HomeMy WebLinkAboutRight-N-Zone Summaryi 1 - SIN YWW'213193 t RIGHT-N ZONE SUNMARY Units: U.S. customary (I—P) Nov 26, 2000 .+ For: -FT. PIERCE MASONIC LODGE f By: WOLF AIR CONDITIONING` Job #: Zone: TWO f V COOLING LOAD 1. DESIGN CONDITIONS at 3 PM Peak load at 3 PM Inside: 75 OF Outside: 90 OF TD: 15 OF RH: 50 % Moisture: 61 gr/lb Mult: 1.0 Ins.wb 63 OF Sensible Latent 2. SOIJLR RADIATION THROUGH GLASS 0 - 3. TRANSMISSION GAINS Sensible 13596 - Walls: 532 - - Glass: 0 - - Doors: 673 - - Partitions: 0 - - Floors: 0 - - Roofs/Ceilings: 5578 - - Return Air Ceiling: 6813 - - 4. INTERNAL HEAT GAIN Sensible Latent 27737 10500 Occupants: 22500 10500 - - Lights: 5 2 3 7 0 - - Motors: 0 0 - - Appliances & Other: 0 0 - - 5. INFILTRATION: Outside air cfm: 0 0 0 6. SUBTOTAL: Space load 41333, 10500 7. SUPPLY DUCT 1240 - 8. SUBTOTAL: Bldg comp's and supply duct 42573 Actual cfm: 1935 at Supply TD: 20 - - 9. VENTILATION: Make—up air cfm: 450 7425 18792 10. RETURN AIR LOAD: Lighting & roof (net) 1916 - 11. RETURN DUCT 0 12. TOTAL LOADS ON EQUIPMENT 5191 2 92 92 HEATING LOAD 13. DESIGN CONDITIONS Mult: 1.0 Inside: 70 OF Outside: 42 OF TD: 28 OF _ 14. TRANSMISSION LOSSES 8679 _ Walls: 1551 Glass: 0 - Doors: 1257 Partitions: 0 - Floors: 1102 - Roofs/Ceilings: 2384 - Return Air Roof: 2384 - 15. INFILTRATION: Outside air cfm: 150 4622 16. SUBTOTAL: Building components 13302 17. SUPPLY DUCT: 665 18. VENTILATION: Make—up air cfm: 450 13860 19. HUMIDIFICATION 7261 20. RETURN DUCT 0 21. TOTAL HEATING LOAD ON EQUIPMENT 35088 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manuai Form N .' SIN RI W213 9 3 RIGHT-N ZONE SiJMIIV1ARY Units; U.S. customary (I—P) For: FT. PIERCE MASONIC LODGE By: WOLF AIR CONDITIONING Job #: Nov 26, 2000 Zone: ONE f� COOLING LOAD 1. DESIGN CONDITIONS at 3PK Peak load at 3PM ° Inside:' 7 5' CO F �' ..Outside:5;.,,:.- 90 .:' F Moisture: 61 TD: Mult: 15 F 1.0 Ins.wb 63 °F RH: 50 % gr/lb Sensible Latent 2. SOLAR RADIATION THROUGH GLASS 5536 - " 3. TRANSMISSION GAINS Sensible 29624 Walls: 2354 - - Glass: 1461 Doors: 8421 Partitions: 0 - Floors: 0 - - Roofs/Ceilings: 7823 Return Air Ceiling: 9565 4. INTERNAL HEAT GAIN Sensible Latent 16875 " 6630 Occupants: 9500 6630 - Lights: 7375 0 _ Motors: 0 0 - Appliances & Other: 0 S. INFILTRATION: Outside air cfm: 0 150 - 2481 6278 6. SUBTOTAL: Space load 54516 1635 12908 7.. SUPPLY DUCT 56152 - 8. SUBTOTAL: Bldg comp's and supply duct Actual cfm: 2675 at Supply TD: 20 750 - 1233795 - 31320 9. VENTILATION: Make—up air cfm: 7 10. RETURN AIR LOAD: Lighting & roof (net) 11. RETURN DUCT 71224 - 44228 12. TOTAL, LOADS ON EQUIPMENT HEATING LOAD 13. DESIGN CONDITIONS Mult: 1.0 OF Inside: 70 OF Outside: 42 OF TD: 28 14. TRANSMISSION LOSSES 36960 Walla: 6495 ' Glass: 2727 - Mors: 15 719 - Partitions: 0 Floors: 5330 Roofs/Ceilings: 3344 - Return Air Roof: 3344 15. INFILTRATION: Outside air cfm: 392 - 12071 16. SUBTOTAL: Building components 49031 2318 17. SUPPLY DUCT: 18. VENTILATION: Make—up air cfm: 750 23100 19. HUMIDIFICATION 13 817 0 20. RETURN DUCT 21. TOTAL HEATING LOAD ON EQUIPMENT 88266 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N r SIN JRNW21393 RIGHT-N ZONE SUMMARI Units: U.S. customary (I—P) % t For: FT. PIERCE MASONIC LODGE By: WOLF AIR CONDITIONING Job #: Nov 26, 2000 Zone: ASSEMBLY ROOM COOLING LOAD 1. DESIGN CONDITIONS at 3 PM ' Peak load at 3 PM Inside: 75 OF Outside: 90 OF TD: i 5 OF RH: 50 % Moisture: 61 qr/lb Mult: 1.0 Ins.wb 63 OF Sensible Latent 2. SOLAR RADIATION THROUGH GLASS 0 - 3. TRANSMISSION GAINS Sensible 13596 - Walls: 532 - - Glass: 0 - - Doors: 673 - - Partitions: 0 - - Floors: 0 - - Roofs/Ceilings: 5578 - - Return Air Ceiling: 6813 - - 4. INTERNAL HEAT GAIN Sensible Latent 27737 10500 Occupants: 22500 10500 - - Lights: 5237 0 - - Motors: 0 0 - - Appliances & Other: 0 0 - - 5. INFILTRATION: Outside air cfm: 0 0 0 6. SUBTOTAL: Space load 41333 10500 7. SUPPLY DUCT 1240 S. SUBTOTAL: Bldg comp's and supply duct 42573, .. _ Actual cfm: 1935 at SupplyTD: 20 - - 9. VENTILATION: Make—up air cfm: 450 7425 18792 10. RETURN AIR LOAD: Lighting & roof (net) 1916 - 11. RETURN DUCT 0 - 12. TOTAL LOADS ON EQUIPMENT 51914 2 92 92 HEATING LOAD 13. DESIGN CONDITIONS , Mult: 1.0 Inside: 7 0 OF Outside: 42 OF TD: 28 OF 14. TRANSMISSION LOSSES 8679 Walls; 1551 - Glass: 0 - Doors: 1257 - Partitions: 0 - Floors: 1102 - Roofs/Ceilings: 2384 - Return Air Roof 2384 - 15. INFILTRATION: Outside air cfm: 150 4622 16. 'SUBTOTAL: Building components 13302 17. SUPPLY DUCT: 665 18. VENTILATION: Make—up air cfm: 450 13860 19. HUMIDIFICATION 7261 20. RETURN DUCT 0 21. TOTAL HEATING LOAD ON EQUIPMENT 35088 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N , f ' S/ N RNW213 9 3 RIGHT-N COMMERCIAL / INDUSTRIAL LOAD CALCULATION Nov 26, 2000 For: FT. PIERCE MASONIC LODGE Zone: ASSEMBLY ROOM Page: 1 Job #: City: Fort Pierce, FL, US By: WOLF AIR CONDITIONING LWH: 48.6 x 38.6 x 16.0 Units: U.S. customary (I-P) 1:. DESIGN CONDITIONS - COOLING ( 3 PM , August ) Dry Blb RH Moisture Range Wet Bib Outdoor Conditions > 90 59 15 78 Indoor -Conditions > 75 50 63 TOD Correction > 0 - Difference 15 61 [ Mult = 1.0 ] -- 2. GLAZING SOLAR HEAT 4 GAIN ( Lat = 27.00 ° N , Const Wt = M ) Type Dir Shad Tilt %ovr Area Sfact Shgf Shad Sens GLAZ 1 E N 90 0.0 0 0.98 64 1.0 0 3. TRANSMISSION GAINS Type Dir GrArea NtArea Uval Grp CLTD Shad Clr Sens GLAZ 1 E 0 0 0.500 15.0 N - 0 WALL 1 S 486 486 0.114 B •9.6 AT L 532 WALL 1 E 0 0 0.114 B 16.1 N L 0 DOOR 1 N 0 0 0.560 15.0 -- - 0 DOOR 2 W 0 0 1.100 15.0 - - 673 FLOR 1 - 49 49 0.810 0.0 - - 0 ROOF 1 - 2129 2129 0.040 R-4. 65.5 - D 5578 RARE 1 - 2129 2129 0.040 R-4 61.5 - - 5237 RACL 1 - 2129 2129 0.800 4:0 - - 6813 4. INTERNAL HEAT GAIN Sens Latent People 100 x Per person: sensible 225 latent 105 22500 10500 0 x Per person: sensible 300 latent 300 0 0 ' Lights Incandescents in RA Ceiling 0 x 3.4 x 60% 0 Fluorescents in RA Ceiling 2129 x 4.1 x 60% 5237 •Incandescents other 0 x 3.4 x 100% 0 Fluorescents other 0 x 4.1 x 100% 0 Motors Nmbr Power Gain Load Fact Usage 1 1 0.00 0 1.00 1.00 0 2 1 ` 0.00 0 1.00 1.00 0 ` 3 1 0.00 0 1.00 1.00 0 Appl. Nmbr Type Sens Latent Usage 1 1 0 0 1.00 0 0 2 1 0 0 1.00 0 0 ' - 3 1 0 0 1.00 0 0 4 1 0 0 1.00 0 0 5 1 0 0 1.00 0 0 Other 1 0 0 1.00 0 0 _ S. INFILTRATION Sens Latent 0 cim > x db Temp Diff 15.0 x 1.1 0 • > x Moist. Diff 61.4 x 0.68 ' 0 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N Jov #: Page: 2 6. SUBTOTAL �OOLING LOAD FOR SPACE 41333 10500 7. SUPPLY DUCT HEAT GAIN Gain factor 0.03 x Line 6 Sensible Gain 1240 8. COOLING FAN SIZING Sum of Duct Gain (7 ), Line (6) & Drawthru Fan = 42573 (L 8 Sens ) / ( 1.1 x Supply TD ) = cfm Est Cooling cfm = ( 42573) / ( 1.1 x 20.0 ) = 1935 . -Actual Cooling Fan > = 1935 9. VENTILATION 450 cfm > x db Tamp Diff 15.0 x 1.1 '7425 > x Moist.' Diff 61.4 x 0.68 18792 10. RETURN AIR LOAD FROM LIGHTING AND ROOF .. - Incandescent Lights 0 Watts x 3.4 x 40% 0 Fluorescent Lights 2129 x 4.1 x 40% 3492 RA Roof Load from Line 3 M 5237 RA Ceiling Load Credit from Line 3 (-) 6813 11. RETURN DUCT HEAT GAIN Gain factor 0.00 x Line 6 Sensible Gain 0 12. TOTAL COOLING LOADS ON EQUIPMENT (Btuh) 51914 29292 SPACE HEATING LOAD CALCULATION 13. HEATING DESIGN TEMPERATURE Heating TD (Inside DB - Outside DB) _ ( 70 - 42) = 28 [ Mutt = 1.0 ] - 14. TRANSMISSION LOSSES Type Expos GrArea NetArea Uval HTD Loss GLAZ 1 E 0 0 0.500 28.0 0 WALL 1 S 486 486 0.114 28.0 1551 WALL 1 E 0 0 0.114 28.0 0 DOOR 1 N 0 0 0.560 28.0 0 DOOR 2 W 0 0 1.100 28.0 1257 FLOR 1 - 49 49 0.810 28.0 1102 ROOF 1 - 2129 2129 0.040 28.0 2384 - 15. INFILTRATION Loss _ 150 cfm x db Temp Diff 28.0 x 1.1 4 62 2 16. SUBTOTAL HEATING LOAD FOR SPACE 13302 17. SUPPLY DUCT HEAT LOSS Loss factor 0.0 5 x Line 16 Loss 665 1& VENTILATION 450 cfm x db Temp Diff 28.0 x 1.1 13860 d Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N :iw-PI #: Page: 3 19. HUMIID ICATION Inside RH desired 4 0.0 (Max = 3 2.0 for 1 pane ) # of Glazing panes 2.0 (Max = 52.0 for 2 pane ) 600 cfm x 3.20 g/100cfm/d = 19.2 gpd 7261 20. PkTUBN DUCT HEAT LOSS �ll Loss factor 0.00 x Line 16 Loss 0 21. TOTAL. HEATINt LOAD ON EQUPMENT (Btuh) 35088 f Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N Y I SIN . RNW213,93 RIGHT-N ZONE SUMMARY Units: U.S. customary (I—P) Nov 26, 2000 For: FT. PIERCE MASONIC LODGE By: WOLF AIR CONDITIONING - Job #: 'Lone:. ENTRY COOLING LOAD 1. DESIGN CONDITIONS at 3 PM Peak load at 6 PM ' Inside: 75 OF Outside: 90 OF TD: 15 OF RH: 50 % Moisture: 61 gr/lb Mult: 1.0 Ins.wb 63 OF Sensible Latent 2. SOLAR RADIATION THROUGH GLASS 1160 - 3. TRANSMISSION GAINS Sensible 3700 - Walls: 206 - - Glass: 306 - - Doors: 673 - - Partitions: 0 - - Floors: 0 - - RooWCeilings: 1132 - - Return Air Ceiling: 1382 - - 4. INTERNAL HEAT GAIN Sensible Latent 2953 1950 Occupants: 1890 1950 - - Lights: 1063 0 - - Motors: 0 0 - - Appliances & Other: 0 0 - - - 5. INFILTRATION: Outside air cfm: 49 809 '2048 6. SUBTOTAL: Space load 8621 3998 7. SUPPLY DUCT 259 - 8. SUBTOTAL: Bldg comp's and supply duct 8880 - Actual cfm: 527 at SupplyTD: 20 - 9. VENTILATION: Make—up air cfm! 0 0 0 10. RETURN AIR LOAD: Lighting & roof (net) 389 - 11. RETURN DUCT 0 - 12. TOTAL LOADS ON EQUIPMENT 9268 3998 HEATING LOAD 13. DESIGN CONDITIONS Mult: 1.0 Inside: 70 OF Outside: 42 OF TD: 28 OF " 14. TRANSMISSION LOSSES 4009 • Walls: 601 - Glass: 571 - Doors: 1257 - Partitions: 0 - Floors: 612 - Roofs/Ceilings: 484 - • Return Air Roof 484 - 15. INFILTRATION: Outside air cfm: • 87 2666 - 16. SUBTOTAL: Building components 6675 17. SUPPLY DUCT: 200 18. VENTILATION: Make—up air cfm: 0 0 . 19. HUMIDIFICATION 1047 20. RETURN DUCT 0 21. TOTAL HEATING LOAD ON EQUIPMENT 7923 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N 1"USTRIALLOAD CALCULATION Nov 26, 2000 For: FT. PIERCE MASONIC LODGE Zone: ENTRY Page: 1 Job #: City: Fort Pierce, FL, US By: WOLF AIR CONDITIONING LVVH: 27.0 x 16.0 x 8.0 Units: U.S. customary (I-P) 1. DESIGN CONDITIONS - COOLING 6PM , August Dry Blb RH Moisture Range Wet Blb Outdoor Conditions > 90 59 15 78 Indoor Conditions > 75 50 63 TOD Correction > 0 Difference 15 61 Mult 1. 0 2. GLAZING SOLAR HEAT GAIN Lat = 27.00 ON, ConstWt = M Type Dir Shad Tilt 0/oovr Area Sfact Shgf Shad Sens GLAZ I W N 90 100.0 41 0.98 88 1.0 1160 3. TRANSMISSION GAINS Type Dir GrArea NtArea Uval Grp CLTD Shad Clr Sens GIAZ 1 W 41 41 0.500 15.0 N - 306 WALL 1 W 270 188 0.114 B 9.6 N L 206 DOOR 2 W 41 41 1.100 15.0 - - 673 FLOR 1 - 27 27 0.810 0.0 - - 0 ROOF I - 432 432 0.040 R-4 65.5 - D 1132 RARF 1 - 432 432 0.040 R-4 61.5 - 1063 RACL 1 432 432 0.800 4.0 - 1382 4. INTERNAL HEAT. GAIN Sens Latent People 6 x Per person: sensible 315 lateni 325 1890 1950 0 x Per person: sensible 300 latent 300 0 0 Lights Incandescents in RA Ceiling 0 x 3.4 x 60% 0 Fluorescents in RA Ceiling 432 x 4.1 x 60% 1063 Incandescents other 0 x 3.4 x 100% 0 Fluorescents other 0 x 4.1 x 100% 0 Motors Nmbr Power Gain Load Fact Usage 1 1 0.00 0 1.00 1.00 0 2 1 0.00 0 1.00 1.00 0 3 1 0.00 0 1.00 1.00 0 Appi. Nmbr Type Sens Latent Usage 1 1 0 0 1.00 0 0 2 1 0 0 1.00 0 3 1 0 0 1.00 0 0 4 1 0 0 1.00 0 0 5 1 0 0 1.00 0 0 Other 1 0 0 1.00 0 0 5. INFILTRATION Sens Latent 49 cfm > x db Temp Diff 15.0 x 1.1 809 > x Moist. Diff 61.4 x 0.68 2048 6. SUBTOTAL COr-- i-,i ;-i z-- ii A :__.-A 3998 Manual N: 4th Edition Right-N: Ver!--'-,,n-,04 .-xilhriv Af iii :ill ' Job #: ' , Page: 2 7. SUPPLY DUCT HEAT GAIN Gain factor 0.03 x Line 6 Sensible Gain 259 8. COOLING FAN SIZING Sum of Duct Gain (7 ), Line (6) & Drawthru Fan = 8880 - (L 8 Sens ) / ( 1.1 x Supply TD ) = cfm Est Cooling cfm = ( 8880) / (1.1 x 20.0 ) = 404 Actual Cooling Fan > = 527 9. VENTILATION 0 cfm > x db Temp Diff 15.0 x 1.1 0 > x Moist. Diff 61.4 x 0.68 0 10. RETURN AIR LOAD FROM LIGHTING AND ROOF Incandescent Lights 0 Watts x 3.4 x 40% 0 Fluorescent Lights 432 x 4.1 x 40% 708 RA Roof Load from Line 3 M 1063 RA Ceiling Load Credit from Line 3 (-) 1382 11, RETURN DUCT HEAT GAIN Gain factor 0.00 x Line 6 Sensible Gain 0 12. TOTAL COOLING LOADS ON EQUIPMENT (Btuh) 9268 3 998 SPACE HEATING LOAD CALCULATION 13. HEATING DESIGN TEMPERATURE Heating TD = (Inside DB - Outside DB) _ ( 70 - 42) = 28 [ Mult = 1. U J - - 14. TRANSMISSION LOSSES Type Expos GrArea NetArea Uval HTD Loss GLAZ 1 W 41 41 0.500 28.0 571. WALL 1 W 270 188 0.114 28.0 601 DOOR 2 W 41 41 1.100 28.0 1257 FLOR 1 - 27 27 0.810 28.0 612 ROOF 1 - 432 432 0.040 28.0 484 15:` E% M.TRATION Loss - 87 cfm x 'db Temp Diff 28.0 x 1.1 2666 16. SUBTOTAL HEATING LOAD FOR SPACE 6675 17. SUPPLY DUCT HEAT LOSS Loss factor 0.03 x Line 16 Loss 200 18. VENTILATION 0 cfm x db Temp Diff 28.0 x 1.1 0 19. HUMIDIFICATION Inside RH desired 40.0 (Max = 32.0 for 1 pane ) # of Glazing panes 2.0 (Max = 52.0 for 2 pane ) 87 cfm x 3.20 g/100cfm/d = 2.8 gpd 1047 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N • -t j'ob #: Page: 3 20. RET'URN- Di1 CT HEAT LOSS Loss factor 0.00 x Line 16 Loss 0 2,1. TOTAL HEATING LOAD ON EQUPMENT (Btuh) 7923 0 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N 0 0;711 v SIN RNW21393 RIGHT-N ZONE SUMMARY Units:, 'U'If S. customary (I—P) Nov 26, 2000 For: FT. PIERCE MASONIC LODGE By:. WOLF AIR CONDITIONING Job #: Z^!)e: LADIES RESTROOM COOLING LOAD 1. DESIGN CONDITIONS at 3 PM Peak load at 3 PM Inside: 75 OF Outside: 9 0 OF TD: 15 OF RH: 50 % Moisture: 61 gr/lb Mult: 1.0 Ins.wb 63 OF Sensible Latent 2. SOLAR RADIATION THROUGH GLASS 0 - 3. TRANSMISSION GAINS Sensible 1951 - Walls: 253 - - "-- Glass: 0 - - Doors: 673 - - Partitions: 0 - - Floors: 0 - - Roofs/Ceilings: 461 - - Return Air Ceiling: 563 - - 4. INTERNAL HEAT GAIN Sensible Latent 853 280 Occupants: 420 280 - - Lights: 433 0 - - Motors: 0 0 - - Appliances & Other: 0 0 - - 5. INFILTRATION: Outside air cfm: 0 0 0 • 6. SUBTOTAL: Space load 2804 280 7. SUPPLY DUCT 84 - 8. SUBTOTAL: Bldg comp's and supply duct 2888 - Actual cfm: 131 at SupplyTD: 20 - - 9. VENTILATION: Make—up air cfm: 150 2475 6264 10. RETURN AIR LOAD: Lighting & roof (net) 158 - 11. RETURN DUCT 0 - 12. TOTAL LOADS ON EQUIPMENT 5521 6544 HEATING LOAD 13. DESIGN CONDITIONS Mult: i.0 " Inside: 70 OF Outside: 42 OF TD: 28 OF 14. TRANSMISSION LOSSES 3001 Walls: 738 - Glass: 0 - Doors: 1257 - Partitions: 0 - Floors: 612 - Roofs/Ceilings: 197 - Return Air Roof 197 - - 15. INFILTRATION: Outside air cfm: 9 271 16. SUBTOTAL: Building components 3272 17. SUPPLY DUCT: 164 18. VENTILATION: Make=up air cfm: 150 4620 19. HUMIDIFICATION 1921 20. RETURN DUCT 0 ` _ 21. TOTAL HEATING LOAD ON EQUIPMENT 9977 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N SM RNW21393 RIGHT-N COMMERCIAL/ INDUSTRIAL LOAD CALCULATION Nov 26, 2000 For: FT. PIERCE MASONIC LODGE Zone: LADIES RESTROOM Page: 1. Job #: ' City: Fort Pierce, FL, US By: WOLF AIR CONDITIONING LWH: 16.6 x 10.6 x 10.0 - Units: U.S. customary (I-P) 1. DESIGN CONDITIONS - COOLING ( 3 PM , August ) Dry Bib RH Moisture Range Wet Bib Outdoor Conditions > 90 59. 15 78 Indoor Conditions > 75 50 63 TOD Correction > 0 Difference 15 61 [ Mult = 1.0 ] - 2. GLAZING SOLAR HEAT GAIN ( Lat = 27.00 ° N , Const Wt = M ) Type Dir ' Shad Tilt "/oovr Area Sfact Shgf Shad Sens GLAZ 1 W N 90 0.0 0 0.98 88 1.0 0 3. TRANSMISSION GAINS Type Dir GrArea NtArea UVal Grp CLTD Shad Clr Sens GLAZ 1 W 0 0 0.500 15.0 N - 0 WALL 1 W 166 125 0.114 B 9.6 N L 137 WALL 1 S 106 106 0.114 B 9.6 N L 116 DOOR 2 W 41 41 1.100 15.0 - - 673 FLOR 1 - 27 27 0.810 0.0 - - 0 ROOF 1 - 176 176 0.040 R-4 65.5 - D 461 RARF 1 - 176 176 0.040 R-4 61.5 - - 433 RACL 1 - 176 176 0.800 4.0 - 563 4. INTERNAL HEAT GAIN People 2 x Per person: sensible 210 latent 140 0 x Per person: sensible 300 latent 300 Lights Incandescents in RA Ceiling 0 x 3.4 x 60% Fluorescents in RA Ceiling 176 x 4.1 x. 60% Incandescents other. 0 x 3.4 x 100% Fluorescents other 0 x 4.1 x 100% Motors Nmbr Power Gain Load Fact Usage . 1 1 0.00 0 1.00 1.00 2 1 0.00 0 1.00 1.00 3 1 1 0.00 0 1.00 1.00 Appl. Nmbr Type Sens Latent Usage 1 1 . 0 0 1.00 2 1 0 0 1.00 3 1 0 0 1.00 4 1 0 0 1.00 5 1 0 0 1.00 Other 1 0 0 1.00 5. INFILTRATION Sens Latent 420 280 0 0 0 433 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Sens Latent 0 cfm > x db Temp Diff 15.0 x 1.1 0 > x Moist. Diff 61.4 x 0.68 0 6.. SUBTOTAL COOLING LOAD FOR SPACE .2804 280 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N Job #: Page: 2 7. SUPPLY DUCT HEAT GAIN " Gain factor 0.03 x Line 6 Sensible Gain 84 S. COOLING FAN SIZING - Sum of Duct Gain (7 ), Line (6) & Drawthru Fan = 2888 (L 8 Sens ) / ( 1.1 x Supply TD ) = cfm Est Cooling cfm = ( 2 8 8 8) / (1.1 x 20.0 ) = 131 Actual Cooling Fan > = 131 9. VENTILATION 150 cfm > x db Temp Diff 15.0 x 1.1 247.5 > x Moist. Diff 61.4 x 0.68 6264 10. RETURN AIR LOAD FROM LIGHTING AND ROOF Incandescent Lights 0 Watts x 3.4 x 40% 0 - Fluorescent Lights 176 x 4.1 x 40% 289 RA Roof Load from Line 3 M 433 RA Ceiling Load Credit from Line 3 563 11. RETURN DUCT HEAT GAIN Gain factor 0.00 x Line 6 Sensible Gain 0 12. TOTAL COOLING LOADS ON EQUIPMENT (Btuh) 5521 6544 SPACE HEATING LOAD CALCULATION 13. HEATING DESIGN TEMPERATURE Heating TD (Inside DB - Outside DB) _ ( 70 - 42) 28 [ Mult = 1.0 ] - 14. TRANSMISSION LOSSES Type Expos GrArea NetArea Uval H'TU Loss GLAZ 1 W 0 0 0.500 28.0 0 TALL 1 W 166 125 0.114 26.0 400 Tn1P,LL 1 S 106 106 0.114 28.0 338 DOOR 2 W 41 41 1.100 28.0 1257 FLOR 1 - 27 27 0.810 28.0 612 ROOF 1 - 176 176 0.040 28.0 197 15. INFILTRATION Loss 9 cfm 'x db Temp Diff 28.0 x 1.1 271 - , 16. SUBTOTAL HEATING LOAD FOR SPACE 3272 " 17. SUPPLY DUCT HEAT LOSS Loss factor 0.05 x Line 16 Loss 164 18. VENTILATION _ 150 cfm x dbTemp Diff 28.0 x 1.1 4620 19. HUMIDIFICATION - Inside RH desired 40.0 (Max = 32.0 for 1 pane ) # of Glazing panes 2.0 (Max = 52.0 for 2 pane ) , • 159 cfm x 3.20 g/100cfm/d = 5.1 gpd 1921 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N Job #: 20. RETURN DUCT HEAT LOSS Loss factor ' 0.00 x Line 16 Loss 21. TOTAL HEATING LOAD ON EQUPMENT (Btuh) Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N Page: 3 0 9977 f SIN ' �4NW21'3'93 RIGHT-N ZONE SUNIIVIARY units: U.S. customary (I—P) Nov 26, 2000 - For: FT. PIERCE MASONIC LODGE By: WOLF AIR CONDITIONING Job #: Zone: KITCHEN COOLING LOAD 1. DESIGN CONDITIONS at 3 PM Peak load at 3 PM Inside: 75 OF Outside: 90 OF TD: 15 OF RH: 50 % Moisture: 61 gr/lb Mult: 1.0 Ins.wb 63 OF Sensible Latent - 2. SOLAR RADIATION THROUGH GLASS 398 - 3. TRANSMISSION GAINS Sensible 2599 - Walls: 66 - - - Glass: 105 - - Doors: 845 - - Partitions: 0 - - Floors: 0 - - Roofs/Ceilings: 713 - - Return Air Ceiling: 870 - - 4. INTERNAL HEAT GAIN Sensible Latent 1179 510 Occupants: 510 510 - - Lights: 669 0 - - Motors: 0 0 - - Appliances & Other: 0 0 - S. INMTRATION: Outside air cfm: 15 253 640 6. SUBTOTAL: Space load 4429 1150 7. SUPPLY DUCT 133 - 8. SUBTOTAL: Bldg comp's and supply duct 4562 - Actual cfm:. 207 at Supply TD: 20' - - 9. VENTILATION: Make=up air cfm: 100 1650 4176 10. RETURN AIR LOAD: Lighting & roof (net) 245 - 11. RETURN DUCT 0 - 12. TOTAL LOADS ON EQUIPMENT 6457 5326 HEATING LOAD 13. DESIGN CONDITIONS Mult: J.: 0 - Inside: 70 OF Outside: 42 OF TD: 28 OF 14. TRANSMISSION LOSSES 2960 Walls: 292 - Glass: 196 - Doors: 1577 - Partitions: 0 - - Floors: 286 - Roofs/Ceilings: 305 - Return Air Roof 305 - 15. INFILTRATION: Outside air cfm: 44 1352 16. SUBTOTAL: Building components 4312 17. SUPPLY DUCT: 216 . 18. VENTILATION:. Make-up air cfm: 100 3080 - 19. HUN®IFICATION 1741 20. RETURN DUCT 0 ,. 21. TOTAL HEATING LOAD ON EQUIPMENT 9349 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N SIN RNW21393 RIGHT-N COMMERCIAL / INDUSTRIAL LOAD CALCULATION Nov 26, 2000 For: FT. PIERCE MASONIC LODGE Zone: KITCHEN Page: .a_ Job #: . City: Fort Pierce, FL, US By: WOLF AIR CONDITIONING LWH: 12.6 x 21.0 x 10.0 Units: U.S. customary (I-P) 1. -- DESIGN CONDITIONS - COOLING ( 3 PM , August ) Dry Blb RH Moisture Range Wet Bib Outdoor Conditions > 90 59 15 78 Indoor Conditions > 75 50 63 TOD Correction > 0 " Difference 15 61 [ Mult = 1.0 ] - 2. GLAZING SOLAR HEAT GAIN ( Lat = 27.00 ON, Const Wt = M ) Type Dir Shad Tilt %ovr Area Sfact Shgf Shad Sens GLAZ 1 N N 90 100.0 14 0.98 29 1.0 398 3. TRANSMISSION GAINS Type Dir GrArea GLAZ 1 N 14 WALL 1 N 126 WALL 1 N 0 DOOR 1 N 20 DOOR 2 W 0 FLOR 1 - 13 ROOF 1 - 272 RARF 1 - 272 RACL 1 - 272 NtArea 14 92 0 20 0 13 272 272 272 Uval Grp 0.500 0.114 B 0.114 B 0.560 1.100 0.810 0.040 R-4 0.040 R-4 0.800 CLTD 15.0 6-3 6.3 15.0 15.0 0.0 65.5 61.5 410 Shad Clr N - N L N L - - - - - - - D - - - - Sens 105 66 0 171 613 0 713 669 870 4. INTERNAL HEAT GAIN Sens Latent People 2 x Per person: sensible 255 latent 255 510 510 0 x Per person: sensible 300 latent 300 0 0 Lights Incandescents in RA Ceiling 0 x 3.4 x 60% 0 Fluorescents in RA Ceiling 272 x 4.1 x 60% 669 Incandescents other 0 x 3.4 x 100% 0 Fluorescents other 0 x 4.1 x 100% 0 Motors Nmbr Power Gain Load Fact Usage 1 1 0.00 0 1.00 1.00 0 2 1 ` 0.00 0 1.00 1.00 0 3 1 0.00 0 1.00 1.00 0 Appl. Nmbr Type Sens Latent Usage 1 1 0 0 1.00 0 0 ' 2 1 0 0 1.00 0 0 - - 3 1 0 0 1.00 0 0 4 1 0 0 1.00 0 0 • 5 1 0 0 1.00 0 0 Other 1 0 0 1.00 0 0 5. INFILTRATION Sens Latent 15 cfm > x db Temp Diff 15.0 x 1.1 253 . > x Moist. Diff 61.4 x 0.68 1640 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N Job #: Page:. 2 6r SUBTOTAL COOLING LOAD FOR SPACE 4429 1150 ^ 7. SUPPLY DUCT HEAT GAIN Gain factor 0.03 x Line 6 Sensible Gain 133 8. COOLING FAN SIZING Sum of Duct Gain (7 ), Line (6) & Drawthru Fan = 4562 (L 8 Sens ) / ( 1.1 x Supply TD ) = .cfm Est Cooling cfm = ( 4562) / ( 1.1 x 20.0 ) = 207 Actual Cooling Fan > = 207 9. VENTILATION 100 cfm > x db Temp Diff 15.0 x 1.1 1650 > x Moist. Diff 61.4 x 0.68 4176 10. RETURN AIR LOAD FROM LIGHTING AND ROOF Incandescent Lights 0 Watts x 3.4 x 40% 0 Fluorescent Lights 272 x 4..1 x 40% 446 RA Roof Load from Line 3 M 669 ^ RA Ceiling Load Credit from Line 3 (-) 870 11. RETURN DUCT HEAT GAIN Gain factor 0.00 x Line 6 Sensible Gain 0 12. TOTAL COOLING LOADS ON EQUIPMENT (Btuh) 6457 5326 SPACE HEATING LOAD CALCULATION 13. HEATING DESIGN TEMPERATURE Heating TD = (Inside DB - Outside DB) _ ( 10 - 4 2) = 28 [ Mult = 1.0 ] - 14. TRANSMISSION LOSSES Type Expos GrArea NetArea Uval HTD Loss GLAZ 1 N 14 14 0.500 28.0 196 WALL 1 N 126 92 0.114 28.0 292 WALL 1 N 0 0 0.114 28.0 0 DOOR 1 N 20 20 0.560 28.0 320 DOOR 2 W 0 0 1.100 28.0 1257 FLOR 1 - 13 13 0.810 28.0 286 ROOF 1 - 272 272 0.040 28.0 305 15. INFILTRATION Loss 4 4' cfm x db Temp Diff 28.0 x 1.1 13,52 16. SUBTOTAL HEATING LOAD FOR SPACE 4 312 17. SUPPLY DUCT HEAT LOSS Loss factor 0.05 x Line 16 Loss 216 18. VENTILATION 100 cfm x db Tamp Diff 28.0 x 1.1 3080 r Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N " Job #: Page: 3 19. HUlyIIDIFICATION Inside RR desired 40.0 (Max = 32.0 for 1 pane ) # of Glazing panes 2.0 (Max = 52.0 for 2 pane ) 144 cfm x 3.20 g/100cfm/d - 4.6 gpd 1741 20. RETURN DUCT BEAT LOSS Loss factor 0.00 x Line 16 Loss 0 21. TOTAL HEATING LOAD ON EQUPMENT (Btuh) 9349 0 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N S/N� ,RNW21393 RIGHT-N ZONE SUMIVIARY Vnfts: t ,U.S. customary (I—P) Nov 26, 2000 , r For: FT. PIERCE MASONIC LODGE By. WOLF AIR CONDITIONING Job #: Zone: MEN' S RESTROOM COOLING LOAD 1. DESIGN CONDITIONS at 3PM Peak load at 3PM Inside: 75 OF Outside: 90 OF TD: 15 OF RH: 50 % Moisture: 61 gr/lb Mult: 1.0 Ins.wb 63 OF Sensible Latent - 2. SOLAR RADIATION THROUGH GLASS 0 - 3. TRANSMISSION GAINS Sensible 1831 - Walls: 250 - - Glass: 0 - - Doors: 673 - - Partitions: 0 - - _ Floors: 0 - - Roofs/Ceilings: 409 - - Return Air Ceiling: 499 - - 4. INTERNAL HEAT GAIN Sensible Latent 804 280 Occupants: 420 280 - - Lights: 384 0 - - Motors: 0 0 - - Appliances & Other: 0 0 - S. INFILTRATION: Outside air cfm: 0 0 0 6. SUBTOTAL: Space load 2635 280 7. SUPPLY DUCT 79 - 8. SUBTOTAL: Bldg comp's and supply.duct 2714 - Actual cfm: 123 at SupplyTD: 20 - - 9. VENTILATION: Make—up air cfm: 100 1650 4176 10. RETURN AIR LOAD: Lighting & roof (net) 140 - 11. RETURN DUCT 0 - 12. TOTAL LOADS ON EQUIPMENT 4504 4456 HEATING LOAD 13. DESIGN CONDITIONS Mult: 1.0 Inside:. 70 OF Outside: 42 OF TD: 2 8•° F 14. TRANSMISSION LOSSES 3026 Walls: 830 - Glass: 0 - . Doors: 1257 - Partitions: 0 - Floors: 590 - _ Roofs/Ceilings: 175 - Return Air Roof 175 - 15. INFILTRATION: Outside air cfm: 8 240 - 16. SUBTOTAL: Building components 3266 17. SUPPLY DUCT: 163 18. VENTILATION: Make—up air cfm: 100 3080 19. HUMIDIFICATION 1304 20. RETURN DUCT 0 r 21. TOTAL HEATING LOAD ON EQUIPMENT 7 814 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N SIN RNW21393 RIGHT-N COMMERCIAL / INDUSTRIAL LOAD CALCULATION Nov 26' 2000 For: FT. PIERCE MASONIC LODGE Zone: MEN' S RESTROOM Page: 1 Job #: City: Fort Pierce, FL, US By: WOLF AIR CONDITIONING - LWH: 16.6 x 9.4 x 10.0 Units: U.S. customary (I-P) 1. DESIGN CONDITIONS - COOLING ( 3 PM , August ) Dry Blb RH Moisture Range Wet Blb Outdoor Conditions > 90 59 15 78 Indoor Conditions > 75 50 63 TOD Correction > 0 Difference 15 61 [ Mult = 1.0 ] - 2. GLAZING SOLAR HEAT GAIN ( Lat = 27.00 °N, Const Wt = M ) Type Dir Shad Tilt %ovr Area Sfact Shgf Shad Sens GLAZ 1 W N 90 0.0 0 0.98 88 1.0 0 3. TRANSMISSION GAINS Type Dir GrArea NtArea Uval Grp CLTD Shad Clr Sens GLAZ 1 W 0 0 0.500 15.0 N - 0 WALL 1 W 166 166 0.114 B 9.6 N L 182 V7ALL 1 N 94 94 0.114 B 6.3 N L 68 DOOR 2 W 0 0 1.100 •15.0 - - 673 FLOR 1 - 26 26 0.810 0.0 - - 0 ROOF 1 - 156 156 0.040 R-4 65.5 - D 409 RARF 1 - 156 156 0.040 R-4 61.5 - - 384 RACL 1 - 156 156 0.800 4.0 - - 499 4. INTERNAL HEAT GAIN Sens Latent People 2 x Per person: sensible 210 latent 140 420 280 0 x Per person: sensible 300 latent 300 0 0 Lights Incandescents in RA Ceiling 0 x 3.4 x 60% 0 ` ` Fluorescents in RA Ceiling 156 x 4.1 x 60% 384 Incandescents other 0 x 3.4 x 100% 0 Fluorescents other 0 x 4.1 x 100% 0 Motors Nmbr Power Gain Load Fact Usage 1 1 0.00 0 1.00 1.00 0 2 1 t 0.00 0 1.00 1.00 0 3 1 0.00 0 1.00 1.00 0 Appl. Nmbr. Type Sens Latent Usage 1 1 0 0 1.00 0 0 _ 2 1 0 0 1.00 0 0 3 1 0 0 1.00 0 0 • 4 1 0 0 1.00 0 0 5 1 0 0 1.00 0 0 Other 1 0 0 1.00 0 0 5. INFILTRATION Sens Latent 0 cfm > x db Temp Diff 15.0 x 1.1 0 > x Moist. Diff 61.4 x 0.68 r 0 6. SUBTOTAL COOLING LOAD FOR SPACE, 2635 280 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N Job #: Page: 2 7. SUPPLY PUCT HEAT GAIN Gain factor 0.03 x Line 6 Sensible Gain 79 8. COOLING FAN SIZING Sum of Duct Gain (7 ), Line (6) & Drawthru Fan = 2 714 (L 8 Sens ) / ( 1.1 x Supply TD ) = cfm Est Cooling cfm = ( 2 714) / (1.1 x 20.0 ) = 123 Actual Cooling Fan > = 123 9. VENTILATION 100 cfm > x db Tamp Diff 15.0 x 1.1 1650 > x Moist. Diff 61.4 x 0.68 4176 10. RETURN AIR LOAD FROM LIGHTING AND ROOF Incandescent Lights 0 Watts x 3.4 x 40% 0 Fluorescent Lights 156 x 4.1 x 40% 256 _ RA Roof Load from Line 3 N 384 RA Ceiling Load Credit from Line 3 (-) 499 11. RETURN DUCT HEAT GAIN Gain factor 0.00 x Line 6 Sensible Gain 0 12. TOTAL COOLING LOADS ON EQUIPMENT (Btuh) 4504 4456 SPACE HEATING LOAD CALCULATION 13. HEATING DESIGN TEMPERATURE Heating TD = (Inside DB - Outside DB) _ ( 70 - 4 2) = 28 [ Mult = 1. 0 ] - 14. TRANSMISSION LOSSES Type Expos GrArea NetArea Uval HTD Loss GLAZ 1 W 0 0 0.500 28.0 0 WALL 1 W 166 166 0.114 28.0 530 WALL 1 N 94 94 0.114 28.0 300 DOOR 2 W 0 0 1.100 28.0 1257 FLOR 1 - 26 26 0.810 28.0 590 ROOF 1 - 156 156 0.040 28.0 17F) 15. INFILTRATION Loss 8 cfm x db Temp Diff 28.0 x 1.1 240 16. SUBTOTAL HEATING LOAD FOR SPACE 3266 17. SUPPLY DUCT HEAT LOSS T.nQQ factnr n_ n S x T .ina 1 AT .nee 1 L{ 2 18. VENTILATION 100 cfm x db Temp Diff 28.0 x 1.1 3080 19. HUMIDIFICATION Inside RH desired 40.0 (Max = 32.0 for 1 pane ) # of Glazing panes 2.0 (Max = 52.0 for 2 pane ) 108 cfm x 3.20 g/100cfm/d = 3.4 gpd Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N 1304 -Job #: 20. RETURN DUC r SAT LOSS Loss factor 0.00 x Line 16 Loss 21. TOTAL HEATING LOAD ON EQUPMENT (Btuh) Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N Page: 3 0 7814 lu r SIN RNW21393 RIGHT-N ZONE SUMMARY dnits: ` 'U.S. customary (I—P) For: FT. PIERCE MASONIC LODGE Nov 26, 2000 By: WOLF AIR CONDITIONING Job#: Zone: PREPARTATION COOLING LOAD 1. DESIGN CONDITIONS at 3PM Peak load at 3PM Inside: 75 OF Outside: 90 OF TD: 1.5 OF `— RH: 50 % Moisture: 61 gr/lb Mult: 1.0 Ins.wb 63 °F - Sensible Latent 2. SOLAR RADIATION THROUGH GLASS 0 - 3. TRANSMISSION GAINS Sensible 1668 - Walls: 69 - - Glass: 0 - - Mors: 673 - - Partitions: 0 - - Floors: 0 - - Roofs/Ceilings: 417 - - Return Air Ceiling: 509 - - 4. INTERNAL HEAT GAIN Sensible Latent 901 510 Occupants: 510 510 - - Lights: 391 0 - - Motors: 0 0 - - Appliances & Other: 0 0 - - 5. INFILTRATION: Outside air cfm: 15 253 640 6. SUBTOTAL: Space load 2822 1150 7. SUPPLY DUCT 85 - 8. SUBTOTAL: Bldg comp's and supply duct 2907 - Actual cfm: 132 at Supply TD: 20 - - 9. VENTILATION: Make=ups?sir=c%s�,QQ.w«lfi&tZ"�"i:,�°" 10. RETURN AIR LOAD: Lighting & roof (net) 143 - 11. RETURN DUCT 0 - 12. TOTAL LOADS ON EQUIPMENT 4700 5326 HEATING LOAD 13. DESIGN CONDITIONS Mult: 1.0 Inside: 70 OF Outside: , 42 OF TD: 28 OF 14. TRANSMISSION LOSSES 2137 Walls: 306 - Glass: 0 - Doors: 1257 - Partitions: 0 - Floors: 218 - Roofs/Ceilings: 178 - Return Air Roof 178 - 15. INFILTRATION: Outside air cfm: 39 1190 16. SUBTOTAL: Building components 3327 17. SUPPLY DUCT: 166 - 18. VENTILATION: Make—up air cfm: 100 3080 19. HUMIDIFICATION 1677 20. RETURN DUCT 0 21. TOTAL HEATING LOAD ON EQUIPMENT 8251 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of ManualForm N SIN RNW21393 RIGHT-N COMMERCIAL/ INDUSTRIAL LOAD CALCULATION Nov 26, 2000 -• - _ For: FT. PIERCE MASONIC LODGE Zone: PREPARTATION Page: 1 Job #: City: Fort Pierce, FL, US By: WOLF AIR CONDITIONING LWH: 9.6 x 16.6 x 10.0 Units: U.S. customary (I-P) 1. DESIGN CONDITIONS - COOLING ( 3 PM , August ) Dry Bib RH Moisture Range Wet Bib Outdoor Conditions > 90 59. 15 78 Indoor Conditions > 75 50 63 TOD Correction > 0 Difference 15 61 Muit = 1.0 ] - [ _ 2. GLAZING SOLAR HEAT GAIN ( Lat = 27.00 ° N , Const Wt = M ) Type Dir Shad Tilt %ovr Area Sfact Shgf Shad Sens GLAZ 1 N N 90 0.0 0 0.98 29 1.0 0 3. TRANSMISSION GAINS Type Dir GrArea NtArea Uval Grp. CLTD Shad Clr Sens GLAZ 1 N 0 0 0.500 15.0 N - 0 WALL 1 N 96 96 0.114 B �.6.3 N L 69 VMLL 1 N 0 0 0.114 B 6.3 N L 0 DOOR 1 N 0 0 0.560 15.0 - - 0 DOOR 2 W 0 0 1.100 15.0 - - 673 FLOR 1 - 10 10 0.810 0.0 - - 0 ROOF 1 - 159 159 0.040 R-4 65.5 - D 417 RARF 1 - 159 159 0.040 R-4 61.5 - - 391 RACL 1 - 159 159 0.800 4.0 - - 509 4. INTERNAL HEAT GAIN Sens Latent People 2 x Per person: sensible 255 latent 255 510 510 0 x Per person: sensible 300 latent 300 0 0 Lights Incandescents in RA Ceiling 0 x 3.4 x 60% 0 Fluorescents in RA Ceiling 159 x 4.1 x 60% 391 Incandescents other 0 x 3.4 x 100% 0 Fluorescents other 0 x 4.1 x 100% 0 ' Motors Nmbr Power Gain Load Fact Usage 1 1 0.00 0 1.00 1.00 0 2 1 ` 0.00 0' 1.00 1.00 0 ' 3 1 0.00 0 1.00 1.00 0 ' Appl. Nmbr Type Sens Latent Usage 1 1 0 0 1.00 0 0 2 1 0 0 1.00 0 0 ' 3 1 0 0 1.00 0 0 4 1 0 0 1.00 0 0 5 1 0 0 1.00 0 0 Other 1 0 0 1.00 0 0 5. INFILTRATION Sens Latent 15 c fm > x db Temp Diff 15.0 x 1.1 253 > x Moist. Diff 61.4 x 0.68 '640 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N Job #: Page: 2 6. W17QTAL COOLING LOAD FOR SPACE 2822 1150 7. SUPPLY DUCT HEAT GAIN Gain factor 0.03 x Line 6 Sensible Gain 85 S. COOLING FAN SIZING Sum of Duct Gain (7 ), Line (6) & Drawthru Fan = 2907 (L 8 Sens ) / ( 1.1 x Supply TD ) = cfm Est Cooling cfm = ( 2907) / (1.1 x 20.0 ) = 132 Actual Cooling Fan > = 132 9. VENTILATION 100 cfm > x db Temp Diff 15.0 x 1.1 1650 > x Moist. Diff 61.4 x 0.68 4176 10. RETURN AIR LOAD FROM LIGHTING AND ROOF - Incandescent Lights 0 Watts x 3.4. x 40% 0 Fluorescent Lights 159 x 4.1 x 40% 261 RA Roof Load from Line 3 N 391 - _ RA Ceiling Load Credit from Line 3 (-) 509 11. RETURN DUCT HEAT GAIN Gain factor 0.00 x Line 6 Sensible Gain 0 12. TOTAL COOLING LOADS ON EQUIPMENT (Btuh) 4700 5326 SPACE HEATING LOAD CALCULATION 13. HEATING DESIGN TEMPERATURE Heating TD = (Inside DB - Outside DB) _ ( 70 - 42) = 28 [ Mult = 1.0 ] - - 14. TRANSMISSION LOSSES Type Expos GrArea NetArea Uval HFD Loss GLAZ 1 N 0 0 0.500 28.0 0 MALL 1 N 96 96 0.114 28.006 WALL 1 N 0 0 0.114 28.0 0 DOOR 1 N 0 0 0.560 28.0 0 DOOR 2 W 0 0 1.100 28.0 1257 FLOR 1 - 10 10 0.810 28.0 218 ROOF 1 - 1'59 159 0.040 28.0 178 S 15. INFILTRATION Loss 39 cfm x db Temp Diff 28.0 x 1.1 1190 16. SUBTOTAL HEATING LOAD FOR SPACE 3327 17. SUPPLY DUCT HEAT LOSS Loss factor 0.05 x Line 16 Loss 166 19. VENTILATION 100 cfm x db Temp Diff 28.0 x 1.1 3080 0 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N -'Job #: ` , Page: 3 19. HUMIDIFICATION `Inside RH desired 40 ..0 (Max = 32.0 for 1 pane ) # of Glazing panes 2.0 (Max = 52.0 for 2 pane ) 139 cfm x 3.20 g/100cfm/d = 4.4 gpd 1677 20. RETURN DUCT HEAT LOSS . Loss factor 0.00 x Line 16 Loss 0 21. TOTAL HEATING LOAD ON EQUPMENT (Btuh) 8251 f Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N " SIN RNW21'3 9 3 RIGHT-N ZONE SUMMARY Units: ,U..S. customary (I—P) Nov 26, 2000 For: FT. PIERCE MASONIC LODGE By: WOLF AIR CONDITIONING Job #: Zone: R . C . WILSON COOLING LOAD 1. DESIGN CONDITIONS at 3 PM Peak load at 3 PM Inside: 75 OF Outside: 90 OF TD: 15 OF RH: 50 % Moisture: 61 gr/lb Mult: 1.0 Ins.wb 63 OF Sensible Latent 2. SOLAR RADIATION THROUGH GLASS 398 - 3. TRANSMISSION GAINS Sensible - 1901 - Walls: 169 - - Glass: 105 - - Doors: 673 - - Partitions: 0 - - - Floors: 0 - - -. .. _ Roofs/Ceilings: 427 - - Return Air Ceiling: 526 - - 4. INTERNAL HEAT GAIN Sensible Latent 666 200 Occupants: 250 200 - - Lights: 416 .0 - Motors: 0 0 - - Appliances & Other: 0 0 - S. INFILTRATION: Outside air cfm: 0 0 0 6. SUBTOTAL: Space load 2964 200 7. SUPPLY DUCT 89 - 8. SUBTOTAL: Bldg comp's and supply duct 3053 - Actual cfm: 139 at Supply TD: 20 - - 9. VENTILATION: Make—up air cfm: 20 330 835 10. 'RETURN AIR LOAD: Lighting & roof (net) 151 - 11. RETURN DUCT 0 - 12. TOTAL LOADS ON EQUIPMENT 3535 1035 HEATING LOAD 13. DESIGN CONDITIONS Mutt: 1.0 Inside: 70 OF Outside: 42 OF TD: 28 OF 14. TRANSMISSION LOSSES 2352 Walls: 294 - Glass: i 9 6 - Doors: 1257 - Partitions: 0 - Floors: 240 - Roofs/Ceilings: 183 - Return Air Roof 183 - 15. INFILTRATION: Outside air cfm: 8 245 16. SUBTOTAL: Building components 2597 17. SUPPLY DUCT: 130 18. VENTILATION: Make—up air cfm: 20 616 19. HUD[IDIIF'ICATION 338 20. RETURN DUCT 0 21. TOTAL HEATING LOAD ON EQUIPMENT 3681 Manual N: 4th Edition Right-N: Ve:.5.V%.04 Certified by ACCA to meet all requirements of Manual Form N • 3 -SIN RNW213 9 3 ' RIGHT-N COMMERCIAL / INDUSTRIAL LOAD CALCULATION Nov 26, 2000 For: FT. PIERCE MASONIC LODGE Zone: R. C . WILSON Page: 1 Job #: City. Fort Pierce, FL, US By. WOLF AIR CONDITIONING - LWH: 15.0 x 10.6 x 10.0 Units: U.S. customary (I-P) 1. DESIGN CONDITIONS - COOLING ( 3 PM , August ) Dry Blb RH Moisture Range Wet Bib Outdoor Conditions > 90 59 15 78 Indoor Conditions > 75 50 63 TOD Correction > 0 Difference 15 61 - [ Mult = 1.0 ] 2. GLAZING SOLAR BEAT GAIN ( Lat = 27.00 ° N , Const Wt = M ) - Type Dir Shad Tilt %ovr Area Sfact Shgf Shad Sens GLAZ 1 E N 90 100.0 14 0.98 64 1.0 398 3. TRANSMISSION GAINS Type Dir GrArea NtArea Uval Grp CLTD Shad CIr Sens GLAZ 1 E 14 14 0.500 15.0 N - 105 MUL 1 E 106 92 0.114 B 16.1 N L 169 MUL 1 E 0 0 0.114 B 16.1 N L 0 DOOR 1 N 0 0 0.560 15.0 - - 0 DOOR 2 W 0 0 1.100 15.0 - - 673 FLOR 1 - 11 11 0.810 0.0 - - 0 ROOF 1 - 163 163 0.040 R-4 65.5 - D 427 RARF 1 - 163 163 0.040 R-4 61.5 - - 401 RACL 1 - 163 163 0.800 4.0 - - 526 4. INTERNAL HEAT GAIN Sens Latent People 1 x Per person: sensible 250 latent 200 250 200 0 x Per person: sensible 300 latent 300 0 0 Lights Incandescents in RA Ceiling 0 x 3.4 x 60% 0 Fluorescents in RA Ceiling 169 x 4.1 x 60% 416 Incandescents other 0 x 3.4 x 100% 0 Fluorescents other 0 x 4.1 x 100% 0 Motors Nmbr Power Gain Load Fact Usage 1 1 0.00 0 1.00 1.00 0 2 1 0.00 0 1.00 1.00 0 3 1 0.00 0 1.00 1.00 0 Appl. Nmbr Type Sens Latent Usage 1 1 0 0 1.00 0 0 2 1 0 0 1.00 0 0 3 1 0 0 1.00 0 0 4 1 0 0 1.00 0 0 5 1 0 0 1.00 0 0 Other 1 0 0 1.00 0 0 5. INMTRATION Sens Latent 0 cfm > x db Temp Diff 15.0 x 1.1 0 > x Moist. Diff 61. 4 x 0.68 0 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N 0 ,SIN RNW21393 RIGHT-N COMMERCIAL/ INDUSTRIAL LOAD CALCULATION Nov 26, 2000 For: FT. PIERCE MASONIC LODGE Zone: R . C . WILSON Page: I Job #: City: Fort Pierce, FL, US By: WOLF AIR CONDITIONING LWH: 15.0 x 10.6 x 10.0 Units: U.S. customary (I-P) 1. DESIGN CONDITIONS - COOLING ( 3 PM , August ) Dry Bib RH Moisture Range Wet Blb Outdoor Conditions > 90 59 15 78 Indoor Conditions > 75 50. 63 TOD Correction > 0 Difference 15 61 [ Mult = 1.0 ] - 2. . GLAZING SOLAR HEAT GAIN ( Lat = 2 7 . •0 0 *N, Const Wt = M ) Type Dir Shad Tilt %ovr Area Sfact Shgf Shad Sens GLAZ 1 E N 90 100.0 14 0.98 64 1.0 398 3. TRANSMISSION GAINS Type Dir GrArea NtArea Uval Grp CLTD Shad Clr Sens GLAZ 1 E 14 14 0.500 15.0 N - 105 WALL 1 E 106 92 0.114 B 16.1 N L 169 WALL 1 E 0 0 0.114 B 16.1 iv L 0 DOOR 1 N 0 0 0.560 15.0 - - 0 DOOR 2 W 0 0 1.100 15.0 - - 673 FLOR 1 - 11 11 0.810 0.0 - - 0 ROOF 1 - 163 163 0.040 R-4 65.5 -• D 427 RRRF 1 - 163 163 0.040 R-4 61.5 - - 401 RACL 1 - 163 163 0.800 4.0 - - 526 4. INTERNAL HEAT GAIN Sens Latent People 1 x Per person: sensible 250 latent 200 250 200 0 x Per person: sensible 300 latent 300 0 0 Lights Incandescents in RA Ceiling 0 x 3.4 x 60% 0 Fluorescents in RA Ceiling 169 x 4.1 x 60% 416 Incandescents other 0 x 3.4 x 100% 0 Fluorescents other 0 x 4.1 x 100% 0 Motors Nmbr Power Gain Load Fact Usage 1 1 0.00 0 1.00 1.00 0 2 1 t 0.00 0 1.00 1.00 0 3 1 0.00 0 1.00 1.00 0 Appl. Nmbr Type Sens Latent Usage 1 1 0 0 1.00 0 0 2 1 0 0 1.00 0 0 • 3 1 0 0 1.00 0 0 4 1 0 0 1.00 0 0 5 1 0 0 1.00 0 0 Other 1 0 0 1.00 0 r) 5. INFILTRATION Sens Latent 0 cfm > x db Tamp Diff 15.0 x 1.1 0. > x Moist. Diff 61.4 x 0. 68 1 0 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N Job #: Page: 2 6. SUBTOTAL`COOLING LOAD FOR SPACE 2964 200 7. SUPPLY DUCT HEAT GAIN Gain factor 0.03 x Line 6 Sensible Gain 89 8. COOLING FAN SIZING Sum of Duct Gain (7 ), Line (6) & Drawthru Fan = 3053 (L 8 Sens ) / ( 1.1 x Supply ID ) = cfm Est Cooling cfm = ( 3053) / ( 1.1 x 20.0 ) = 139 Actual Cooling Fan > = 139 ' 9. VENTILATION 2 0 c fm > x db Temp Diff 15.0 x 1.1 330 > x Moist. Diff 61.4 x 0.68 835 10. RETURN AIR LOAD FROM LIGHTING AND ROOF Incandescent Lights 0 Watts x 3.4 x 40% 0 Fluorescent Lights 169 x 4.1 x 40% 277 RA Roof Load from Line 3 (+) 401 RA Ceiling Load Credit from Line 3 (-) 526 11. RETURN DUCT HEAT GAIN ' Gain factor 0.00 x Line 6 Sensible Gain 0 12, TOTAL COOLING LOADS ON EQUIPMENT (Btuh) 3535 1035 SPACE HEATING LOAD CALCULATION 13. HEATING DESIGN TEMPERATURE Heating TD = (Inside DB - Outside DB) _ ( 70 - 4 2) = 28 [ Mult = 1.0 ] - 14. TRANSMISSION LOSSES Type Expos GrArea NetArea Uval HTD Loss GLAZ 1 E 14 14 0.500 28.0 196 WALL 1 E 106 92 0.114 28.0 294 WALL 1 E 0 0 0.114 28.0 0 DOOR 1 N 0 0 0.560 28.0 0 DOOR 2 W 0 0 1.100 28.0 1257 FLOR 1 - 11 11 0.810 28.0 240 ROOF 1 - 163 163 0.040, 28.0 183 15. INFILTRATION Loss 8 c fm x db Temp Diff 28.0 x 1.1 245 - 16. SUBTOTAL HEATING LOAD FOR SPACE 2597 17. SUPPLY DUCT HEAT LOSS Loss factor 0.05 x Line 16Loss 130 18. VENTHATION - 20 c fm x db Temp Diff 28.0 x 1.1 616 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N Job #: Page: 3 19. HUMIDIFICATION Inside RH aesired 40.0 (Max = 32.0 for 1 pane ) # of Glazing panes 2.0 (Max = 52.0 for 2 pane ) 28 cfm x 3.20 g/100cfm/d = 0.9 gpd 338 ` 20. RETURN DUCT HEAT LOSS Loss factor 0.00 x Line 16 Loss 0 21. TOTAL HEATING LOAD ON EQUPMENT (Btuh) 3 681 A Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N SIN ' 12NW21393 RIGHT-N ZONE SUMMARY Units:. 'U;S. customary (I—P) Nov 26, 2000 For: FT. PIERCE MASONIC LODGE By: WOLF AIR CONDITIONING Job #: Zone: SOCIAL AREA Xiii) I)Iati RoJ:111 1. DESIGN CONDITIONS at 3 PM Peak load at 3 PM Inside: 75 OF Outside: 90 OF TD: 15 OF RH: 50 % Moisture: 61 gr/lb Mult: i.0 Ins." 63 OF Sensible Latent 2. SOLAR RADIATION THROUGH GLASS 1592 3. TRANSMISSION GAINS Sensible 5807 - Walls: 195 - - • - Glass: 420 - - Doors: 845 - - Partitions: 0 - - Floors: 0 - - Roofs/Ceilings: 1957 - - Return Air Ceiling: 2390 - - 4. INTERNAL HEAT GAIN Sensible Latent 6338 2100 Occupants: 4500 2100 - - Lights: 1838 0 - - Motors: 0 0 - - Appliances & Other: 0 0 - - 5. INFILTRATION: Outside air cfm: 63 1045 2645 - 6. SUBTOTAL: Space load 14781 4745 7. SUPPLY DUCT - 443 S. SUBTOTAL: Bldg comp's and supply duct 15225 - Actual cfm: 692 at Supply TD: 20 - - 9. VENTILATION: Make—up air cfm: 200 3300 8352 10. RETURN AIR LOAD: Lighting & roof (net) 672 - 11. RETURN DUCT 0 - 12. TOTAL LOADS ON EQUIPMENT 19197 13097 BEATING -LOAD 13. DESIGN CONDITIONS Mult: 1.0 • Inside: 70 OF Outside: 42 OF TD: 28 OF 14. TRANSMISSION LOSSES, 5679 Wallg: 861 - - Glass: 784 - • Doors: 1577 - Partitions: 0 - • Floors: 785 - • Roofs/Ceilings: 837 - Return Air Roof 837 - 15. INFILTRATION: Outside air cfm: 150 4610 16. SUBTOTAL: Building components 10289 17. SUPPLY DUCT: 514 18. VENTILATION: Make—up air cfm: 200 6160 19. HUMIDIFICATION 4231 20. RETURN DUCT 0 + 21. TOTAL HEATING LOAD ON EQUIPMENT 21194 Manual N: 4th Edition Right-N: Ver,3.6.04 Certified by ACCA to meet all requirements of Manual Form N SIN R1*21393 RIGHT-N COMMERCIAL / INDUSTRIAL LOAD CALCULATION Nov 26, 2000 For: FT. PIERCE MASONIC LODGE Zone: SOCIAL AREA Page: 1 _ Job #: City: Fort Pierce, FL, US By: WOLF AIR CONDITIONING LWH: 34.6 x 21.0 x 10.0 Units: U.S. customary (I-P ) 1. DESIGN CONDITIONS - COOLING ( 3 PM , August ) Dry Blb RH Moisture Range Wet Blb Outdoor Conditions > 90 59 15 78 Indoor Conditions > 75 50 63 TOD Correction > 0 Difference 15 61 [ Mult = 1.0 J - ` 2. GLAZING SOLAR HEAT GAIN ( Lat = 27.00 'N, Const'Wt = M ) Type Dir Shad Tilt %ovr Area Sfact Shgf Shad Sens - GLAZ 1 N N 90 100.0 56 0.98 29 1.0 1592 3. TRANSMISSION GAINS Type Dir GrArea NtArea Uval Grp CLTD Shad Clr Sens GLAZ 1 N 56 56 0.500 15.0 N - 420 WALL 1 N 346 270 0.114 B 6.3 N L 195 WALL 1 N 0 0 0.114 B .6.3 N L 0 DOOR 1 N 20 20 0.560 15.0 - - 1-71 DOOR 2 W 0 0 1.100 15.0 - - 673 FLOR 1 - 35 35 0.810 0.0 - - 0 ROOF 1 - 747 747 0.040 R-4 65.5 - D 1957 - RARF 1 - 747 747 0.040 R-4 61.5 - - 1838 RACL 1 - :747 747 0.800 4.0 - - 2390 4. INTERNAL HEAT GAIN Sens Latent People 20 x Per person: sensible 225 latent 105 4500 2100 0 ' x Per person: sensible 300 latent 300 0 0 Lights Incandescents in RA Ceiling 0 x 3.4 x 60% 0 Fluorescents in RA Ceiling 747 x 4.1 x 60% 1838 Incandescents other 0 x 3.4 x 100% 0 Fluorescents other 0 x 4.1 x 100% 0 Motors Nmbr Power Gain Load Fa-: Usage 1 1 ` 0.00 0 1.00 1.00 0 ` 2 1 0.00 0 1.00 1.00 0 3 1 0.00 0 1-.00 1.00 0 Appl. Nmbr Type Sens Latent Usage 1 1 0 0 1.00 0 0 2 1 0 0 1.00 0 0 3 1 0 0 1.00 0 0 4 1, 0 0 1.00 0 0 5 1 0 G. 1.00 0 0 Other 1 0 0 1.00 0 0 S. INFILTRATION Sens Latent 63 cfm > x db Temp Diff 15.0 x 1.1 1045 > x Moist. Diff 61.4 x 0.68 2645 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N f Job #: Page: 2 6. SUBTOTAL COOLING LOAD FOR SPACE 14781 4745 7. SUPPLY DUCT HEAT GAIN Gain factor 0.03 x Line 6 Sensible Gain 443 S. COOLING FAN SIZING Sum of Duct Gain (7 ), Line (6) & Drawthru Fan = 15225 _ (L 8 Sens ) 1 ( 1.1 x Supply TD ) = cfm Est Cooling cfm = ( 15225) / (1.1 x 20.0 ) = 692 Actual Cooling Fan > = 692 9. VENTILATION 200 cfm > x db Temp Diff 15.0 x 1.1 3300 > x Moist. Diff 61.4 x 0.68 8352 10. RETURN AIR LOAD FROM LIGHTING AND ROOF Incandescent Lights 0 Watts x 3.4 x 40% 0 Fluorescent Lights 747 x 4.1 x 40% 1225 - RA Roof Load from Line 3 M 1838 RA Ceiling Load Credit from Line 3 (-) 2390 - 11. RETURN DUCT HEAT GAIN 12. TOTAL COOLING LOADS ON EQUIPMENT (Btuh) 19197 13097 SPACE HEATING LOAD CALCULATION 13. HEATING DESIGN TEMPERATURE Heating TD = (Inside DB - Outside DB) - ( 70 4 2) = 28 [ Mult = 1.0 J - 14. TRANSMISSION LOSSES Type Expos GrArea NetArea Uval HTD Loss GLAZ 1 N 56 56 0.500 28.0 784 - WALL 1 N 346 270 0.114 28.0 861 WALL 1 N 0 0 0.114 28.0 0 DOOR 1 N 20 20 0.560 28.0 320 DOOR 2 W 0 0 1.100 28,0 1257 FLOR 1 - 35 35 0.810 28.0 785 ROOF 1 - 747 747 0.040 28.0 837 S 15. INFILTRATION Loss -- 15 0 c fm x db Temp Diff 28.0 x 1.1 4 610 • - 16. SUBTOTAL HEATING LOAD FOR SPACE 10289 17. SUPPLY DUCT HEAT LOSS Loss factor 0.05 x Line 16 Loss 514 18. VENTILATION 200 cfm x db Temp Diff 28.0 x 1.1 6160 r Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N . Job #: Page: 3 19. HU'MM171CATION Inside RH desired 40.0 (Max = 32.0 for 1 pane ) # of Glazing panes 2.0 (Max = 52.0 for 2 pane ) 350 cfm x 3.20 g/100cfm/d = 11.2 gpd 4231 20. RETURN DUCT HEAT LOSS Loss factor 0.00 x Line 16 Loss 0 21. TOTAL HEATING LOAD ON EQUPMENT (Btuh) 21194 P Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N SIN RNW21393 RIGHT-N ZONE SUMMARY Units:' U.S. customary (I—P) For: FT. PIERCE MASONIC LODGE By: WOLF AIR CONDITIONING Job #: COOLING LOAD Nov 26, 2000 Zone: MULIT—BODY OFFICE 1. DESIGN CONDITIONS at 3 PM Peak load at 3 PM Inside: 75 OF Outside: 90 OF TD: 15 OF RH: 50 % Moisture: 61 gr/lb Mult: 1.0 Ins.wb 63 OF • Sensible Latent 2. SOLAR RADIATION THROUGH GLASS 398 - 3. TRANSMISSION GAINS Sensible 2113 - • Walls: 206 - - Glass: 105 - - Doors: 673 - - Partitions: 0 - - Floors: 0 - - Roofs/Ceilings: 508 - - Return Air Ceiling: 621 - - 4. INTERNAL HEAT GAIN Sensible Latent 727 200 Occupants: 250 200 - - Lights: 477 0 - - Motors: 0 0 Appliances & Other: 0 0 - - 5. INFILTRATION: Outside air cfm: 0 0 0 6. SUBTOTAL: Space load 3238 200 7. SUPPLY DUCT 97 - 8. SUBTOTAL: Bldg comp's and supply duct 3335 - Actual cfm: 152 at Supply TD: 20 - - 9. VENTILATION: Make—up air cfm: 20 330 835 10. RETURN AIR LOAD: Lighting & roof (net) 175 - 11. RETURN DUCT 0 - _ 12. TOTAL LOADS ON EQUIPMENT 3840 1035 HEATING LOAD 13. DESIGN CONDITIONS Mult: 1.0 _ Inside: - 70 OF Outside: 42 OF TD: 28 OF 14. TRANSMISSION LOSSES 2530 - Walls: 358 - • Glass: 196 - Doors: 1257. - • Partitions: 0 - • Floors: 286 - Roofs/Ceilings: 217 - Return Air Roof. 217 - 15. INFILTRATION: Outside air cfm: 9 291 16. SUBTOTAL: Building components 2822 17. SUPPLY DUCT: 141 • 18. VENTILATION: Make—up air cfm: 20 616 19. HUDI MEFICATION 356 20, RETURN DUCT 0 " 21. TOTAL HEATING LOAD ON EQUIPMENT 3935 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N f SIN RNW213 93 RIGHT-N COMMERCIAL / INDUSTRIAL LOAD CALCULATION Nov 26, 2000 For: FT. PIERCE MASONIC LODGE Zone: MULIT-BODY OFFICE Page: Job #: City: Fort Pierce, FL, US By: WOLF AIR CONDITIONING LWH: 15.0 x 12.6 x 10.0 Units: U.S. customary (I-P) • 1. DESIGN CONDITIONS - COOLING ( 3 PM , August ) Dry Bib RH Moisture Range Wet Bib Outdoor Conditions > 90 59 15 78 Indoor Conditions -> 75 50 63 TOD Correction > 0 Difference 15 61 [ Mult = 1.0 ] - 2. GLAZING SOLAR HEAT GAIN ( Lat = 27.00 *N, Const Wt = M ) . Type Dir Shad Tilt %ovr Area Sfact Shgf Shad Sens GLAZ 1 E N 90 100.0 14 0.98 64 1.0 398 3. TRANSMISSION GAINS Type Du GrArea NtArea Uval Grp CLTD Shad Clr Sens GLAZ 1 E 14 14 0.500 15.0 N - 105 WALL 1 E 126 112 0.114 B 1'6.1 =: L 206 WALL 1 E 0 0 0.114 B 16.1 N L 0 DOOR 1 N 0 0 0.560 15.0 - - 0 DOOR-- 2 W 0 0 1.100 15.0 - - 673 FLOR 1 - 13 13 0.810 0.0 - - 0 ROOF 1 194 194 0.040 R-4 65.5 - D 508 RARF 1 - 194 194 0.040 R-4 61.5 - - 477 RACL 1 - 194 194 0.800 4.0 - 621 4. INTERNAL HEAT GAIN Sens Latent People 1 x Per person: sensible 250 latent 200 250 200 0' x Per person: sensible 300 latent 300 0 0 Lights Incandescents in RA Ceiling 0 x 3.4 x 60% 0 Fluorescents in RA Ceiling 194 x 4.1 x 60% 477 Incaudescents other 0 x 3.4 x 100% 0 Fluorescents other 0 x 4.1 x 100% 0 Motors Nmbr Power Gain Load Fact Usage 1 1 0.00 0 1.00 1.00 0 2 1 0.00 0 1.00 1.00 0 3 1 0.00 0 1.00 1.00 0. Appl. Nmbr Type Sens Latent Usage 1 1 0 0 1.00 0 0 2 1 0 0 1.00 0 0 3 1 0 0 1.00 . 0 0 4 1 0 0 1.00 0 0 5 1 0 0 1.00 0 0 Other 1 0 0 1.00 0 0 5. INFILTRATION Sens Latent ' 0 c fm > x db Temp Diff 15.0 x 1.1 0. > x Moist. Diff 61.4 x 0.68 f 0 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N . I Job #: .Page: • 2 6. SU$TOTAI4 COOLING LOAD FOR SPACE 3238 '200 7. SUPPLY DUCT HEAT GAIN Gain factor 0.03 x Line 6 Sensible Gain 97 - S. COOLING FAN SIZING Sum of Duct Gain (7 ), Line (6) & Drawthru Fan = 3335 (L 8 Sens ) / ( 1.1 x Supply ID ). = cfm Est Cooling cfm = ( 3335) / ( 1.1 x 20.0 ) = 152 - Actual Cooling Fan _, ,: _;: -: ,;:: > = 152 9. VENTILATION 20 cfm > x db Temp Diff 15.0 x 1.1 330 > x Moist. Diff 61.4 x 0.68 835 10. RETURN AIR LOAD FROM LIGHTING AND ROOF Incandescent Lights 0 Watts x 3.4 x 40% 0 Fluorescent Lights 194 x 4.1 x 40% 318 RA Roof Load from Line 3 N 477 - RA Ceiling Load Credit from Line 3 (-) 621 11. RETURN DUCT HEAT GAIN Gain factor 0.00 x Line 6 Sensible Gain 0 12. TOTAL COOLING LOADS ON EQUIPMENT (Btuh) 3840 1035 SPACE HEATING LOAD CALCULATION 13. HEATING DESIGN TEMPERATURE Heating TD = (Inside DB - Outside DB) _ ( 70 - 4 2) = 28 [ Mult = 1.0 ] - 14. TRANSMISSION LOSSES Type Expos GrArea NetArea Uval HTD Loss GLAZ 1 E 14 14 0.500 2.8.0 196 Tn1P,LL 1 E 126 112 0.114 28.0 358 WML 1 E 0 0 0.114 28.0 0 DOOR 1 N 0 0 0.560 28.0 0 DOOR 2 W 0 0 1.1100 28.0 1257 FLOR 1 - 13 13 0.810 28.0 2-86 • ROOF 1 - 194 194 0.040 28.^ 217 15. INFILTRATION Loss 9 cfm x db Temp Diff 28.0 x 1.1 291 16. SUBTOTAL HEATING LOAD FOR SPACE 2 8 2 2 17. SUPPLY DUCT HEAT LOSS Loss factor 0.05 x Line 16 Loss 141 18. VENTILATION 2 0 cfm x db Temp Diff 28.0 x 1.1 616 9 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N Job #: I Page: 3 19. HUMIDIFICATION ' Inside 1%1H desired 40.0 (Max = 32.0 for 1 pane ) # of Glazing panes 2.0 (Max = 52.0 for 2 pane ) 29 cfm x 3.20 g/100cfm/d = 0.9 gpd 356 20. RETURN DUCT HEAT LOSS Loss factor 0.00 x Line 16 Loss 0 21. TOTAL HEATING LOAD ON EQUPMENT (Btuh) 3935 0 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N SIN, PNW21393 RIGHT-N ZONE SUMMARI' Units: U.S. customary (I—P) For: FT. PIERCE MASONIC LODGE By: WOLF AIR CONDITIONING Job #: Nov 26, 2000 Zone: PARAPH 3 COOLING LOAD 1. DESIGN CONDITIONS at 3PM Peak load at 3PM Inside: 75 OF Outside: 90 OF TD: 15 OF RH: 50 % Moisture: 61 gr / lb Mult: 1.0 Ins.wb 63 OF Sensible Latent 2. SOLAR RADIATION THROUGH GLASS 796 - 3. TRANSMISSION GAINS Sensible 2726 - Walls: 411 - - Glass: 210 - - Doors: 673 - - Partitions: 0 - - Floors: 0 - - Roofs/Ceilings: 645 - - Return Air Ceiling: 787 - - 4. INTERNAL HEAT GAIN Sensible Latent 855 200 Occupants: 250 200 - - Lights: 605 0 - - Motors: 0 0 - - Appliances & Other: 0 0 - - 5. INFILTRATION: Outside air cfm: 0 0 0 6. SUBTOTAL: Space load 4377 200 7. SUPPLY DUCT 131 - 8. SUBTOTAL: Bldg comp's and supply duct 4508 - Actual cfm: 205 at Supply TD: 20 - - 9. VENTILATION: Make=up,air cfm: 20 330 835 10. RETURN AIR LOAD: Lighting & roof (net) 221 - 11. RETURN DUCT 0 - 12. TOTAL LOADS ON EQUIPMENT 5059 1035 HEATING LOAD 13. DESIGN CONDITIONS Mult: 1.0 Inside: 7 0 OF Outside: 42 OF TD: 28 OF 14. TRANSMISSION LOSSES 3825 Walls: 913 - Glass: 392 - Doors: 1257 - Partitions: 0 - Floors: 712 - Roofs/Ceilings: 276 - Return Air Roof. 276 - 15. INFILTRATION: Outside air cfm: 12 370 16. SUBTOTAL: Building components 4194 17. SUPPLY DUCT: 210 18. VENTILATION: Make—up air cfm: 20 616 19. HUMIDIFICATION 387 20. RETURN DUCT 0 r 21. TOTAL HEATING LOAD ON EQUIPMENT 5407 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N SIN RNW21393 RIGHT-N COMMERCIAL / INDUSTRIAL LOAD CALCULATION Nov 26, 2000 For: FT. PIERCE MASONIC LODGE - Zone: PARAPH 3 Page: 1 Job #: City: Fort Pierce, FL, US By: WOLF AIR CONDITIONING LWH: 15.0 x 16.0 x 10.0 Units: U.S. customary (I-P) 1. DESIGN CONDITIONS - COOLING ( 3 PM , August ) Dry Blb RH Moisture Range Wet Bib Outdoor Conditions > 90 59 15 78 Indoor Conditions > 75 50 63 TOD Correction > 0 Difference 15 61 [ Mult = 1.0 ] - 2. GLAZING SOLAR BEAT GAIN ( Lat = 27.00 ON, Const Wt = M ) Type Dir Shad Tilt %ovr Area Sfact Shgf Shad Sens GLAZ 1 E N 90 100.0 28 0.98 64 1.0 796 3. TRANSMISSION GAINS Type Dir GrArea NtArea Uval Grp CLTD Shad Clr Sens GLAZ 1 E 28 28 0.500 15.0 N - 210 WALL 1 S .154 154 0.114 B 9.6 N L 169. WALL 1 E 160 132 0.114 B 16.1 N L 242 DOOR 1 N 0 0 0.560 15.0 - - 0 DOOR 2 W 0 0 1.100 15.0 - - 673 FLOR 1 - 31 31 0.810 0.0 - - 0 ROOF 1 - 246 246 0.040 R-4 65.5 - D 645 RARF 1 - 246 246 0.040 R-4 61.5 - - 605 RACL 1 - 246 246 0.800 4.0 - 787 4. INTERNAL HEAT GAIN Sens Latent People 1 x Per person: sensible 250 latent 200 250 200 0 x Per person: sensible 300 latent 300 0 0 Lights Incandescents in RA Ceiling 0 x 3.4 x 60% 0 Fluorescents in RA Ceiling 246 x 4.1 x 60% 605 Incandescents other 0 x 3.4 x 100% 0 Fluorescents other 0 x 4.1 x 100% 0 Motors Nmbr Power Gain Load Fact Usage 1 1 0.00 0 1.00 1.00 0 2 1 5 0.00 0 1.00 1.00 0 3 1 0.00 0 1.00 1.00 0 Appl. Nmbr Type Sens Latent Usage 1 1 0 0 1.00 0 0 2 1 0 0 1.00 0 0 3 1 0 0 1.00 0 0 4 1 0 0 1.00 0 0 5 1 0 0 1.00 0 0 Other 1 0 0 1.00 0 0 S. INFILTRATION Sens Latent 0 cfm > x db Tamp Diff 15.0 x 1.1 0 • > x Moist. Diff 61.4 x 0.68 ' 0 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N . Page: 2 6. SUBTOTAL COOLING LOAD FOR SPACE 4377 200 7. SUPPLY DUCT HEAT GAIN Gain factor 0.03 x Line 6 Sensible Gain 131 & COOLING FAN SIZING Sum of Duct Gain (7 ), Line (6) & Drawthru Fan = 4508 (L 8 Sens , ) / (1.1 x Supply TD ) = cfm Est Cooling cfm = ( 4508) / ( 1.1 x 20.0 ) = 205 Actual Cooling Fan > = 205 9. VENTILATION 20 cfm > x , db Temp Diff 15.0 x 1.1- 330 > x Moist. Diff 61.4 x 0.68 835 10. RETURN AIR LOAD FROM LIGHTING AND ROOF Incandescent Lights 0 Watts x 3.4 x 40% 0 Fluorescent Lights 246 x 4.1 x 40% 403 RA Roof Load from Line 3 N 605 RA Ceiling Load Credit from Line 3 (-) 787 11. RETURN DUCT HEAT GAIN Gain factor ' 0.00 x Line 6 Sensible Gain 0 12. TOTAL COOLING LOADS ON EQUIPMENT (Btuh) 5059 1035 SPACE HEATING LOAD CALCULATION 13: • HEATING DESIGN TEMPERATURE Heating TD = (Inside DB - Outside DB) _ ( 70 - 4 2) = 28 [ Mult = 1.0 j - 14. TRANSMISSION LOSSES y Type Expos . GrArea NetArea Uval HTD Loss GLAZ 1 E 28 28 0.500 28.0 392 WALL 1 S 154 154 0.114 28.0 492 WALL 1 E 160 132 0.114 28.0 421 DOOR 1 N 0 0 0.560 28.0 0 DOOR 2 W 0 0 1.100 28.0 1257 FLOR 1 - 31 31 0.810 28.0 712 ROOF 1 - 246 246 0.040 28.0 276 15. INMTRATION Loss 12 cfm x db Temp Diff 28.0 x 1.1 370 16. SUBTOTAL HEATING LOAD FOR SPACE 4194 17. SUPPLY DUCT HEAT LOSS Loss factor 0.0 5 x Line 16 Loss 210 I& VENTILATION 20 c fm x db Temp Diff 28.0 x 1.1 616 u Manual N: 4th Edition Right-N: Ver,10.04 Certified by ACCA to meet all requirements of Manual Form N.., i Job #: ' Page: 3 19. HUMIDIFICATION In§ider Rai dasired 4 0.0 (Max = 32.0 for 1 pane ) # of Glazing panes 2.0 (Max = 52.0 for 2 pane ) 32 cfn x 3.20 g/100cfm/d = 1.0 gpd 387 20. RETURN DUCT HEAT LOSS Loss factor 0.00 x Line 16 Loss 0 21. TOTAL HEATING LOAD ON EQUPMENT (Btub) 5407 S Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N n � 1 SIN RNW21393 RIGHT-N ZONE SUMMARY SUnits: U.S. customary (I-P) Nov 26, 2000 For: FT. PIERCE MASONIC LODGE By: WOLF AIR CONDITIONING Job #: Zone: PARAPH 2 COOLING LOAD 1. DESIGN CONDITIONS at 3 PM Peak load at 3 PM Inside: 75 OF Outside: 90 OF TD: 15 OF RH: 50 % Moisture: 61 gr/lb Mult: 1.0 Ins.wb 63 OF Sensible Latent 2. SOLAR RADIATION THROUGH GLASS 398 - 3. TRANSMISSION GAINS Sensible 1901 - Wads: 169 _ Glass: 105 Doors: 673 Partitions: 0 Floors: 0 Roofs/Ceilings: 427 Return Air Ceiling: 526 4. INTERNAL HEAT GAIN Sensible Latent 666 200 Occupants: 250 200 - _ Lights: 416 0 _ Motors: 0 0 Appliances & Other: 0 0 S. INFILTRATION: Outside air cfm: 0 0 0 _ 6. SUBTOTAL: Space load 2964 200 7. SUPPLY DUCT 89 _ S. SUBTOTAL: Bldg comp's and supply duct 3053 - Actual cfm: 139 at Supply TD: 20 - _ 9. VENTILATION: Make-up air cfm: 20 330 835 10. RETURN AIR LOAD: Lighting & roof (net) 151 - 11. RETURN DUCT 0 _ 12. TOTAL LOADS ON EQUIPMENT 3535 1035 HEATING LOAD 13. DESIGN CONDITIONS Mult: 1.0 Inside: 70 OF Outside: 42 OF TD: 28 OF 14. TRANSMISSION LOSSES 2352 Walls: 294 _ Glass: 196 _ Doors: 1257 _ Partitions: 0 _ _ Floors: 240 _ Roofs/Ceilings: 183 _ Return Air Roof 183 _ 15. INFILTRATION: Outside air cfm: 8 245 16. SUBTOTAL: Building components 2597 17. SUPPLY DUCT: 130 18. VENTILATION: Make-up air cfm: 20 616 19. HU11'II0I1FICATION 338 20. RETURN DUCT 0 21. TOTAL HEATING LOAD ON EQUIPMENT 3681 Manual N: 4th Edition Right-N: Ver.3-0.04 ' Certified by ACCA to meet all requirements of Manual Form N C N uuo3 IonmY1i3o S;u*=.gnbaJ Hu Paw (n do0d Aq pagiva0 b0'0':,'6JaA :N-Iq2RI uoipPE[ q;b :H jvnuwW 8 9' U x P' T 9 $Ia Isiow,, x < . 0 TT x 0' S T jFa daaaZ qp x < tu; 0 0 ;°m'I SwS MOLLVILLmaM '9 0 0 0 0' T 0 0 T aaq;o 0 0 00'T 0 0 T S 0 0 00'T 0 0 T b 0 0 00'T 0 0 T £ 0 0 00'T 0 0 T Z 0 0 00'T 0 0 T I osesfl WWII sues QCRJ, JgtaN •lddy 0 00'T 00'T 0 00'0 T £ 0 00'T 00'T 0 00'0 T Z 0 00'T OD'T 0 .0010 ' T I aSesfl 10e3 pe011 tnuJ Jomod JgtaN SJ%0I41 0 %00I x T'% x 0 Jatpo spoosaJonid 0 %OOI x 5'£ x 0 Jag;o s;uaosopwoul. 9 T P %09 x T' P x 6 9 T 2tsclia0 vI qT s;uaasaJonl 4 0 %09 x PIC x 0 SugjQD VE u! s;uaosopueoui s;gBlZ 0 0 00£ lualmi 00£ olq►sues :uosmdJad x 0 O O Z O S Z O O Z MOM O S Z olglsues : uosiod .tad x T old luals-I SwS NlV9 J.VXH'1VKHZIM Is, 9zS - - 0'b 008'0 C9T 89T - T 'IOVH TOP - - S'T9 P-d OPO'0 £9T £9T' - T al2i LZP Q 9'99 P-d OPO'0 £9T £9T - T aOOH 0 - - 010 OT8' 0 TT TT - T IlOI3 £L9 - - 0' ST OOT' T 0 0 M Z HOOCI 0 - - 0'9T 09910 0 0- N T 21000: 0 U N T'9T 8 PTT'O 0 0 a T 'ITV] 69T 'I N T'9T g PTT-0 Z6 90T a T =04 SOT - N 0' ST OOS' 0 PT bT a T Z qS sues go pegS a.L Io dJ IeAn tsalvix 80.1VJo JTa adt,L Smwf) NOISSMSNVKL '£ 866 0'T b9 86'0 PT O'OOT 06 N, T ZVUE) Sues pSgS jggS I093S eaJd JAo% ;It.L PRS •na ad&l, ( InI = IM isuo� ` N o 0 0 ' L Z = Irl AIIV9 lVaH IIV'IOS 9AIIZV'I9 'Z — 0 ' T = IInW T 9 S T aoualop T :aSed OOOZ '93 AoN 0 <— uoTPau03 aol £ 9 09 S L <— suoMpuo0,Taopul - 8 L S T 69 06 <— suoT;ipu00 Joop;no ' gig 3aM a$msg aJnis►oW HE qjS A•ta ( IsngnV Wd£ ) 9mrio0a - Smolillamoo WHS79 'T (d-I) Axemoqsno •S-n :s;lun O'OT x 9'OT x O'ST :HM'I JNINOI1I¢N00 'dlV a'IOM :Ag Sfl ''Ia 'aoaaia gaoa :A4T3 : # qof z Hdvuva :ouoz SJQO'I aINOS'VK SOdaId ' Z3 :103 moiLvrla7'IVa QVO'I'IVRI,ISflam /'IVI3v3mwoj N-J 9III S6£TZMNH NA � � �.� _ .}� i .,,L.. .y.. �., _. ..L Job #: ' Page: 2 6. SUBTOTAL COOLING LOAD FOR SPACE 2964 200 7. SUPPLY DUCT BEAT GAIN Gain. factor 0.03 z Liine 6 Sensible "Gain 89 S. COOLING FAN SIZING Sum of Duct Gain (7 ), Line (6) & Drawthru Fan = 3053 (L 8 Sens ) / ( 1.1 x Supply TD ) = cfm Est Cooling cfm = ( 3053) / (1.1 x 20.0 ) = 139 Actual Cooling Fan > = 139 9. VENTILATION 20 cfm > x db Tamp Diff 15.0 x 1.1 330 > x Moist. Diff 61.4 x 0.68 835 10. RETURN AIR LOAD FROM LIGHTING AND ROOF Incandescent Lights 0 Watts x 3.4 x 40% 0 FluorescentLights 169 x 4.1 x 40% 277 RA Roof Load from Line 3 M 401 RA Ceiling Load Credit from Line 3 (-) 526 11. RETURN DUCT HEAT GAIN Gain factor 0.00 x Line 6 Sensible Gain 0 12. TOTAL COOLING LOADS ON EQUIPMENT (Btuh) 3535 1035. SPACE BEATING LOAD CALCULATION 13. BEATING DESIGN TEMPERATURE Heating TD = (Inside DB - Outside DB) _ ( 70 - 42) = 28 [ Mult = 1.0 ] - 14. TRANSMISSION LOSSES Type Expos GrArea NetArea Uval HTD Loss GLAZ 1 E 14 14 0.500 28.0 196 WALL 1 E 106 92 0.114 28.0 294 WALL 1 E 0 0 0.114 28.0 0 DOOR 1 N 0 0 0.560 28.0 0 DOOR 2 W 0 0 1.100 28.0 1257 FLOR 1 - •11 11 0.810 28.0 240 ROOF 1 - 163 163 0.040 28.0 183 S 15. INFILTRATION Loss 8 cfm x db Temp Diff 28.0 x 1.1 2 4 5 16. SUBTOTAL HEATING LOAD FOR SPACE 2597 • 17. SUPPLY DUCT BEAT LOSS Loss factor 0.05 x Line 16Loss 130 -18. VENTILATION 20 cfm x db Temp Diff 28.0 x 1.1 616 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N Job #: ' Page: 3 19. EWWM ICATION Inside R11 desired 4 0.0 (Max = 32.0 for 1 pane ) # of Glazing panes 2.0 (Max = 52.0 for 2 pane ) 28 cfm x 3.20 g/100cfm/d = 0.9 gpd 338 20. RETURN DUCT HEAT LOSS Loss factor 0.00 x Line 16Loss 0 21. TOTAL HEATING LOAD ON EQUPMENT (Btah) 3681 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N 1 ` SIN RNW21393 RIGHT-N ZONE SUMMARY Units U.S. customary (I—P) Nov 26, 2000 " For: FT. PIERCE MASONIC LODGE By: WOLF AIR CONDITIONING Job #: Zone: PARAPH 1 COOLING LOAD 1. DESIGN CONDITIONS at 3PM Peak load at 3PM Inside: 75 OF Outside: 90 OF TD: 15 OF RH: 50 % Moisture: 61 gr/lb Mult: 1.0 Ins.wb 63 OF Sensible Latent 2. SOLAR RADIATION THROUGH GLASS 398 - 3. TRANSMISSION GAINS Sensible 2049 - Walls: 288 - _ Glass: 105 Doors: 673 Partitions: 0 Floors: 0 - Roofs/Ceilings: 443 - Return Air Ceiling: 541 - _ 4. INTERNAL HEAT GAIN Sensible Latent 666 200 Occupants: 250 200 - - Lights: 416 0 - - Motors: 0 0 - - Appliances & Other: 0 0 - - S. INFILTRATION: Outside air cfm: 0 0 0 6. SUBTOTAL: Space load 3113 200 7. SUPPLY DUCT 93 - 8. SUBTOTAL: Bldg comp's add supply duct 3206 - Actual cfm: 146 at Supply TD: 20 9. VENTILATION: Make—up air cfm: 20 330 835 10. RETURN AIR LOAD: Lighting & roof (net) 152 - 11. RETURN DUCT 0 - 12. TOTAL LOADS ON EQUIPMENT 3689 1035 HEATING LOAD 13. DESIGN CONDITIONS Mult: 1.0 Inside: 70 OF Outside: 42 OF TD: 28 OF _ 14. TRANSMISSION LOSSES 3228 Walls: 798 - _ Glass: 196 _ Doors: 1257 _ Partitions: 0 _ Floors: 599 - Roofs/Ceilings: 189 _ Return Air Roof 189 _ _ 15. INMTRATION: Outside air cfm: 8 254 16. SUBTOTAL: Building components 3482 17. SUPPLY DUCT: 174 18. VENTILATION: Make—up air cfm: 20 616 19. HUMIDIFICATION 342 20. RETURN DUCT 0 21. TOTAL HEATING LOAD ON EQUIPMENT 4 614 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N SIN RNW21393 RIGHT-N COMMERCIAL/ INDUSTRIAL LOAD CALCULATION Nov 26, 2000 / For: FT. PIERCE MASONIC LODGE " Zone: PARAPH 1 Page: 1 Job #: City: Fort Pierce, FL, US By: WOLF AIR CONDITIONING LWH: 15.0 x 11.0 x 10.0 Units: U.S. customary (I-P) 1. --• DESIGN CONDITIONS - COOLING ( 3 PM , August ) Dry Bib RH Moisture Range Wet Bib Outdoor Conditions > 90 59 15 78 Indoor Conditions => 75 50 63 TOD Correction > 0 Difference 15 61 [ Mult = 1.0 ] - 2. GLAZING SOLAR HEAT GAIN ( Lat = 27.00 ° N , Const Wt = M ) . Type Dir Shad Tilt "/oovr Area Sfact Shgf Shad Sens GLAZ 1 E N 90 100.0 14 0.98 64 1.0 398 3. TRANSMISSION GAINS Type Dir GrArea NtArea Uval Grp CLTD Shad Clr Sens GLAZ 1 E 14 14 0.500 15.0 IT - 105 WALL 1 N 154 154 0.114 B 6.3 N L ill WALL 1 E 110 96 0.114 B 16.1 N L 176 DOOR 1 N 0 0 0.560 15.0 - - 0 DOOR 2 W 0 0 1.100 15.0 - - 673 FLOR 1 - 26 26 0.810 0.0 - - 0 ROOF 1 - 169 169 0.040 R-4 65.5 - D 443 RARF 1 - 169 169 0.040 R-4 61.5 - - 416 RACL 1 - 169 169 0.800 4.0 �, - - 541 4. INTERNAL HEAT GAIN Sens Latent People 1 x Per person: sensible 250 latent 200 250 .200 0 x Per person: sensible 300 latent 300 0 0 Lights Incandescents in RA Ceiling 0 x 3.4 x 60% 0 Fluorescents in RA Ceiling 169 x 4.1 x 60% 416 Incandescents other 0 x 3.4 x 100% 0 Fluorescents other 0 x 4.1 x 100% 0 Motors Nmbr Power Gain Load Fact Usage 1 1 t 0.00 0 1.00 1.00 0 2 1 0.00 0 1.00 1.00 0 3 1 0.00 0 1.00 1.00 0 Appl. Nmbr Type Sens Latent Usage 1 1 0 0 1.00 0 0 2 1 0 0 1.00 0 0 3 1 0 0 1.00 0 0 4 1 0 0 1.00 0 0 5 1 0 0 1.00 0 0 Other 1: 0 0 1.00 0 0 S. INFILTRATION Sens Latent 0 cfm > x db Temp Diff 15.0 x 1.1 0 • > x Moist. Diff 61.4 x 0.68 ' 0 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N Job #: page: 2 6. SUBTOTAL COOLING LOAD FOR SPACE 3113 200 7. SUPPLY DUCT HEAT GAIN Gain factor 0.03 x Line 6 Sensible Gain 93 S. COOLING FAN SIZING Sum of Duct Gain (7 ), Line (6) & Drawthru Fan = 3206 (L 8 Sens ) / ( 1.1 x Supply TD ) = cfm Est Cooling c fm = ( 3 2 0 6) / ( 1.1 x 2 0.0 ) = 146 Actual Cooling Fan > = 146 9. VENTILATION 20 c fm > x db Tamp Diff 15.0 x 1.1 330 > x Moist. Diff 61.4 x 0.68 6,35 10. RETURN AIR LOAD FROM LIGHTING AND ROOF Incandescent Lights 0 Watts x 3.4 x 40% 0 Fluorescent Lights 169 x 4.1 x 40% 277 RA Roof Load from Line 3 M 416 RA Ceiling Load Credit from Line 3 (-) 541 11. RETURN DUCT HEAT GAIN Gain factor 0.00 x Line 6 Sensible Gain 0 12. TOTAL COOLING LOADS ON EQUIPMENT (Btuh) 3689 1035 --- SPACE HEATING LOAD CALCULATION 13. HEATING DESIGN TEMPERATURE Heating TD = (Inside DB - Outside DB) _ ( 70 - 42) = 28 [ Mult = 1.0 ] - - 14. TRANSMISSION LOSSES Type Expos GrArea NetArea Uval HTD Loss GLAZ 1 ' E 14 14 0.500 28.0 196 WALL 1 N 154 154 0.114 28.0 492 WALL 1 E 11.0 96 0.114 28.0 806 DOOR 1 N 0 0 0.560 28.0 0 DOOR 2 W 0 0 1.100 28.0 1257 FLOR 1 - 26 26 0.810 28.0 599 ROOF 1 - 169 169 0.040 28.0 189 15. INFILTRATION Loss 8 c fm x db Temp Diff 28.0 x 1.1 2� 4 16. SUBTOTAL HEATING LOAD FOR SPACE 3482 17. SUPPLY DUCT HEAT LOSS Loss factor 0.05 x Line 16 Loss 174 18. VENTILATION 20 c fm x db Temp Diff 28.0 x 1.1 616 r Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N Job #: Page: 3 19. HUMIDIFICATION Inside RH desired 40.0 (Max = 32.0 for 1 pane ) # of Glazing panes 2.0 (Max = 52.0 for 2 pane ) 28 cfm x 3.20 g/100cfm/d = 0.9 gpd 342 20. RETURN DUCT HEAT LOSS Loss factor 0.00 x Line 16 Loss 0 21. TOTAL HEATING LOAD ON EQUPMENT (Btuh) 4 614 s Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N ti S%N RNW21393 RIGHT-N ZONE SUMMARY Units: U.S. customary (I-P) Nov 26, 2000 For: 1 FF'. PIERCE MASONIC LODGE By: WOLF AIR CONDITIONING Job #: Zone: STORAGE/HALL COOLING LOAD 1. DESIGN CONDITIONS at 3 PM Peak load at 3 PM - Inside: 75 OF Outside: 90 OF TD: 15 OF RH: 50 % Moisture: 61 gr/lb Mult: 1.0 Ins.wb 63 OF Sensible Latent 2. SOLAR RADIATION THROUGH GLASS 0 - 3. TRANSMISSION GAINS Sensible 1380 - Walls: 72 Glass: 0 _ _ • Doors: 673 _ _ Partitions: 0 - _ Floors: 0 _ _ Roofs/Ceilings: 286 - Return Air Ceiling: 349 - _ 4. INTERNAL HEAT GAIN Sensible Latent 268 0 Occupants: 0 0 - _ Lights: 268 0 - - Motors: 0 0 Appliances & Other: 0 0 S. INFILTRATION: Outside air cfm: 7 121 305 6. SUBTOTAL: Space load 1768 305 _ 7. SUPPLY DUCT 53 _ S. SUBTOTAL: Bldg comp's and supply duct 1822 - Actual cfm: 83 at Supply TD: 20 9. VENTILATION: Make—up air cfm: 0 0 0 10. RETURN AIR LOAD: Lighting & roof (net) 98 - 11. RETURN DUCT 0 _ 12. TOTAL LOADS ON EQUIPMENT 1920 305 HEATING LOAD - 13. DESIGN CONDITIONS Mult: 1.0 Inside: 70 OF Outside: 42 OF TD: 28 OF • 14. TRANSMISSION LOSSES 1861 Walls: 211 _ Glass: 0 _ Doors: 1257 _ - Partitions: 0 _ Floors: 150 _ _ Roofs/Ceilings: 122 _ • Return Air Roof 122 _ 15. INFILTRATION: Outside air cfm: 11 337 16. SUBTOTAL: Building components 2199 17. SUPPLY DUCT: 110 I& VENTILATION: Make—up air cfm: 0 0 19. HUMIDIFICATION 133 20. RETURN DUCT 0 21. TOTAL HEATING LOAD ON EQUIPMENT 2441 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N ` SIN RNW21393 RIGHT-N COMMERCIAL / INDUSTRIAL LOAD CALCULATION ' Nov 26, 2000 • r For: FT. PIERCE MASONIC LODGE Zone: STORAGE/HALL Page: 1 Job #: City: Fort Pierce, FL, US By. WOLF AIR CONDITIONING LWH: 6.6 x 16.6 x 10.0 Units: U.S. customary (I-P) 1. DESIGN CONDITIONS - COOLING ( 3PM , August ) Dry Blb RH Moisture Range Wet Bib Outdoor Conditions > 90 59 15 78 Indoor Conditions > 75 50 63 TOD Correction > 0 • Difference 15 61 [ Mult = 1. Q ] - 2. GLAZING SOLAR HEAT GAIN27.00 ( Lat = 2 7.0 0 ° N , Const Wt 1 = M ) Type Dir Shad Tilt %ovr Area Sfact Shgf Shad Sens GLAZ 1 N N 90 0.0 0 0.98 29 1.0 0 3. TRANSMISSION GAINS Type Dir GrArea NtArea UVal Grp CLTD Shad Clr Sens GLAZ 1 N 0 0 0.500 15.0 N - 0 WILL 1 S 66 66 0.114 • B 9.6 N L 72 WALL 1 N 0 0 0.114 B 6.3 N L 0 DOOR 1 N 0 0 0.560 15.0 - - 0 DOOR 2 W 0 0 1.100 15.0 - - 673 FLOR 1 - 7 7 0.810 0.0 - - 0 ROOF 1 - 109 109 0.040 R-4 65.5 - D 286 RARF 1 - 109 109 0.040 R-4 61.5 - - 268 RACL 1 - 109 109 0.800 4.0 - - 349 4. INTERNAL HEAT GAIN Sens Latent People 0 x Per person: sensible 255 latent 255 0 0 0 x Per person: sensible 300 latent 300 0 0 Lights Incandescents in RA Ceiling 0 x 3.4 x 60% 0 Fluorescents in RA Ceiling 109 x 4.1 x 60% 268 Incandescents other 0 x 3.4 x 100% 0 Fluorescents other 0 x 4.1 x 100% 0 • Motors Nmbr Power Gain Load Fact Usage 1 1 0.00 0 1.00 1.00 0 2 1 0.00 0 1.00 1.00 0 3 1 0.00 0 1.00 1.00 0 - Appl. Nmbr Type Sens Latent Usage 1 1 0 0 1.00 0 0 2 1 0 0 1.00 0 0 3 1 0 0 1.00 0 0 4 1. 0 0 1.00 0 0 5 1 0 0 1.00 0 0 Other 1 0 C 1.00 0 0 5. INFILTRATION Sens Latent 7 cfm > x db Temp Diff 15.0 x i .1 121 . > x Moist. Diff 61.4 x n.68 305 Manual N: 4th Edition Right-N: Ver.3.0.04 -� Certified by ACCA to meet all requirements of Manual Form N 0 \ Job 0: Page: 2 6. SUBTOTAL COOLING LOAD FOR SPACE 1768 305 7. SUPPLY DUCT HEAT GAIN Gain factor 0.03 x Line 6 Sensible Gain 53 8. COOLING FAN SIZING - , Sum of Duct Gain (7 ), Line (6) & Drawthru Fan = 1822 (L 8 Sens ) / ( 1.1 x Supply TD ) = cfm Est Cooling cfm = ( 18 2 2) / (1.,1 x 20.0 ) = 83 Actual Cooling Fan > = 83 9. VENTILATION 0 cfm > x db Temp Diff 15.0 x 1.1 0 > x Moist. Diff 61.4 x 0.68 0 10. RETURN AIR LOAD FROM LIGHTING AND ROOF Incandescent Lights 0 Watts x 3.4 x 40% 0 Fluorescent Lights 109 x 4.1 x 40% 179 RA Roof Load from Line 3 M 268 RA Ceiling Load Credit from Line 3 (-), 349 11. RETURN DUCT HEAT GAIN Gain factor 0.00 x Line 6 Sensible Gain 0 12. TOTAL COOLING LOADS ON EQUIPMENT (Btuh) 1920 305 SPACE HEATING LOAD CALCULATION 13. HEATING DESIGN TEMPERATURE Heating TD = (Inside DB - Outside DB) _ ( 70 - 42) = 28 [ Mult = 1.0 ] 14. TRANSMISSION LOSSES Type Expos GrArea NetArea Uval HTD Loss GLAZ 1 N 0 0 0.500 28.0 0 WALL 1 S 66 66 0.114 28.0 211 WALL 1 N 0 0 0.114 28.0 0 DOOR 1 N 0 0 0.560 28.0 0 DOOR 2 W 0 0 1.100 28.0 1257 FLOR 1 - 7 7 0.810 28.0 15D ROOF 1 - 109 109 0.040 28.0 122 15. INFILTRATION Loss 11 cfm x db Temp Diff 28.0 x 1.1 3 37 16. SUBTOTAL HEATING LOAD FOR SPACE 2199 17. SUPPLY DUCT HEAT LOSS .--Loss factor 0.05 x Line 16 Loss .110 18. VENTILATION 0 cfm x db Temp Diff 28.0 x 1.1 0 0 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N Job #: • Page: 3 19: • HUMW]FICATYON Inside RH desired 40.0. (Max = 32.0 for 1 pane ) # of Glazing panes 2.0 (Max = 52.0 for 2 pane ) 11 cfm x 3.20 9/100cfm/d — 0.4 gpd 133 20. RETURN DUCT HEAT LOSS Loss factor 0.00 x Line 16 Loss 0 21. TOTAL HEATING LOAD ON EQUIPMENT (Btuh) 2441 Manual N: 4th Edition Right-N: Ver.3.0.04 Certified by ACCA to meet all requirements of Manual Form N .