License CAC1815254 CertifiedHVAC DESIGN FOR
AEM & ASSOCIATES
RESIDENTIAL RENOVATION
General Notes
Please note not all notes may apply.
1.CONTRACTOR SHALL PROVIDE A COMPLETE AND OPERABLE MECHANICAL SYSTEM.
2.THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE. CAREFUL ATTENTION SHALL BE PAID TO PRECISE LOCATION AND
COORDINATION OF DIFFUSERS, REGISTERS, AND GRILLES WITH STRUCTURAL FRAMING AND ELECTRICAL FIXTURES AT
CEILING LOCATIONS. ELECTRICAL FIXTURES AT CEILING TAKE PRIORITY OVER DUCT LAYOUT. ELECTRICAL FIXTURES AT
CEILING ARE NOT TO BE MOVED FROM THEIR PROPOSED LOCATIONS. SEE THE REFLECTED CEILING PLANS, WHERE
AVAILABLE, FOR EXACT LOCATIONS OF CEILING FIXTURES. NO STRUCTURAL MEMBER SHALL BE CUT WITHOUT PERMISSION
FROM STRUCTURAL ENGINEER.
3.THE CONTRACTOR SHALL OBTAIN, AT HIS EXPENSE, ALL NECESSARY FEES, PERMITS, AND TESTS.
4.ALL WORK SHALL COMPLY WITH APPLICABLE CODES, REGULATIONS, ORDINANCES AND REQUIREMENTS OF AUTHORITIES
HAVING JURISDICTION. NO CONTRACTOR SHALL BID UNLESS FAMILIAR WITH THESE CODES. ALL WORK SHALL BE
EXECUTED IN A WORKMANLIKE MANNER AND SHALL PRESENT A NEAT, PROFESSIONAL APPEARANCE WHEN COMPLETED.
ALL MATERIALS AND EQUIPMENT SHALL BE NEW. STORE AND INSTALL MATERIALS AND EQUIPMENT IN ACCORDANCE WITH
THE MANUFACTURER'S INSTRUCTIONS.
5.THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE HVAC SYSTEM(S) TO BE INSTALLED (REFRIGERANT LINES, EQUIPMENT,
DUCTWORK, GRILLES, ETC.). ADDITIONAL OFFSETS, TRANSITIONS, ETC. MAY BE REQUIRED TO PROVIDE A COMPLETE
SYSTEM. NO ABRUPT TRANSITIONS SHALL BE PERMITTED. THE MECHANICAL WORK HEREIN INCLUDES COMPLETE
SYSTEMS OF HEATING, AIR CONDITIONING (TEMPERATURE AND HUMIDITY CONTROL), VENTILATION, BATHROOM EXHAUST,
KITCHEN EXHAUST, AND ALL DUCTWORK. THE CONTRACTOR SHALL PROVIDE EACH ELEMENT THEREOF, AS INDICATED
HEREIN, OR REASONABLY INFERRED (WHETHER OR NOT SPECIFICALLY CALLED FOR BY ITEM), REASONABLY NECESSARY TO
FACILITATE EACH SYSTEM'S FUNCTIONING AS INDICATED BY THE DESIGN AND EQUIPMENT SPECIFIED. CONTRACTOR SHALL
VERIFY SPACE CONDITIONS PRIOR TO THE FABRICATION OR INSTALLATION OF ANY WORK.
6.THE CONDENSING UNIT AND AIR HANDLING UNIT EQUIPMENT SHALL BE AS SPECIFIED OR ARCHITECT APPROVED
SUBSTITUTE.
7.PRIOR TO START OF THE HVAC WORK, THE CONTRACTOR SHALL SUBMIT, TO THE ARCHITECT, AN UPDATED MANUAL J LOAD
ANALYSIS, BASED ON THE FINAL CONTRACTOR DOCUMENTS AND ACTUAL MATERIALS AND PRODUCTS SELECTED (ie:
BUILDING ENVELOPE INSULATION, EXTERIOR DOOR GLAZING, AND ANY OTHER APPLICABLE FACTORS THAT WOULD AFFECT
THE UPDATED MANUAL J LOAD ANALYSIS). THE SIZING OF THE ACTUAL HVAC SYSTEMS TO BE UTILIZED (REFRIGERANT
LINES, EQUIPMENT, DUCTWORK, GRILLES, ETC.) SHALL BE BASED ON THE UPDATED MANUAL J LOAD ANALYSIS. THE
CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR PROPERLY SIZING THE HVAC SYSTEM.
8.THE CONTRACTOR SHALL COORDINATE A "MECHANICAL WALK-THROUGH" MEETING, WHICH IS TO OCCUR PRIOR TO THE
START OF THE MECHANICAL ROUGH-IN. THE PURPOSE FOR THIS MEETING IS TO ALLOW THE OWNER, ARCHITECT, AND
CONTRACTOR TO REVIEW AND COORDINATE FINAL DUCT AND AIR DEVICE LOCATIONS. THE MECHANICAL
SUBCONTRACTOR'S FOREMAN IS TO ATTEND THIS MEETING AS WELL.
9.NO CHANGES TO THE HVAC PLANS OR NOTES SHALL BE PERMITTED WITHOUT PROCALCS, LLC. PRIOR APPROVAL.
10.REFRIGERANT PIPING SHALL BE TYPE "L" SOFT DRAWN COPPER, ASTM B280, AND SHALL BE MILL CLEANED, DRIED AND
CAPPED. INSULATE REFRIGERANT SUCTION LINE WITH " WALL FOAMED PLASTIC INSULATION SLIPPED OVER TUBING AND
ALL JOINTS THOROUGHLY SEALED. PAINT REFRIGERANT PIPING INSULATION WITH TWO (2) COATS OF ACRYLIC PROTECTIVE
PAINT WHERE INSULATION IS EXPOSED TO WEATHER.
11.ALL FIBERGLASS DUCTWORK SHALL BE 1-1/2" FIBROUS GLASS ANTI-MICROBIAL DUCTBOARD INSTALLED IN ACCORDANCE
WITH THE LATEST EDITION OF S.M.A.C.N.A. FIBROUS GLASS DUCT CONSTRUCTION STANDARDS. 1" FIBROUS GLASS
ANTI-MICROBIAL DUCTBOARD MAY BE USED IN THOSE LOCATIONS WHERE ALLOWED BY CODE. NO ABRUPT TRANSITIONS
SHALL BE PERMITTED. PROVIDE AIR TURNING VEINS IN ALL 90 DEGREE RECTANGULAR DUCT ELBOWS.
12.FLEXIBLE DUCTWORK SHALL BE THERMAFLEX M-KA TYPE WITH 1-1/2" ONE-POUND DENSITY INSULATION AND VINYL VAPOR
BARRIER OR ARCHITECT APPROVED SUBSTITUTE. NO ABRUPT TRANSITIONS SHALL BE PERMITTED.
13.DUCT SIZES SHOWN ARE INSIDE NET DIMENSIONS.
14.ALL AIR DEVICES SHALL BE MANUFACTURED BY TITUS, 250 SERIES, OR APPROVED SUBSTITUTE. COLOR TO BE APPROVED
BY THE PROFESSIONAL OF RECORD PRIOR TO PAINTING GRILLES BUT ASSUMED TO BE WHITE FOR BID/BUDGET PURPOSES.
SUPPLY AIR REGISTERS SHALL BE DOUBLE DEFLECTION TYPE WITH OPPOSED BLADE DAMPERS. ALL SIZES AND PATTERNS
ARE NOTED ON THE MECHANICAL PLANS.
15.FOR EACH RETURN AIR GRILLE, PROVIDE 3M FILTRETE 1000 MICRO ALLERGEN PLEATED AIR FILTERS (3M, 800-49403552,
www.filtrete.com, MERV RATING: 11, PRESSURE DROP: .2 @ 300 FPM, OR APPROVED SUBSTITUTE). PRIOR TO INSTALLATION,
THE CONTRACTOR SHALL VERIFY THAT THE AIR VELOCITY NOICE ACROSS EACH RETURN AIR FILTER WILL BE LOW, BASED
ON THE PRESSURE DROP FOR PROPOSED FILTER TYPE AND THE PROPOSED RETURN AIR GRILLE SIZE(S). ANY RETURN AIR
FILTER GRILLES THAT ARE REQUIRED TO BE RESIZED BY THE CONTRACTOR, ARE TO BE SIZED FOR FILTER SIZES THAT ARE
READILY AVAILABLE AT HOME SUPPLY STORES. CUSTOM SIZES ARE NOT PERMITTED.
16.ALL BATH, KITCHEN, AND DRYER EXHAUST(S) SHALL BE VENTED TO THE EXTERIOR.
17.ALL BATH EXHAUST FANS SHALL BE DUCTED WITH 4" R-FIN. SLOPE AND FULLY SUPPORT ALL BATHROOM EXHAUST DUCTS
TO AVOID ANY SNAGS IN THE DUCT AND TO ALLOW FOR PROPER DRAINAGE. TERMINATE AT SOFFIT WITH SCREENED
GRILLE, UNLESS OTHERWISE NOTED.
18.PROVIDE BACKDRAFT DAMPERS FOR ALL EXHAUST FANS.
19.ALL EXHAUST AIR DUCTS SHALL BE GALVANIZED SHEET METAL CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH
ASHRAE AND SMACNA STANDARDS.D
20.TESTING, ADJUSTING, AND BALANCING: THE CONTRACTOR SHALL BALANCE THE AIRFLOW DISTRIBUTION SYSTEMS,
INCLUDING SUB MAINS, BRANCHES, AND TERMINALS TO QUANTITIES INDICATED ON THE UPDATED MANUAL J LOAD
ANALYSIS (FOR RESIDENTIAL PROPERTIES) AND MANUAL J (COMMERCIAL PROPERTIES).
21.PROVIDE DRAW-THROUGH CONDENSATE TRAP AT EACH UNIT CONDENSATE DRAIN. DEPTH SHALL BE AT LEAST 1-1/2 TIMES
THE TOTAL S.P DROP OF THE UNIT.
22.PROVIDE PROGRAMMABLE SERIES 7-DAY THERMOSTAT. PRIOR TO ORDERING THE THERMOSTAT, THE CONTRACTOR SHALL
VERIFY THAT THE SPECIFIED THERMOSTAT WILL OPERATE PROPERLY WITH THE PROPOSED AIR CONDITIONING EQUIPMENT.
IF A SUBSTITUTE IS REQUIRED, CONTRACTOR MUST SUBMIT PRODUCT INFORMATION TO ARCHITECT FOR PRODUCT
APPROVAL. COORDINATE THERMOSTAT LOCATION WITH FURNITURE/EQUIPMENT LAYOUTS, WINDOWS AND DOOR SWINGS.
THERMOSTAT MUST BE LOCATED AT 54" A.F.F. AND NOT LOCATED ON AN OUTSIDE WALL.
23.SUPPLY AND RETURN AIR GRILLES SHALL MAINTAIN A MINIMUM DISTANCE OF 3'-0" FROM CEILINGS FANS.
24.ALL DUCT BRANCHES, PER ACCA MANUAL D, SHOULD INCLUDE DAMPERS FOR PROPER AIR FLOW AND BALANCING.
25.NO EQUIPMENT SHALL BE PURCHASED UNTIL REVIEW BY THE PROFESSIONAL OF RECORD, EVEN IF EQUIPMENT HAS BEEN
SPECIFIED.
26.ANY VARIATION FROM THE DESIGN PRESENTED COULD AFFECT SYSTEM PERFORMANCE.
27.EQUIPMENT SHALL BEAR A U.L. OR OTHER RECOGNIZED LABEL, NAMEPLATES, WIRING DIAGRAMS, AND ENERGY RATINGS,
AS APPLICABLE.
28.CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND ACCESSORIES SO THAT IT IS READILY ACCESSIBLE FOR SERVICING,
TESTING, BALANCING AND REPLACEMENT.
29.CONTRACTOR SHALL PROVIDE A WRITTEN GUARANTEE AGAINST DEFECTS INALL MATERIALS AND WORKMANSHIP FOR ONE
(1) YEAR FROM ACCEPTANCE WITH FOUR ADDITIONAL YEARS OF WARRANTY ON COMPRESSORS.
30.PRIOR TO ACCEPTANCE BY THE OWNER, THE SYSTEMS SHALL BE TESTED AND BALANCED BY A AABC OR NEBB CERTIFIED
T&B CONTRACTOR EXPERIENCED WITH THIS SYSTEM. THE CONTRACTOR SHALL CERTIFY THE TESTING AND BALANCING
WITHIN +/- 10% OF DESIGN CFMS AND PROVIDE BALANCE TEST SHEETS.
31.AIR BALANCE TO BE PERFORMED BY THE AIR CONDITIONING CONTRACTOR TO THE OWNER'S COMFORT. ALL SUPPLY AND
RETURN DUCTWORK SHALL BE INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS AND LOCAL BUILDING CODES.
32.PROVIDE ALL CONTROLS, STARTERS, CONTROL WIRING, DISCONNECTS, AND OTHER ELECTRICAL EQUIPMENT AS REQUIRED
FOR A COMPLETE AND OPERATIONAL SYSTEM. MECHANICAL CONTRACTOR IS TO COORDINATE WITH OTHER
CONTRACTORS TO ENSURE THAT ALL ITEMS REQUIRED ARE INCLUDED IN
33.COORDINATE ALL POWER AND CONTROL WIRING WITH ELECTRICIAN.
Signatures can only be verified
and validated with electronic
copy of documents.Residential Renovation1633 NW Sweetbay CirclePalm City, FL 34990AEM & Associates
PO Box 3752
Jupiter, FL 33469
DF
11/18/2020
M-1
OFFICE
LIVING/DINING CLOSET
BREAKFAST NOOK
MASTER BEDROOM
KITCHEN
LAUNDRY
FOYERUTILITY
BEDROOM 2
GARAGE BATH 2 BATH 3
BEDROOM 3
6"
12 x 8
118 cfm
Connect to
Existing Duct
System at
Closest Point
at AH
For:
Checked By:
Sheet
Date:
Scale:
No.Revision/Issue Date
Drawn By:
1 Issue
TP
As Shown
First Floor HVAC Plan
1/4"=1'-0"Copyright ProCalcs, LLC, 2020CPO Box 882032
Port Saint Lucie, FL 34988
Phone: 772-882-5700
www.ProCalcs.Net
tom@procalcs.net
License CAC1815254 CertifiedGENERAL NOTES:
1.All supply ducts are designed per ACCA Manual D.
2.All supply branches are designed according to ACCA Manual D for
the highest CFM's required Heating or Cooling, for the room load
per ACCA Manual J.
3.It is the installing HVAC Contractor's responsibility to install air
volume dampers to adjust appropriate air flow accordingly.
4.Field coordinate all grille locations with other trades prior to
installation to maintain proper clearances required by applicable
codes.
11/18/2020
Supply grille
Legend
ThermostatT
Exhaust fan
Please note not all symbols may apply.
Return grille
Condensing unit
Riser duct up/down
SDD Smoke Duct Detector
12 x 12
148 cfm
8"
Grill Size
Grill CFM
Branch Duct Size
Signatures can only be verified
and validated with electronic
copy of documents.Residential Renovation1633 NW Sweetbay CirclePalm City, FL 34990AEM & Associates
PO Box 3752
Jupiter, FL 33469
DF
11/18/2020
M-2
CONDENSING UNIT BOLTED TO
CONCRETE PAD TO WITHSTAND
HURRICANE FORCE WINDS. AS
PER FBCM 301.12
CONDENSING UNIT MOUNTING DETAIL NTS
4" CONCRETE SLAB. TOP OF
SLAB.
NOTE:
CONDENSING UNITS TO BE INSTALLED ABOVE FLOOD LEVEL CRITERIA.
ISOMODE PAD (TYPICAL)
COND. UNIT
ISOMODE PAD
4" CONC. PAD
16 GA. HURRICANE
STRAP
1/4" X 2" SELF-DRILLING
SHEET METAL SCREW
3/8" X 2 1/2" QUICK-BOLT
EXPANSION ANCHOR.
(TYPICAL OF 4 ONE PER
CORNER OF UNIT)
NOTES:
1. ALLOW SUFFICIENT SPACE BELOW DRAIN
PAN FOR TRAP.
2. PITCH DRAIN FOR PROPER RUNOFF.
3. MANUALLY PRIME FILL TRAP BEFORE
START-UP TO FORM INITIAL DRAIN SEAL.
4. SUPPORT LENGTHY DRAIN LINES TO
PREVENT SAG AND CONDENSATE OVERFLOW.
THIS STANDARD DETAIL
MUST BE REVIEWED AND
SITE ADAPTED BY
CONTRACTOR PRIOR TO USE
FOR FINAL EQUIPMENT.
A/C UNIT
DRAIN PAN
PITCH
DRAIN PIPE TO
MATCH DRAIN
OUTLET SIZE.
DRAW THROUGH UNIT CONDENSATE TRAP NTS
CLEANOUT
(TYPICAL)
PITCH
(a)
(b)
(c)
(a) THIS DIMENSION IN INCHES MUST BE
EQUAL TO THE MAXIMUM FAN SUCTION
(NEGATIVE) STATIC PRESSURE IN INCHES WC
(WITH DIRTY FILTERS, COILS, AND MAXIMUM
AIR FLOW) + 1" W.C.
(b) THIS DIMENSION IN INCHES MUST BE
EQUAL TO MIN. 1/2 OF THE (a) ABOVE.
(c) EQUAL (a) + (b) + PIPE DIA. + INSULATION.
(d) TRAP SEAL SHALL BE 2" MIN. ON UNITS
LARGER THAN 3 TONS SHALL BE 3" MIN. PER
F.B.C. -4606.7 WHERE APPLICABLE.
(e) TRAP SEAL SHALL BE 2" MIN. TO 4" MAX.
PER S.B.C.C.I. -1002.4 WHERE APPLICABLE.
VENT LINE PERFORATED CAP. 1/2"
ABOVE BOTTOM OF DRAIN PAN
NTSDUCTWORK SUPPORT DETAILS
SUPPORT
2" WIDE METAL BAND
CEILING SYSTEM
SUSPENDED TYPE LOUVERED FACE CEILING DIFFUSER
TYPICAL DIFFUSER DETAIL
IF INSTALLED IN UNCONDITIONED SPACE
PROVIDE THERMAL INSULATION BLANKET
ADAPTER
ROUND
SQUARE TO
1-1/2" X 1-1/2" X 1/8" GALV.
ANGLE OR STRAP PER SMACNA
AND SEAL WITH TAPE/MASTIC OUTERDUCT
CONNECT INNER DUCT WITH DRAWBAND
AT NECK CONNECTION
LOCKING QUADRANT
TO BE EXPOSED
FLEXIBLE DUCT WITH
VAPOR BARRIER
INSULATION &
TIE TO
STRUCTURAL
SUPPORTS
GALV. STEEL ROD OR
STRAP SUPPORTS PER
SMACNA STANDARDS
WITH DAMPER, BELL MOUTH
SIDE TAKE-OFF FITTING
OR SHOETAP TYPE (SEE NOTE)
DUCT, SEE PLANS FOR
MAIN SUPPLY AIR
TYPE AND INSULATION
NOTE: PROVIDE CABLE CONTROL DAMPER FOR HARD CEILING AREAS.
NTS VERTICAL AHU DETAIL NTS
For:
Checked By:
Sheet
Date:
Scale:
No.Revision/Issue Date
Drawn By:
1 Issue
TP
As Shown Copyright ProCalcs, LLC, 2020CPO Box 882032
Port Saint Lucie, FL 34988
Phone: 772-882-5700
www.ProCalcs.Net
tom@procalcs.net
License CAC1815254 CertifiedCFM
Throw (ft)
16
18
20
19
4-way
3-way
2-way
1-way
220
12 x 8
N/A
N/A
N/A
N/A
N/A
11/18/2020
NOMINAL TONNAGE
SEER/EER
MODEL
CONDENSING UNITNOTES: RUUD
CAPACITY TOTAL/SENS.
STAGES
CU NUMBER
EQUIPMENT SCHEDULE
CU-1
RLA - LRA
WEIGHT
4 ton(s)
Single
45201/35796 Btuh
16.00/13.00
RA1648AJ1NB
17 - 124
225 Lbs
AIR HANDLERELECTRIC HEATER
REF LINES SIZES
WEIGHT
DIMENSIONS H x W x D
AHU NUMBER
CFM
FAN MOTOR HP - FLA
REFRIGERANT
AHU-MODEL
LOCATION
STATIC PRESSURE
AHU-1
R-410A
Utility
1608
3/4 - 6.9
50.5 x 21 x 19.5 in
128 Lbs
3/8, 7/8
0.60
RH1T4821STANJA
AHRI #: 201294088
kW 10.8 (208V) - 14.4(240V)
Model Number RXBH-1724A15C
Phase Single Three
Voltage 208 240 460
MCA/MOP 43/45 (208V) - 49/50 (240V)
Phase Single Three
Voltage 208/230 X 460
MCA/MOP 25/40
X
XX X
Signatures can only be verified
and validated with electronic
copy of documents.
GRILLE SCHEDULE
Titus Series 250
Size Velocity (FPM)400 500 Residential Renovation1633 NW Sweetbay CirclePalm City, FL 34990AEM & Associates
PO Box 3752
Jupiter, FL 33469
DF
11/18/2020