HomeMy WebLinkAboutAPPROVED Thelma Motel_6585 N. US 1_Window Pressures_RJL Sealed 09-09-20 DESIGN CRITERIA: Ronald J Applicable Codes,Regulations,and Standards
1. The 6th Edition(2017)Florida Building Code,specifically Chapter
16 Structural Design,Chapter 20 Aluminum,and Chapter 23 Wood. Lederk
2.ASCE 7-10.
Wind Loads Digitally signed by
1. Building Occupancy Category,Paragraph 1604.5 and Table 1604.5:
Risk Category 3. Ronald J Leder Jr
2. Basic Wind Speed,Table 1609C,State of Florida Debris Region&
Basic Wind Speed,Paragraph 1609.3.1 and Table 1609.3.1 Date: 2020.09.09
Equivalent Basic Wind Speed:VuLT=170 MPH,VAsD=131 MPH
3. Exposure Category,Paragraph 1609.4.3: C 10:42:00 -04 00
ENGINEER'S SEAL
Scope of Work:
Replacement of (3)Glass Windows(east side). LL V)
Z
1. Windows not within 3 feet from corners. O
Oa NQ
Builder/Permit Application is to provide Florida Product Approvals w d w J
= — 0 M Z)
meeting required design pressures. W . a U
OPENING SCHEDULE O o O u
J m
w
MARK SIZE (W"xH") MANUFACTURER SERIES # APPROVALS DESIGN PRESSURES ALLOWABLE PRESSURES LU
z J , z z
zh 35" x 37" JELD-WEN W&D BUILDERS VINYL (V-2500) SH FL14104.8 +38.1/-51.1 PSF +50.0/-55.0 PSF Z o
LU
35" x 37" JELD-WEN W&D BUILDERS VINYL (V-2500) SH FL14104.8 +38.1/-51.1 PSF +50.0/-55.0 PSF
35" x 37" JELD-WEN W&D BUILDERS VINYL (V-2500) SH FL14104.8 +38.1/-51.1 PSF +50.0/-55.0 PSF
J OU
Q J
z a
J ��
O J
00(D
w
g JWaW � Q33,_6„ L.L Z r
O
�mra_
DC U (D 00 z
35" x 37" a 0 '0 d z
a
N m a
Q cF =:2
CL
N J >Q M
LU > J
CC J 2 LL
~ 2 W
9'-6" HEIGHT < co W
a
cal O w L
= LoO
35" x 37" N a ~ C.0 LL
DRAWN BY
RJL
DATE DRAWN
07/22/20
REVISION
Al -
0 1 Al -
35 x 37 SHEET NO:
A- 1
Fib
.40
Ah
3 -
- Ronald J
- Leder Jr
PROJECT ADDRESS:
� Digitally signed by
Ronald J Leder Jr
THELMA MOTEL, LLC h • Date: 2020.09.09
� �
6585 N. US HIGHWAY 1 � 10:42:46 -04'00'{
FORT PIERCE, FL 34946 . ' lick [per(
Project Name: THELMA MOTEL
Project Location: 6585 N. US HIGHWAY 1, FT. PIERCE, FL 34946
Date: July 22, 2020
Wind Speed (V,it): 170 mph Exposure Category: �C Wind Speed (Vasa): 132 mph
Building dimensions (rectangular footprint): Length (ft): 12.5
Width (ft): 33.5
Width of End Zone (Zone 5):0ft Mean Roof Height: 9.5 (MRH)
REQUIRED DESIGN PRESSURES
ASD PRESSURES PER ASCE7-10 Dimensions (ft) AREA Positive Negative Pressures
ID# Opening Description Width Height (sgft) (4 & 5) Zone 4 Zone 5
1 BUILDERS VINYL (V-2500) SH 2.92 3.08 9.0 38.1 -41.0 -51.1
2 BUILDERS VINYL (V-2500) SH 2.92 3.08 9.0 38.1 -41.0 -51.1
3 BUILDERS VINYL (V-2500) SH 2.92 3.08 9.0 38.1 -41.0 -51.1
Ronal Digitally
signed by
d J Ronald J
Leder Jr
Leder Date:
2020.09.09
J r 10:43:07
-04'00'
ATC Hazards by Location Page 1 of 1
OTCHazards by Location
Search Information I � i„ sEALMuseum
Address: N US Hwy 1,Fort Pierce,FL,USA
_ Ft Pierce Inlet
Coordinates: 27.459249,-80.3286116 _ _ _ —,r.:r,�, State Park
12ft
Elevation: 12 ft --
Timestamp: 2020-07-22T07:31:05.580Z _ =` ,II_. II - 3P' '�'-♦ ,A,�o�
Hazard Type: Wind �';.-- -- --
GOt7 le ac Fort Pierce
9 N Map d®ap&Uff0iPeogtle
ASCE 7-16 ASCE 7-10
MRI 10-Year ----------------------- 88 mph MRI 10-Year ------------------------------------ 88 mph
MR125-Year .-- 106 mph MR!25-Year 106 mph
MRI 50-Year -------------------------------, .- 119 mph MRI 50-Year ----------------- 119 mph
MRI 100-Year --------------------------------- A 130 mph MRI 100-Year --------------------------------- A 130 mph
You are in a wind-borne debris region if you are also within 1 You are in a wind-borne debris region if you are also within 1
mile of the coastal mean high water line. mile of the coastal mean high water line.
Risk Category I ----------------------------------- 147 mph Risk Category I ----------------------------------- 147 mph
Risk Category II ------------------------------- A 159 mph Risk Category II ------------------------------- A 159 mph
You are in a wind-borne debris region. You are in a wind-borne debris region.
Risk Category III ------------------------------ A 170 mph Risk Category III-IV --------------------------- A 170 mph
If the structure under consideration is a healthcare facility and If the structure under consideration is a healthcare facility and
you are also within 1 mile of the coastal mean high water line, you are also within 1 mile of the coastal mean high water line,
you are in a wind-borne debris region.If other occupancy,use you are in a wind-borne debris region.If other occupancy,use
the Risk Category II basic wind speed contours to determine if the Risk Category II basic wind speed contours to determine if
you are in a wind-borne debris region. you are in a wind-borne debris region.
Risk Category IV ------------------------------ A 182 mph
You are in a wind-borne debris region.
ASCE 7-05
ASCE 7-05 Wind Speed ---------------------- A 140 mph
You are in a wind-borne debris region.
The results indicated here DO NOT reflect any state or local amendments to the values or any delineation lines made during the building code adoption process.Users should confirm any
output obtained from this tool with the local Authority Having Jurisdiction before proceeding with design.
Disclaimer
Hazard loads are interpolated from data provided in ASCE 7 and rounded up to the nearest whole integer.Per ASCE 7,islands and coastal areas outside the last contour should use the
last wind speed contour of the coastal area-in some cases,this website will extrapolate past the last wind speed contour and therefore,provide a wind speed that is slightly higher.NOTE:
For queries near wind-borne debris region boundaries,the resulting determination is sensitive to rounding which may affect whether or not it is considered to be within a wind-borne debris
region.
Mountainous terrain,gorges,ocean promontories,and special wind regions shall be examined for unusual wind conditions.
While the information presented on this website is believed to be correct,ATC and its sponsors and contributors assume no responsibility or liability for its accuracy.The material presented
in the report should not be used or relied upon for any specific application without competent examination and verification of its accuracy,suitability and applicability by engineers or other
licensed professionals.ATC does not intend that the use of this information replace the sound judgment of such competent professionals,having experience and knowledge in the field of
practice,nor to substitute for the standard of care required of such professionals in interpreting and applying the results of the report provided by this website.Users of the information from
this website assume all liability arising from such use.Use of the output of this website does not imply approval by the governing building code bodies responsible for building code approval
and interpretation for the building site described by latitude/longitude location in the report.
Ronal Digitally
signed by
d J Ronald J
Leder Jr
LederDate:
2020.09.09
J r 10:43:38
-04'00'
https://hazards.atcouncil.org/ 7/22/2020