The door and window opening design loads for the above referenced address are
as follows:
Code Used ASCE 7-10
Design Wind Speed 170 mph (Nominal 131.7mph)
Building Category II Hurricane
Exposure D
Height Above Ground 40'
Mean Roof Height 200'
Infernal Pressure Enclosed
Building Length W%
Building Width 60'
Roof Slope 0
End Zone 12.0'
Window/Door Numbers Zone Ht. Width Length Pressure
1 Kitchen 4 4 26" 38" +53.4 psf -57.9 psf
2 Bath 4 4 25" 26" +53.4 psf -57.9 psf
3 Bedroom Egress 4 4 37" 5W +52.6 psf -57.0 psf
4 Bedroom Egress 4 4 37" 50" +52.6 psf -57.0 psf
5' Hall 4 4 71.5" 33" +51.7 psf -56.2 psf