HomeMy WebLinkAboutProject Information.'1- irvr�gla#�vft® Project Summary Entire -House QUICK CALCS, INC. Job: Date: By. For: WYNNE DEVELOPMENT THE WINDSOR IMPACT, FT. PIERCE, FL , \� Notes: Design Infor• Weather: Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF . Design TD 28 OF Design TD 15. OF Daily range L . Relative humidity 50 % Moisture difference 61 grflb Heating Summary Sensible Cooling Equipment Load Sizing Structure 20795 Btuh Structure 16420 Btuh Ducts 6191 Btuh Ducts 9337 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh Humnone. idifidation 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 26986 Btuh Use manufacturer's data n Rate/swin multiplier 0.95 Infiltration Equipmen sense le load 24470 Btuh. Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2495 Btuh . Ducts 2546 Btuh Centralvent (0 d1m) 0 Btuh. Heatingg Cool' (none) Area (fF) 1753 1753 Equipment latent load 5041 Btuh . Volume (ft3) 16478 16478 Airchanges/hour 0.38 0.20 Equipment Total Load (Sen+Lat) 29511 Btuh Equiv AVF (cfm) 104 55 Req. total capacity at 0.70 SHR 2.9 ton Heating Equipment Summay Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIERAIR CONDITIONING Trade CARRIERAIR CONDITIONING Model 25HBC536A*030 Cond 25HBC536KO30 AHRI ref 7914585 Coil FX4DN(B,F)037 AHRI ref 7914585 Efficiency 8.5 HSPF Efficiency 12.0 EER,15 SEER . Heating Input Sensible cooling 24360 Btuh Heating output 34600 . Btuh @ 470F Latent cooling 10440 Btuh Temperature rise 27 OF Total cooling 34800 Btuh Actual airflow 1160 df Actual airflow 1160 cfm. Air flow factor 0.043 cfm/Btuh Air flow factor 0.045 cfm/Btuh Static pressure 0 in H2O Static pressure 0 . in H2O Space thermostat Load sensible heat ratio 0.84 Capacity balance point = 36 OF Backup: Input = 7 kW, Output = 23009 Btuh,100"AFUE Calculations approved byACCA-to meet all requirements of Manual J 8th Ed. 41:- wr igHtsoft- 2020-Jar081622:01 n�iie^ •�^�� Right-Sute®.Uriversal2019.19.0.07 RSU08101 Pa e 1 rs\WrigtdsoftWAC\WYNNE-THEWINDSOR-IMPACT.np Calc=MJ8 FrontDoorfaces: N g - vurightsof� Right=J@ Worksheet Job:. Entire House Date: QUICK CALLS, INC. By, 317 ST. LUCIE LN., Fr.. PIERCE; FL 34946 Phone: 772466.6799 Fax 772-466-6796 Email: QUICKCALCS@,AOL.COM 1 2 3 4 5 Room name • Exposed wall Room height Room dimensions Room area Entire House 180.6 It 9A It d 1753.0 IF BEDROOM 41.0 ft 94 it healicool 14.0 x 20.0 it 280.0 flz Ty Construction number U-value (Bluh/il{°F) Or HTM (Btuh/it=) Area (ftz) or perimeter (ft) Load (Btuh) Area (1F) or perimeter (ft) Load (Btuh) Heat Cool Gross , N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 13A-4as 1A�1om 4A5.2om 13AAocs 1.3AAoca 1A-lorn '• 13AAocs 43A flocs 1A clom ;:. 13AAocs 1A-clom 1A-clom 4A5-2om 12C-0sn(. 16A30md. 22A-fpl`' 0.143 . 1270 0.770 0.143 0.143 1270 0.390 0.143 0:143 1270 0.143 1270 1270 0.770 .0.091 0.032 0.989 n -.,n. :n ne a ,e e: as s �,'s•: w w w w ' -. - = 4:00 35:5fi 21.56 4.00 4.00: 3556 10.92 4.00 4:00 :35.56 4.00 35B6 3556 21.56 9.65: 0.90 27.69: 2.55 '34.77 19.31 2.56 2.55 87.06..20: " 11:31 2.55 2.55 34.77 2.55 54.53 , 54.53 45.63 ,. 1.28 2.32 , " 0.00 - 649 15 - : 38, 27 141 21 27 _ 536 6 320 12 12 41 ': 254 ' 1753 .: _ .1753 596 ' 0 0 27 100 1 21 • '' 27 530 ; .: .. ,6 255 1 1 2 :'' . 254 1753 '' : 181 2386 633 815 106 400 711 229.: 106 2121 , . 2.13 1022 415 427 880 .: 647 1571 '.' 5001 1517 522 130 68, 255 1741 :238 68 1349 209 649 636 654 1862 .. 326 4067 0 66 0 0 0 0 0 0 0 188 0 132 12 12 0 : 0. 280., 280, 66 0 0 . 0 . 0 ' . 0 :0 0 188 "' . .,0 108 1 1 0 1 .:0 280 41 263 0 0 0 0 0. 0,: 0 753 6 432 415 427 0 .. ' 0 '251 1135 167 0 0 0 0 0. 1 0 0 479 , =:,0 .275 636 654 0 0 650, ; <0 W W P C F. 6 c) AED excursion 397 488 Envelope loss(gain 17583 15285 3676 3349 12 a) Infiltration b) Room ventilation' 3211 0 905 0 729 0 205 0 13 Internal gains. Occupants@ 230 1 230 0 0 Appliances/other 0 0 Subtotal (lines 6to 13) 20795 16420 4405 3554 Less external load 0 0' 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal' 20795 16420 4405 3554' 151 Ductloads 30% 57% 6191 . 9337 30% 57% 1312.1 2021 Total room load M986 25757 5717 5575. Airrequired(dm) 1160 1160 246 251 Calculations approved. bvACCAto meet all-reguirerrients of Manual J 8th Ed. wrs9lh►>tso1�" 2020-Jatr08.16:22:01 .4 P► Right-Sute®Ur versa1201919.0.07-RSU08101, Page 1 ts\WdgMsoftWACIWYNNE-THEWINDSOR-IMPACT.np Caic=MJ8 FrortDoorfaces: N i- wrightsow Right-J' Worksheet Job: Entire House bate: QUICK CALCS,' I.NC. sy 317 ST. LUCIE LN., Fr.. PIERCE, FL 34946 Phore: 772-466-6799 Fax 772-46"1796 ;Emall: QUICKCALCS@IOL.COM . 1 Room name WIC MASTER BATH 2 Evosed wall 0' ft 9.0 fi 3 Room height 9.4 ft heaNcoot 94 ft heall000l 4. Room dimensions 7D x 9D ft 7.0 x 9D ft 5 Room area 63D ft2 . 63.0 it= Ty Construc lion U-value Or HTM Area - Load number (Bhch/ftz-°F) (BhrhHlz} or perimeter (ft) (Btuh orb perim�r (ft) (B h) Heat Cool Gross N/P/S Heat Cool Gross NIPS Heat Cool 6 13AAocs 0.143 n 4.00 2.55 0 0 0 0 0 0 0: G 1A-L1om 1270 n 35.56' 34:77 0 0 0 0 0 .0 '0 :0 0 4AS2om 0.770: n 21.56 19.31 -0 0 -0 0 0 0 `0: 0 W 13A4ocs 0.143 ne 4.00 2.55 0 0 0 0 0 0 0 0 11 13AAo s- 0.143 e- 4.00 255 0 0 0 0 0 .. 0 0 7Ac1om 1270 e, 35.56 87.06 0 0 0 0 0 0 0 .0' `0 D '11p0. 0.390 =.,e. . 10.92 ,.' .. 11.31 .... p .. 0 0 0 p p : 0 ...0 W 13Altacs 0.143 se 4.00 2.55 0 0 0 0 0 .0 0 6 13A�ots . 0:143 i� 4.00 `2 55 0 0 0 0 85 ; " 85 339 215 G 1A Glom - 1270s. 35.56 34iTL U 0 :. 0 p 0 , 0 . _ 0 .. .. 0: 13rljcs 0.143 w 4.00 2.55 0 0 0 0 0 0 0 0 1A�tom 1270. w 35.56 54.53 0 0 0 0 0 0 0 0 T�G G 1Ac1om 1270 'w 35.56 54.53 0 0 0 0 0 0 0 0 4A5-2om 0.770 w 21.56, 45.63 0 0 0 0 0 0 0 0 P 1260s 0.091 :: -: 2 , . -1.28 ° ... p p p 0 .. 0 0 0 C ,16A30md 0.032 .- 0.90. 2,32 63 " 63 56 146 _0 63 63 56 146 p 22Atpp 0989:'.- 27:69 0.00 63': .. 0 0' 0 . 9 249. 6 c) AED excursion, -10 -28 EnvelopeloWgain 56 136 644 334 12 a) Infiltration 0 0 160 45 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 p 0 p Applianceslother 0 0 Subtotal(lines 6to13) 56 136 804 379 Less extemalload 0 0 0 0 Lesstransfer 0 0 0: 0 Redlstribufion 0 0 0 0 14 Subtotal 56 136 804 ' 379 15 Dud loads 30% 57% 17 77 30% 57% 239 216 Total room load Air required (cfm) 73 214 . 1044 595 3 10 45 CalCula6ons approved bvACCA to meet all requirements of Manual J 8th Ed 2020-Ja!-081622:01 AM = Right<SuteO Universal 201919.0.07 RSU08101 Page 2 ...ts\wdgttmftWACIWYNNE-THE.WINDSOR-IMPACT.rLp Calc=:MJ8 Front Door faces: N AL wtigh Right-J, @ Worksheet �°" Enfire House Date: `QUICK CALLS, INC. By 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@/10L.COM 1 Room name M BATH KITCHEN 2 Exposed volt 8.0 ft 0 ft 3 4 5 Room height Room dimensions Room area 9.4 It , heaV000l 7D x 8.0 ft 56D ft 9A ft heat/cool 1.0 x 172.0 ft 172.0 ftz T.y Construction number U-value (BtuWF) Dr HTM (Btuh/F) Area (W) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter ($) Load (Btuh) Heat Cool -:Gross NIPS Heat Cool Gross NIPS Heat Cool 6 11 13A floes 1A-c1om. '0&2om 13A-4as 13A4ois 1A�lom: ',11D0 13A-4ocs 13A flocs :1Ac1om 13A4ocs 1A-c1om IA-clom 4A5-2om 16A-30md 0.143 1270 0.770 0.143 0.143 1270 0:390 0.143 0.143 4270 0.143 1270 1270 0.770, 0.091 0.032 0.9819-: n n: . n no a .e. :e:• se , s w w w w . -- . - - . 4.00 35:56 21.56 4.00 4.00 3556 1.0.92. 4.00 4.OQ 35.56 4.00 35.56 35.56 21.56 2.55, 0.90 •27.69 2.55 34:77 19.31 2.55 2.55 87:06 11.31 2.65 2.55 34.77 2.55 54.53 54.53 45.63 128 2.32 .: 0.00 .0 0 0 0 0- 0 0 0 75 6 0 0 0 0 0 56 - . 5s ' 0 0 . 0 0 0 0 .. 0 0 69 6 0 0 0 0 ; ; 0 58 _ 8 0 0 0 0 0 0 . .0 0 27Z 213 0 .0 0 0 0, 50 222 0 0 0 0 0 0 .0 0 :.176 209 - 0 0 0 0 0 130 .. . 0 0 0 .0. 0 0. 0 0 0 ; 0 0 0 0 0 0 _ , `75 172 172 0 0 0 0 0 .0 ,0.. 0 : 0 0' 0 0 0 0 75 172 .. 0 0- 0. ° 0.. 0 a 0 0 0; 0 ,0 U 0 0 0 0, 192 154. 0 0 0 0. 0 0: 0. 0 0 U 0 0 0' 0 0 ' . 96 399 ' . , .. 0 G W W G G P . .:.12C-Osw C 6 c) AED excursion -38 �34 Envelope loss(gain 762 477 346 462 12 a) Infiltration b) Room ventilation 142 0 40 0 0 0 0 0 13 Internal gains: Oocupants@ 230 0 0 0 0 Applianceslother 0 0 Subtotal (lines 6 to 13) 904 517 346.. 462 Less ademal load 0 01 0 0 14 Less transfer Redistribution Subtotal 0 0 904 0 0 .517 0 0 346 0 0 462 15 Dudloads 301/o 57% 266 294 30% 57% 103 263 Total room load 1174 811 449 725 Air required (dm) 50 37 19 33 Calculations approved WACCAto meet all requirements of Manual J 8th'Ed. 2020-Jan-081622:01 Aft tiigtt-Su'te@ Uriversal 20l9 l9.0.07 RSU0810l Page 3 tslWrighlsoftHVAC1WYNNE- THE WINDSOR-IMPACT.rLp Calc=.W8 FrontDoorfaces: N -9- wrightsoft° Right-J® Worksheet Entire House QUICK CALCS, INC. 317 ST.,LUCIE LN., FT. PIERCE, FL 34946 Phone:772-466-6799 Fax 772-46"796 Email: QUICKCALCS@�40L.COM Job: Date: By. 1 2 3 4 5 Room name E)q)osed wall Room height Room dimensions Room area BATH 5.0 ft 9.4 ft heall000l 9.0 x 5.0 ft 45.0 ft2 BEDROOM2 42.6 It 9.4 ft heatl000l . 1.0 x 204.0 it 204.0 F Ty Construclion number U-value (BtuhRF--°F) Or HTM (Btuh/ft') Area (ft2) or perimeters (ft) Load (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 -W W 13A-4ocs IA-c16m 4A5.2om 13A-4ocs 13A4ois AA-clom 13A4ors �1Ac1om . IA-c1om IA-ciom 4A5-2om 120-0sw 16A-30md 22A-1pi- 0.143 1270 0.770 0.143 0.143 1.270 0.390, 0.143 .0.143- • 1270 0.143 1270 1270 0.770 0.691 0.032 0.989 ' n ' n' n ne .a a e: se s " s,:':. w w w w - . - 4.00 35b6. 211% 4.00 4.00 35.56 10.92 4.00 4.00 35.56 4.00 35.56 35.56 21.56 2L..5 0.9.0 27.69 2.55 . 34.77 19.31 2.55 .2.55 87.06 - 11.31 2.55 2:55 34:77 2.55 54.53 54.53 _ 45.63 - 1.28. 2.32 0.00 47 0 0 0 0 0 0 0 0 0 0 0 0 0 0 45 45 47 0 0 0 0 0 0 0 ; ; 0 .0 0 0 0 0 0 45 " 5 188 0 0 0 -0 0 0: 0 0 0 0 0 0 0 0 46 138 120 0 0 0 0 0 0 0 0 0 0 0 0 0 0 104 0 132 0 0 27 85 j 20 .. 0 27 132 0 0 0 0 0 0 204 204' 132 0 0 27 65 1 0 27 ' 132 0, 0 0 0 0 0 204 43. 527 :0 0: 106 "" 259 711 0 106 7 . 52 0 0 0 0 0 0 183. 1179 335. , 0 0 68 164: . 1741 0 68 .335 : 0 0 0 0 0 0 473 0 D::11D0' W �13A4ocs G: VVy�13A4ocs G P C F 6 c) AED excursion -17 -99 Envelope loss/gain 367 207 3599 3085 12 - a) Infiltration b) Room ventilation 89 0 25 0 758 0 214 0 13 Intemalgains: Occupants@ 230 0 0 0 0 Appliences/other 0 0 Subtotal (Ilnes6to13) 456 232 4357.. 3299 Less external load 0 0 0 0 14 Lesstransfer Redistribution Subtotal 0 0 456 0 0 232 0 0 4357 0 0 3299 15 Dud loads 30% 57% 136 132 30% 57%1 1297 1876 Total room load Air required (i!m) 592 25 364 16 5654 2431. 5176 233 Calculations approved bvACCA to meet all reaulrements of Manual J 8th Ed. wr7gl�tso `' 2020-Jan-081622:01 MgktSLite@)Uriversal 20l9 l9.0.07 RSU08101 ACC Page 4 ...ts\WdghfsoftHVAC1WYNNE-THEWINDSOR=IMPACT.np CaIc=MJ6 Front Door faces: N wtiightsoW Righ#-J® Worksheet Job: Entire House Date: QUICK CALLS, INC. By 317 ST. LUCIE LN., Fr.. PIERCE, FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name ENTRY LAUNDRY 2 .E)posedmell 6D ft 6.0 It 3 Room height 9.4 'ft heat/cool 9.4 ft heat/000l 4. Room dimensions 1.0 x 92.0 it 7.0 x 6D It 5 Room area 92D ft2 42D ft Ty Construction U-value Or HTM Area Load ter number (Btuhl F) (Btuh&) or perimeter.. (ft) (Btuh) oorperim (ft) (Eituh) Heat Cool Gross N/P/S Heat Cool " Gross N/P/S Heat Cool 6 1 13A4ocs 0.143 n 4.00. 2.55 0 0 0 0 0 0 6 0• G LG 1A-clom '4A5-tom 1270 - n 35.56: 34.77 0' 0 0 0 0 '0 . 0 0:770 ': n 21 S6 . • 1911 .0 0 0 0 0 p p . : p. W 13A4ocs 0.143 ne 4.00 2.55 ' 0 0 0 0 0 0 0 0 11 13Aos 0.143 . ; e 4:00 • .2.55 56 35 142 90 0 , 0. ; 0 . -0 L-i 1Ao1om '11D0 1270 `e 35.56 87.06 0 0 0 0 0 0. 0 0 0.990 .•e: 10.92 : 11;31 21 21 229 : 238 0' 0 W 13A4ocs 0.143 se 4.00 2.55 0 0 0 0 _ 0 0 0 0. 'G 13A�1ors 0:143 .: s' 4:00 2.55 0 A 0 0 56 56 : 226 144 AA�dom .: ;1270 s... 3556 34:77 0 . . 0 0 0 -D .p 0. 0 VVV�13A4ocs 0.143 w 4.00 2.55 0 0 0. 0 0 0 0 0 1A-clom 1270 w 35.56 54.53 0 0 0 0 0 0 0 0 G 1A-clom 1270 w 35.56 54.53 0 0 0 0 0 0 0 0 4A5-2om 0.770 w. 21.56 45.63 0 0 0 0. 0 0 0 0 P 12C-0sw 0.091 ' , '2:56 -. 113 ; 11.3 287, 145 - 66 66 ` 168 84: C 16A-30md 0.032. - 0.90 .128.1 2.32 92 92 82 213 42 42 38. 97 F 22A tpl 0.989 . - 27.69 o.ob ' 92 ' 6 166 0 42 ' 6 166 ,'. ' 0 6 c) AED excursion -49 -24 Envelope lossrgain 907 637 597 301 12 a) .Infiltration 107 30 107 30 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliancestother 0 .0 Subtotal (lines 6 to 13) 1014 667 704 331 Less extemalload 0 0 0 0 Less transfer 0 0 0. 0 Redistribution 0 .0 0 0 14 Subtotal 1014. 667 704 331 15 Duct -loads 30% 57% 302 379 300/. 57% 210 188 Total room load 1367 1047 939 52 Airrequired(dm) 57 47 39 23 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. • wrigti ol9t` 2020-Jarr081622.01 Nght-Sute® Uriversa1201919.0.07 RSU08101 Page 5 ...tslWdghtsoftWACIWYNNE-THEWINDSOR-IMPACT.rup Calc='MJ8 Front Do or faces: N �+ welb' htsofr* Right-M Worksheet Job: Entire House Date: QUICK CALLS, INC. By. 317 ST. LUCIE LN., Fr.. PIERCE, FL 34946 Phone:772-466-6799 Fax 772-466-6796 Emafl: QUICKCALCS AOL.COM 1 Room name GREAT/DWING Room7 2 3 .Exposedvirall Room height SOD It 9.4 ft heat/cool 13.0 1t 9.4 ft heaVcool 4 5 Room dimensions Room area 1.0 x 567.0 ft 567.0 ftz 13.0 x 13.0 ft 169.0 i Ty Construction U-value Or HTM Area � Load number (Btuh/fF-'F) (Bluh/Itz) or perimeter r (ft) (Btuh) orperimeetter (ft) (Btuh) Heat Cool Gross NIPS Heat Cool Gross N/P/S Heat Cool 6 13A-40rs 1Ac1om '4A5-tom 0.143 1270 0.770 n : n n 4.00 35.56 21.66 255 - 34.77 19.31 282 0 38 244 0 0 978 .0 815 622 0 730 . .122 15 - 0 107 - .0 0 429 533 0 273 522 0 11 W 13AAocs 13AAois 0.143 0:143 ne a 4.00 4.00 2.55 2.55 0 0 0 0 0 -0 0 0 0 0.- 0 '0 0 - 0' 0 0 1Ac1om . '11D0 13A-4oc s 1270 0.390 0.143 a e: se 35M 10.92 4.00. 87.06 11.31 2.55 .0 0 0 '0 0 0 0 0 0 0 : 0 0 0- 0 0 6 :0 0 0 0 0 0 : 0 0 D. W. -13A-40cs G',1X616m: ' , 0.143 1270 .. s s 4-.00 35.56 2.55 34,77 ' 0 0 0 -. 0 0 0 ; 0- 0, 0: 0' 0 0 0 0 0. 0 13AAo s IA-clom 1Aclom 0.143 1270 1270 w w w 4.00 35.56 35.56 2.55 54.53 54.53 188 0 0 147 0 0 589 0 0 375 0 0 0 0 0 0 0 0 0 0 0 0 0 0 F-G L�-CG P' - ..::12C-0sw 4A5-2om 0770 0091 w 21.56 2.55.:. 45.6.3 128 41 : 0. 2 0 880 0 1862 0 0 0 0 0 0 0 0 0 C F. 16A30md 22A7tpl- 0.032 0.989 - 0.90 27.69 2.32 0.06 567 567 567 50 506 1385 1315 0 169 169 169 13 151 AM . 392 0 6 c) AED excursion 307 -100 Envelope loss(gain 5154 5210 1474 1086 12 a) Infiltration _ 889 251 231 65 b) Room ventilation 0 .0 0 0 13 Internal gains: Oorupants@ 230 0 0 1 230 Appliancestother 10 0 Subtotal (lines6to 13) 6043 5461 1705, 1381 Less exlemalload 0 0 0 0 Lesstransier 0 0 0 0 Redistribution 0 0 0 0 14 .Subtotal 6043 5461 17.05 1381 15 Ductloads 30% 57% 1799 3105 30% 57% 608 785 Total room load 7843 8566 2213 2167 Air required (dm) 337 386 95. _ 98 Calculations approved WACCAto meet all requirements of Manual J 8th Ed. '� wrigt�tsoTe^ 2020-Jan-081622:01 '" " ..°"" ^ "' Right-Sute® Universal 20191.9.0.07 RSU08101 Page 6 IslWrigtdsoftWAC1WYNNE-THEWINDSOR-IMPACT.nQ CaIc=W8. FrontDoorfaces: N - 1- wrightsoft. Duct System=Summary Entire House QUICK CALCS INC. 317 ST. LUCIE LN., FT. PIERCE, FL 34946.Phone:772-466-6799 Fax 772-466-6796 Email: QUICKCALCS AOL.COM For: WYNNE DEVELOPMENT THE W INDSOR IMPACT, FT. PIERCE, FL Job. Date: By. Heating Cooling Bdemal-static pressure 0 in H2O 0 in H2O Pressure losses 0 in H2O 0 in H2O Available.static pressure 0 in H2O 0 in H2O Supply/:return available pressure 0.000 / 0.000 in H2O 0.000 /0.000 in H2O Lowest friction rate 0 in/100ft 0 in/10Oft Actual airflow 1160 ofm 1160 cfm Total effective length (TEL) 0 ft SupplyDetail Table Name Design (Btuh) Htg (Cfm) CIg (Cfm) Design FR Diam . (in) H x W (in) Duct Mat Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH h .364 25 16 0 0 Ox 0 ShMt 0 0 BEDROOM C 2788 123 126 0 0 Ox 0 ShMt 0 0 BEDROOM2 h 2587 122 117 0 0 Ox0 ShMt 0 0 BEDROOM2-A h 2587 122 117 D 0 Ox0 ShMt 0 0 BEDROOM -A C 2788 123 126 0 0 Ox 0 ShMt 0 0 ENTRY h 1047 57 47 0. 0 .. Ox 0 ShMt 0 0 GREAT/DINING C 2855 112 129 0 0 Ox'0 ShMt 0 0 GREAVDINING-A ' C 2855 112 129 0 0 Ox 0 ShMt 0 0 GREAVDINING-B C 2855 112 129 0 ,- 0 Ox 0 ShMt 0 0 KrrCHEN c 725 19 33 0 0 Ox 0 ShMt. 0 0 LAUNDRY h 520 39 23 0 0 Ox 0 ShMt 0 0 M. BATH' h 811 50 37 0 0 Ox 0 ShMt 0 0 MASTERBATH h 595 45 27 0 0 ox0 ShMt 0 0 Room7 C 2167 95 98 0 0 Ox 0 ShMt 0 0 WIC C 214 3 10 Q 0 ox0 ShMt 0 0 Return Branch Detail Table wil Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Mati Trunk rb1 Ox 0 1160 1160 0 0 0 0 Ox 0 ShMt 2020-Jan-0816:22,02 Wr�gil$SOft® Page 1 �� t�aseue�.b�rrA.w.ar RightSute®Uriversa1201919.0.07RSU08101 ...tlWrigttmftWACIWYNNE-THEWINDSOR=IMPACT.rLp Calc=MJ8 FrontDoorfams: N