Board -Max
(Optional) Additional layers
Board -Max
Duro-Last/SB I or WB II
-45.0
surface cap sheet
of base insulation
R 8.
Existing asphaltic BUR or mineral
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A
Board -Max
(Optional) Additional layers
Board -Max
Duro-Last, Duro-Last EV or
45.0
surface cap sheet
of base insulation
Duro-Tuff / 5B IV or WB II
R 9
Existing asphaltic BUR or mineral
Min. 1.5-inch ACFoam 11, Duro-Guard 150 11-A
Board -Max
(Optional) Additional layers
Board -Max
Duro-Last / WB 1
-82.5
surface cap sheet
of base insulation
R-10.
Existing smooth surface BUR or
Min. 0.25-inch SECUROCK Gypsum -Fiber
Board -Max
None
N/A
Duro-Last, Duro-Last EV or
-245.0
granule surface modified bitumen
Roof Board
Duro-Tuff / SB IV or WB II
R-11.
Existing smooth surface BUR or
Min. 1.5-inch ACFoam II, Duro-Guard ISO II-
A, H-Shield, Duro-Guard ISO 11-H, ENRGY 3 or
Board -Max
Min. 0.25-inch SECUROCK
Board -Max
Duro-Last, Duro-Last EV or
-247.5
granule surface modified bitumen
g
Duro-Guard ISO 11-G
G
Gypsum -Fiber Roof Board
Duro-Tuff / SB IV or WB II
Existing smooth -surface asphalt
R-12.
BUR or granule -surface modified
Min. 0.75-inch Duro-Guard EPS Type IX
Board -Max
Min. 0.25-inch SECUROCK
Board -Max
Duro-Last, Duro-Last EV or
-247.5
bitumen
Gypsum -Fiber Roof Board
Duro-Tuff / 5B IV or WB II
Existing smooth -surface asphalt
R-13.
BUR or granule -surface modified
Min. 0.75-inch Duro-Guard EPS Type IX
Board -Max
Min. 0.25-inch SECUROCK
Board -Max
Duro-Last, Duro-Last EV or
-255.0
bitumen
Gypsum -Fiber Roof Board
Duro-Tuff / SB IV or WB II
R-14.
Existing asphaltic BUR or mineral
(Optional) Min. 1.5-inch ACFoam II, Duro-
CR-20
Min. 0.25-inch Dens Deck
CR-20
Duro-Last / WB 1
-37.5
surface cap sheet
Guard ISO II -A
R 15.
Existing asphaltic BUR or mineral
Min. 1.5-inch ACFoam II, Duro-Guard I50 II -A
CR 20
(Optional) Additional layers
CR 20
Duro Last / SB I or WB II
45.0
surface cap sheet
of base insulation
R 16.
Existing asphaltic BUR or mineral
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A
CR-20
(Optional) Additional layers
CR-20
Duro-Last, Duro-Last EV or
45.0
surface cap sheet
of base insulation
Duro-Tuff / SB IV or WB II
NEMO ETC, LLC
Certificate of Authorization #32455
©2019 NEMO ETC, LLC
6TH EDITION (2017) FBC NON-HVHZ EVALUATION
Duro-Last Single Ply Roof Systems; (800) 248-0280
Evaluation Report D9750.05.08-1110 for FL1559-1113
Revision 10: 10/17/2019
Appendix 1, Page 36 of 44
ONEMOletc.
TABLE 7A: RECOVER APPLICATIONS
SYSTEM TYPE A: BONDED INSULATION,
BONDEDROOF COVER
Base Insulation Layer
Top Insulation Layer
System
Substrate
MDP
Type
Attach
Type
Attach
No.
(Notes 1 & 12)
Roof Cover (Note 16)
(psf)
(Notes 6 & 7)
(Notes 6 & 7)
R-17.
Existing asphaltic BUR or mineral
Min. 1.5-inch ACFoam 11, Duro-Guard 150 II -A
CR-20
(Optional) Additional layers
CR-20
Duro-Last / WB 1
-82.5
surface cap sheet
of base insulation
Existing smooth surface modified
(Optional) Min. 1.5-inch ACFoam 11, Duro-
Min. 0.25-inch SECUROCK
Duro-Last, Duro-Last EV or
R-18.
bitumen
Guard ISO II -A, H-Shield, Duro-Guard ISO II-
CR-20
Gypsum -Fiber Roof Board
CR-20
Duro-Tuff / SB IV or WB II
222 5
H, ENRGY 3 or Duro-Guard ISO II-G
R-19.
Existing smooth -surface 5135
Min. 0.75-inch Duro-Guard EPS Type 11, VIII
Min. 0.25-inch SECUROCK
Duro-Last, Duro-Last EV or
modified bitumen
or IX
CR-20
Gypsum -Fiber Roof Board
CR-20
Duro-Tuff / SB IV or WB II
222 5
R-20.
Existing smooth surface BUR or
Min. 0.25-inch SECUROCK Gypsum -Fiber
CR-20
None
N/A
Duro-Last, Duro-Last EV or
-245.0
granule surface modified bitumen
Roof Board
Duro-Tuff / SB IV or WB II
Existing smooth surface BUR or
Min. 1.5-inch ACFoam 11, Duro-Guard ISO II-
Min. 0.25-inch SECUROCK
Duro-Last, Duro-Last EV or
R-21.
granule surface modified bitumen
A, H-Shield, Duro-Guard ISO II-H, ENRGY 3 or
CR-20
Gypsum -Fiber Roof Board
CR-20
Duro-Tuff / SB IV or WB II
-247.5
Duro-Guard I5O II-G
Existing smooth -surface asphalt
R-22.
BUR or granule -surface modified
Min. 0.75-inch Duro-Guard EPS Type II, VIII
CR-20
Min. 0.25-inch SECUROCK
CR-20
Duro-Last, Duro-Last EV or
247 5
bitumen
or IX
Gypsum -Fiber Roof Board
Duro-Tuff / SB IV or W8 II
Existing smooth -surface asphalt
R-23.
BUR or granule -surface modified
Min. 0.75-inch Duro-Guard EPS Type II, VIII
CR-20
Min. 0.25-inch SECUROCK
CR-20
Duro-Last, Duro-Last EV or
-255.0
bitumen
or IX
Gypsum -Fiber Roof Board
Duro-Tuff /SB IV or WB II
R-24.
Existing asphaltic BUR or mineral
Min. 1.5-inch ACFoam II, Duro-Guard 150 II -A
Hot asphalt
(Optional) Additional layers
Hot asphalt
Duro-Last / SB I or WB II
-45.0
surface cap sheet
of base insulation
R-25.
Existing asphaltic BUR or mineral
Min. 1.5-inch ACFoam 11, Duro-Guard I5O II -A
Hot asphalt
(Optional) Additional layers
Hot asphalt
Duro-Last, Duro-Last EV or
-45.0
surface cap sheet
of base insulation
Duro-Tuff / 513 IV or WB II
Existing asphaltic BUR or mineral
(Optional) Additional layers
R-26.
surface cap sheet
Min. 1.5-inch ACFoam 11, Duro-Guard ISO II -A
Hot asphalt
of base insulation
Hot asphalt
Duro-Last / WB 1
-75.0
Existing asphaltic BUR or mineral
(Optional) Min. 1.5-inch ACFoam 11, Duro-
R 27
surface cap sheet
Guard ISO II -A
Insta-Stik
Min. 0.25-inch Dens Deck
Insta-Stik
Duro-Last / WB I
-37.5
R 28
Existing asphaltic BUR or mineral
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A
Insta-Stik
(Optional) Additional layers
Insta-Stik
Duro-Last / SB 1 or WB II
-45.0
surface cap sheet
of base insulation
R 29
Existing asphaltic BUR or mineral
Min. 1.5-inch ACFoam 11, Duro-Guard ISO II -A
Insta-Stik
(Optional) Additional layers
Insta-Stik
Duro-Last, Duro-Last EV or
-45.0
surface cap sheet
of base insulation
Duro-Tuff / 5B IV or WB II
R-30.
Existing asphaltic BUR or mineral
Min. 1.5-inch ACFoam 11, Duro-Guard 150 II -A
Insta-Stik
(Optional) Additional layers
Insta-Stik
Duro-Last / WB 1
-82.5
surface cap sheet
of base insulation
Existing asphaltic BUR or mineral
Min. 1.5-inch ACFoam 11, Duro-Guard 150 II-
Min. 0.25-inch SECUROCK
Duro-Last, Duro-Last EV or
R-31.
surface cap sheet
A, H-Shield, Duro-Guard ISO II-H, ENRGY 3 or
Insta-Stik
Gypsum -Fiber Roof Board
Insta-Stik
Duro-Tuff / 513 IV or WB If
-127.5
Duro-Guard ISO II-G
NEMO ETC, LLC Evaluation Report D9750.05.08-1310 for FL3559-R33
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 37 of 44
ONEMO I etc.
TABLE 7A: RECOVER APPLICATIONS
SYSTEM TYPE A: BONDED INSULATION,
BONDED ROOF COVER
Base Insulation Layer
Top Insulation Layer
System Substrate
Roof Cover (Note 16)
MDP
Attach
Attach
No. (Notes 1 & 12)
Type
Type
APO)(Notes
6 & 7)
(Notes 6 & 7)
R-32.
Existing asphalt built-up roof
(Optional) Min. 1.5-inch ACFoam 11, Duro-
OlyBond 500
Min. 0.25-inch Dens Deck
OlyBond 500
Duro-Last / WB 1
-37.5
Guard ISO II -A
R-33.
Existing asphalt built-up roof
(Optional) Min. 1.5-inch ACFoam 11, Duro-
OlyBond 500
(Optional) Additional layers
OlyBond 500
Duro-Last / SB I or WB II
45.0
Guard ISO II -A
of base insulation
R-34.
Existing asphalt built-up roof
(Optional) Min. 1.5-inch ACFoam 11, Duro-
OlyBond 500
(Optional) Additional layers
OlyBond 500
Duro-Last, Duro-Last EV or
-45.0
Guard ISO 11-A
of base insulation
Duro-Tuff / SB IV or WB II
R-35.
Existing asphalt built-up roof
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A
OlyBond 500
(Optional) Additional layers
OlyBond 500
Duro-Last / WB 1
-82.5
of base insulation
(Optional) Min. 1.5-inch ACFoam II, Duro-
Min. 0.25-inch SECUROCK
Duro-Last, Duro-Last EV or
R-36.
Existing asphalt built-up roof
Guard ISO II -A, H-Shield, Duro-Guard ISO 11-
OlyBond 500
Gypsum -Fiber Roof Board
OlyBond 500
Duro-Tuff / SB IV or WB II
-120.0
H, ENRGY 3 or Duro-Guard ISO II-G
DURO-FLEECE OR DURO-FLEECE PLUS MEMBRANE APPLICATIONS:
R-37.
Existing asphaltic BUR or mineral
Min. 1.5-inch ACFoam 11, Duro-Guard ISO 11-A
Ashland Pliodeck,
(Optional) Additional layers
Ashland Pliodeck,
Duro-Fleece or Duro-Fleece
-45.0
surface cap sheet
6-inch o.c
of base insulation
6-inch o.c
Plus / WB 11
Existing asphaltic BUR or mineral
Ashland Pliodeck,
Min. 0.25-inch SECUROCK
Ashland Pliodeck,
Duro-Fleece or Duro-Fleece
R-38.
surface cap sheet
Min. 2-inch ISO 95+ GL
6-inch o.c.
Gypsum -Fiber Roof Board
6-inch o.c.
Plus / Duro-Fleece CR-20
-172.5
(splatter) or WB II
R-39.
Existing asphaltic BUR or mineral
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A
Board -Max
(Optional) Additional layers
Board -Max
Duro-Fleece or Duro-Fleece
-45.0
surface cap sheet
of base insulation
Plus / WB II
Existing smooth surface BUR or
Min. 0.25-inch SECUROCK Gypsum -Fiber
Duro-Fleece or Duro-Fleece
R-40.
granule surface modified bitumen
Roof Board
Board -Max
None
N/A
Plus / Duro-Fleece CR-20
-245.0
(splatter) or WB 11
Existing smooth surface BUR or
Min. 1.5-inch ACFoam 11, Duro-Guard ISO 11-
Min. 0.25-inch SECUROCK
Duro-Fleece or Duro-Fleece
R-41.
granule surface modified bitumen
A, H-Shield, Duro-Guard ISO II-H, ENRGY 3 or
Board -Max
Gypsum -Fiber Roof Board
Board -Max
Plus / Duro-Fleece CR-20
-247.5
Duro-Guard ISO 11-G
(splatter) or WB II
Existing smooth -surface asphalt
Min. 0.25-inch SECUROCK
Duro-Fleece or Duro-Fleece
R-42.
BUR or granule -surface modified
Min. 0.75-inch Duro-Guard EPS Type IX
Board -Max
Board -Max
Plus / Duro-Fleece CR-20
-247.5
bitumen
Gypsum -Fiber Roof Board
(splatter) or WB II
Existing smooth -surface asphalt
Min. 0.25-inch SECUROCK
Duro-Fleece or Duro-Fleece
R-43.
BUR or granule -surface modified
Min. 0.75-inch Duro-Guard EPS Type IX
Board -Max
Board -Max
Plus / Duro-Fleece CR-20
-255.0
bitumen
Gypsum -Fiber Roof Board
(splatter) or WB II
R-44.
Existing asphaltic BUR or mineral
Min. 1.5-inch ACFoam 11, Duro-Guard ISO II -A
CR-20
(Optional) Additional layers
CR-20
Duro-Fleece or Duro-Fleece
-45.0
surface cap sheet
of base insulation
Plus / WB II
Existing smooth surface modified
(Optional) Min. 1.5-inch ACFoam 11, Duro-
Min. 0.25-inch SECUROCK
Duro-Fleece or Duro-Fleece
R-45.
bitumen
Guard ISO II -A, H-Shield, Duro-Guard 150 11-
CR-20
Gypsum -Fiber Roof Board
CR-20
Plus / Duro-Fleece CR-20
-222.5
H, ENRGY 3 or Duro-Guard ISO 11-G
(splatter) or WB 11
NEMO ETC, LLC
- Certificate of Authorization H32455
©2019 NEMO ETC, LLC
6TM EDITION (2017) FBC NON-HVHZ EVALUATION
Duro-Last Single Ply Roof Systems; (800) 248-0280
Evaluation Report D9750.05.08-1110 for FL1559-Ri3
Revision 10: 10/17/2019
Appendix 1, Page 38 of 44
ONEMOletc.
TABLE 7A: RECOVER APPLICATIONS
SYSTEM TYPE A: BONDED INSULATION,
BONDEDROOF COVER
Base Insulation Layer
Top Insulation Layer
System
Substrate
MDP
Type
Attach
Type
Attach
No.
(Notes 1 & 12)
Roof Cover (Note 16)
(psf)
(Notes 6 & 7)
(Notes 6 & 7)
Duro-Fleece or Duro-Fleece
R-46.
Existing smooth -surface SBS
Min. 0.75-inch Duro-Guard EPS Type II, VIII
CR-20
Min. 0.25-inch SECUROCK
CR-20
Plus /Duro-Fleece CR-20
-222.5
modified bitumen
or IX
Gypsum -Fiber Roof Board
(splatter) or WB II
Existing smooth surface BUR or
Min. 0.25-inch SECUROCK Gypsum -Fiber
Duro-Fleece or Duro-Fleece
R-47.
CR-20
None
N/A
Plus / Duro-Fleece CR-20
-245.0
granule surface modified bitumen
Roof Board
(splatter) or WB II
Existing smooth surface BUR or
Min. 1.5-inch ACFoam II, Duro-Guard ISO II-
Min. 0.25-inch SECUROCK
Duro-Fleece or Duro-Fleece
R-48.
granule surface modified bitumen
A, H-Shield, Duro-Guard ISO II-H, ENRGY 3 or
CR-20
Gypsum -Fiber Roof Board
CR-20
Plus / Duro-Fleece CR-20
-247.5
Duro-Guard ISO II-G
(splatter) or WB II
Existing smooth -surface asphalt
Duro-Fleece or Duro-Fleece
R-49.
BUR or granule -surface modified
Min. 0.75-inch Duro-Guard EPS Type II, VIII
CR 20
Min. 0.25-inch SECUROCK
CR-20
Plus / Duro-Fleece CR-20
-247.5
bitumen
or IX
Gypsum -Fiber Roof Board
(splatter) or WB II
Existing smooth -surface asphalt
Duro-Fleece or Duro-Fleece
R-50.
BUR or granule -surface modified
Min. 0.75-inch Duro-Guard EPS Type II, VIII
CR 20
Min. 0.25-inch SECUROCK
CR-20
Plus / Duro-Fleece CR-20
-255.0
bitumen
or IX
Gypsum -Fiber Roof Board
(splatter) or WB II
Existing asphaltic BUR or mineral
(Optional) Additional layers
Duro-Fleece or Duro-Fleece
R-51.
surface cap sheet
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A
Hot asphalt
of base insulation
Hot asphalt
Plus / WB II
-45.0
R-52.
Existing asphaltic BUR or mineral
Min. 1.5-inch ACFoam II, Duro-Guard ISO II -A
Insta-Stik
(Optional) Additional layers
Insta-Stik
Duro-Fleece or Duro-Fleece
-45.0
surface cap sheet
of base insulation
Plus / WB II
Existing asphaltic BUR or mineral
Min. 1.5-inch ACFoam II, Duro-Guard ISO II-
Min. 0.25-inch SECUROCK
Duro-Fleece or Duro-Fleece
R-53.
surface cap sheet
A, H-Shield, Duro-Guard ISO II-H, ENRGY 3 or
Insta-Stik
Gypsum -Fiber Roof Board
Insta-Stik
Plus / Duro-Fleece CR-20
-127.5
Duro-Guard ISO II-G
(splatter) or WB II
R-54.
Existing asphalt built-up roof
(Optional) Min. 1.5-inch ACFoam II, Duro-
OlyBond 500
(Optional) Additional layers
OlyBond 500
Duro-Fleece or Duro-Fleece
-45.0
Guard ISO II -A
of base insulation
Plus / WB II
(Optional) Min. 1.5-inch ACFoam II, Duro-
Duro-Fleece or Duro-Fleece
R-55.
Existing asphalt built-up roof
Guard ISO II -A, H-Shield, Duro-Guard ISO II-
OlyBond 500
Min. 0.25-inch SECUROCK
OlyBond 500
Plus / Duro-Fleece CR-20
-120.0
H, ENRGY 3 or Duro-Guard ISO II-G
Gypsum -Fiber Roof Board
(splatter) or WB II
NEMO ETC, LLC Evaluation Report D9750.05.08-1110 for FL3559-1113
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 39 of 44
ONEMOletc.
RECOVER OVER STEEL SUBSTRATE
PLATE-BONDEDTABLE713:
SYSTEM TYPE C-2- ROOF COVER
(All areas where the existing metal panels do not lay flush on the underlying purlin shall have a 0.25-inch diameter pilot hole pre -drilled into the panel priorto driving the Purlin Fastener into the purlin.)
System Substrate Attachment MDP
Insulation Layer Roof Cover
No. (Note 1) Fasteners (Note 11) Spacing (Psf)
RHINOBOND INDUCTION WELD:
Existing standing seam or lap seam metal roof covers
One or more layers, any
Trufast #12 Purlin Fasteners
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil)
R-56.
having min. 16 gauge (0.0598 inch), 50 ksi or min. 12 gauge
combination,
with RHINOBOND Insulation
12-inch o.c. along
or Duro-Tuff (min. 80-mil) induction welded to
-30.0
(0.105 in.), 36 ksi steel purlins spaced max. 60-inch o.c.
preliminarily fastened
Plate (PVC)
purlins 60-inch o.c.
RHINOBOND Insulation Plate (PVC) using
RHINOBOND Installation Tool
Existing standing seam or lap seam metal roof covers
One or more layers, any
Trufast #12 Purlin Fasteners
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil)
R-57.
having min. 16 gauge (0.0598 inch), 50 ksi or min. 12 gauge
combination,
with RHINOBOND Insulation
6-inch o.along
.
or Duro-Tuff (min.80-mil) induction welded to
-45.0
(0.105 in.), 36 ksi steel purlins spaced max. 120-inch o.c.
preliminarily fastened
Plate (PVC)
purlins 120-inch o.c.
RHINOBOND Insulation Plate (PVC) using
RHINOBOND Installation Tool
Existing standing seam or lap seam metal roof covers
One or more layers, any
Trufast #12 Purlin Fasteners
Duro-Last (min., 60 mil), Duro-Last EV (min. 50 mil)
R-58.
having min. 16 gauge (0.0598 inch), 50 ksi or min. 12 gauge
combination,
with RHINOBOND Insulation
12-inch o.c. along
or Duro-Tuff (min. 80-mil) induction welded to
-45.0
(0.105 in.), 36 ksi steel purlins spaced max. 48-inch o.c.
preliminarily fastened
Plate (PVC)
purlins 48-inch D.C.
RHINOBOND Insulation Plate (PVC) using
RHINOBOND Installation Tool
Existing standing seam or lap seam metal roof covers .
One or more layers, any
Trufast #12 Purlin Fasteners
Duro-Last (min. 40-mil), Duro-Tuff (min. 50-mil) or
R-59.
having min. 16 gauge (0.0595 inch), 50 ksi or min. 12 gauge
combination,
with RHINOBOND Insulation
6-inch o.c. along
Duro-Last EV (min. 50-mil) induction welded to
-52.5
(0.105 in.), 36 ksi steel purlins spaced max. 72-inch o.c.
preliminarily fastened
Plate (PVC)
purlins 72-inch o.
RHINOBOND Insulation Plate (PVC) usingc.
RHINOBOND Installation Tool
Existing standing seam or lap seam metal roof covers
One or more layers, any
Trufast #12 Purlin Fasteners
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil)
R-60.
having min. 16 gauge (0.0598 inch), 50 ksi or min. iZ gauge
combination,
with RHINOBOND Insulation
6-inch o.c. along
or Duro-Tuff (min. 80-mil) induction welded to
-52.5
(0.105 in.), 36 ksi steel purlins spaced max. 96-inch o.c.
preliminarily fastened
Plate (PVC)
purlins 96-inch o.
RHINOBOND Insulation Plate (PVC) usingc.
RHINOBOND Installation Tool
Existing standing seam or lap seam metal roof covers
One or more layers, any
Trufast #12 Purlin Fasteners
Duro-Last (min. 40-mil), Duro-Tuff (min. 50-mil) or
R-61.
having min. 16 gauge (0.0598 inch), 50 ksi or min. 12 gauge
combination,
with RHINOBOND Insulation
6-inch D.C. along
Duro-Last EV (min. 50-mil) induction welded to
-82.5
0.105 in. , 36 ksi steel purlins spaced max. 48-inch o.c.
( ) p p
preliminarily fastened
Plate (PVC)
purlins 48-inch o.c.
RHINOBOND Insulation Plate (PVC) using
RHINOBOND Installation Tool
Existing standing seam or lap seam metal roof covers
One or more layers, any
Trufast #12 Purlin Fasteners
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil)
R-62.
having min. 16 gauge (0.0598 inch), 50 ksi or min. 12 gauge
combination,
with RHINOBOND Insulation
6-inch o.c. along
or Duro-Tuff (min. 80-mil) induction welded to
-82.5
(0.105 in.), 36 ksi steel purlins spaced max. 60-inch o.c.
preliminarily fastened
Plate (PVC)
purlins 60-inch o.c.
RHINOBOND Insulation Plate (PVC) using
RHINOBOND Installation Tool
Existing standing seam or lap seam metal roof covers
One or more layers, any
Trufast #12 Purlin Fasteners
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil)
R-63.
having min. 16 gauge (0.0598 inch), 50 ksi or min. 12 gauge
combination,
with RHINOBOND Insulation
6-inch o.c. along
or Duro-Tuff (min. 80-mil) induction welded to
-90.0
(0.105 in.), 36 ksi steel purlins spaced max.48-inch o.c.
preliminarily fastened
Plate (PVC)
purlins 48-inch D.C.
RHINOBOND Insulation Plate (PVC) using
RHINOBOND Installation Tool
ISOWELD INDUCTION WELD:
Existing standing seam or lap seam metal roof covers
One or more layers, any
SFS Purlin Fastener with
Duro-Last (min. 40 mil), Duro-Last EV (min. 50 mil)
R-64.
having min. 16 gauge (0.0598 inch), 50 ksi steel purlins
combination,
isoweld® Fl-P-6.8-PVC
12-inch D.C. along
or Duro-Tuff (min. 50 mil) induction welded to SFS
-45.0
spaced max. 60-inch o.c.
preliminarily fastened
Plates
purlins 60-inch o.c.
isoweld® Fi-P-6.8-PVC Plates with SFS isoweld®
3000 stand-up tool
NEMO ETC, LLC
Certificate of Authorization #32455
©2019 NEMO ETC, LLC
6- EDITION (2017) FBC NON-HVHZ EVALUATION
Duro-Last Single Ply Roof Systems; (800) 248-0280
Evaluation Report D9750.05.08-R10 for F1.3559-1313
Revision 10: 10/17/2019
Appendix 1, Page 40 of 44
ONEMOjetc.
RECOVER OVER STEEL SUBSTRATE
PLATE-BONDEDTABLE7B:
SYSTEM TYPE C-2: ROOF COVER
(All areas where the existing metal panels do not lay flush on the underlying purlin shall have a 015-inch diameter pilot hole pre -drilled into the panel prior to driving the Purlin Fastener into the purlin.
System Substrate Attachment MDP
Insulation Layer Roof Cover
No. (Note 1) Fasteners (Note 11) Spacing (psf)
Existing standing seam or lap seam metal roof covers One or more layers, any
5FS Purlin Fastener with
Duro-Last (min. 40 mil), Duro-Last EV (min. 50 mil)
R-65.
having min. 16 gauge (0.0598 inch), 50 ksi steel purlins combination,
isoweld® Fl-P-6.8-PVC
6-inch_o.c. along or Duro-Tuff (min. 50 mil) induction welded to SFS
-90.0
spaced max. 60-inch o.c. preliminarily fastened
Plates
purlins 60-inch o.c. isoweld® Fl-P-6.8-PVC Plates with SFS isoweld®
3000 stand-up tool
TRUFAST INDUCTION WELD:
Existing standing seam or lap seam metal roof covers
One or more layers, any
Duro-Last (min. 40 mil), Duro-Last EV (min. 50 mil)
R-66.
having min. 16 gauge (0.0598 inch), 50 ksi or min. 12 gauge
combination,
Trufast #12 Purlin Fastener
12-inch o.c. along
or Duro-Tuff (min. 50 mil) induction welded to
-45.0
(0.105 in.), 36 ksi steel purlins spaced max. 60-inch o.c.
preliminarily fastened
with Trufast PVC IW Plate
purlins 60-inch o.c.
Trufast PVC IW Plates with Trufast Induction
Welding Tool and Magnets
Existing standing seam or lap seam metal roof covers
One or more layers, any
Trufast #12 Purlin Fastener
12-inch o.c. along
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil)
R-67.
having min. 16 gauge (0.0598 inch), 50 ksi or min. 12 gauge
combination,
with Trufast PVC IW Plate
purlins 48-inch o.c.
induction welded to Trufast PVC IW Plates with
-52.5
(0.105 in.), 36 ksi steel purlins spaced max. 48-inch o.c.
preliminarily fastened
Trufast Induction Welding Tool and Magnets
Existing standing seam or lap seam metal roof covers
One or more layers, any
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil)
R-68.
having min. 16 gauge (0.0595 inch), 50 ksi or min. 12 gauge
combination,
Trufast #12 Purlin Fastener
12-inch o.c. along
or Duro-Tuff (min. 60 mil) induction welded to
-60.0
0.105 in. 36 ksi steel purlins spaced max. 48-inch o.c.
( ), p p
preliminarily fastened
with Trufast PVC IW Plate
purlins 48-inch o.c.
Trufast PVC IW Plates with Trufast Induction
Welding Tool and Magnets
Existing standing seam or lap seam metal roof covers
One or more layers, any
Trufast #12 Purlin Fastener
12-inch o.c. along
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil)
R-69.
having min. 16 gauge (0.0598 inch), 50 ksi or min. 12 gauge
combination,
with Trufast PVC IW Plate
purlins 36-inch o.c.
induction welded to Trufast PVC IW Plates with
-60.0
(0.105 in.), 36 ksi steel purlins spaced max. 36-inch o.c.
preliminarily fastened
Trufast Induction Welding Tool and Magnets
Existing standing seam or lap seam metal roof covers
One or more layers, any
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil)
R-70.
having min. 16 gauge (0.0598 inch), 50 ksi or min. 12 gauge
combination,
Trufast #12 Purlin Fastener
12-inch o.c. along
or Duro-Tuff (min. 60 mil) induction welded to
-82.5
(0.105 in.), 36 ksi steel purlins spaced max. 36-inch o.c.
preliminarily fastened
with Trufast PVC IW Plate
purlins 36-inch o.c.
Trufast PVC IW Plates with Trufast Induction
Welding Tool and Magnets
Existing standing seam or lap seam metal roof covers
One or more layers, any
Trufast #12 Purlin Fastener
6-inch o.c. along
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil)
R-71.
having min. 16 gauge (0.0598 inch), 50 ksi or min. 12 gauge
combination,
with Trufast PVC IW Plate
purlins 72-inch o.c.
induction welded to Trufast PVC IW Plates with
-67.5
(0.105 in.), 36 ksi steel purlins spaced max. 72-inch o.c.
preliminarily fastened
Trufast Induction Welding Tool and Magnets
Existing standing seam or lap seam metal roof covers
One or more layers, any
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil)
R-72.
having min. 16 gauge (0.0598 inch), 50 ksi or min. 12 gauge
combination,
Trufast #12 Purlin Fastener
6-inch o.c. along
or Duro-Tuff (min. 60 mil) induction welded to
-75.0
(0.105 in.), 36 ksi steel purlins spaced max. 72-inch o.c.
preliminarily fastened
with Trufast PVC IW Plate
purlins 72-inch o.c.
Trufast PVC IW Plates with Trufast Induction
Welding Tool and Magnets
Existing standing seam or lap seam metal roof covers
One or more layers, any
Trufast #12 Purlin Fastener
6-inch o.c. along
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil)
R-73.
having min. 16 gauge (0.0598 inch), 50 ksi or min. 12 gauge
combination,
with Trufast PVC IW Plate
purlins 60-inch o.c.
induction welded to Trufast PVC IW Plates with
-75.0
(0.105 in.), 36 ksi steel purlins spaced max. 60-inch o.c.
preliminarily fastened
Trufast Induction Welding Tool and Magnets
Existing standing seam or lap seam metal roof covers
One or more layers, any
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil)
R-74.
having min. 16 gauge (0.0598 inch), 50 ksi or min. 12 gauge
combination,
Trufast #12 Purlin Fastener
6-inch o.c. along
or Duro-Tuff (min. 60 mil) induction welded to
-90.0
(0.105 in.), 36 ksi steel purlins spaced max. 60-inch o.c.
preliminarily fastened
with Trufast PVC IW Plate
purlins 60-inch o.c.
Trufast PVC IW Plates with Trufast Induction
Welding Tool and Magnets
NEMO ETC, LLC Evaluation Report D9750.05.08-1110 for FL1559-1113
Certificate of Authorization #32455 CH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 41 of 44
OMEMO I etc.
RECOVER OVER STEEL SUBSTRATE
PLATE-BONDEDTABLE713:
SYSTEM TYPE C-2: ROOF COVER
(All areas where the existing metal panels do not lay flush on the underlying purlin shall have a 0.25-inch diameter pilot hole pre -drilled into the panel
priorto drivingthe Purlin Fastener into the purlin.)
System Substrate Attachment
Insulation Layer
MDP
Roof Cover
No. (Note 1) Fasteners (Note 11) Spacing
(psf)
Existing standing seam or lap seam metal roof covers
One or more layers, any
Trufast #12 Purlin Fastener
6-inch o.c. along
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil)
R-75.
having min. 16 gauge (0.0598 inch), 50 ksi or min. 12 gauge
combination,
with Trufast PVC IW Plate
purlins 48-inch o.c.
induction welded to Trufast PVC IW Plates with
-90.0
(0.105 in.), 36 ksi steel purlins spaced max. 48-inch o.c.
preliminarily fastened
Trufast Induction Welding Tool and Magnets
Existing standing seam or lap seam metal roof covers
One or more layers, any
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil)
R-76.
having min. 16 gauge (0.0598 inch), 50 ksi or min. 12 gauge
combination,
Trufast #12 Purlin Fastener
6-inch o.c. along
or Duro-Tuff (min. 60 mil) induction welded to
-112.5
(0.105 in.), 36 ksi steel purlins spaced max. 48-inch o.c.
preliminarily fastened
with Trufast PVC IW Plate
purlins 48-inch o.c.
Trufast PVC IW Plates with Trufast Induction
Welding Tool and Magnets
Existing standing seam or lap seam metal roof covers
One or more layers, any
Trufast #12 Purlin Fastener
6-inch o.c. along
Duro-Last (min. 40 mil) or Duro-Tuff (min. 50 mil)
R-77.
having min. 16 gauge (0.0598 inch), 50 ksi or min. 12 gauge
combination,
with Trufast PVC IW Plate
purlins 36-inch o.c.
induction welded to Trufast PVC IW Plates with
-112.5
(0.105 in.), 36 ksi steel purlins spaced max. 36-inch o.c.
preliminarily fastened
Trufast Induction Welding Tool and Magnets
Existing standing seam or lap seam metal roof covers
One or more layers, any
Duro-Last (min. 60 mil), Duro-Last EV (min. 50 mil)
R-78.
having min. 16 gauge (0.0598 inch), 50 ksi or min. 12 gauge
combination,
Trufast #12 Purlin Fastener
6-inch o.c. along
or Duro-Tuff (min. 60 mil) induction welded to
-150.0
(0.105 in.), 36 ksi steel purlins spaced max. 36-inch o.c.
preliminarily fastened
with Trufast PVC IW Plate
purlins 36-inch o.c.
Trufast PVC IW Plates with Trufast Induction
Welding Tool and Magnets
NEMO ETC, LLC
Certificate of Authorization #32455
©2019 NEMO ETC, LLC
6TH EDITION (2017) FBC NON-HVHZ EVALUATION
Duro-Last Single Ply Roof Systems; (800) 249-0280
Evaluation Report D9750.05.08-R10 for FL1559-1113
Revision 10: 10/17/2019
Appendix 1, Page 42 of 44
ONEMOletc.
RECOVER OVER STEEL SUBSTRATE
ATTACHEDTABLEX:
SYSTEM TYPE D-1: PRELIMINARILY INSULATION, MECHANICALLY ATTACHED ROOF COVER
(All areas where the existing metal panels do not lay flush on the underlying purlin shall have a 0.25-inch diameter pilot hole pre -drilled into the panel priorto driving the Purlin Fastener intothe purlin.)
Insulation (Note 14) Roof Cover
System Substrate
MDP
No. (Note 1) Type Attach
Membrane Fasteners (Note 11) Attachment
(psf)
(Note 5)
Standard Lao System fastened 12-inch
Min. 22 ga., Type B, Grade 60 steel with
One or more layers, any
Duro-Tuff,
Duro-Last #15 Extra Heavy Duty
o.c. within 6-inch wide laps spaced
R 79.
existing single ply roof cover
combination
Prelim. attached
min. 50 mil
Drill Point Fastener with Duro-Last
114-inch o.c. Laps sealed with 1.5-inch
-22.5
Poly -Plate
heat weld.
Min. 22 ga., Type B, Grade 60 steel with
One or more layers, any
Duro-Last,
Duro-Last #15 Extra Heavy Duty
Standard Lao System fastened 12-inch
R-80.
existing single ply roof cover
combination
Prelim. attached
min. 40 mil
Drill Point Fastener with Duro-Last
o.c. within 3-inch wide tabs spaced 60-
-30.0
Cleat Plates
inch o.c.
Min. 22 ga., Type B, Grade 60 steel with
One or more layers, any
Duro-Last,
Duro-Last #15 Extra Heavy Duty
Standard Lao System fastened 12-inch
R-81.
existing single ply roof cover
combination
Prelim. attached
min. 40 mil
Drill Point Fastener with Duro-Last
o.c. within 6-inch wide tabs spaced
-30.0
Cleat Plates
120-inch o.c.
Existing standing seam or lap seam metal
roof covers having min. 16 gauge (0.0598
One or more layers, any
Duro-Last,
Trufast #12 Purlin Fasteners with
Standard Lao System fastened 9-inch
R 82
inch), 50 ksi or min. 12 gauge (0.105 in.), 36
combination
Prelim. attached
min. 40 mil
Duro-Last Poly -Plate
o.c. within 3-inch wide tabs spaced 60-
-45.0
ksi steel purlins spaced max. 120-inch o.c.
inch o.c. along purlins
Min. 0.5-inch DURO-
Duro-Last #14 Heavy
Type B Min. 22 ga., , Grade 40 steel with
GUARD EPS FAN FOLD-
Duty with Duro-Last 3-
Duro-Last,
Duro-Last #15 Extra Heavy Duty
Standard Lao System fastened 12-inch
R-83.
existing asphalt built-up roof (BUR)
inch
inch Metal Plates; 1 per
min. 40 mil
Drill Point Fastener with Duro-Last
c.c. within 3-inch wide tabs spaced 60-
-52.5
5.3 ft'; 6 parts per 4x8 ft
Poly -Plate or Duro-Last Cleat Plate
inch o.c.
GUARD XPS FAN
GAN FOLD F
section
Min. 0.5-inch DURO-
Duro-Last #14 Heavy
Standard Lao System fastened 12-inch
Min. 22 ga., Type B, Grade 40 steel with
GUARD EPS FAN FOLD
Duty with Duro-Last 3-
Duro-Tuff,
Duro-Last #15 Extra Heavy Duty
o.c. within 6-inch wide laps spaced 54-
R-84.
existing asphalt built-up roof (BUR)
or 3/8-inch DURO-
inch Metal Plates; 1 per
min. 50 mil
Drill Point Fastener with Duro-Last
inch o.c. Side laps sealed with 1.5-inch
-52.5
5.3 ft ; 6 parts per 4x8 ft
Poly -Plate or Duro-Last Cleat Plate
GUARD XPS FAN FOLD
heat -weld
section
NEMO ETC, LLC Evaluation Report D9750.05.08-1110 for F1.1559-1113
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 43 of 44
ONEMOjetc.
RECOVERTABLE 7D: OVER CEIVIENTITIOUS WOOD FIBER SUBSTRATE
SYSTEM TYPE E-1: NON -INSULATED, MECHANICALLY ATTACHED ROOF
Roof Cover
System
Substrate (Note 1)
Fasteners (Note 11)
MDP
No.
Membrane
Attach
(psf)
Type
ENERFOAM Installation
Min. 2-inch Tectum I
Through-fastened 6-inch o.c. in rows 48-inch o.c.
R-85.
with existing single
Duro-Last,
Duro-Last Auger Fastener (min. 2-
N/A
-30.0
Fastener rows sealed with 10-inch wide strip of Duro-
ply roof cover
min. 40-mil
inch embedment)
Last, with a 1.5-inch heat weld on all sides
Min. 3-inch Tectum I
Auger Fastener (min. 2-
7/16-inch diameter x 2.5-inch deep pilot holt filled with
Through -fastened 6-inch o.c. in rows 96-inch o.c.
R-86.
with existing single
DurDuro-Last
inch embedment) with 2" Auger
Dupont ENERFOAM followed by fastener installation
Fastener rows sealed with 10-inch wide strip of Duro-
-67.5
ply roof cover _
mino-Last,
min. 40-mil
Plate and Dupont ENERFOAMT1
within 20-40 seconds after dispensing the foam
Last, with a 1.5-inch heat weld on all sides
RECOVERTABLE 7E: •
System No. Substrate (Notes 1 & 12) Primer / Treatment Roof Cover (Note 16) MDP (psf)
Existing asphaltic roof system with mechanically fastened and/or adhered
Duro-Fleece or Duro-Fleece Plus / Duro-Fleece CR-20 (splatter
R-87. underlying components (insulation, coverboard or base sheet) and with existing
None
applied) -150.0
granule -surface BUR or granule -surface SBS or APP modified bitumen cap sheet
Existing asphaltic roof system with adhered underlying components (insulation,
Duro-Fleece or Duro-Fleece Plus / Duro-Fleece CR-20 (splatter
R-88. coverboard or base sheet) over monolithic deck and with existing smooth- or
None
applied) -370.0
granule -surface BUR or granule -surface SBS or APP modified bitumen cap sheet
NEMO ETC, LLC Evaluation Report D9750.05.08-1110 for FL1559-R13
Certificate of Authorization #32455 6TH EDITION (2017) FBC NON-HVHZ EVALUATION - Revision 10: 10/17/2019
©2019 NEMO ETC, LLC Duro-Last Single Ply Roof Systems; (800) 248-0280 Appendix 1, Page 44 of 44