Loading...
HomeMy WebLinkAboutChecklistST. LUCIE COUNTY CHECKLIST SUMMARY L*21010453*PLAN.BL BUILDING DIVISION CHECKLIST STATUS DATE OP ID DESCRIPTION / COMMENTS NO 02/27/01 BLD32 3. Building Department Review Complete COMMENT 2/27/01 1.provide total square footage by area. 2. provide number of occupants per area as per sbc chapter 10. 3.ext. bearing wall reqd provide calculated or ul# per sbc T600. and chapter 7. ' 4.provide floor plan for mechanical room and balcony. provide occupancy for balcony. 5. provide ul # for. two hour separation. 6. provide opening protective for two hour wall and -penetrations. 7.fire blocking and draft stopping reqd. 8.interior finishes specified for occupancy. 9.occupant load reqd for means of egress review. 10. stairway details reqd complying with sbc 1007.1,705.3,1007.5,1007.6 and 1007.8. ll.exit regmnts by occupancy re: assembly and educational must comply with sbc 1019 and 1021. 12.restrooms must comply withsbc 1204. - 13.provide product approval for roofing,windows and doors. worst case wind pressure is 67.5 psf 14. rovide balcony live load per t1604.1 sbc. ,V�?Fsce 7-88 not allowed to be mixed with sbc 997.revise plans. current asce adopted by st lucie o y 1-2 7-95. CptS` C 6 1�- t�4c access reqd. 70C9v $� rovide truss dwgs to inspector reviewed and I 1 ��•roved by designer of record. 18.provide hvac outside air intakes per sbc 2810. 19.provide acessibility per fac to pavilionand B�,A sanctuary. ®1atkG1�Y 20. detectable warning reqd to sanctuary handicap parking. 21.vertical accessibility to balcony and stage per fac. 22.provide details for fac for handrails , G 5 fountain,water closet toilet stall,urinal, toilet ® rooms,and stage. 23. provide educational average daily attendence. 24. educational occupancy requires 2 male water closets and 2 female water closets 1 male lav and 1 female lay. assembly requires 1 fountain and educational requires 1 fountain. 25. provide approved site plan for over 6000 squar s foot. 3/29/01 1. item 7 draftstopping still open sbc 23, 2.item 10 still open sbc 1007.5 and 1007.8. f A 3.ite 1 o en sbc 21.)< 4.item 13 still open. i em 5 sti open. see dwg a-4 and a-13_ 6.sbc 403.1.2,403.1.2.1,403.1. a .2.3 occupant content as determined by building official. DIVISIOIvi $T. LL?CIE GOU UTY RL'II..Z I\r VIE)N D FUR C RF IENVED B a ''DATE VPT ON JOB SLAM�tiD PERMIT �i ST Bh KE S INSPECTION dVRL BE NI LkDE' HP Fax Series 900 -Plain Paper Fax/Copier .Last Fax Date Time Toe Mar 29 12: 1 1pm Sent -A)lack:and white f�x Identification. S15614650553 Fax History Report for Building Zoning SLC 561 462 1735 Mar 29 2001 12:12pm Duration Pages Result 1:03 3 OK -VT DGSION ST. LITCYF- COT L c FXVIENVLD i REVIENVED B ON JOB ]DATE 77 7 7D PLANS NN, PER MADE. ORNO INSPECTION A0 STATUS NO r ST. LUCIE COUNTY CHECKLIST SUMMARY L*21010453*PLAN.BL BUILDING DIVISION CHECKLIST DATE OP ID DESCRIPTION / COMMENTS 02/27/01 BLD32 3. Building Department Review Complete COMMENT 2/27/01 i.provide total square footage by area. VZ 2. provide number of occupants per area as per sbc chapter 10. 3.ext. bearing wall reqd provide calculated or ul# per sbc T600. and chapter 7. / 4.provide floor plan for mechanical room and balcony.✓ px-o occupancy for balcony k / 5. pro ul # for two hour separation. 6. provide o ng protective for two hour wall and M penetrations. 7.fire blocking and draft stopping reqd. / terior finishes specs ie or occupancy.✓ 9.occu load reqd for means of egress review. & 10. sjirwa details reqd complyi wit x1007.1,705.3,1007.5 1007.6)and 1007. 11.exit regmnts by occupancy re: assembly and educational must comply with sbc 1019 nd 1021. 12.restrooms must comply withsb 120 1 provide produc approval for roofing,windows and doors. worst case wind pressure is 67.5 sf 14.provide balconv live oad 1per t1604.1 sbc.. C19:.97re.vise asce - not allowed to be mixed wit=stlucie plans. current asce adopted co attia-Lccess, re d.✓ .prpev,iootruss dwgs to inspector reviewed and y'�'b desi ner of ord. / .de hvac outside air intakes per sbc 2810./v de essibility per fac to pavilionandt" uary / c a67 warning reqd to sanctuary handicap parking. �T.verrtc= accessibility to balcon%jand stage per fac. 22.provide details for fac for handrails , fountain,water closet toilet stall,urinal, toilet rooms,and stage. 23. provide educational average daily attendence.� 24. educational occupancy requires 2 male water closets and 2 female water closets 1 male lav and 1 female lay. assembly requires 1 fountain and educational requires 1 fountain. 25. provide approved site plan for over 6000 square foot. CAS k EST �-LO3. L-S- I 2 COMMERCIAL & MULTI -FAMILY CHECKLIST Dale Reviewed By no C3-ro�c'� i��a 1 'So �1 • �3Ry .Q:��c Occupancy t-v% �+ Sq Ftgs (see last page) ,,Miscellaneous �- 1. DATE OF APPROVALS P/Z _1C�eQ-9 Eng LRECD Water F/R Welltieid SFWMD Hotel, Restaurant Bldg No Permit No 2 1C 1 0 y 53 Project Name.' AP >T- - Vaa.'sry Owner �y3 �=3,er�NT, Const Typ Spk_ Prot j��Hei�ght�Stories Units I 5. Energy Code '✓ 6. Notice of Commencement 7. Soil Tests: A B C 8. Truss Layout: �M7_anu Desgnr Eng �c. 9. Plans s/s by AX t__ V A 6 10. Developer Agreement Other gbPops tt (, 11. Speci li Insp Form #1 - #2 2. Application Complete 12. Value" 2- ', 2a 3. Flood Dev Zone FFE ft. 13. Designer Cert Form 4; _,Survey Site Plan 14. Spec Book _r DACS food establishment info 15�5. Prod Appr Eng PR3.96 Check if requirements of ALL appropriate sections are met. 11 CHAPTER 3 OCCUPANCY TYPE Classification 4@9?Lk--\ o w� p Subclassification c'M�,, CHAPTER 4 SPECIAL OCCUPANCY requirements met Primary_ Occupancy Type'(grandstand, automotive,, etc). Section Comments - rNeaTFR s NFI[,NT AND AREA requirements met oars a sheet for square footage breakdown, total and value of building.) lit Modifications: Roof Top �_ Mezzanine_ BasementUnlimited Height 503.3 Area Modification Used: Sec, Increase Amnl _ 504 Bldg on Same Lot TABLE 500 Occupancy 11N-1. 1'�4js 0 A - 2__ Const Type SpkO Proti_ Proposed: Sq Fig per Flr b 3 Total Bldg ''> L 3 Height ! 3 S. Stories Allowed. Sq Fig per Fir Total Bldg (v w o Hey _ Stories 2 Table 500 Notes Used Comments L"`'"1CCIRv sot CHAPTER 6 CONSTRUCTION TYPES requiremeq.t�'Ep BY 59 YT ON Proposed 609.2.4 Partition PXT - Y�E Sri 1 onst Type ,.2 Height Limits 610.3 O�Tctf`ctrC TABLE 600 REQUIRED FIRE RESISTANCE met Const Type P np Party/Fire Wall_ hr Typ Sec Int Brg Wall_ hr Typ Section Nonbrg Wall_ hr Typ Section Columns hr. Typ Section Bms, Gders, etc hr Typ Section _ Floor/Ceiling hr' Typ Section Roof and Ceiling _ tir Typ Section Exterior Bearing Wall I Kwo r hr Typ Section 2t_.Q `> % Openings L— E x_ rior Nonbrg Wa11 _ hr Typ Section % Openings Design Ref Numbers Notes Used lemments CHAPTER 7 FIRE RESISTANT MATERIALS, AND CONSTRUCTION requirements met 701.3 Column Fire Resistancey 701'.5 Exceptions Used 703 Materials for Fire Resistance TABLE 704.1 OCCUPANCY SEPARATION REQUIREMENTS (List occijpancy of each area) Occupancy " is L Separation Z hr Occupancy, Separation hr4 Occupancy" Separation �_ hr Occupancy Separation hr } 704.1.2 Accessory Occupancy Section used for 704.1.3 Special Occupancy Separation used for I 5 S C_- �_�j i>- Comments TABLE 704.1.4 HAZARD OCCUPANCY SEPARATION REQUIREMENTS Occup. H1 H2 r l n Secs) used / . 704.2 Interior Wall, Partition Se (s) for occ 704.3 Tenant Fire Separation se 70 a arapet 705.1.1.3 Protection of Opening: Ext Wall Exception Int Wall Exception Comments 705.1.3. Fire Window, Door, Shutter: Class Rated Self Closing Exception used 61 705.1.2.2 Fire Dampers Old Comments _ TABLE 705.1.3.E WIRE GLASS LIM a 3e Rat Max Area Max Hght Max Width Comments G z ®1 TABLE 700 MINIMUM FI►,9�'' , 705.1.5 Stairway Enclosure Door Component �c� ,v �a ,tti Prot ' Component Wall/Part Ovna/Prot Shaft Eric (stor+s 9 Refuse,Lndry Chute Access _Lhr %\ Refuse Shute � hr Incinerator Rooms / � hr Fire Walls � $ � hr _ Refuse,Lndry Chute End hr Int Tenant Partitions O�hr Hazardous Occup Ctrl Area hr Tenant Separation hr High Rise Buildings hr Horizontal Exit Covere Ildin s Exit Access Corridor r �4 Assembly Buildings hr L Smoke Barriers Bathrooms, estrooms hr " OCCUPANCY SE ART 7,hr Exterior Walls hr Notes used C 75.2.1.74F7eDpers05.2.2 Shaft Enclosures - Exception # Used 705.2.3 Shaft Eric Const Exception # Used 705.2.4 Refuse/Lndry Chute C Comments 705.3.1 Fireblocking, Draftstopping GQ scellaneous TECTION OF NON -FIRE RESISTANT ASSEMBLY Conduit, Pipe, Tube Location C _N _Method Ducts Location C N Method Fctry Bit Vent, Chimney Location C _N _Method Cables, Wires Location C _N _Method 705.4 PENETRATION OF FIRE RESISTANT ASSEMBLIES 705.4.3 Walls, Shaft Enc Method 705.4.4 Floor, Roof, Ceiling Method TABLE 705.4.4 PENETRATION PROTECTION OF FIRE RESISTANT ASSEMBLY Conduit, Pipe Tube Location C — N _Method Ducts Location C _ N _Method _ Fctry Bit Vent, Chimney Location C _ N _Method' Cables, Wires Location C _ N _Method a 706 Combustible In Fire Rated Assembly 707 in Concealed Spaces 707.2 In Plenums 709 Calculated Fire Resistance req'mnts met for Floors Walls Colum s CHAPTER 8 INTERIOR FINISHES requirements rnet I? J • Occup ' "� .. •c. S 8GS.6 Floor Finis CHAPTER 9 FIRE .8 Inl Finish STEMS reauiremen s met r (-.,, Cc,",- e S>-15 \ -� 90Sprinklers Req'd per Sec(s) for Occupancy Atandpipe 905.1 Manual Fire Alarm 905.2 Auto Fire Detection Comments CHAPTER 10 MEANS OF EGRESS requirements met "C� ABLE 1003.1 MINIMUM OCCUPANT LOAD (Write on floor plan the occupant .load of each area) lPrimary se Z Area SgFt Cp 34 3 Area Per Occup = /1003.2 Measuremnt M of E 1003 73 Capacity M'of E 1004.1 Exit Number, Arrangement TABLE 1004 TRAVEL DISTANCE, DEAD END, EXIT, MEANS OF EGRESS Occup Max Travel DeadEnd Egress Width Corridor Clear Opening Stair Unsp Spk Corridor Level Stair or Aisle Exit Doors Width ®,� Holes used and comments TABLE 1004.1.4 used 004.2 Minimum # of Exits (check each area) 1��°��e� r�;l�'rtTtfoi�d Accessible M of E 004.3.5 Areas of Refuge OTL'`O Comment CIAL EXIT REQMNT 1005.1 Boller, etc 1005.2 Dead -End 1005.3 Exit Acc Corridor 1005.4 Emer Egress Opng 1005.5 Smokeprf Eric 1005.6 Mezz Exits req'd TABLE 1005.6 1005.6.3 Egress Comments 1005.7 Burglar Bar- STAIRWAY PROTECTION 1006.1 Enclosed Stair �C Exception # _ 1006.2.Ext Exit Stair j Comment CTAMVAIAV- ection 1007.1 General F�e, C-10 �1007.5 Handrail (21 10117.8 Special Stair Type 1009 Horizontal Exits 1011 Flre Escape Garage Door Sizes Comments 1013 Ram- 1 5 Guardrail RE 1 a5 p 1007.4 Landing 007.6 Width fL' q 0 1 07.7 Headroom 08 Access to rq3/f �Fxit Discharge 1012 Door Door Schedule i , r _ Product Approval Anchoring 1.014 Balcony, e c Guardrail Detail �LiE:�.1,016EAISIgn r* a and secondary occupancies) Z01�9Assembly CL ling Layout 1020 Business 1021 Educational 1022 Factory -Industrial 1023 Hazardous 1024 Institutional 1025 Merchantile 1026 Residential 1027 Storage Comments CHAPTER 11 ACCESSIBLITY (see orida Accessiblity Code) CHAPTER 12 INTERIOR ENVIRO ENT reuuir 1203 Light, Ventilation 04 Sanitation �- 205 Rodent Proof 0 ments CHAPTER 13 ENERGY CONSERVATION (See Florida Model Energy Code) CHAPTER 14 EXTERIOR WALL COVERING requirements met K, 6f Z.1ok 0 4 s3 RECOMMENDED PROCEDURES TO FOLLOW TO USE THE STANDARD BUILDING CODE 1. Determine Occupancy Classification of the structure. Select occupancy classification which most accurately fits the use of the building. (Chapter 3) 2. Determine actual physical properties of building. 3(a) Determine building area each floor. (Area definition Chapter 2) (b) Determine grade elevation for building. (Grade definition Chapter 2) 'a (c) Determine building height in feet above grade. (Height definition Chapter 2) 3 1app�oy. (d) Determine building height in stories. (Story defuution Chapter 2) 1 (e) Determine separation distance from exterior walls to assumed and common property lines. (Property line definition Chapter 2) 5 o ' %,.. ', " (f) Determine percent of exterior openings per floor. �. Determine minimum Type of Construction necessary to accommodate proposed structure. (Chapter 6) (a) Determine maximum allowable heights and floor areas for Types of Construction and Occupancy classification. (Table 500) ® � (b) Check allowable height and area increases permitted. (Chapter 5) p 4. Check detailed Occupancy requirements. (Chapter 4) 5. Check detailed Construction requirements. (a) Fire Protections of Structural Members (Chapter 6 and Table 600) (b) Fire Protection Requirements (Chapter 7 and Table 705.1.2) (c) Means of Egress Requirements (Chapter 10) (d) Special, restrictions if in Fire District. (Appendix F. The provisions of Appendix F are applicable only where specifically adopted by ordinance.) VISION 6. Review design as related to standards. (Chapters 16-26) fit;£ b "� tia , 7. Check other requirements as necessary. (a) Construction projecting into public property (Cha Pter 3 )�p1F UZ O JOB 'iEU. s 'el (b) Elevators and conveying systems (Chapter 30) TI,OS '"� PE .®N % L E (c) Sprinklers, standpipes and alarm systems (Chapter 9)BNO`; (d) Use of combustible materials on the interior (Chapter (e) Roofs and roof structures (Chapter 15) (f) Light, ventilation and sanitation (Chapter 12) (g) Other These steps are naturally varied in sequence by individual preferences; however, the first three are standard steps which should be followed in proper order to assist in design or review of buildings. - �0 STANDARD BUILDING CODE®1997 vii �-- 3 q z LION - vcw CO APT ON SOS BL S ��D pt DN WILL ORS