HomeMy WebLinkAboutTSP50554 MICHAEL JOHNSON 09 17 2020 plans stamp 9 18 2020SYSTEM CAPACITY: 8.58 KW DC / 6.24 KW AC PV PANELS: (26) SIL-TITAN 330 NL (60 CELL) BY SILFAB INVERTER: (26) IQ7 MICROINVERTER BY ENPHASE RACKING SYSTEM: RL UNIVERSAL ROOF MOUNT BY SNAPNRACK OF 9 12221 N US HIGHWAY 301 THONOTASASSA, FL 33592 (813) 982 -9001 #EC13008093 CONTRACTOR CONTACT INFORMATION REV DESCRIPTION CONTRACTOR LOGO DATE ENGINEERING STAMPENGINEER CONTACT INFORMATION C.A.32661 255 GIRALDA AVE CORAL GABLES, FL 33134 DESIGN@ENGIPARTNERS.COM 786 - 393 - 4740 MICHAEL JOHNSON 09-16-2020 8600 BROOKLINE AVE FORT PIERCE FL 34951 SHEET TITLE: SHEETS: ENG. RAFAEL A. GONZALEZ SOTO, PE SHEET NAME: PROJECT ADDRESS: CUSTOMER: ENGINEER OF RECORD: DATE: 1301-608-0246-000-9 PARCEL NUMBER: PROJECT ID: TSP50554 ISSUED FOR PERMIT 09-17-2020 ENGIPARTNERS, LLC TITAN SOLAR POWER FL COVER SHEET C-1 1 PROJECT LATITUDE PROJECT LONGITUDE WIND EXPOSURE MIN AMBIENT TEMP MAX AMBIENT TEMP AHJ 27.555221 -80.411475 º C MAX WIND SPEED PROJECT DESCRIPTION C-1 COVER SHEET E-1 E-2 S-1 S-2 D-1 PV MODULES DATA SHEET GENERAL NOTES B 157 SAINT LUCIE COUNTY D-2 D-3 SMART MONITORING DATA SHEET INVERTER DATA SHEET PER FL. STATUTE 377.705 (REVISED 7/1/2017), I RAFAEL A. GONZALEZ SOTO, P.E. 83104 AN ENGINEER LICENSED PURSUANT TO CHAPTER 471, CERTIFY THAT THE PV ELECTRICAL SYSTEM AND ELECTRICAL COMPONENTS ARE DESIGNED AND APPROVED USING THE STANDARDS CONTAINED IN THE MOST RECENT VERSION OF THE FLORIDA BUILDING CODE. APPLICABLE CODES: 2017 FLORIDA BUILDING CODE 6TH, ASCE 7-10 MINIMUM DESIGN LOADS FOR BUILDING AND OTHER STRUCTURES, NEC 2014 ELECTRICAL CODE ALL WIND DESIGN CRITERIA AND PARAMETERS ARE FOR HIP AND GABLE RESIDENTIAL ROOFS, CONSIDERING FROM A 7° TO A MAXIMUM 27° (2/12 TO A MAXIMUM 6/12 PITCH ROOF IN SCHEDULE. ALL RESIDENTIAL ROOFS SHALL NOT EXCEED 30'-0" MEAN ROOF HEIGHT. ROOF SEALANTS SHALL CONFORM TO ASTM C920 AND ASTM 6511, AND IS RESPONSIBILITY OF THE CONTRACTOR TO PILOT FILL ALL HOLES. CONTRACTOR SHALL ENSURE ALL ROOF PENETRATIONS TO BE INSTALLED AND SEALED PER 2017 FLORIDA BUILDING CODE OR LOCAL GOVERNING CODE. ALL WIRING METHODS AND INSTALLATION PRACTICES SHALL CONFORM TO THE NATIONAL ELECTRICAL CODE (NEC) 2014, LOCAL STATE CODES, AND OTHER APPLICABLE LOCAL CODES. MEANS SHALL BE PROVIDED TO DISCONNECT ALL CURRENT CARRYING CONDUCTORS OF THE PHOTOVOLTAIC POWER SOURCE FROM ALL OTHER CONDUCTORS IN THE BUILDING. CONNECTORS TO BE TORQUED PER DEVICE LISTING, OR MANUFACTURERS RECOMMENDATIONS. NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING. REQUIRED SAFETY SIGNS AND LABELS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE, OR OTHER MECHANICAL MEANS, LABELS SHALL COMPLY WITH ARTICLE 690 VI OF THE NEC 2014 OR OTHER APPLICABLE STATE AND LOCAL CODES. SEE LABELS AND MARKING PAGE FOR MORE INFORMATION. RACKING ROOF MOUNT SYSTEM SHALL BE INSTALLED FOLLOWING MANUFACTURERS INSTRUCTION SPEC'S, INCLUDING ALL GROUNDING WEEB CLIPS, GROUND LUGS, AND RAIL SPLICE KITS FOR ELECTRICAL CONTINUITY. MECAWIND TOOL IS BASED ON THE C&C WIND LOADS FOR ENCLOSED BUILDINGS. DESIGN WIND PRESSURES ARE CALCULATED USING ASCE 7-10 EQUATION 30.6-1. ALL NOTES IN FIGURES ASCE 7-10 30.4-1 AND 30.4-2(A,B AND /67C) HAVE BEEN INCORPORATED. MEAN ROOF HEIGHT MUST BE LESS THAN 60 FEET. RACKING PLAN SAFETY LABELS STRUCTURAL PLAN ONE LINE RISER DIAGRAM 35 0 º C MPH C-2 SAFETY PLANS ROOF PLAN VIEW / BOS LOCATION1N.T.S. LOCATION MAP / WIND ZONES2N.T.S. IRRADIANCE MAP3N.T.S. 3D RENDERING4N.T.S. DRAWINGS INDEX "PROPERTY SIDE FACING STREET" PROJECT INFORMATION NORTH PV DISCONNECT IQ COMBINER BOX EXISTING ELECTRICAL METER NORTH SAFETY PLAN C-2 2 OF 9 12221 N US HIGHWAY 301 THONOTASASSA, FL 33592 (813) 982 -9001 #EC13008093 CONTRACTOR CONTACT INFORMATION REV DESCRIPTION CONTRACTOR LOGO DATE ENGINEERING STAMPENGINEER CONTACT INFORMATION C.A.32661 255 GIRALDA AVE CORAL GABLES, FL 33134 DESIGN@ENGIPARTNERS.COM 786 - 393 - 4740 MICHAEL JOHNSON 09-16-2020 8600 BROOKLINE AVE FORT PIERCE FL 34951 SHEET TITLE: SHEETS: ENG. RAFAEL A. GONZALEZ SOTO, PE SHEET NAME: PROJECT ADDRESS: CUSTOMER: ENGINEER OF RECORD: DATE: 1301-608-0246-000-9 PARCEL NUMBER: PROJECT ID: TSP50554 ISSUED FOR PERMIT 09-17-2020 ENGIPARTNERS, LLC TITAN SOLAR POWER FL NOTES: 1.INSTALLERS SHALL DRAW IN DESIGNATED SAFETY AREA AROUND HOME 2.INSTALLERS SHALL UPDATE NAME ADDRESS AND PHONE NUMBER OF NEAREST URGENT CAR FACILITY RELATIVE TO THE SITE BEFORE STARTING WORK NAME: LOCATION OF NEAREST URGENT CARE FACILITY ADDRESS: PHONE NUMBER: SAFETY PLAN1N.T.S. "PROPERTY SIDE FACING STREET" PV DISCONNECT IQ COMBINER BOX EXISTING ELECTRICAL METER 6 2320$ 2320$-% 4 1EM$3R 5 PV RAILS TO BE BONDED WITH #8 BARE WIRE 1 A1.1 A1.2 A1.3 A1.4 A1.5 A1.6 A1.7 A1.8 A1.9 A1.10 A1.11 A1.12 A1.13 BRANCH #1 A2.8 B2.9 B2.10 B2.11 B2.12 B2.13 2 1 A2.1 A2.2 A2.3 A2.4 A2.5 A2.6 BRANCH #2 2 A2.7 3 3 8 UNFUSED 60A 97 EXISTING UNDERGROUNG SERVICE 240V/120V 200A BUS BAR 3 #2/0 THWN-2 INVERTER TOTAL OUTPUT: 26A SAFETY RATING (125%): 32.5A TOTAL PV SYSTEM OCPD: 40A MAIN BREAKER RATING: 200A BUS BAR RATING: 200A 120% BACKFEED RATING: 40A METER200$ 40$10 16T+:12*R281' 11 (26) SIL-TITAN 330 NL (60 CELL) BY SILFAB REFER TO D-1 SHEET NEMA 3R JUNCTION BOX LEGEND: 1 2 3 5 4 7 8 96 IQ7 240V MICROINVERTER FROM ENPHASE POWER: 250W, IMAX: 1.25A EFF @240V: 97.5% 2 ENPHASE Q CABLE #12 AWG THWN-2 1 #8 BARED WIRE GROUND 3/4" EMT CONDUIT 2 #8 L1,L2 THWN-2 1 #8 THWN-2 NEUTRAL 1 #8 THWN-2 GROUND 3/4" EMT CONDUIT 4 #10 THWN-2 1 #8 THWN-2 GROUND 3/4" EMT CONDUIT ENPHASE IQ COMBINER BOX RATED FOR 125A REFER TO D-2 SHEET REFER TO D-3 SHEET 10 11 UTILITY ELECTRICAL SERVICE PV SYSTEM DISCONNECT PV INTERCONNECTION POINT 2 #8 L1,L2 THWN-2 1 #8 THWN-2 NEUTRAL 3/4" EMT CONDUIT WIRE SIZES, QUANTITY & TYPE RACEWAY SIZE, TYPE, LOCATION & INFO.WIRE AMPACITY CALCULATIONS ADDITIONAL INFORMATION WIRE TAG CONDUCTOR QTY. SIZE & TYPE NEUTRAL QTY. SIZE & TYPE GROUND QTY. SIZE & TYPE RACEWAY SIZE & TYPE RACEWAY LOCATION RACEWAY HEIGHT ABOVE ROOF OUTPUT CURRENT 125% OF OUTPUT CURRRENT MIN OCPD WIRE DE-RATED CALCULATION DIST.VOLTAGE VOLTAGE DROP % CONDUIT FILL %WIRE RATING AMBIENT TEMP # OF COND. FINAL AMPACITY AC.1 (BEFORE JB) AC.2(FROM JB TO COMBINER BOX) AC.3(FROM COMBINER BOX TO SERVICE) (2)Q CABLE #12 AWG THWN-2 (4) #10 AWG THWN-2 (2) #8 AWG THWN-2 (1) #8 AWG THWN-2 (1) #8 AWG BARE COPPER (1) #8 AWG THWN-2 (1) #8 AWG THWN-2 NOT APPLICABLE 3/4" EMT CONDUIT 3/4" EMT CONDUIT UNDER ARRAY ABOVE ROOF EXTERIOR WALL 1/2" TO 3-1/2" 1/2" TO 3-1/2" "N/A" 13A 13A 26A 16.25A 16.25A 32.5A 20A 20A 40A 40A X 0.76 X 1 = 30.4 A 40A X 0.76 X 0.8 = 24.3 A 55A X 0.76 X 1 = 41.8 A 10 FT. 20 FT. 5 FT. 350V 350V 240V 0.11% 0.21% 0.1% 6.4% 8.1% 7.7% OF 9 12221 N US HIGHWAY 301 THONOTASASSA, FL 33592 (813) 982 -9001 #EC13008093 CONTRACTOR CONTACT INFORMATION REV DESCRIPTION CONTRACTOR LOGO DATE ENGINEERING STAMPENGINEER CONTACT INFORMATION C.A.32661 255 GIRALDA AVE CORAL GABLES, FL 33134 DESIGN@ENGIPARTNERS.COM 786 - 393 - 4740 MICHAEL JOHNSON 09-16-2020 8600 BROOKLINE AVE FORT PIERCE FL 34951 SHEET TITLE: SHEETS: ENG. RAFAEL A. GONZALEZ SOTO, PE SHEET NAME: PROJECT ADDRESS: CUSTOMER: ENGINEER OF RECORD: DATE: 1301-608-0246-000-9 PARCEL NUMBER: PROJECT ID: TSP50554 ISSUED FOR PERMIT 09-17-2020 ENGIPARTNERS, LLC TITAN SOLAR POWER FL ONE LINE RISER DIAGRAM E-1 3 ONE LINE RISER DIAGRAM1N.T.S. WARNING ELECTRICAL SHOCK HAZARD DO NOT TOUCH TERMINALS TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION LABEL LOCATION: AC DISCONNECT, POINT OF INTERCONNECTION PER CODE: NEC 690.17 (E) ELECTRICAL SHOCK HAZARD THE DC CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM ARE UNGROUNDED AND MAY BE ENERGIZED WARNING TURN OFF PHOTVOLTAIC AC DISCONNECT PRIOR TO WORKING INSIDE PANEL WARNING ELECTRICAL SHOCK HAZARD IF A GROUND FAULT IS INDICATED NORMALLY GROUNDED CONDUCTORS MAY BE UNGROUNDED AND ENERGIZED CAUTION PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED WARNING PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED DUAL POWER SOURCE DO NOT DISCONNECT UNDER LOAD WARNING INVERTER OUTPUT CONNECTION. DO NOT RELOCATE THIS OVERCURRENT DEVICE WARNING PHOTOVOLTAIC DC DISCONNECT WARNING: PHOTOVOLTAIC POWER SOURCE CAUTION: SOLAR ELECTRIC SYSTEM CONNECTED PHOTOVOLTAIC SYSTEM EQUIPPED WITH RAPID SYSTEM SHUTDOWN 1 AMPS 264 VOLTS MAX SYSTEM VOLTAGE RATED MPP VOLTAGE MAX CIRCUIT CURRENT RATED MPP CURRENT PHOTOVOLTAIC AC DISCONNECT MAXIMUM AC OPERATING CURRENT: NOMINAL OPERATING AC VOLTAGE: 26 A 240V 48 VDC 16 AMPS LABEL LOCATION: DC DISCONNECT, INVERTER PER CODE: NEC 690.35 (F) LABEL LOCATION: MAIN SERVICES DISCONNECT, DC CONDUIT PER CODE: NEC 690.31 (E) (3) LABEL LOCATION: DC DISCONNECT PER CODE: NEC 690.14 (C) (2), NEC 690.53LABEL LOCATION: AC DISCONNECT, MAIN PANEL PER CODE: NEC 110.27 (C) OSHA 1910.145(f)(7) MAIN PHOTOVOLTAIC SYSTEM DISCONNECT LABEL LOCATION: INVERTER PER CODE: NEC 690.05 (C) LABEL LOCATION: INVERTER PER CODE: NEC 690.52 LABEL LOCATION: AC DISCONNECT PER CODE: NEC 690.54 LABEL LOCATION: AC DISCONNECT POINT OF INTERCONNECTION PER CODE: NEC 690.58(C) LABEL LOCATION: AC DISCONNECT PER CODE: NEC 690.54 LABEL LOCATION: POINT OF INTERCONNECTION PER CODE: NEC 690.64 NEC 705.12(D)(4) LABEL LOCATION: POINT OF INTERCONNECTION PER CODE: NEC 690.64 NEC 705.12(D)(4) LABEL LOCATION: MAIN SERVICE PANEL PER CODE: NEC 705.10 NEC 690.45(B)(5) LABEL LOCATION: POINT OF INTERCONNECTION PER CODE: NEC 690.33(E)(2) LABEL LOCATION: POINT OF INTERCONNECTION PER CODE: NEC 690.15, NEC 690.13(B) INVERTER #1 APP= MAX POWER POINT PHOTOVOLTAIC SYSTEM DC DISCONNECT SAFETY LABELS E-2 4 OF 9 12221 N US HIGHWAY 301 THONOTASASSA, FL 33592 (813) 982 -9001 #EC13008093 CONTRACTOR CONTACT INFORMATION REV DESCRIPTION CONTRACTOR LOGO DATE ENGINEERING STAMPENGINEER CONTACT INFORMATION C.A.32661 255 GIRALDA AVE CORAL GABLES, FL 33134 DESIGN@ENGIPARTNERS.COM 786 - 393 - 4740 MICHAEL JOHNSON 09-16-2020 8600 BROOKLINE AVE FORT PIERCE FL 34951 SHEET TITLE: SHEETS: ENG. RAFAEL A. GONZALEZ SOTO, PE SHEET NAME: PROJECT ADDRESS: CUSTOMER: ENGINEER OF RECORD: DATE: 1301-608-0246-000-9 PARCEL NUMBER: PROJECT ID: TSP50554 ISSUED FOR PERMIT 09-17-2020 ENGIPARTNERS, LLC TITAN SOLAR POWER FL PV SAFETY LABELS DATA1N.T.S. NORTH IQ COMBINER BOX PV DISCONNECT EXISTING ELECTRIC METER SOLAR MODULE - TYP. SEE 2-1 ROOF MOUNTS LOCATED AT CENTER OF ROOF TRUSS - TYP. WOOD TRUSSES/RAFTERS LOCATION - INSTALLER MUST VERIFY IN FIELD OBS OBS OBS OBS OBS OBS OBS OBS 5'-51 4" 5'-51 4" ARRAY B TILT=20.14º AZIMUTH= 180º (S) ARRAY A TILT=20.14º AZIMUTH= 180º (S) A1.1 A2.8 B2.9 B2.13 A1.13 A2.1 66.9" 39.4" SIL-TITAN 330 NL (60 CELL) UL 1703 CERTIFIED MAX. PV MODULE SURFACE LOAD: 83.5 psf APPLIED WIND LOAD: 42.39 psf NOTES: -INSTALL MID CLAMPS BETWEEN MODULES AND ENDS CLAMPS AT THE END OF EACH ROW OF MODULES. -ALUMINUM RAILS SHOULD ALWAYS BE SUPPORTED BY MORE THAN ONE FOOTING ON BOTH SIDES OF THE SPLICE. RISK CATEGORY ZONES 1 2 3 (PSF) -24.35 -42.39 -42.39 PRESSURES SPAN (FT) MAX. 4' 2' N/A CANTILEVER (IN) MAX. 16" 24" N/A EXPOSURE CATEGORY ROOF SLOPE (°) ROOF TYPE ULTIMATE WIND SPEED NOMINAL WIND SPEED mph mph PRESSURE ZONE: MEAN ROOF HEIGHT: PERIMETER WIDTH: KD KZT KZ VELOCITY PRESSURE (q) = 0.00256* KZKZTKDV2 VELOCITY PRESSURE (ASD) 22.55 EXTERNAL PRESSURE COEFFICIENT Z1 EXTERNAL PRESSURE COEFFICIENT Z2 EXTERNAL PRESSURE COEFFICIENT Z3 0.5 0.5 0.5 -0.9 -1.7 -1.7 TOTAL ROOF AREA 3721.95 26 475.77 42.39 20167.89 87 231.81 sq.-ft sq.-ft TOTAL MODULES: TOTAL PHOTOVOLTAIC AREA: WIND LOAD (PSF): TOTAL WIND LOAD (LBS): TOTAL ROOF MOUNTS: TENSION FORCE PER MOUNT (LBS): 175 157 II B 20.14 HIPPED 1&2 13.6 5.44 0.85 1.0 0.85 INTERNAL PRESSURE COEFFICIENT 0.18 OBS ROOF OBSTRUCTIONS PV MODULES TRUSSES OR RAFTERS ROOF MOUNTS ROOF SLOPE XX.X ARRAY # STRING # MODULE # STRUCTURAL PLAN S-1 5 OF 9 12221 N US HIGHWAY 301 THONOTASASSA, FL 33592 (813) 982 -9001 #EC13008093 CONTRACTOR CONTACT INFORMATION REV DESCRIPTION CONTRACTOR LOGO DATE ENGINEERING STAMPENGINEER CONTACT INFORMATION C.A.32661 255 GIRALDA AVE CORAL GABLES, FL 33134 DESIGN@ENGIPARTNERS.COM 786 - 393 - 4740 MICHAEL JOHNSON 09-16-2020 8600 BROOKLINE AVE FORT PIERCE FL 34951 SHEET TITLE: SHEETS: ENG. RAFAEL A. GONZALEZ SOTO, PE SHEET NAME: PROJECT ADDRESS: CUSTOMER: ENGINEER OF RECORD: DATE: 1301-608-0246-000-9 PARCEL NUMBER: PROJECT ID: TSP50554 ISSUED FOR PERMIT 09-17-2020 ENGIPARTNERS, LLC TITAN SOLAR POWER FL STRUCTURAL ROOF PLAN & PV MODULES LAYOUT1N.T.S. SOLAR MODULE N.T.S.2 LEGEND & SYMBOLS OF 9 12221 N US HIGHWAY 301 THONOTASASSA, FL 33592 (813) 982 -9001 #EC13008093 CONTRACTOR CONTACT INFORMATION REV DESCRIPTION CONTRACTOR LOGO DATE ENGINEERING STAMPENGINEER CONTACT INFORMATION C.A.32661 255 GIRALDA AVE CORAL GABLES, FL 33134 DESIGN@ENGIPARTNERS.COM 786 - 393 - 4740 MICHAEL JOHNSON 09-16-2020 8600 BROOKLINE AVE FORT PIERCE FL 34951 SHEET TITLE: SHEETS: ENG. RAFAEL A. GONZALEZ SOTO, PE SHEET NAME: PROJECT ADDRESS: CUSTOMER: ENGINEER OF RECORD: DATE: 1301-608-0246-000-9 PARCEL NUMBER: PROJECT ID: TSP50554 ISSUED FOR PERMIT 09-17-2020 ENGIPARTNERS, LLC TITAN SOLAR POWER FL2'' CLEARANCE TYP . <25% M O D U L E L E N G T H T Y P. 1/4" SS 18-8 BOLT 1/4" SS SERRATED FLANGE NUT ASPHALT SHINGLES NOTE: SEAL BASE MOUNT TO EXISTING ROOF UNDERLAYMENT WITH ROOF SEALANT AND MEMBRANE SNAPNRACK 5/16" SS LAG BOLT 5/16" SS FENDER WASHER 2X TRUSSES 24" O.C. PV MODULES RACKING PLAN S-2 6 SHINGLE ROOF MOUNT DETAIL & DATA1N.T.S. EQ.EQ. "A" "A" CL EXIST. 2X WD. TRUSSES OR RAFTERS SECTION "A-A" FLASHING LAG BOLT N.T.S. PLACE BOLT AT C.L. OF TRUSS OR RAFTER Lag Screw Installation Guidelines 1. Determine location for the Mount on roof by drilling through the center of truss from bottom with 5/32" drill bit. 2. Mark mounting holes for Mount on underlayment. Mounting holes should be centered on the trusses. 3. Drill 15/64" pilot hole. 4. Apply sealant to bottom of Mount. 5. Place Mount over roof underlayment with holes in roof. 6. Apply sealant to bottom of Mount, apply sealant to lag screws and fasten Mount securely to trusses. 7. Apply additional sealant to top assembly to be sure all penetrations are sealed. Notes: (1) Thread must be embedded in the side grain of a Trusses or other structural member integral with the building structure. (2)Lag Bolts must be located in the middle third of the structural member. (3)These values are not valid for wet services. (4)This table does not include shear capacities. If necessary, contact a local engineer to specify lag bolt size with regard to shear forces. (5)Install lag bolts with head ad washer flush to surface (no gap). Do nor over-torque. (6)Withdrawal design values for lag screw connections shall be multiplied by applicable adjustment factors if necessary. See table 10.3.1 in the American Wood Council NDS for Wood Construction. ASCE 7-10 Velocity Pressure qz10 = 0.00256Kz Kzt Kd V2 Where: qz10 = ASCE 7-10 velocity pressure evaluated at mean roof height (psf) Kz = velocity pressure exposure coefficient Kzt = topographic factor Kd = wind directionality factor V = basic wind speed (mph) from ASCE 7-10 maps referred to as ultimate wind speed maps in 2012 IBC. As an example, for an array having an area of 158.04 sq.-ft., the total uplifting (resultant) force acting on the array would be -39.1 psf x 158.04 sq. ft. = -6,179.364 lb. Knowing this resultant force, the design engineer can now determine the number of attachment points and the size of the mounting hardware necessary to safely carry this load. Live Loads: Live loads associated with photovoltaic systems are usually assumed to be distributed uniformly and are small, on the order of 4 psf or less. Uni-Rac Specs. Lag pull-out (withdrawal) capacities (lbs) in typical roof lumber (ASD) STAINLESS STEEL Lag screw specifications Specific gravity per inch thread depth 516" shaft, * Douglas Fir, Larch Douglas Fir, South Engelman Spruce, Lodgepole Pine (MSR 1650 f & higher) Hem, Fir, Redwood (close grain) Hem, Fir (North) Southern Pine Spruce, Pine, Fir Spruce, Pine, Fir (E of 2 million psi and higher grades of MSR and MEL) Sources: American Wood Council, NDS 2005, Table 11.2A, 11.3A. 0.50 0.46 0.46 0.43 0.46 0.55 0.42 266 235 212 235 307 235 205 0.50 266 Spruce, Pine,Per inch Thread Depth 266lbs SS Lag Bolt 5/16" x 4"Min. Thread Depth 0'-3" Wood Strength x Thread Depth = Pull Out Strength 266 lbs. x 3 in = 798 lbs. Allowable Pull Out Strength per Lag Bolt 798 lbs. Max. Pull Out Strength Required per Lag Bolt 231.1 Lag Bolt Pull Out Strength Safety Factor 3.44 LAG BOLT PULL OUT CALCULATIONS PV MODULES DATASHEET D-1 7 OF 9 12221 N US HIGHWAY 301 THONOTASASSA, FL 33592 (813) 982 -9001 #EC13008093 CONTRACTOR CONTACT INFORMATION REV DESCRIPTION CONTRACTOR LOGO DATE ENGINEERING STAMPENGINEER CONTACT INFORMATION C.A.32661 255 GIRALDA AVE CORAL GABLES, FL 33134 DESIGN@ENGIPARTNERS.COM 786 - 393 - 4740 MICHAEL JOHNSON 09-16-2020 8600 BROOKLINE AVE FORT PIERCE FL 34951 SHEET TITLE: SHEETS: ENG. RAFAEL A. GONZALEZ SOTO, PE SHEET NAME: PROJECT ADDRESS: CUSTOMER: ENGINEER OF RECORD: DATE: 1301-608-0246-000-9 PARCEL NUMBER: PROJECT ID: TSP50554 ISSUED FOR PERMIT 09-17-2020 ENGIPARTNERS, LLC TITAN SOLAR POWER FL SMART MONITORING DATASHEET D-2 8 OF 9 12221 N US HIGHWAY 301 THONOTASASSA, FL 33592 (813) 982 -9001 #EC13008093 CONTRACTOR CONTACT INFORMATION REV DESCRIPTION CONTRACTOR LOGO DATE ENGINEERING STAMPENGINEER CONTACT INFORMATION C.A.32661 255 GIRALDA AVE CORAL GABLES, FL 33134 DESIGN@ENGIPARTNERS.COM 786 - 393 - 4740 MICHAEL JOHNSON 09-16-2020 8600 BROOKLINE AVE FORT PIERCE FL 34951 SHEET TITLE: SHEETS: ENG. RAFAEL A. GONZALEZ SOTO, PE SHEET NAME: PROJECT ADDRESS: CUSTOMER: ENGINEER OF RECORD: DATE: 1301-608-0246-000-9 PARCEL NUMBER: PROJECT ID: TSP50554 ISSUED FOR PERMIT 09-17-2020 ENGIPARTNERS, LLC TITAN SOLAR POWER FL INVERTER DATASHEET D-3 9 OF 9 12221 N US HIGHWAY 301 THONOTASASSA, FL 33592 (813) 982 -9001 #EC13008093 CONTRACTOR CONTACT INFORMATION REV DESCRIPTION CONTRACTOR LOGO DATE ENGINEERING STAMPENGINEER CONTACT INFORMATION C.A.32661 255 GIRALDA AVE CORAL GABLES, FL 33134 DESIGN@ENGIPARTNERS.COM 786 - 393 - 4740 MICHAEL JOHNSON 09-16-2020 8600 BROOKLINE AVE FORT PIERCE FL 34951 SHEET TITLE: SHEETS: ENG. RAFAEL A. GONZALEZ SOTO, PE SHEET NAME: PROJECT ADDRESS: CUSTOMER: ENGINEER OF RECORD: DATE: 1301-608-0246-000-9 PARCEL NUMBER: PROJECT ID: TSP50554 ISSUED FOR PERMIT 09-17-2020 ENGIPARTNERS, LLC TITAN SOLAR POWER FL