ST LUCIE COUNTY FIRE DISTRICT
BUREAU OF FIRE PREVENTION
PLAN REVIEW
Telephone: 561-462-2312
FAX: 561-462-2323
(vJ New Construction ( )Tenant Improvement ( )Addition ( )Renovation/alterations
( )Shell Only
Jurisdiction: SLC F.P.B.:
B-01-48
Occupancy: Masonic Lodge Building Dept:
21010464
Address: 4590 Oleander Blvd Number of stories:
1
Contractor G.M. Worley, Inc Phone #
863-467-2541
Contractor's Address' 110 NW 5th St. City:
Okeechobee
Architect/Engineer: Moseley C. Collins Phone #
863-763-1600
Building Owner: Review Date:
4/10/2001
Occupancy Type: Assembly >300 Automatic sprinklers:
Yes
Gross sq ft: 4,992 Net sq ft:
Occupant Load: Based On:
Construction Type: SBCCI Type:
VI unp
NOTE
,1.
All revisions must be in compliance before the final inspection.
2. The Fire Marshal requires 24 hour notice on all inspections.
3. The respective Building Department shall schedule all final inspections through. the Fire Marshal's Office.
4. Permit fees are required to be paid in full prior to any inspections.
5. Failed inspections require payment of fee prior to rescheduling of further inspections.
6. A copy of the required revision/s have been transmitted to the Architect ( X ) Contractor
( X ).
7. Penetrations through rated assemblies shall be of proper UL design.
8. UL design criteria shall be submitted with the construction plans.
REVISIONS REQUIRED
KNOX BOX IS REQUIRED (XX ) KNOX KEY SWITCH REQUIRED ( )
04 2.
oK 3.
pv. 4.
-0�- 5.
o4 6.
7.
0- 8.
dl 9.
ojC 10
Based on the maximum probable occupancy load of the space under consideration the building
occupant load is in excess of 300 persons. Therefore an automatic fire sprinkler system installed
in acordance with NFPA 13, 1999 edition is required.
A separate permit is required for the installation of the fire sprinkler system.
The installation of a fire alarm system is required under separate permit.
An application for the KNOX Box may be obtained at this office.
The fixed fire protection system required shall be interconnected with the fire alarm system.
A separate permit is required for the installation. of the fixed fire protection system.
Assembly occupancies over 30 persons require exit access to be separated from the remainder of
the building by 1 hour construction. Therefore the hall and entry areas shall be rated 1 hour.
Automatic fan shutdown is required for the HVAC system. See attached requirements.
See note 7 above.
Store room in entry area: Change the door swing so when the door is open it will not block the
required exit door from the "Assembly area." Provide a door closer.
Provide an exit light fixture above the south exit door of the assembly room.
Stairs and ramps are required to have handrails on both sides of the stairs.
B-01-48
continued
11�—1 1. Exit doors are required to have panic hardware. This includes doors leading out of the assembly
room.
gf- 12. Provide an exit light fixture above the exterior kitchen exit door.
13. Portable fire protection is required every 75 feet of travel distance. Minimum classification is
2A-10B:C
Reviewed by: ��J2/ `�l1
Date: 4/10/2001