MUL R, V LELU° 38 S.E. Naronja Ave
AN.CHO R07 Pt St. Lucie, FL. 34983
AR # 0010459 Phone (561) 871-2457
PERMIT # Z10-I01--S3 ADDRESS: 1505 N. 43rd St. Fort Pierce
A/E: RAUL R. VALELLA CONTRACTOR: MR. LEROY BENNETT
APPROVED BY: DATE: 10--26-02
TYPE OF INSPECTION: STRAPS FOR JACKS E7 TO 1 PLY GiDER FG 1
INSTALLED SIMPSON H2.5 STRAPS W/ 5— 8d TO EACH JACKS
AND 5-8d TO EACH GIRDER 'FG1
UPLIFT REQUIRED = LESS THAN 300#
UPLIFT TIE DOWN PROVIDED = 415#
Simpson Strong -Tie
HZ,5
fit, Lucie County Public Works
7
o A UL R. VALELL° 38 S.E. Naranja Ave
A°- RCH07IM07 Pt St. Lucie, FL. 34983
AR # 0010459 Phone : (561) 871-7457
addedum to job at 1505 n..43rd St. Fort Pierce
Correction to as built per notice by building, dept
1.) USE 2" WASHERS ON ALL ANCHOR BOLTS AS PER BLDG DEPT NOTICE
2.) a. AT FG3 BEARING TO N. E. CORNER (EXISTING 2 HETA16 W/11 1Od X 1 1/2" = 1365 X 2 = 2730#
INSTALL NEW TWIST STRAP 1) HTSM16 W/ 8 10d TO TRUSS AND 4— 1/4 X 2 1/4" TAPCONS = 1260#
2730 + 1260 = 3990# > 3534#
b. AT FG2 BEARING TO N. W. CORNER (EXISTING 2 HETA16 W/10 10d = 1240#
INSTALL 2 NEW TWIST STRAP 2) HTSM16 W/ 8 10d TO TRUSS AND 4) 1/4" X 2 1/4" TITEN = 2520#
2520 + 1240 = 3760# > 3534#'
3.) ADD STRAP .TO KING JACKS SIMPSON MTS12
4.) 722 3PLY GIRDER HAS 1) HETA 20 W/16-10d x1 1/2 =1890# REQUIRES 3257#
ADDO2) + T2SM2106#d W/BTRUSSS5AND 4) 1/4" X 2 Ile TITENS TO CONC BM 1260 X2 =2520#
5.) ALL STRAPS THAT MISSED THE TRUSS OVER 3/4" OF AN INCH ; INSTALL 1) KTSM16
W/ 8) 10d AND 4) 1/4 X 2 1/4" 11TEN TO CONC BM
6.) FRAMING CONTRACTOR HAS LETTER OF INSPECTION CHECK IF BLDG DEPT. ACCEPTS THIS LETTER
7.) 00 DRAFT STOP AS REQUIRED
8.) WALL OVER ENTRY NOT STRAPPED .(CALLED FOR SP-4) INSTALL SIMPSON H8
W/ 5)10d TO PLATE & 5) 10d TO STUDS
9.) DO SMOKE BARRIER AS PER
JA-6 04-AJ S Pr 40 o �� 00
10.) SIMPSON STRAP H-7 INSTALLED SEE SECTION 1/A-10
11.) 2" X 6" INTERIOR BEARING WALKS REQUIRES STRAPING AND INTERMIDIATE BLOCKING AS SHOWN 1/A-10
12.) TRUSS COMPANY TO ISSUE T-34 .GIRDER ENGINEERING SHEET
13.) ARCHITECT REVISED DETAIL XX/A-12 SEE REVISIONS TO 1/A-7 AND 1/A-9 '
14.) WHERE GIRDER. T-34 REST ON 2 X 6 BEARING WALL DO DETAIL AS PER 3/A-12 A4V1'r Vi i
15.) T-4 INSTALLED BACKWARDS ASK TRUSS COMPANY FOR LETTER OF APPROVAL
16.) INSTALL TRUSS BRACING AS REQUIRED, ON T32. T18. T34
17.) F03 AND FG2 TRUSSES INSTALLED UPSIDEDOWN ASK TRUSS COMPANY FOR LETTER OF APPROVAL
1$:) KNEE WALLS FG3 AND FG2 NOT STRAPED TO TRUSSES AS PER DETAIL 1/A-8 SP-4
INSTALL MTS16 AT EACH STUD TO TRUSS W/ 14-10d AT BASE AND TOP 'PLATES
19.) F03 STRAP NOT NAILED AT NORTH EAST CORNER
NAIL EXISTING STRAP TO TRUSS W/ 10— 1Od PLUS 00 COMMENT #2 ABOVE
20.) BOLTS LOOSE AT FRAME WALL OVER . ENTRY
INSTALL 2" WASHERS AND TIETEN
�_16 Coun1Y Public iN -