Loading...
HomeMy WebLinkAboutFL5896_R4_II_(a) Inst 5896.1 (SOFFIT)Amerimax HOME iRoPRODUCTS,RiN7INC. 450 6o4 PHONE: 717-228-3714 STANDARD V PANEL & STANDARD PERFORATED V PANEL ALUMINUM SOFFIT GENERAL NOTES 1. This product has been evaluated and is in compliance with the 6th Edition (2017) Florida Building Code (FBC) structural requirements including the "High Velocity Hurricane Zone" (HVHZ). 2. Product anchors shall be as listed and spaced as shown on details. Anchor embedment to base material shall be beyond wall dressing or stucco. 3. Site conditions that deviate from the details of this drawing require further engineering analysis by a licensed engineer or registered architect. 4. For design pressure ratings see chart this sheet. 5. Wood/CBS wall construction by others, must be designed properly to receive loads from the soffit and/or 2" x 2" batten strips. 6. All connectors shall be corrosion resistant. 7. Aluminum soffits shall conform to the specification and labeling requirements of FBC Section 1709.10. 8. The perforated panel soffit has been tested for Wind Driven Rain according to TAS 100(A). TABLE OF CONTENTS HOME iRoPRODUCTS,RiN7INC. 450 6o4 PHONE: 717-228-3714 STANDARD V PANEL & STANDARD PERFORATED V PANEL ALUMINUM SOFFIT GENERAL NOTES 1. This product has been evaluated and is in compliance with the 6th Edition (2017) Florida Building Code (FBC) structural requirements including the "High Velocity Hurricane Zone" (HVHZ). 2. Product anchors shall be as listed and spaced as shown on details. Anchor embedment to base material shall be beyond wall dressing or stucco. 3. Site conditions that deviate from the details of this drawing require further engineering analysis by a licensed engineer or registered architect. 4. For design pressure ratings see chart this sheet. 5. Wood/CBS wall construction by others, must be designed properly to receive loads from the soffit and/or 2" x 2" batten strips. 6. All connectors shall be corrosion resistant. 7. Aluminum soffits shall conform to the specification and labeling requirements of FBC Section 1709.10. 8. The perforated panel soffit has been tested for Wind Driven Rain according to TAS 100(A). TABLE OF CONTENTS SHEET # DESCRIPTION 1 Typical elevation, design pressures & general notes 2 Typical anchoring details & soffit details 3 Typical anchoring details & soffit details 4 Bill of materials & components ALUM. 3105-H25 12" STANDARD V PANEL (MAX 24" SPAN) tA' 6 3 z VAAAVAVAAAA\\ kit\\ ALUM. 3105-H25 12" STANDARD PERFORATED V PANEL (MAX 24" SPAN) DESIGN PRESSURE (PSI) SOFF17 T MODEL POSITIVE NEGATIVE 12" STANDARD V PANEL SOFFITT +50.0 -50.0 12 STANDARD V PANEL SOFFITT +50.0 -50.0 (PERFORATED) .�� Lo to '••�; % J=U M c °' `� '0+� orn m in O N z a; Z 0 a t0 m c W a V)rri 56. r m d- m na D_ LL m C C6 E 0 V C W 0 3, U]w z W CDo �C� inz U �I_ p J ono zw Cr Lw cn o z °' QQD zii =W� LLJ '> � wV) C Q Li, XQz Q Qct� H ¢� O UC/) LLJ } W LLJ CL d Q CL d m m DATE: 03/23/09 SCALE: N. T. S. DWG. BY: DWS CHK. BY: LFS DRAWING NO.: FL-5896.1 SHEET 1 OF 4 �:' ••. Lo 17' MAX. 12" MAX. = Z' a0 Q -z n U' rn z° 41: O.: � ACTUAL ROOF PITCH VARIES 00% y,; z °o M RAFTER (G = 0.42 OR BETTER) "- j•'•..••• ���` to MAX. 24" O.C. SPACING �1i •`� `�� > > _M m ACTUAL ROOF PITCH VARIES m V N RAFTER (G = 0.42 OR BETTER) EMBEDMENT v 0 x z d o V MAX. 24" O.C. SPACING (\ a s m 25 z 00 c w U It -' o a n NIt man.m 7 a c-�'- a =Z a e cw 7 7 16" O.C. MAX. $ 9 a a O J a a 24" O.C. a EDGE z w J MAX. a a a a a Q DISTANCE Q Lam—,_ a a cr Li- o J o�0 cn o�<- oQ-� zw ° a z r O� a w-'d �� m =L� �JZ:) :2 z� OwJ W O a e =Z4 a Qtn 3 2 2 1 _qw Q �wz �� 00 SEE DETAIL "A" FOR 3 oLn o it LL J CHANNEL INSTALLATION a `=Lo 0- ^ TYP INSTALLATION ON A WOOD WALL SEE DETAIL "B" FOR o SOFFIT INSTALLATION (TYP.) TYP INSTALLATION ON A CBS WALL SEE DETAIL "A" FOR m J CHANNEL INSTALLATION SEE DETAIL "B" FOR tn SOFFIT INSTALLATION (TYP.) m m .3 ^� 0 o N ti Z w no o O EXISTING STRUCTURE EXISTING STRUCTURE 7 > ��o m00 8 6 F- 7 �w- �L-ucl Q 8 4 9 » a 0 Lli 4 INSTALLED AT EACH � M o Q o @ 12" O.C. PANEL OVERLAP JOINT HORIZONTALLY (12" MAX. O.C.) f N „ O if DATE: 03/23/09 < 2 1 SCALE: N.T.S. DWG. BY: DWS E DETAIL "A" DETAIL "B" CHK. BY: LFS J CHANNEL INSTALLATION SOFFIT INSTALLATION DRAWING NO.: Q FL-5896.1 SHEET 2 of 4 v' VA 3 0. om 24" O.C. MAX. SPACING FOR THE STRUCTURAL SUPPORT (BY OTHERS) OF THE 2" X 2" BATTEN STRIPS (211 24" MAX. INSTALLED AT EACH 5 f_JPANEL OVERLAP JOINT. (TYP.) / 4 SEE DETAIL "A" SHEET #2 FOR J CHANNEL INSTALLATION 7 V SEE DETAIL "B" SHEET #2 FOR SOFFIT INSTALLATION TYP. INSTALLATION ON A WOOD WALL TYP. INSTALLATION ON A CBS WALL 24" O.C. MAX. ACTUAL ROOF PITCH VARIES RAFTER (G = 0.42 OR BETTER) MAX. 24" O.C. SPACING 7 16" O.C. MAX. 8 7 16" O.C. MAX. 8 ACTUAL ROOF PITCH VARIES RAFTER (G = 0.42 OR BETTER) MAX. 24" O.C. SPACING 2" BATTEN Sl SOFFIT OVE CUT OU CL EDGE DISTANCE 1 LOOKING UP @ SOFFIT 3 N. T. S. A, . ir rn lx...3 o M Q=Z J •;�j Tell: Qz vi z00 co- 3 •''••• .�` J > (D m cn O rci o0 z6 m� U 04 •• a Z D Z U Ern m � 0. tO c W d NM � z00- m 0 0 oz o c ui o � a z � J 00o a1L5zw E2c� w43� m oz� zz< inQO xa¢w a �� CK 0 §�z 0 CL � �� a a a v m oo� ui `D L o 000Q lu-, 000 ct n. ci DATE: 03/23/0 SCALE: N. T. S. DWG. BY: DWS CHK. BY: LFS DRAWING NO.: FL-5896.1 SHEET 3 OF 4 I om um BILL OF MATERIALS ITEM DESCRIPTION MATERIAL 1 STANDARD V PANEL SOFFIT 0.017' THK. ALUMINUM 3105 H25 ALUMINUM 2 STANDARD PERFORATED V PANEL SOFFIT 0.017" THK. ALUMINUM 3105 H25 ALUMINUM 3 STANDARD "J" CHANNEL 0.0175" THK. ALUMINUM ALUMINUM 4 11 GA. 0.125" MIN. x 1" LONG ROOFING NAIL WITH 7/16" DIA. HEAD STEEL 5 #8 x 1" PPH SMS STEEL 6 2" x 2" BATTEN STRIP SOUTHERN YELLOW PINE G = 0.55 OR BETTER WOOD 7 10d COMMON NAIL 3" LONG STEEL 8 #8 x 2-1 /2" PFH WOOD SCREW STEEL 9 13/1 G" x 2-3/4" ELCO ULTRACON CONCRETE SCREW; EMBEDMENT = 1.25" MIN., EDGE DISTANCE = 1" MIN., CENTERLINE TO ADJACENT ANCHORS = 4" MIN. STEEL SUBSTRATE NOTES: 1. WOOD SUBSTRATE: G = 0.42 OR BETTER 2. MASONRY SUBSTRATE: 3,000 PSI CONCRETE (ACI 301) OR HOLLOW BLOCK (ASTM C90). "V' PANEL AIR FLOW SOFFff FREE FLOW AREA % FREE FLOW fn2/ft2) AREA PERFORATED 11.23 7.8% I.R..250" Typ .072" MIN t�- - VIEWA - A PERFORATION DETAIL 2X SCALE I'i'1�1�1'1'I'1 6" 1.21" <O C7 M TYP. C) O.R..020" TYP. �—.25a' x I I I II I �I I I I I I II I � II C* i t I II I I II 1 6" «M M O.R..029' TYP. I-- .250" F- A �-- A 0.5" TYP. 1.81z' 5.963N' OSTANDARD PERFORATED V PANEL SOFFIT 0.27' 1" F� M CO v, y ` ZI OSTANDARD V PANEL SOFFIT h d o � Ii II 0.125" M a TYP. o 0.25' TYP. RIB.125 R X.02 DP. NI RIB .125RX.02DIP. / .039' R.085" 1 � A / to to Q0 CD 0 t M 1 U N .. _Z 0 zU l� o E0 m \, m 0 -� 0 III �� m n a m .259' o a z l�tl U [ Li a: 0 J I I z' W —C)En CV M c�OOt�i Z ono wz Q aLd V) Q o a w� m , L- O_J� W OU zJ Q J_z D W O a Qc~n° a NCC j VIEW SHOWN FOR REFERENCE .470" R.050" TYP. OUTSIDE .259' O STANDARD "J" CHANNEL I 04 = m c^C5 Ulu N N T z Woo O W 0 0 0 a d Q- tl 0 0 z W N M O < F I 0 0 V) o L9 z U "z DATE:03123109 i 0 SCALE: N. T. S. 5 DWG. BY: DWS m CHK. BY: LFS 3 DRAWING NO.: m FL-5896.1 0 N SHEET 4 OF 4