Component Performance Method for Commercial Buildings Form 400B-97
ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Community Affairs
FLA/COM-97 Version 2.2
PROJECT NAME -APOSTLE CHURCH OF DELIVERAN PERMITTING OFFICE:
ADDRESS: 1505 N. 43RD ST. _Fort Pierce
------------ -----------------
_FORT PIERCE, FL__ _ CLIMATE ZONE: _6____N_
OWNER: _ -CONGREGATION PERMIT NO:
-------------
AGENT: ____________ JURISDICTION NO: 661100
BUILDING TYPE: -_Service Establishments_____
CONSTRUCTION CONDITION: New construction
DESIGN COMPLETION: _Finished Building__________
CONDITIONED FLOOR AREA: _8000_________ NUMBER OF ZONES: 4
MAX. TONNAGE OF EQUIPMENT PER SYSTEM: 5___________�_____
COMPLIANCE CALCULATION:
METHOD B
DESIGN
CRITERIA
RESULT
------
-----------------
ENVELOPE PERFORMANCE
------
34.29
--------
64.99
PASSES
. OTHER ENVELOPE REQUIREMENTS
PASSES
LIGHTING
INTERIOR LIGHTING
4810.00
12588.30
PASSES
" EXTERIOR LIGHTING
206.00
392.00
PASSES
LIGHTING CONTROL REQUIREMENTS
PASSES
HVAC EQUIPMENT
COOLING EQUIPMENT
1. SEER
10.00
10.00
PASSES
2. SEER
10.00
10.00
PASSES
3. SEER
10.00
10.00
PASSES
4. SEER
10.00
10.00
PASSES
HEATING EQUIPMENT
1. Et
0.88
N/A
2. Et
0.88
N/A
3. Et
0.88
N/A
4. Et
0.88
N/A
AIR DISTRIBUTION SYSTEM INSULATION
REQUIREMENTS
1. Conditioned Space
6.00
0.00
N/A
2. Conditioned Space
6.00
0.00
N/A
3. Conditioned Space
6.00
0.00
N/A
4. Conditioned Space
6.00
0.00
N/A
REHEAT SYSTEM TYPES USED
NO REHEAT SYSTEM is USED
WATER HEATING EQUIPMENT
1. EF
0.88
0.54
PASSES
PIPING INSULATION REQUIREMENTS
1. Non -Circulating
1.00
0.62
PASSES
----------------------------------------------------------------------------
COMPLIANCE CERTIFICATION:
I hereby certify that the plans and Review of the plans and specifica-
specifications covered by this calcu- tions covered by this calculation
lation are in compliance with the indicates compliance with the
F1.0rida Energy Efficiency Code.
PREPARED BY : __J-4(--X_Q'__
DATE - __y
- ------ ---------------- ----
r
I hereby certify that this building is
in compliance with the Florida Energy
Efficiency Code.
OWNER/AGENT:
DATE -__ ------
Florida Energy Efficiency Code.
Before construction is completed,
this building will be inspected
for compliance in accordance with
Section 553.908, Florida Statutes.
BUILDING OFFICIAL:
DATE:
I hereby certify(*) that the system design is in compliance with the Florida
Energy Ffficiency Code.
SYSTEM DESIGNER REGISTRATION/STATE
ARCHITECT ._ _ _ _ _ _________
MECHANICAL__`____='-----------------------
PLUMBING-----------------------------------------------------------------
ELECTRICAL:
-----------------------------------------------------------------
LIGHTING
(*) Signature is required where Florida law requires design to be performed
by registered design professionals. Typed names and registration numbers may
be used where all relevant information is contained on signed/sealed plans.
BUILDING ENVELOPE SYSTEMS
COMPLIANCE
CHECK
*01.------GLAZING--ZONE
1----------------------------------------------�-v-
Elevation
"---------
Type
---------------
U SC VLT Shading
---- ---- ---- --------------
Krea(Sgft)
----------I
West
Commercial
1.31 .6 .7 None
601
South
Commercial
1.31 .6 .7 None
241
North
Commercial
1.31 .6 .7 None
1261
East
Commercial
1.31 .6 .7 None
601
Total Glass Area in Zone 1 =
2701
401; ------
GLAZING --ZONE
2------------------------------------------------ v-
Elevation
Type
---------------
U SC VLT Shading
---- ---- ---- --------------
Area(Sgft)l
----------
---------
East
Commercial
1.31 .59 .6 Continuous Ove
5401
'North
Commercial
1.31 .59 .6 Continuous Ove
201
South
Commercial
1.31 .59 .6 Continuous Ove
201
Total Glass Area in Zone 2 =
5801
401.------GLAZING--ZONE
3------------------------------------- ---v-
Elevation
Type
U SC VLT Shading
---- ---- ---- --------------
Area(Sgft)l
----------
---------
South
---------------
Commercial
1.31 .59 .6 Continuous Ove
11
North
Commercial
1.31 .59 .6 Continuous Ove
201
Total Glass Area in Zone 3 =
211
401.------GLAZING--ZONE
4------------------------------------------------ v-
Eievation
Type
U SC VLT Shading
---- ---- ---- --------------
Area(Sgft)l
----------I
---------
South
---------------
Commercial
1:31 .59 .6 Continuous Ove
401
West
Commercial
1.31 .59 .6 Continuous Ove
401
North
Commercial
1.31 .59 .6 Continuous Ove
321
Total Glass Area in Zone 4 =
1121
Total Glass Area =
9831
402.------WALLS--ZONE
1------------------------------------------------ I ---
Elevation
Type
U Insul R
----- -------
Gross(Sgft)l
-----------I
---------
North
--------------------------------
8"CMU/3/4"ISO
Btwn 24"oc/5/8"Gyp 0.151 6
6721
East
81-CMU/3/4"ISO
Btwn 24"oc/5/8"Gyp 0.151 6
8401
South
8"CMU/3/4"ISO
Btwn 24"oc/5/8"Gyp 0.151 6
7841
West
811CMU/3/411ISO
Btwn 24"oc/5/8"Gyp 0.151 6
8401
Total Wall Area in Zone 1 =
31361
402.------WALLS--ZONE 2----------------------- -------------------------I---
Elevation
Type
U Insul R
----- -------
Gross(Sgft)l
-----------I
=--------
West
--------------------------------
811CMU/3/4"ISO
Btwn 24"oc/5/8"Gyp 0.151 6
3601
South
8"CMU/3/4"ISO
Btwn 24"oc/5/8"Gyp 0.151 6
1501
East
81-CMU/3/411ISO
Btwn 24"oc/5/8"Gyp 0.151 6
3601
North
811CMU/3/411ISO
Btwn 24"oc/5/8"Gyp 0.151 6
1501
Total Wall Area in Zone 2 =
10201
402.------WALLS--ZONE 3 ------------------------------------------------ I ---
Elevation
Type
U Insul R
----- -------
Gross(Sgft)l
-----------I
---------
West
--------------------------------
8"CMU/3/4"ISO
Btwn 24"oc/5/8"Gyp 0.151 6
4321
South
8"CMU/3/4"ISO
Btwn 24"oc/5/8"Gyp 0.151 6
5521
East
81-CMU/3/4"ISO
Btwn 24"oc/5/8"Gyp 0.151 6
4801
North
8"CMU/3/4"ISO
Btwn 24"oc/5/8"Gyp 0.151 6
4321
Total Wall Area in Zone 3 =
18961
40'2.------WALLS--ZONE 4------------------------------------------------ I ---
Elevation
Type
U Insul R
Gross(Sgft)l
M
- --- -- - -- - - ---- - - - - - - -- - - - - - - - - - - -- - - - - -- --- - - -- --- - - - - -- -- -- - - - I
West 8"CMU/3/4"ISO Btwn 24"oc/5/8"Gyp 0.151 6 4321
South 8"CMU/3/4"ISO Btwn 24"oc/5/8"Gyp 0.151 6 5521
East 81'CMU/3/4"ISO Btwn 24"oc/5/8"Gyp 0.151 6 480I
North 8"CMU/3/4"ISO Btwn 24"oc/5/8"Gyp 0.151 6 w 4321
Total Wall Area in Zone 4 = 18961
Total Gross Wall Area = 79481
403.------DOORS--ZONE 1 ------------------------------------------------
Elevation Type U Area(Sgft)I
--------------------------------------------------- ----- ---------
South- 1-3/4 Steel Door-Fiberglass/Mineral woo 0.60 60I
North r 1-3/4 Steel Door-Fiberglass/Mineral woo 0.60 20I
Total Door Area in Zone 1 = 80I
403.------DOORS--ZONE 2---------------------------- -------------------- I---
Ele'vation Type U Area(Sgft)I
--------------------------------------------------- ----- ----------
South 1-3/4 Steel Door -Polystyrene core (18 g 0.35 20I
Total Door Area in Zone 2 = 20I
403.------DOORS--ZONE 3 ------------------------------------------------ I ---
Elevation Type U Area(Sgft)I.:
--------------------------------------------------- ----- ----------I
South 1-3/4 Steel Door -Solid core flush 0.40 20I
Total Door Area in Zone 3 = 20I
403.------DOORS--ZONE 4 ------------------------------------------------ I ---
Elevation Type U Area(Sgft)I
--------------------------------------------------- ----- ----------I
South 1-3/4 Steel Door -Solid core flush 0.40 20I
Total Door Area in Zone 4 = 20I
Total Door Area = 140I
404------- ROOFS --ZONE 1 ------------------------------------------------ I ---
Type Color U Insul R Area(Sgft)I
------------------------------------ ------ ----- ------- ----------I
Conc Tile/l/2"WD Deck/WD Truss/ Medium 0.028 30 3120I
Total Roof Area in Zone 1 = 3120I
404------- ROOFS --ZONE •2------------------------------------------------ I ---
Type Color U Insul R Area(Sgft)I
------------------------------------ ------ ----- ------- ----------I
Conc Tile/1/2"WD Deck/WD Truss/ Medium 0.028 30 540I
Total Roof Area in Zone 2 = 540I
404.------ROOFS--ZONE 3 ------------------------------------------------ I ---
Type Color U Insul R Area(Sgft)I
------------------------------------- ------ ----- ------- ----------I
Shngl/1/2"WD Deck/WD Truss/6"Ba Light 0.040 19 15751
Total Roof Area in Zone 3 = 15751
404.------ROOFS--ZONE 4 ------------------------------------------------ I ---
Type Color U Insul R Area(Sgft)I
------------------------------------ ------ ----- ------- ----------I
Conc Tile/1/2"WD Deck/WD Truss/ Medium 0.028 30 15751
Total Roof Area in Zone 4 = 15751
Total Roof Area = 6810I
405------- FLOORS -ZONE 1------------------------------------------------ I ---
Type Insul R Area(Sgft)I
-----------------------------------------------------------------I
Stab on Grade/Uninsulated 0 28801
Total Floor Area in Zone 1 = 2880I
.405.------FLOORS-ZONE 2------------------------------------------------ I ---
Type Insul R Area(Sgft)I
-----------------------------------------------------------------I
Slab on Grade/Uninsulated 1
5401
Total Floor Area in Zone 2 =
5401
405.------FLOORS-ZONE 3 ------------------------------------------------
.Type r Insul R
Area(Sgft)l
----------I
-------------------------------------------------------
Slab on Grade/Uninsulated 1
15751
Total Floor Area in Zone 3 =
15751
.405.------FLOORS-ZONE 4------------------------------------------------ I ---
Type Insul R
Area(Sgft)l
--------------------------------------------------------
Slab on Grade/Uninsulated 1
----------I
15751
Total Floor Area in Zone 4 =
15751
• Total Floor Area =
65701
406..------INFILTRATION -------------------------------------------------- I---
(CHECKI
Infiltration Criteria in 406.1.ABCD have been met.
1 I
MECHANICAL SYSTEMS
CHECK
------------------------------------------------------------------1-----1---
HVAC load sizing has been performed. (407.1.ABCD)
I 1
407.------COOLING SYSTEMS -----------------------------------------------
Type No Efficiency IPLV
------------- ----- --------------I
Tons)
----------------------------
1. Split System 3 10 10
5.001
2. Split System 1 10 10
1.501
3. Split System 1 10 10
5.001
A. Split System 1 10 10
5.001
408.------HEATING SYSTEMS ----------------------------------------------- I ---
Type No Efficiency
-------------------------------- --- ---------- --------------I
BTU/hrl
1. Electric Resistance 3 .88
340001
2. Electric Resistance 1 .88
170001
3. Electric Resistance 1 .88
340001
4. Electric Resistance 1 .88
340001
409.------VENTILATION ------------------------------------- --------------- I---
ICHECKI
Ventilation Criteria iri 409.1.ABCD have been met.
1 1
410.-----AIR DISTRIBUTION SYSTEM ---------------------------------------- I---
------------------------------------------------------------------1-----1---
CHECKI
Duct sizing and design have been performed. (410.1.ABCD)
I I
AHU Type Duct Location
R-value)
---------------------------------------------------------
1. Constant Volume Conditioned Space
-------I
61
'2. Constant Volume Conditioned Space
61
3. Constant Volume Conditioned Space
61
4. Constant Volume Conditioned Space
61
CHECKI
------------------------------------------------------------------I-----I---
Testing and balancing will be performed. (410.1.ABCD)
I 1
411------ PUMPS AND PIPING -ZONE --------------------------------
Basic prescriptive requirements in 411.1.ABCD have been met. 1 1
PLUMBING SYSTEMS
411------ PUMPS AND PIPING -ZONE 1---------------------------------------I---
Type R-value/in Diameter
Thicknessl
- .------------------------
1. Non -Circulating
---------------------------
I
411.-----PUMPS AND PIPING -ZONE 2--------------------------------------- I---
' Type t
R-value/in Diameter ,Thicknessl
------------------------
1. Non -Circulating
---------------------------
6 1 11
• 411.-----PUMPS AND PIPING -ZONE 3--------------------------------------- I ---
Type
------------------------
R-value/in Diameter Thicknessl
---------------------------1
411.-----PUMPS AND PIPING -ZONE 4 ---------------------------------------
Type
---r--------------------
R-value/in Diameter Thicknessl
---------------------------I
41.2.-----WATER HEATING
SYSTEMS -ZONE 1 ----------------------------------
Type
------------------------
Efficiency StandbyLoss InputRate Gallonsl
----------------------------------------I
412.-----WATER HEATING
SYSTEMS -ZONE 2 ----------------------------------
Type
Efficiency StandbyLoss InputRate Gallonsl
----------------------------------------I
•------------------------
1. <=75,000 Btuh
.88 1 .87 401
412.-----WATER HEATING
SYSTEMS -ZONE 3---------------------------------- I ---
Type
Efficiency StandbyLoss InputRate Gallonsl
----------------------------------------i
------------------------
412.-----WATER HEATING
SYSTEMS -ZONE 4 ----------------------------------
Type
------------------------
Efficiency StandbyLoss InputRate Gallonsl
----------------------------------------I
ELECTRICAL SYSTEMS
CHECRI
413.-----ELECTRICAL POWER DISTRIBUTION ----------------------------
Metering criteria in 413.1.ABCD have been met. 1 1
414.-----MOTORS ---------------------------------------------------1-----I---
Motor efficiencies in 414.1.ABCD have been met. I 1
415.-----LIGHTING SYSTEMS -ZONE I ---------------------------------------
Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft)I
---------- ----------------- ----------------- --- ------ ----------I
Auditorium 1 On/Off 5 On/Off 2 2620 30551
Total Watts for Zone 1 = 26201
Total Area for Zone 1 = 30551
415.-----LIGHTING SYSTEMS -ZONE 2--------------------------------------- I ---
Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft)l
---------- ----------------- ----------------- --- ------ ----------I
•Bedroom 1 On/Off 2 On/Off 2 470 5251
Total Watts for Zone 2 = 4701
Total Area for Zone 2 = 5251
415------- LIGHTING SYSTEMS -ZONE 3 ---------------------------------------
Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft)l
---------- ----------------- ----------------- --- ------ ----------I
Reading, T 1 On/Off 2 On/Off 2 860 16101
Total Watts for Zone 3 = 8601
Total Area for Zone 3 = 16101
415.-----LIGHTING SYSTEMS -ZONE 4--------------------------------------- I ---
Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft)I
---------- ----------------- ----------------- --- ------ ----------I
Reading, T 1 On/Off 2 On/Off 2 860 16101
Total Watts for Zone 4 = 8601
Total Area for Zone 4 = 16101
Total Watts = 48101
Total Area = 68001
h �
• ICHECKI
Lighting criteria in 415.1.ABCD have been met. I 1
------------------------------------------------------------------I--�- I---
16% Operatiop/maintenance manual will be provided to owner.(102.1)1 I
70- SJN 1812
i
For:
By:
Job #: 99197
RIGHT-N ZONE SUMMARY
APOSTLE FAITH CHURCH OF DELIVERANCE
Jack Jewell P.E.
C O O L I N G L O A D
4-20-2000
4
ZONE: ZONE 1 APOSTLE
1. DESIGN CONDITIONS at 3PM Peak load at 3PM
r Inside: 75 F Outside: 90 F TD: 15 deg F
RH: 50 % Grains: 62 Mult: 1.0
Sensible Latent
2. SOLAR RADIATION THROUGH GLASS 5926 -
3. TRANSMISSION GAINS Sensible 20711 -
Walls: 3611 - -
Glass: 1710 - -
Doors: 1512 - -
Partitions: 100 - -
Floors: 1500 - -
Roofs/Ceilings: 11318 - -
Return Air Ceiling: 960 - -
4. INTERNAL HEAT GAIN' Sensible Latent 89057 45000
Occupants: 45000 45000 - -
Lights: 17013 0 - -
Motors: 23744 0 - -
Appliances & Other: 3300 0 - -
5. INFILTRATION: Outside air CFM: 200 3300 8432
6. SUBTOTAL: Space load 118994 53432
7. SUPPLY DUCT 35698 -
8. SUBTOTAL: Bldg comp's and supply duct 154692 -
Actual CFM: 7033 at Supply TD: 20 - -
9. VENTILATION: Make-up air CFM: 600 9900 25296
10. RETURN AIR LOAD: Lighting & roof (net) 9972 -
11. RETURN DUCT 11899 -
12. TOTAL LOADS ON EQUIPMENT 186463. 78728 1
H E A T I N G L 0 A D
13. DESIGN CONDITIONS Mult: 1.0
Inside: 70 F Outside: 42 F TD: 28 deg F J
141. TRANSMISSION LOSSES 19315 ,��. 0
Walls: 5475 /
v�10
Glass: 3192 ^`TY.BUILD�iG _ -
Doors: CO nL -
Partitions:o�C!/ -
Floors:
B�pT-pT�
Roofs/Ceilings: 0�� 38 ��iIT E E-
Return Air Roof : �LeNS VNI) 1Q1aI�r1LLB _
15. INFILTRATION: Outside alaN 403 12419
16. SUBTOTAL: Building components 31734
17. SUPPLY DUCT 3173
18. VENTILATION: Make-up air CFM: 0 0
19. HUMIDIFICATION 2189
-• 20. RETURN DUCT 952
21. TOTAL HEATING LOAD ON EQUIPMENT 38048
MANUAL N: 4th Ed.
RIGHT-N: V1.15
rVDTTWTVn QV nrrn Mn M17FT AT.T. R17n11TRRMRNTS ni? MANHAT. FORM N
®0 SIN 1812 70RIGHT-N ZONE SUMMARY
4-20-2000
For: APOSTLE FAITH CHURCH OF DELIVERANCE
By: a Jack Jewell P.E.
Job #: 99197 ZONE: ZONE 2 APARTMENT
C 0 0 L.I N G L
0 A D
1.
DESIGN CONDITIONS at 3PM Peak
load at
3PM
Inside: 75 F Outside: 90 F
TD: 15
deg F
RH: 50 % Grains: 62
Mult:
1.0
Sensible
Latent
2.
SOLAR RADIATION THROUGH GLASS
940
-
3.
TRANSMISSION GAINS Sensible
4668
-
Walls: 666
-
-
Glass: 549
-
-
Doors: 252
-
-
Partitions: 320
-
-
Floors: 900
-
-
Roofs/Ceilings: 1981
-
-
Return Air Ceiling: 0
-
-
4.
INTERNAL HEAT GAIN Sensible
Latent
5871
900
Occupants: 900
900
-
-
Lights: 1311
0
-
-
Motors: 2360
0
-
-
Appliances & Other: 1300
0
-
-
5.
INFILTRATION: Outside air CFM:
27
444
1133
6.
SUBTOTAL: Space load
11923
2033
7.
SUPPLY DUCT
1192
-
8.
SUBTOTAL: Bldg comp's and supply
duct
13115
-
Actual CFM: 596 at Supply TD: 20
-
-
9.
VENTILATION: Make-up air CFM:
240
3960
10118
10.
RETURN AIR LOAD: Lighting & roof (net)
738
-
11.
RETURN DUCT
1192
-
12.
TOTAL LOADS ON EQUIPMENT
19005
12152
H E A T I N G L
O A DZ�
13.
DESIGN CONDITIONS
Mult:
1.0
Inside: 70 F Outside: 42 F
TD: 28
deg F
14.
TRANSMISSION LOSSES
5654
Walls: 1034
-
Glass: 1025,
-
Doors: 470
-
Partitions: 597
-
Floors: 1680
-
Roofs/Ceilings: 847
-
Return Air Roof: 0
-
t�
1n
15.
INFILTRATION: Outside air CFM:
40
1242
16.
SUBTOTAL: Building components
6895
17.
SUPPLY DUCT
0
18.
VENTILATION: Make-up air CFM:
0
0
19.
HUMIDIFICATION
219
20.
RETURN DUCT
0
21.
TOTAL HEATING LOAD ON EQUIPMENT
7114
MANUAL N: 4th Ed.
RIGHT-N: V1.15