HomeMy WebLinkAboutEVANS- MANUAL J (1)Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Nov-13 12:43:47
Right-Suite® Universal 2019 19.0.08 RSU08101 Page 1
...nets\Wrightsoft HVAC\EVANS RESIDENCE- AVE T.rup Calc = MJ8 Front Door faces: N
Job:Project Summary Nov 13, 2020Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
Project Information
KEITH EVANSFor:
3003 AVENUE T, FORT PIERCE, FL
Notes:
Design Information
Fort Pierce, FL, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F42 Outside db °F90
Inside db °F70 Inside db °F75
Design TD °F28 Design TD °F15
Daily range M
Relative humidity %50
Moisture difference gr/lb61
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh14722 Struc ture Btuh14025
Ducts Btuh2673 Ducts Btuh3884
Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0
(none)(none)
Humidification Btuh0 Blower Btuh0
Piping Btuh0
Equipment load Btuh17395 Use manufacturer's data n
Rate/swing multiplier 0.95
Infiltration Equipment sensible load Btuh17013
Method Latent Cooling Equipment Load SizingSimplified
Construction quality Average
0Fireplaces Structure Btuh2766
Ducts Btuh1023
Central vent (0 cfm)Btuh0
CoolingHeating (none)
988988Area (ft²)Equipment latent load Btuh3789
79047904Volume (ft³)
Air changes/hour 0.230.45 Equipment Total Load (Sen+Lat)Btuh20802
Equiv. AVF (cfm)3059 Req. total capacity at 0.70 SHR ton2.0
Heating Equipment Summary Cooling Equipment Summary
Make Make Goodman Mfg.
Trade Trade GOODMAN
Model Cond GSX16S241A
AHRI ref Coil ASPT30C14A
AHRI ref 201786067
Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW4.7 Sensible cooling Btuh16520
Heating output Btuh16156 Latent cooling Btuh7080
Temperature rise °F19 Total cooling Btuh23600
Actual air flow cfm787 Actual air flow cfm787
Air flow factor cfm/Btuh0.045 Air flow factor cfm/Btuh0.044
Static pressure in H2O1.00 Static pressure in H2O1.00
Space thermostat Load sensible heat ratio 0.83
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Nov-13 12:43:47
Right-Suite® Universal 2019 19.0.08 RSU08101 Page 1
...nets\Wrightsoft HVAC\EVANS RESIDENCE- AVE T.rup Calc = MJ8 Front Door faces: N
Job:Right-J® Worksheet
Nov 13, 2020Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name Entire House BEDROOM 2
2 Exposed wall 134.0 ft 21.0 ft
3 Room height 8.0 ft 8.0 heat/coolft
4 Room dimensions ft116.0x1.0
5 Room area 988.0 ft²116.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 200 164 655 358 0 0 0 0
.GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 nn 29.4029.40 20.9920.99 16 0 470 336 0 0 0 0
.DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 20 20 223 211 0 0 0 0
.WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 336 294 1177 643 80 68 272 149
11 GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ee 29.4029.40 39.7739.77 18 0 529 716 0 0 0 0
GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ee 29.4029.40 39.7739.77 24 0 706 955 12 0 353 477
WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 200 200 801 438 88 88 352 193
WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 336 281 1127 616 0 0 0 0
GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ww 29.4029.40 39.7739.77 9 0 265 358 0 0 0 0
GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ww 29.4029.40 39.7739.77 9 0 272 368 0 0 0 0
GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ww 29.4029.40 39.7739.77 16 0 470 636 0 0 0 0
DD 11D011D0 0.3900.390 ww 10.9210.92 10.3410.34 20 20 223 211 0 0 0 0
CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 988 988 885 1581 116 116 104 186
FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 988 134 5095 0 116 21 799 0
6 c) AED excursion 0 -69
Envelope loss/gain 12898 7425 1880 935
12 a) Infiltration 1824 499 286 78
b) Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 6100 1000
Subtotal (lines 6 to 13)14722 14025 2166 2013
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 105 41
14 Subtotal 14722 14025 2270 2055
15 Duct loads 18%28%2673 3884 18%28%412 569
Total room load 17395 17909 2683 2624
Air required (cfm)Air required (cfm)787 787 121 115
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Nov-13 12:43:47
Right-Suite® Universal 2019 19.0.08 RSU08101 Page 2
...nets\Wrightsoft HVAC\EVANS RESIDENCE- AVE T.rup Calc = MJ8 Front Door faces: N
Job:Right-J® Worksheet
Nov 13, 2020Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name CLST 2 MASTER BEDROOM
2 Exposed wall 2.0 ft 25.0 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft7.0x2.0 ft13.0x12.0
5 Room area 14.0 ft²156.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 nn 29.4029.40 20.9920.99 0 0 0 0 0 0 0 0
.DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0
.WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0
11 GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ee 29.4029.40 39.7739.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ee 29.4029.40 39.7739.77 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 16 16 64 35 96 96 384 210
WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 104 88 352 193
GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ww 29.4029.40 39.7739.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ww 29.4029.40 39.7739.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ww 29.4029.40 39.7739.77 0 0 0 0 16 0 470 636
DD 11D011D0 0.3900.390 ww 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0
CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 14 14 13 22 156 156 140 250
FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 14 2 76 0 156 25 951 0
6 c) AED excursion -2 132
Envelope loss/gain 153 55 2298 1420
12 a) Infiltration 27 7 340 93
b) Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 0 1200
Subtotal (lines 6 to 13)180 63 2638 2713
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution -180 -63 88 43
14 Subtotal 0 0 2726 2756
15 Duct loads 18%28%0 0 18%28%495 763
Total room load 0 0 3220 3520
Air required (cfm)Air required (cfm)0 0 146 155
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Nov-13 12:43:47
Right-Suite® Universal 2019 19.0.08 RSU08101 Page 3
...nets\Wrightsoft HVAC\EVANS RESIDENCE- AVE T.rup Calc = MJ8 Front Door faces: N
Job:Right-J® Worksheet
Nov 13, 2020Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name BEDROOM 3 M CLST
2 Exposed wall 13.0 ft 0 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft13.0x10.0 ft2.0x7.0
5 Room area 130.0 ft²14.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 nn 29.4029.40 20.9920.99 0 0 0 0 0 0 0 0
.DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0
.WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 104 92 368 201 0 0 0 0
11 GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ee 29.4029.40 39.7739.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ee 29.4029.40 39.7739.77 12 0 353 477 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ww 29.4029.40 39.7739.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ww 29.4029.40 39.7739.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ww 29.4029.40 39.7739.77 0 0 0 0 0 0 0 0
DD 11D011D0 0.3900.390 ww 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0
CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 130 130 116 208 14 14 13 22
FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 130 13 494 0 14 0 0 0
6 c) AED excursion -64 -1
Envelope loss/gain 1332 822 13 22
12 a) Infiltration 177 48 0 0
b) Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 1000 0
Subtotal (lines 6 to 13)1509 1871 13 22
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 15 26 -13 -22
14 Subtotal 1524 1897 0 0
15 Duct loads 18%28%277 525 18%28%0 0
Total room load 1801 2422 0 0
Air required (cfm)Air required (cfm)81 106 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Nov-13 12:43:47
Right-Suite® Universal 2019 19.0.08 RSU08101 Page 4
...nets\Wrightsoft HVAC\EVANS RESIDENCE- AVE T.rup Calc = MJ8 Front Door faces: N
Job:Right-J® Worksheet
Nov 13, 2020Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name M BATH LAUNDRY
2 Exposed wall 6.0 ft 8.0 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft42.0x1.0 ft8.0x8.0
5 Room area 42.0 ft²64.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 nn 29.4029.40 20.9920.99 0 0 0 0 0 0 0 0
.DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0
.WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0
11 GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ee 29.4029.40 39.7739.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ee 29.4029.40 39.7739.77 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 48 48 192 105 64 55 220 120
GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ww 29.4029.40 39.7739.77 0 0 0 0 9 0 265 358
GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ww 29.4029.40 39.7739.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ww 29.4029.40 39.7739.77 0 0 0 0 0 0 0 0
DD 11D011D0 0.3900.390 ww 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0
CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 42 42 38 67 64 64 57 102
FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 42 6 228 0 64 8 304 0
6 c) AED excursion -15 94
Envelope loss/gain 458 157 846 674
12 a) Infiltration 82 22 109 30
b) Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 250 250
Subtotal (lines 6 to 13)540 430 955 954
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 4 7 2 4
14 Subtotal 544 437 958 958
15 Duct loads 18%28%99 121 18%28%174 265
Total room load 642 558 1131 1224
Air required (cfm)Air required (cfm)29 24 51 54
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Nov-13 12:43:47
Right-Suite® Universal 2019 19.0.08 RSU08101 Page 5
...nets\Wrightsoft HVAC\EVANS RESIDENCE- AVE T.rup Calc = MJ8 Front Door faces: N
Job:Right-J® Worksheet
Nov 13, 2020Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name BATH 2 AHU/WH CLST
2 Exposed wall 0 ft 0 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft8.0x4.0 ft3.0x4.0
5 Room area 32.0 ft²12.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 nn 29.4029.40 20.9920.99 0 0 0 0 0 0 0 0
.DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0
.WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0
11 GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ee 29.4029.40 39.7739.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ee 29.4029.40 39.7739.77 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ww 29.4029.40 39.7739.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ww 29.4029.40 39.7739.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ww 29.4029.40 39.7739.77 0 0 0 0 0 0 0 0
DD 11D011D0 0.3900.390 ww 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0
CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 32 32 29 51 12 12 11 19
FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 32 0 0 0 12 0 0 0
6 c) AED excursion -15 -1
Envelope loss/gain 29 36 11 19
12 a) Infiltration 0 0 0 0
b) Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 400 0
Subtotal (lines 6 to 13)29 436 11 19
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 16 27 -11 -19
14 Subtotal 44 463 0 0
15 Duct loads 18%28%8 128 18%28%0 0
Total room load 52 591 0 0
Air required (cfm)Air required (cfm)2 26 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Nov-13 12:43:47
Right-Suite® Universal 2019 19.0.08 RSU08101 Page 6
...nets\Wrightsoft HVAC\EVANS RESIDENCE- AVE T.rup Calc = MJ8 Front Door faces: N
Job:Right-J® Worksheet
Nov 13, 2020Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name HALL LIVING RM
2 Exposed wall 0 ft 28.0 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft13.0x3.0 ft185.0x1.0
5 Room area 39.0 ft²185.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 104 68 271 148
.GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 nn 29.4029.40 20.9920.99 0 0 0 0 16 0 470 336
.DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 0 0 0 0 20 20 223 211
.WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 120 102 408 223
11 GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ee 29.4029.40 39.7739.77 0 0 0 0 18 0 529 716
GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ee 29.4029.40 39.7739.77 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ww 29.4029.40 39.7739.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ww 29.4029.40 39.7739.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 1.0502 glazing, clr low-e 1.050 ww 29.4029.40 39.7739.77 0 0 0 0 0 0 0 0
DD 11D011D0 0.3900.390 ww 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0
CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 39 39 35 62 185 185 166 296
FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 39 0 0 0 185 28 1065 0
6 c) AED excursion -2 -94
Envelope loss/gain 35 60 3132 1836
12 a) Infiltration 0 0 381 104
b) Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 0 800
Subtotal (lines 6 to 13)35 60 3513 2740
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution -35 -60 6 10
14 Subtotal 0 0 3519 2750
15 Duct loads 18%28%0 0 18%28%639 762
Total room load 0 0 4158 3512
Air required (cfm)Air required (cfm)0 0 188 154
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Nov-13 12:43:47
Right-Suite® Universal 2019 19.0.08 RSU08101 Page 7
...nets\Wrightsoft HVAC\EVANS RESIDENCE- AVE T.rup Calc = MJ8 Front Door faces: N
Job:Right-J® Worksheet
Nov 13, 2020Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name KITCHEN
2 Exposed wall 31.0 ft
3 Room height 8.0 heat/coolft
4 Room dimensions ft184.0x1.0
5 Room area 184.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area Load
number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 W 13A-4ocs 0.143 n 4.00 2.19 96 96 384 210
.G 2 glazing, clr low-e 1.050 n 29.40 20.99 0 0 0 0
.D 11D0 0.390 n 10.92 10.34 0 0 0 0
.W 13A-4ocs 0.143 e 4.00 2.19 32 32 128 70
11 G 2 glazing, clr low-e 1.050 e 29.40 39.77 0 0 0 0
G 2 glazing, clr low-e 1.050 e 29.40 39.77 0 0 0 0
W 13A-4ocs 0.143 s 4.00 2.19 0 0 0 0
W 13A-4ocs 0.143 w 4.00 2.19 120 90 362 198
G 2 glazing, clr low-e 1.050 w 29.40 39.77 0 0 0 0
G 2 glazing, clr low-e 1.050 w 29.40 39.77 9 0 272 368
G 2 glazing, clr low-e 1.050 w 29.40 39.77 0 0 0 0
D 11D0 0.390 w 10.92 10.34 20 20 223 211
C 16B-30ad 0.032 -0.90 1.60 184 184 165 294
F 22A-tph 1.358 -38.02 0.00 184 31 1179 0
6 c) AED excursion 37
Envelope loss/gain 2713 1388
12 a) Infiltration 422 116
b) Room ventilation 0 0
13 Internal gains:Occupants @ 230 0 0
Appliances/other 1200
Subtotal (lines 6 to 13)3135 2704
Less external load 0 0
Less transfer 0 0
Redistribution 3 5
14 Subtotal 3138 2709
15 Duct loads 18%28%570 750
Total room load 3707 3459
Air required (cfm)168 152
2020-Nov-13 12:43:51
Right-Suite® Universal 2019 19.0.08 RSU08101 Page 1
...nets\Wrightsoft HVAC\EVANS RESIDENCE- AVE T.rup Calc = MJ8 Front Door faces: N
Job:Duct System Summary Nov 13, 2020Date:
Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
Project Information
KEITH EVANSFor:
3003 AVENUE T, FORT PIERCE, FL
CoolingHeating
External static pressure in H2O1.00in H2O1.00
Pressure losses in H2O0in H2O0
Available static pressure in H2O1.00in H2O1.00
Supply / return available pressure 0.500 / 0.500 in H2O in H2O0.500 / 0.500
Lowest friction rate in/100ft1.000in/100ft1.000
Actual air flow cfm787cfm787
Total effective length (TEL)ft137
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv
Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk
95.02.0VlFx0x05.01.000262591cBATH 2
st1115.022.2VlFx0x07.01.0001151212683hBEDROOM 2
st1115.017.3VlFx0x07.01.000106812422cBEDROOM 3
st2115.010.0VlFx0x08.01.0001521683707hKITCHEN
st2115.013.1VlFx0x06.01.00054511224cLAUNDRY
st2115.014.4VlFx0x08.01.0001541884158hLIVING RM
st1115.016.1VlFx0x05.01.0002429642hM BATH
st1115.014.2VlFx0x08.01.0001551463520cMASTER BEDROOM
Supply Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
st1 Peak AVF 377 401 1.000 735 10.0 0x0 VinlFlx
st2 Peak AVF 407 360 1.000 746 10.0 0x0 VinlFlx
Return Branch Detail Table
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk
rb1 0x 7870 787 0 0 0 0 x0 0 VlFx
���������������������������������������������������������������������������
���������������������������������������������������������������������������������
�����������������������������������������������������