HomeMy WebLinkAboutEnergy Conservation ChecklistFlorida Building Code,. -Fifth Edition (2014) - Energy Conservation
EnergyGauge Summit@ Fla/Com-2015, Effective -Date: June 30, 2015
ASHRAE.90J, -2010 -!,Energy Cost Budget Option
Check List
Applications for compliance with the Florida Building Code, Energy Conservation shall
include:
❑ This Checklist
❑ An Input report generated from the software just after completing compliance
calculations without any further changes
❑ The full compliance report generated by the software that contains the project
summary, complaince summary, certifications and detailed component compliance
reports
❑ Boxes appropriately checked in the Miscellanous report generated by the software at
the end of the compliance report
,( 4
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
3/27/2017 Page 1 of 16
PROJECT SUMMARY
Short Desc: 16019 TCERDA Description: 16019 TCERDA
Owner: Sunshine Kitchen
Addressl: 2199 South Rock Rd City: Fort Pierce
Address2: State: FL
Zip: 34945
Type: Dining: Family Class: Renovation to existing
Jurisdiction: FORT PIERCE, ST LUCIE COUNTY, FL (661100)
Conditioned Area: 4018 SF Conditioned & UnConditioned Area: 4018 SF
No of Stories: 1 Area entered from Plans 4000 SF
Permit No: 0 Max Tonnage 8.3
If different, write in:
Compliance Summa
Component
Gross Energy Cost (in $)
LIGHTING CONTROLS
EXTERNAL LIGHTING
HVAC SYSTEM +
PLANT
WATER HEATING SYSTEMS
PIPING SYSTEMS
Met all required compliance from Check List?
Design
2_
Criteria Result
2,534.0 PASSED
PASSES
PASSES
PASSES
No Entry
Not Checked
Not Checked
Yes/No/NA
IMPORTANT MESSAGE
Info 5009 -- -- -- An input report of this design buildings must be submitted along with this
Compliance Report
EnergyGauge Summit@ Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
3/27/2017 Page 2 of 16
CERTIFICATIONS
I hereby certify that the plans and specifications covered by this calculation are in compliance with the
Florida Energy Code Rc 4E Ss tug
Prepared By: Kyle J. Cartier I G Building Official:
Date:
Date:
I certify that this building is in compliance with the Florida Energy Efficiency Code
Owner Agent:
Date:
If Required by Florida law, I hereby certify (") that the system design is in compliance with the Florida
Energy Efficiency Code
Architect: Edlund Dritenbas Binkley Arc
Electrical Designer: Samuel R. Alexander
Lighting Designer: Samuel R. Alexander
Mechanical Designer: Kyle J. Cartier
Reg No: AR -AA C000886
Reg No: 55422
Reg No: 55422
Reg No: 53269
Plumbing Designer: Kyle J. Cartier Reg No: 53269
(*) Signature is required where Florida Law requires design to be performed by registered design
professionals. Typed names and registration numbers may be used where all relevant information is
contained on signed/sealed plans.
3/27/2017
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Page 3 of 16
Project: 16019 TCERDA
Title: 16019 TCERDA
Type: Dining: Family
(WEA File: DAYTONABEACH.TMY)
Building End Uses
" 1) Proposed 2) Baseline
Total 141.20 162.60
$2,211
$2,534
ELECTRICITY(MBtulkWhl$) 141.20
162.60
41400
47627
$2,211
$2,534,
AREA LIGHTS 25.60
38.00
7488
11132
$400
$592
MISC EQUIPMT
41.30
41.30
12108
12108
$647
$644
PUMPS & MISC
0.50
0.50
158
156
$8
$8
SPACE COOL
45.30
29.00
13284
8483
$709
$451
SPACE HEAT
9.60
8.50
2814
2483
$150
$132
VENT FANS
18.90
45.30
5548
13265
$296
$706
Credits Applied: None I PASSES
Passing Criteria = 2534
Design (including any credits) = 2211
Passing requires Proposed Building cost to be at most 100% of
Baseline cost. This Proposed Building is at 87.3%
EnergyGauge Summit® FlalCom-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
3/27/2017 Page 4 of 16
Project: 16019 TCERDA
Title: 16019 TCERDA
Type: Dining: Family
(WEA File: DAYTONABEACH.TMY)
External Lighting Compliance
Description Category Tradable? Allowance Area or Length ELPA CLP
(W/Unit) or No. of Units (W) (W)
(Sgft or ft)
Ext Light 1 Uncovered Parking Areas -- Yes 0.15 30,000.0 4,500 1,400
Parking lots and Drives
Tradable Surfaces: 1400 (W) Allowance for Tradable: 3750 (W) PASSES
All External Lighting: 1400 (W)
Complicance check includes a excess/Base allowance of 750.00(W)
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
3/27/2017 Page 5 of 16
Project: 16019 TCERDA
Title: 16019 TCERDA
Type: Dining: Family
(WEA File: DAYTONABEACH.TMY)
Lighting Controls Compliance
Acronym Ashrae Description
Area
Design
Min
Compli-
ID
(sq.ft)
CP
CP
ance
Office 1
17 Office - Enclosed
90
1
1
PASSES
Office 2
17 Office - Enclosed
90
1
1
PASSES
Office 3
17 Office - Enclosed
90
1
1
PASSES
Office 4
17 Office - Enclosed
90
1
1
PASSES
Office 5
17 Office - Enclosed
90
1
1
PASSES
Office 6
17 Office - Enclosed
90
1
1
PASSES
Office 7
17 Office - Enclosed
64
1
1
PASSES
Office 8
17 Office - Enclosed
100
1
1
PASSES
Office 9
17 Office - Enclosed
100
1
1
PASSES
W RR
6 Toilet and Washroom
60
1
1
PASSES
M RR
6 Toilet and Washroom
60
1
1
PASSES
CORRIDOR
5 Corridor
100
1
1
PASSES
CORRIDOR
5 Corridor
100
1
1
PASSES
LOBBY
12 Lobby (General) - Reception and
400
1
1
PASSES
Waiting
KITCHEN
7 Food Service - Kitchen
400
2
1
PASSES
OFFICE 10
17 Office - Enclosed
64
1
1
PASSES
CAGED DRY ST(
3 Storage & Warehouse - Bulky
200
1
1
PASSES
Active Storage
CORRIDOR
5 Corridor
50
1
1
PASSES
KITCHEN
7 Food Service - Kitchen
400
2
1
PASSES
JANITOR
1 Electrical Mechanical Equipment
64
1
1
PASSES
Room - General
VESTIBULE
5 Corridor
176
2
1
PASSES
PrOZo3Sp4
1 Electrical Mechanical Equipment
100
1
1
PASSES
Room - General
KITCHEN
7 Food Service - Kitchen
400
2
1
PASSES
KITCHEN
7 Food Service - Kitchen
400
2
1
PASSES
DRY STORAGE
3 Storage & Warehouse - Bulky
240
1
1
PASSES
Active Storage
PASSES
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
3/27/2017 Page 6 of 16
Project: 16019 TCERDA
Title: 16019 TCERDA
Type: Dining: Family
MEA File: DAYTONABEACH.TMY)
System Report Compliance
AHU-2 System 3
Constant Volume Air Cooled No.
of Units
Split System < 65000 Btu/hr
1
Component
Category
Capacity
Design Eff Design IPLV
Comp-
Eff Criteria IPLV Criteria
liance
Cooling System
Air Conditioners Air Cooled
57700
13.00 13.00 13.00
PASSES
Split System < 65000 Btu/h
Cooling Capacity
Heating System
Electric Furnace
36860
1.00 1.00
PASSES.
Air Handling
Air Handler (Supply) -
2000
0.37 0.82
PASSES
System -Supply
Constant Volume
Air Distribution
Not in Check list -
6.00 6.00
N/A
System (Sup)
Compliance Ignored
Air Distribution
Not in Check list -
6.00 6.00
N/A
System (Ret)
Compliance Ignored
Ji
TMAU-1 System 4
Constant Volume Packaged No. of Units
System
1
Component
Category
Capacity
Design Eff Design IPLV
Comp-
Eff Criteria IPLV Criteria
liance
Cooling System
Air Conditioners Air Cooled
100000
12.40 11.20 13.00 11.40
PASSES
65000 to 135000 Btu/h
Cooling Capacity
Heating System
Electric Furnace
69666
1.00 1.00
PASSES
Air Handling
Air Handler (Supply) -
1800
0.82 0.82
PASSES
System -Supply
Constant Volume
Air Distribution
Not in Check list -
6.00 6.00
N/A
System (Sup)
Compliance Ignored
TMAU-2 System 4
Constant Volume Packaged No. of Units
System
1
Component
Category
Capacity
Design Eff Design IPLV
Comp-
Eff Criteria IPLV Criteria
liance
Cooling System
Air Conditioners Air Cooled
f 00000
12.40 11.20 13.00 11.40
PASSES
65000 to 135000 Btu/h
Cooling Capacity
Heating System
Electric Furnace
69666
1.00 1.00
PASSES
Air Handling
Air Handler (Supply) -
1800
0.82 0.82
PASSES
System -Supply
Constant Volume
Air Distribution
Not in Check list -
6.00 6.00
N/A
System (Sup)
Compliance Ignored
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
3/27/2017 Page 7 of 16
AHU-1 System 8
Variable Air Volume Packaged No. of Units
System
1
Component
Category
Capacity
Design
Eff Design IPLV
Comp-
Eff
Criteria IPLV Criteria
liance
Cooling System
Air Conditioners Air Cooled
80000
12.50
11.20 13.00 11.40
PASSES
65000 to 135000 Btu/h
Cooling Capacity
Heating System
Electric Furnace
61400
1.00
1.00
PASSES
Air Handling
Air Handler (Supply) -
2750
0.83
1.12
PASSES
System -Supply
Variable Volume
Air Distribution
Not in Check list -
6.00
6.00
N/A
System (Sup)
Compliance Ignored
Air Distribution
Not in Check list -
6.00
6.00
N/A
System (Ret)
Compliance Ignored
Energy Recovery
Compliance Not Applicable
PASSES
Unit
AHU-3 System 8
Variable Air Volume Packaged No. of Units
System
1
Component
Category
Capacity
Design
Eff Design IPLV
Comp-
Eff
Criteria IPLV Criteria
liance
Cooling System
Air Conditioners Air Cooled
76000
12.50
11.20 13.00 11.40
PASSES
65000 to 135000 Btu/h
Cooling Capacity
Heating System
Electric Furnace
61400
1.00
1.00
PASSES
Air Handling
Air Handler (Supply) -
2475
0.90
1.12
PASSES
System -Supply
Variable Volume
Air Distribution
Not in Check list -
6.00
6.00
N/A
System (Sup)
Compliance Ignored
Air Distribution
Not in Check list -
6.00
6.00
N/A
System (Ret)
Compliance Ignored
AHU-4 System 13
Constant Volume Air Cooled No. of Units
Split System < 65000 Btu/hr
1
Component
Category
Capacity
Design
Eff Design IPLV
Comp-
Eff
Criteria IPLV Criteria
liance
Cooling System
Air Conditioners Air Cooled
12650
21.50
13.00 16.00
PASSES
Split System < 65000 Btu/h
Cooling Capacity
Heating System
Electric Furnace
17000
1.00
1.00
PASSES
Air Handling
Air Handler (Supply) -
375
0.23
0.82
PASSES
System -Supply
Constant Volume
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
3/27/2017 Page 8 of 16
PASSES
Plant Compliance
Description, Installed Size Design Min Design Min Category Comp
No Eff Eff IPLV IPLV liance
None
Project: 16019 TCERDA
Title: 16019 TCERDA
Type: Dining: Family
(WEA File: DAYTONABEACH.TMY)
Water Heater Compliance
Description Type Category Design Min
Eff Eff
Design Max Comp
Loss Loss liance
Water Heater 1 Gas Instantaneous Unknown 0.95
Not Checked
water heater
Not Checked
Project: 16019 TCERDA
Title: 16019 TCERDA
Type: Dining: Family
(WEA File: DAYTONABEACH.TMY)
Piping System Compliance
Category Pipe Dia Is Operating Ins Cond
Ins Req Ins Compliance
[inches] Runout? Temp [Btu-in/hr Thick [in] Thick [in]
[F] .SF.F]
Cooling Systems (Chilled Water, Brine 0.25 True 35.00 0.28
0.50 0.50 PASSES
and Refrigerant)
Domestic and Service Hot Water 1.25 False 140.00 0.28
1.00 1.50 Not Checker
Systems
Not Checked
EnergyGauge Summit@) Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
3/27/2017 Page 9 of 16
Mandatory Requirements (as applicable) Mandatory requirements compiled by US Department
of iEnergy and Pacific Northwest National Laboratory.
Adopted with permission
Topic Section Component Description
Yes NIA Ex
1. To be checked by Designer, or'Engineer
T
Fenestration 5.8.2.3,5.5.3.E Envelope
U-factor of opaque doors associated with the
Br
building thermal envelope meets requirements.
Insulation 6.4.4.1.5 Envelope
Bottom surface of floor structures incorporating
ar
radiant heating insulated to >=R-3.5.
Insulation 5.5.3.1.1 Envelope
High-albedo roofs satisfy one of the following:
Solar reflectance >= 0.55 and thermal emittance
— 0.75, Solar reflectance index >= 64.0, or
increased insulation (assembly <= U-0.03 or >_
Rinsulation).g
Wattage 9.4.3 Exterior Lighting
Exterior lighting grounds lighting over 100 W provides >60
❑ ❑
Im/W unless on motion sensor or fixture is exempt
from scope of code or from external LPD.
Wattage 9.4.2 Interior Lighting
Exit signs do not exceed 5 watts per face.
❑ ❑
Controls 10.4.3 Mechanical
Elevators are designed with the proper lighting,
ventilation power, and standby mode.
HVAC 6.5.6.1 Mechanical
Exhaust air energy recovery on systems meeting
Table 6.5.6.1.
SYSTEM —SPECIFIC 6.5.1.4 Mechanical
Economizer operation will not increase heating
energy use during normal operation.
SYSTEM —SPECIFIC 6.5.2.2.1 Mechanical
Three -pipe hydronic systems using a common
return for hot and chilled water are not used.
SYSTEM —SPECIFIC 6.5.2.2.3 Mechanical
Hydronic heat pump systems connected to a
common water loop meet heat rejection and heat
addition requirements.
SYSTEM —SPECIFIC 6.5.2.4 Mechanical
Water economizer specified on hydronic cooling
❑ ❑
and humidification systems designed to maintain
inside humidity at >35 OF dewpoint if an
economizer is required.
SYSTEM —SPECIFIC 6.5.3.1.1 Mechanical
HVAC fan systems at design conditions do not
❑ ❑
exceed allowable fan system motor nameplate hp
or fan system bhp.
SYSTEM —SPECIFIC 6.5.3.1.2 Mechanical
HVAC fan motors not larger than allowable limits.
❑ ❑
SYSTEM —SPECIFIC 7.4.2 Mechanical
Service water heating equipment meets efficiency
requirements.
SYSTEM —SPECIFIC 7.5.2 Mechanical
Service water heating equipment used for space
13 e
heating complies with the service water heating
equipment requirements.
^A� I To be checked by Plan Reviewer
Air Leakage 5.4.3.4 Envelope
Vestibules are installed where building entrances
separate conditioned space from the exterior, and
meet exterior envelope requirements. Doors have
self -closing devices, and are >=7 ft apart.
Insulation 5.8.1.7.3 Envelope
Insulation in contact with the ground has <=0.3%
13 ❑
water absorption rate per ASTM C272.
Plan Review 4.2.2,5.4.3.1.1,5.7 Envelope
Plans and/or specifications provide all information
with which compliance can be determined for the
building envelope and document where
exceptions to the standard are claimed.
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
3/27/2017 Page 10 of 16
Plan Review 9.7 Exterior Lighting Plans, specifications, and/or calculations provide
all information with which compliance can be
determined for the exterior lighting and electrical
systems and equipment and document where
exceptions to the standard are claimed.
Information provided should include exterior
lighting power calculations, wattage of bulbs and
ballasts, transformers and control devices.
Wattage 9.4.3 Exterior Lighting
Exterior lighting power is consistent with what is
shown on the approved lighting plans,
demonstrating proposed watts are less than or
equal to allowed watts.
Plan Review 4.2.2,9.4.4,9.7 Interior Lighting
Plans, specifications, and/or calculations provide
all information with which compliance can be
determined for the interior lighting and electrical
systems and equipment and document where
exceptions to the standard are claimed.
Information provided should include interior
lighting power calculations, wattage of bulbs and
ballasts, transformers and control devices.
HVAC 6.4.3.4.4 Mechanical
Ventilation fans >0.75 hp have automatic controls
to shut off fan when not required.
HVAC 6.4.3.9 Mechanical
Demand control ventilation provided for spaces
>500 ft2 and >40 people/1000 ft2 occupant
density and served by systems with air side
economizer, auto modulating outside air damper
control, or design airflow >3,000 cfm.
HVAC 6.4.4.1.4 Mechanical
Thermally ineffective panel surfaces of sensible
❑
0
heating panels have insulation — R-3.5.
HVAC 6.5.2.3 Mechanical
Dehumidification controls provided to prevent
reheating, recooling, mixing of hot and cold
airstreams or concurrent heating and cooling of
the same airstream.
HVAC 6.5.4.1 Mechanical
HVAC pumping systems >10 hp designed for
variable fluid flow.
HVAC 6.5.7.1.1 Mechanical
Kitchen hoods >5,000 cfm have make up air
> 50% of exhaust air volume.
HVAC 6.5.7.2 Mechanical
Fume hoods exhaust systems > 15,000 cfm have
VAV hood exhaust and supply systems, direct
make-up air or heat recovery.
HVAC 6.5.8.1 Mechanical
Unenclosed spaces that are heated use only
radiant heat.
HVAC 6.4.3.3.2 Mechanical
Setback controls allow automatic restart and
temporary operation as required for maintenance.
Other Equipment 10.4.1 Mechanical
Electric motors meet requirements where
applicable.
Plan Review 4.2.2,6.4.4.2.1,6.7.2 Mechanical
Plans, specifications, and/or calculations provide
all information with which compliance can be
determined for the mechanical systems and
equipment and document where exceptions to the
standard are claimed. Load calculations per
acceptable engineering standards and
handbooks.
Plan Review 4.2.2,7.7.1,10.4.2 Mechanical
Plans, specifications, and/or calculations provide
all information with which compliance can be
determined for the service water heating systems
and equipment and document where exceptions
to the standard are claimed. Hot water system
sized per manufacturer's sizing guide.
Plan Review 6.7.2.4 Mechanical
Detailed instructions for HVAC systems
commissioning included on the plans or
specifications for projects > 50,000 U.
SYSTEM —SPECIFIC 6.4.3.10 Mechanical
Single zone HVAC systems with fan motors > 5
hp have variable airflow controls. Air conditioning
equipment with a cooling capacity > 110,000
Btu/h has variable airflow controls.
EnergyGauge Summit@ Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
3/27/2017 Page 11 of 16
SYSTEM —SPECIFIC 6.5.1,6.5.1.1,6.5.1.3 Mechanical
Air economizers provided where required, meet
❑
the requirements for design capacity, control
signal, ventilation controls, high -limit shut-off,
integrated economizer control, and provide a
means to relieve excess outside air during
operation.
SYSTEM —SPECIFIC 6.5.1,6.5.1.2,6.5.1.3 Mechanical
Water economizers provided where required,
0011
meet the requirements for design capacity,
maximum pressure drop and integrated
economizer control.
SYSTEM —SPECIFIC 6.5.3.2.1 Mechanical
VAV fan motors > 10 hp to be driven by variable
speed drive, have'a vane -axial fan with variable
pitch blades, or have controls to limit fan motor
demand.
SYSTEM —SPECIFIC 6.5.3.2.3 Mechanical
Reset static pressure setpoint for DDC controlled
VAV boxes reporting to central controller based on
the zones requiring the most pressure.
SYSTEM —SPECIFIC 6.5.3.3 Mechanical
Multiple zone VAV systems with DDC of individual
❑
11
zone boxes have static pressure setpoint reset
controls.
SYSTEM —SPECIFIC 6.5.3.4 Mechanical
Multiple zone HVAC systems have supply air
❑
temperature reset controls.
SYSTEM —SPECIFIC 6.5.4.2 Mechanical
Reduce flow in pumping systems >10 hp. to
multiple chillers or boilers when others are shut
down.
SYSTEM —SPECIFIC 6.5.4.3 Mechanical
Temperature reset by representative building
loads in pumping systems >10 hp for chiller and
boiler systems >300,000 Btu/h.
SYSTEM —SPECIFIC 6.5.4.4.1 Mechanical
Two -position automatic valve interlocked to shut
11
off water flow when hydronic heat pump with
pumping system >10 hp is off.
SYSTEM —SPECIFIC 6.5.4.4.2 Mechanical
Hydronic heat pumps and water-cooled unitary air
❑ ❑
❑
conditioners with pump systems >5 hp have
controls or devices to reduce pump motor
demand.
SYSTEM —SPECIFIC 6.5.5.2 Mechanical
Fan systems with motors —7.5 hp associated
❑ 0
❑
with heat rejection equipment to have capability to
operate at 2/3 of full -speed and auto speed
controls to control the leaving fluid temperature or
condensing temp/pressure of heat rejection
device.
SYSTEM —SPECIFIC 6.5.6.2 Mechanical
Condenser heat recovery system that can heat
❑ ❑
water to 85 OF or provide 60% of peak heat
rejection is installed for preheating of service hot
water in 24/7 facility, water cooled systems reject
>6 MMBtu, SHW load > 1 MMBtu.
SYSTEM —SPECIFIC 6.5.7.1.2 Mechanical
Conditioned supply air to space with a kitchen
❑ 0
❑
hood shall not exceed the greater of a) supply flow
required to meet space heating or cooling, or b)
hood exhaust flow minus the available air transfer
from available spaces.
SYSTEM —SPECIFIC 6.5.7.1.3 Mechanical
Kitchen hoods with a total exhaust airflow rate
>5000 cfm meet, replacement air, ventilation
system, or energy recovery requirements shown in
Table 6.5.7.1.3.
SYSTEM —SPECIFIC 6.5.7.1.4 Mechanical
Kitchen hoods with a total exhaust airflow rate
>5000 cfm meet, replacement air, ventilation
system, or energy recovery requirements.
SYSTEM —SPECIFIC 6.5.9 Mechanical
Hot gas bypass limited to:
❑ El
11
< 240 kBtu/h — 50%
>240 kBtu/h — 25%
SYSTEM 7.5.1 Mechanical
Combined space and water heating system not
—SPECIFIC
allowed unless standby loss less than calculated
maximum. AHJ has approved or combined
connected load <150 kBtu/h.
SYSTEM —SPECIFIC 6.4.3.1.1 Mechanical
Heating and cooling to each zone is controlled by
❑ ❑
a thermostat control.
SYSTEM —SPECIFIC 6.4.3.3.3 Mechanical
Systems with air capacity >10,000 cfm include
optimum start controls.
SYSTEM —SPECIFIC 6.4.3.5 Mechanical
Heat pump controls prevent supplemental electric
resistance heat from coming on when not needed.
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
3/27/2017 Page 12 of 16
J
SYSTEM —SPECIFIC 7.4.4.3 Mechanical Public lavatory faucet water temperature < 110°F.
❑
0
❑
Controls 8.4.2 Project At least 50% of all 125 volt 15- and 20-Amp
receptacles are controlled by an automatic control
device.
Plan Review 4.2.2,8.4.1.1,8.4.1.2 Project Plans, specifications, and/or calculations provide
0
❑
❑
all information with which compliance can be
determined for the electrical systems and
equipment and document where exceptions are
claimed. Feeder connectors sized in accordance
with approved plans and branch circuits sized for
maximum drop of 3%.
Air Leakage
5.4.3.1
Envelope
Continuous air barrier is wrapped, sealed,
caulked, gasketed, and/or taped in an approved
manner, except in semiheated spaces and in
climate zones 1-6.
Air Leakage
5.4.3.2
Envelope
Factory -built fenestration and doors are labeled as
❑
❑
❑
meeting air leakage requirements.
Air Leakage
5.4.3.1
Envelope
All sources of air leakage in the building thermal
❑
❑
❑
envelope are sealed, caulked, gasketed, weather
stripped or wrapped with moisture
vapor -permeable wrapping material to minimize
air leakage.
Fenestration
5.8.2.1
Envelope
Fenestration products rated in accordance with
❑
❑
El
NFRC.
Fenestration
5.8.2.2
Envelope
Fenestration products are certified as to
performance labels or certificates provided.
Insulation
5.8.1.2
Envelope
Below -grade wall insulation installed per
11❑
❑
manufacturer's instructions.
Insulation
5.8.1.2
Envelope
Slab edge insulation installed per manufacturers
instructions.
Insulation
5.5.3.1
Envelope
Roof R-value. For some ceiling systems,
❑
0
Verification may need to occur during Framing
Inspection.
Insulation
5.8.1.2,5.8.1.3
Envelope
Roof insulation installed per manufacturer's
instructions. Blown or poured loose -fill insulation
is installed only where the roof slope is < 3 in 12.
Insulation
&5.3.1
Envelope
Skylight curbs are insulated to the level of roofs
❑
❑
❑
with insulation above deck or R-5.
Insulation
5.8.1.2
Envelope
Above -grade wall insulation installed per
❑
❑
❑
manufacturer's instructions.
Insulation
5.8.1.2
Envelope
Floor insulation installed per manufacturer's
instructions.
Insulation
5.8.1.1
Envelope
Building envelope insulation is labeled with
R-value or insulation certificate providing R-value
and other relevant data.
Insulation
5.8.1:4
Envelope
Eaves are baffled to deflect air to above the
❑
❑
❑
insulation.
Insulation
5.8.1.5
Envelope
Insulation is installed in substantial contact with
❑
13
❑
the inside surface separating conditioned space
from unconditional space.
Insulation
5.8.1.6
Envelope
Recessed equipment installed in building
❑
❑
❑
envelope assemblies does not compress the
adjacent insulation.
Insulation
5.8.1.7
Envelope
Exterior insulation is protected from damage with
a protective material. Verification for exposed
foundation insulation may need to occur during
Foundation Inspection.
Insulation
5.8.1.7.1
Envelope
Attics and mechanical rooms have insulation
protected where adjacent to attic or equipment
access.
Insulation
5.8.1.7.2
Envelope
Foundation vents do not interfere with insulation.
❑
0
❑
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
3/27/2017 Page 13 of 16
Insulation 5.8.1.8 Envelope
Insulation intended to meet the roof insulation
requirements cannot be installed on top of a
suspended ceiling. Mark this requirement
compliant if insulation is installed accordingly.
Controls 9.4.1.7 Exterior Lighting
Automatic lighting controls for exterior lighting
installed.
Controls 9.4.1.1 Interior Lighting
Automatic controls to shut off all building lighting
installed in buildings >5,000 U.
Controls 9.4.1.2 Interior Lighting
Independent lighting controls installed per
approved lighting plans and all manual controls
readily accessible and visible to occupants.
Controls 9.4.1.3 Interior Lighting
Parking garage lighting is equipped with required
lighting controls and daylight transition zone
lighting.
Controls 9.4.1.4 Interior Lighting
Primary sidelighted areas —250 ft2 are equipped
with required lighting controls.
Controls 9.4.1.5 Interior Lighting
Enclosed spaces with daylight area under
skylights and rooftop monitors >900 ft2 are
equipped with required lighting controls.
Controls 9.4.1.6 Interior Lighting
Separate lighting control devices for specific uses
installed per approved lighting plans.
Wattage 9.6.2 Interior Lighting
Additional interior lighting power allowed for
special functions per the approved lighting plans
and is automatically controlled and separated from
general lighting.
Wattage 9.6.3 Interior Lighting
Where space LPD requirements are adjusted
based on room cavity ratios, dimensions are
consistent with approved plans.
Wattage 9.2.2.3 Interior Lighting
Interior installed lamp and fixture lighting power is
consistent with what is shown on the approved
lighting plans, demonstrating proposed watts are
less than or equal to allowed wafts.
HVAC 6.4.3.8 Mechanical
Freeze protection and snow/ice melting system
sensors for future connection to controls.
HVAC 6.4.1.4,6.4.1.5 Mechanical
HVAC equipment efficiency verified. Non-NAECA
HVAC equipment labeled as meeting 90.1.
HVAC 6.4.3.4.1 Mechanical
Stair and elevator shaft vents have motorized
dampers that automatically close.
HVAC 6.4.3.4.2,6.4.3.4.3 Mechanical
Outdoor air and exhaust systems have motorized
0
dampers that automatically shut when not in use
and meet maximum leakage rates. Check gravity
dampers where allowed.
HVAC 6.4.3.4.5 Mechanical
Enclosed parking garage ventilation has automatic
contaminant detection and capacity to stage or
modulate fans to 50% or less of design capacity.
HVAC 6.4.4.1.1 Mechanical
Insulation exposed to weather protected from
damage. Insulation outside of the conditioned
space and associated with cooling systems is
vapor retardant.
HVAC 6.4.4.1.2 Mechanical
HVAC ducts and plenums insulated. Where ducts
or plenums are installed in or under a slab,
verification may need to occur during Foundation
Inspection.
HVAC 6.4.4.1.3 Mechanical
HVAC piping insulation thickness. Where piping is
installed in or under a slab, verification may need
to occur during Foundation Inspection.
HVAC 6.4.4.2.1 Mechanical
Ducts and plenums sealed based on,static
pressure and location.
HVAC 6.5.7.1.5 Mechanical
Approved field test used to evaluate design air
flow rates and demonstrate proper capture and
containment of kitchen exhaust systems.
HVAC 6.4.3.1.2 Mechanical
Thermostatic controls have a 5 °F deadband.
HVAC 6.4.3.2 Mechanical
Temperature controls have setpoint overlap
restrictions.
HVAC 6.4.3.3.1 Mechanical
HVAC systems equipped with at least one
automatic shutdown control.
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
3/27/2017 Page 14 of 16
HVAC 6.4.3.7
Mechanical
When humidification and dehumidification are
provided to a zone, simultaneous operation is
prohibited.
SYSTEM —SPECIFIC 7.4.4.1
Mechanical
Temperature controls installed on service water
11110
heating systems (< 120°F to maximum
temperature for intended use).
SYSTEM —SPECIFIC 7.4.4.2
Mechanical
Automatic time switches installed to automatically
switch off the recirculating hot-water system or
heat trace.
SYSTEM —SPECIFIC 7.4.6
Mechanical
Heat traps installed on non -circulating storage
11011
water tanks.
SYSTEM —SPECIFIC 6.4.1.5.2
Mechanical
PTAC and PTHP with sleeves 16 in. by 42 in.
labeled for replacement only.
SYSTEM —SPECIFIC 6.4.4.2.2
Mechanical
Ductwork operating >3 in. water column requires
❑
air leakage testing.
SYSTEM —SPECIFIC 6.5.2.1
Mechanical
Zone controls can limit simultaneous heating and
cooling and sequence heating and cooling to each
zone.
SYSTEM —SPECIFIC 6.5.2.2.2
Mechanical
Two -pipe hydronic systems using a common
distribution system have controls to allow a
deadband > 15 OF, allow operation in one mode
for at least 4 hrs before changeover, and have
rest controls to limit heating and cooling supply
temperature to 30 OF.
SYSTEM —SPECIFIC 6.5.3.2.2
Mechanical
VAV fans have static pressure sensors positioned
so setpoint —1/3 total design pressure.
SYSTEM —SPECIFIC 7.4.4.4
Mechanical
Controls are installed that limit the operation of a
recirculation pump installed to maintain
temperature of a storage tank.
SYSTEM —SPECIFIC 7.4.5.1
Mechanical
Pool heaters are equipped with on/off switch and
no continuously burning pilot light.
SYSTEM —SPECIFIC 7.4.5.2
Mechanical
Pool covers are provided for heated pools and
pools heated to >90°F have a cover > R-12.
SYSTEM —SPECIFIC 7.4.5.3
Mechanical
Time switches are installed on all pool heaters and
pumps.
SYSTEM —SPECIFIC 7.4.3
Mechanical
All piping in circulating system insulated
SYSTEM —SPECIFIC 7.4.3
Mechanical
First 8 ft of outlet piping is insulated
SYSTEM —SPECIFIC 7.4.3
Mechanical
All heat traced or externally heated piping
insulated
cost uonstructlon
U. i.1
Interior I-ignting
I-urmsneo as -Dunn orawmgs Tor electric power
U
U
U
systems within 30 days of system acceptance.
Post Construction
8.7.2
Interior Lighting
Furnished O&M instructions for systems and
equipment to the building owner or designated
representative.
HVAC
6.7.2.4
Mechanical
HVAC control systems have been tested to ensure
proper operation, calibration and adjustment of
controls.
Post Construction
6.7.2.1
Mechanical
Furnished HVAC as -built drawings submitted
❑
❑
01
within 90 days of system acceptance.
Post Construction
6.7.2.2
Mechanical
Furnished O&M manuals for HVAC systems within
0❑
❑
90 days of system acceptance.
Post Construction
6.7.2.3
Mechanical
An air and/or hydronic system balancing report is
❑
provided for HVAC systems serving zones >5,000
ft2 of conditioned area.
EnergyGauge Summit@ Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
3/27/2017 Page 15 of 16
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
3/27/2017 Page 16 of 16
EnergyGauge Summit® v5.20
INPUT DATA REPORT
Pro_i ect Information
Project Name:
16019 TCERDA
Orientation:
North
Project Title:
16019 TCERDA
Building Type:
Dining: Family
Address:
2199 South Rock Rd
Building Classification:
Renovation to existing building
State: Fl, No.of Stories: 1
Zip: 34945 GrossArea: 4018 SF
Owner: Sunshine Kitchen
Zones
No
Acronym
Description
Type
Area
Multiplier
Total Area
[sfJ
[sfl
1
AHU-2
Zone 1
CONDITIONED
1524.0
1
1524.0
❑
2
AHU-3
Zone 2
CONDITIONED
714.0
1
714.0
❑
3
AHU-1
Zone 3
CONDITIONED
740.0
1
740.0
❑
4
TMAU-1
Zone 4
CONDITIONED
400.0
1
400.0
❑
5
TMAU-2
Zone 5
CONDITIONED
400.0
1
400.0
❑
6
AHU-4
Zone 6
CONDITIONED
240.0
1
240.0
❑
3/27/2017 EnergyGauge Summit® v5.20 1
Spaces
No Acronym
Description
Type
Depth
Width
Height
Multi
Total Area
Total Volume
[ft]
[ft]
[ft]
plier
[sf]
[cf]
In Zone: AHU-2
1
Office 1
Zo0Sp1
Office - Enclosed
9.00
10.00
10.00
1
90.0
900.0
❑
2
Office 2
Zo0Sp1
Office - Enclosed
9.00
10.00
10.00
1
90.0
900.0
❑
3
Office 3
Zo0Sp1
Office - Enclosed
9.00
10.00
10.00
1
90.0
900.0
11
4
Office 4
Zo0Sp1
Office - Enclosed
9.00
10.00
10.00
1
90.0
900.0
❑
5
Office 5
Zo0Sp1
Office - Enclosed
9.00
10.00
10.00
1
90.0
900.0
❑
6
Office 6
Zo0Sp1
Office - Enclosed
9.00
10.00
10.00
1
90.0
900.0
❑
7
Office 7
Zo0Sp1
Office - Enclosed
8.00
8.00
10.00
1
64.0
640.0
El
8
Office 8
Zo0Sp1
Office - Enclosed
10.00
10.00
10.00
1
100.0
1000.0
❑
9
Office 9
Zo0Sp1
Office - Enclosed
10.00
10.00
10.00
1
100.0
1000.0
❑
10
W RR
Zo0Sp10
Toilet and Washroom
10.00
6.00
10.00
1
60.0
600.0
❑
11
M RR
Zo0Sp10
Toilet and Washroom
10.00
6.00
10.00
1
60.0
600.0
❑
12
CORRIDOR
Zo0Spl2
Corridor
5.00
20.00
10.00
1
100.0
1000.0
13
CORRIDOR
Zo0Sp12
Corridor
5.00
20.00
10.00
1
100.0
1000.0
14
LOBBY
Zo0Sp14
Lobby (General) - Reception
8.00
50.00
10.00
1
400.0
4000.0
and Waiting
In Zone: AHU-3
1
KITCHEN
Zo0Sp1
Food Service - Kitchen
20.00
20.00
10.00
1
400.0
4000.0
2
OFFICE 10
Zo0Sp2
Office - Enclosed
8.00
8.00
10.00
1
64.0
640.0
❑
3
CAGED DRY Zo0Sp3
Storage & Warehouse -
8.00
25.00
10.00
1
200.0
2000.0
Bulky Active Storage
4
CORRIDOR
Zo0Sp4
Corridor
10.00
5.00
10.00
1
50.0
500.0
In Zone:
AHU-1
1
KITCHEN
Zo0Sp1
Food Service - Kitchen
20.00
20.00
10.00
1
400.0
4000.0
2
JANITOR
Zo0Sp2
Electrical Mechanical
8.00
8.00
10.00
1
64.0
640.0
Equipment Room - General
3/27/2017 EnergyGauge Summit® v5.20 2
r
3 VESTIBULE ZoOSp3
Corridor
8.00
22.00
10.00
1 176.0
1760.0
4 PrOZo3SP4 ZoOSp4
Electrical Mechanical
10.00
10.00
10.00
1 100.0
1000.0
Equipment Room - General
In Zone: TMAU-1
1 KITCHEN Zo0Sp1
Food Service - Kitchen
20.00
20.00
10.00
1 400.0
4000.0
In Zone: TMAU-2
1 KITCHEN ZoOSp1
Food Service - Kitchen
20.00
20.00
10.00
1 400.0
4000.0
In Zone: AHU-4
1 DRY STORACZo0Sp1
Storage & Warehouse -
10.00
24.00
10.00
1 240.0
2400.0
Bulky Active Storage
Lighting
No Type
Category
No. of
Watts per
Power
Control Type
No.of
Luminaires
Luminaire
[W]
Ctrl pts
In Zone: AHU-2
In Space: Office 1
1 Compact Fluorescent
General Lighting
2
41
82
Occupancy sensor without
1
❑
Daylighting
In Space: Office 2
1 Compact Fluorescent
General Lighting
2
41
82
Occupancy sensor without
1
❑
Daylighting
In Space: Office 3
1 Compact Fluorescent
General Lighting
2
41
82
Occupancy sensor without
1
❑
Daylighting
In Space: Office 4
1 Compact Fluorescent
General Lighting
2
41
82
Occupancy sensor without
1
❑
Daylighting
In Space: Office 5
1 Compact Fluorescent
General Lighting
2
41
82
Occupancy sensor without
1
❑
Daylighting
In Space: Office 6
1 Compact Fluorescent
General Lighting
2
41
82
Occupancy sensor without
1
El
_
Daylighting
In Space: Office 7
1 Compact Fluorescent
General Lighting
1
41
41
Occupancy sensor without
1
Daylighting
In Space: Office 8
3/27/2017 EnergyGauge Summit® v5.20
I Compact Fluorescent
General Lighting
2
41
82
Occupancy sensor without
1
Daylighting
In Space:
Office 9
1 Compact Fluorescent
General Lighting
2
41
82
Occupancy sensor without
1
Daylighting
In Space:
W RR
1 Compact Fluorescent
General Lighting
1
68
68
Occupancy sensor without
1
Daylighting
In Space:
M RR
1 Compact Fluorescent
General Lighting
1
68
68
Occupancy sensor without
1
Daylighting
In Space:
CORRIDOR
1 Compact Fluorescent
General Lighting
2
41
82
Manual On/Off
1
In Space:
CORRIDOR
1 Compact Fluorescent
General Lighting
2
41
82
Manual On/Off
1
In Space:
LOBBY
1 Compact Fluorescent
General Lighting
4
41
164
Occupancy sensor without
1
Daylighting
In Zone: AHU-3
In Space:
KITCHEN
1 Compact Fluorescent
General Lighting
4
41
164
Occupancy sensor without
2
Daylighting
In Space:
OFFICE 10
1 Compact Fluorescent
General Lighting
2
41
82
Occupancy sensor without
1
Daylighting
In Space:-
CAGED DRY STORAGE
1 Compact Fluorescent
General Lighting
3
41
123
Occupancy sensor without
1
El
Daylighting
In Space:
CORRIDOR
1 Compact Fluorescent
General Lighting
1
41
41
Occupancy sensor without
1
Daylighting
In Zone: AHU-1
In Space:
KITCHEN
1 Compact Fluorescent
General Lighting
4
41
164
Occupancy sensor without
2
El
Daylighting
In Space:
JANITOR
1 Compact Fluorescent
General Lighting
1
41
41
Occupancy sensor without
1
Daylighting
In Space:
VESTIBULE
1 Compact Fluorescent
General Lighting
3
41
123
Occupancy sensor without
2
El
Daylighting
3/27/2017
EnergyGauge Summit® v5.20
4
In Space: PrOZo3Sp4
1 Compact Fluorescent General Lighting
2
68
136 Occupancy sensor without
1
Daylighting
In Zone: TMAU-1
In Space: KITCHEN
1 Compact Fluorescent General Lighting
4
41
164 Occupancy sensor without
2
Daylighting
In Zone: TMAU-2
In Space: KITCHEN
1 Compact Fluorescent General Lighting
4
41
164 Occupancy sensor without
2 El
Daylighting
In Zone: AHU-4
In Space: DRY STORAGE
1 Compact Fluorescent General Lighting
2
41
82 Occupancy sensor without
1 El
Daylighting
Walls
No Description Type Width H (Effec) Multi
Area
Orientation Conductance Heat Dens.
R-Value
[ft]
[ft]
plier
[sf]
[Btu/hr. sf. F] Capacity [lb/cf]
[b.sf.FBtu]
[Btu/sf.F]
In Zone: AHU-2
1 PrOZo1Wal Metal 10.00
15.00
1
150.0
West
0.0920 1.072 19.38
10.9 ❑
siding/2x4@24"+Rl
1Batt15/8"Gyp
2 PrOZo1Wa1 Metal 10.00
15.00
1
150.0
West
0.0920 1.072 19.38
10.9 ❑
siding/2x4@24"+Rl
1Batt/5/8"Gyp
3 PrOZo1Wa1 Metal 10.00
15.00
1
150.0
West
0.0920 1.072 19.38
10.9 ❑
siding/2x4@24"+Rl
1Batt/5/8"Gyp
4 PrOZo1Wa1 Metal 10.00
15.00
1
150.0
North
0.0920 1.072 19.38
10.9 ❑
siding/2x4@24"+Rl
1 Batt/5/8"Gyp
5 PrOZo1Wa1 Metal 10.00
15.00
1
150.0
North
0.0920 1.072 19.38
10.9 ❑
siding/2x4@24"+Rl
1Batt/5/8"Gyp
6 PrOZo1Wa1 Metal 10.00
15.00
1
150.0
North
0.0920 1.072 19.38
10.9 ❑
siding/2x4@24"+Rl
1Batt/5/8"Gyp
3/27/2017 EnergyGauge Summit® v5.20 5
7
PrOZo1Wal
Metal
10.00
15.00
1
150.0
North
0.0920
1.072
19.38
10.9
❑
siding/2x4@24"+Rl
1Batt/5/8"Gyp
8
PrOZo 1 Wa9
Metal
10.00
15.00
1
150.0
West
0.0920
1.072
19.38
10.9
❑
siding/2x4@24"+Rl
1Batt/5/8"Gyp
In Zone: AHU-3
1
PrOZo2Wal
Metal
20.00
15.00
1
300.0
West
0.0920
1.072
19.38
10.9
❑
siding/2x4@24"+Rl
1Batt/5/8"Gyp
2
Pr0Zo2Wa2
Metal
8.00
15.00
1
120.0
West
0.0920
1.072
19.38
10.9
❑
siding/2x4@24"+Rl
1Batt/5/8"Gyp
In Zone: AHU-1
1
Pr0Zo3Wa1
Metal
20.00
15.00
1
300.0
West
0.0920
1.072
19.38
10.9
❑
siding/2x4@24"+Rl
1Batt/5/8"Gyp
2
PrOZo3Wa2
Metal
8.00
15.00
1
120.0
West
0.0920
1.072
19.38
10.9
❑
siding/2x4@24"+Rl
1Batt/5/8"Gyp
3
PrOZo3Wa2
Metal
8.00
15.00
1
120.0
South
0.0920
1.072
19.38
10.9
❑
siding/2x4@24"+Rl
1Batt/5/8"Gyp
4
Pr0Zo3Wa4
Metal
22.00
15.00
1
330.0
South
0.0920
1.072
19.38
10.9
❑
siding/2x4@24"+Rl
1Batt/5/8"Gyp
5
PrOZo3Wa5
Metal - --
10.00
15.00
1
150.0
South
0.0920
1.072
19.38
10.9
❑
siding/2x4@24"+Rl
1Batt/5/8"Gyp
Windows
No Description Orientation
Shaded U
SHGC
Vis.Tra
W H (Effec)
Multi
Total Area
[Btu/hr sf F]
IN [ft]
plier
[sf]
In Zone: AHU-1
In Wall: Pr0Zo3Wa1
1 PrOZ0%l Wil West
No
0.4500
0.52
0.57
15.00 8.00
1
120.0
3/27/2017 EnergyGauge Summit® v5.20
In Zone: AHU-2
In Wall: PrOZo1Wa1
1 PrOZolWalWil West
No
0.4500
0.52
0.57
4.00
4.00
1
16.0
❑
1 PrOZolWalWil West
No
0.4500
0.52
0.57
4.00
4.00
1
16.0
❑
1 PrOZolWalWil West
No
0.4500
0.52
0.57
4.00
4.00
1
16.0
❑
1 PrOZol Wal Wil North
No
0.4500
0.52
0.57
8.00
8.00
1
64.0
❑
1 PrOZolWalWil _North
No
0.4500
0.52
0.57
8.00
8.00
1
64.0
❑
1 PrOZol Wal Wil North
No
0.4500
0.52
0.57
8.00
8.00
1
64.0
❑
1 PrOZolWalWil North
No
0.4500
0.52
0.57
8.00
8.00
1
64.0
❑
In Wall: PrOZo1Wa9
1 PrUo1Wa9Wi1 West
No
0.4500
0.52
0.57
5.50
6.00
1
33.0
❑
In Zone: AHU-3
In Wall: PrOZo2Wa1
1 PrUo2WalWil West
No
0.4500
0.52
0.57
15.00 8.00
1
120.0
❑
Doors
No Description Type
Shaded? Width
H (Effec) Multi
Area
Cond.
Dens. Heat Cap.
R-Value
IN
[ft]
plier
[sf] [Btu/hr. A. F] [lb/cf] [Btu/sf. F]
[h.sf.FBtu]
In Zone:
In Wall:
Roofs
No Description Type
Width
H (Effec)
Multi
Area
Tilt
Cond.
Heat Cap
Dens.
R-Value
[ft]
[ft]
plier
[sf]
[deg] [Btu/hr. SE F]
[Btu/sf. F]
[lb/cf]
[h.sf.F/Btu]
In Zone: AHU-2
1 PrOZolRfl Mtl Bldg Roof/R-19
1524.00
1.00
1
1524.0
0.00
0.0492
1.34
9.49
20.3
❑
Batt
In Zone: AHU-3
1 PrOZo2Rfl Mtl Bldg Roof/R-19
1114.00
1.00
1
1114.0
0.00
0.0492
1.34
9.49
20.3
❑
Batt
In Zone: AHU-1
1 PrOZo3Rfl Mtl Bldg Roof/R-19
1140.00
1.00
1
1140.0
0.00
0.0492
1.34
9.49
20.3
❑
Batt
3/27/2017 EnergyGauge Summit® v5.20
In Zone:
TMAU-1
1
PrOZo4Rfl
Mtl Bldg Roof/R-19
20.00 20.00 1
400.0
0.00 0.0492
1.34
9.49 20.3
❑
Batt
In Zone:
TMAU-2
1
PrOZo5Rfl
Mtl Bldg Roof/R-19
20.00 20.00 1
400.0
0.00 0.0492
1.34
9.49 20.3
❑
Batt
In Zone:
AHU-4
1
PrOZo6Rfl
Mtl Bldg Roof/R-19
24.00 10.00 1
240.0
0.00 0.0492
1.34
9.49 20.3
❑
Batt
Skylights
No Description Type
U SHGC
Vis.Trans
W H (Effec) Multiplier
Area Total Area
[Btu/hr sf F]
[ft] [ft]
[Sf] [Sf]
In Zone:
In Roof:
Floors
No Description
Type
Width H (Effec) Multi
Area
Cond. Heat Cap. Dens.
R-Value
[ft] [ft]
plier
[sf] [Btu/hr. sf. F] [Btu/sf. F]
[lb/cf]
[h.sf.FBtu]
In Zone:
AHU-2
1
PrOZolFll
1 ft. soil, concrete
1524.00 1.00
1
1524.0
0.2681 34.00
113.33
3.73
❑
floor, carpet and
rubber pad
In Zone:
AHU-3
1
PrOZo2Fl1
1 ft. soil, concrete
1114.00 1.00
1
1114.0
0.2681 34.00
113.33
3.73
❑
floor, carpet and
rubber pad
In Zone:
AHU-1
1
PrOZo3F11
1 ft. soil, concrete
1140.00 1.00
1
1140.0
0.2681 34.00
113.33
3.73
❑
floor, carpet and
rubber pad
In Zone:
TMAU-1
3/27/2017 EnergyGauge Summit® v5.20
I Pr0Zo4F11
1 ft. soil, concrete 20.00 20.00 1 400.0 0.2681 34.00 113.33 3.73
❑
floor, carpet and
rubber pad
In Zone: TMAU-2
1 Pr0Zo5F11
1 ft. soil, concrete 20.00 20.00 1 400.0 0.2681 34.00 113.33 3.73
❑
floor, carpet and
rubber pad
In Zone: AHU-4
1 PrMo6F11
1 ft. soil, concrete 24.00 10.00 1 240.0 0.2681 34.00 113.33 3.73
❑
floor, carpet and
rubber pad
Systems
AHU-2
System 3
Constant Volume Air Cooled Split No. Of Units 1
System < 65000 Btu/hr
Component
Category
Capacity Efficiency IPLV
1
Cooling System
57700.00 13.00 13.00
❑
2
Heating System
36860.00 1.00
❑
3
Air Handling System -Supply
2000.00 0.37
❑
4
Air Distribution System (Sup)
6.00
❑
5
Air Distribution System (Ret)
6.00
❑
TMAU-1
System 4
Constant Volume Packaged System No. Of Units 1
Component
Category
Capacity Efficiency IPLV
1
Cooling System
100000.00 12.40 13.00
❑
2
Heating System
69666.00 1.00
❑
3
Air Handling System -Supply
1800.00 0.82
❑
4
Air Distribution System (Sup)
6.00
❑
3/27/2017
EnergyGauge Summit® v5.20
E
TMAU-2
System 4
Constant Volume Packaged System
No. Of Units 1
Component
Category
Capacity Efficiency
IPLV
1
Cooling System
100000.00 12.40
13.00
El
2
Heating System
69666.00 1.00
3
Air Handling System -Supply
1800.00 0.82
4
Air Distribution System (Sup)
6.00
AHU-1
System 8
Variable Air Volume Packaged
System
No. Of Units 1
Component
Category
Capacity Efficiency
IPLV
1
Cooling System
80000.00 12.50
13.00
ID
2
Heating System
61400.00 1.00
ID
3
Air Handling System -Supply
2750.00 0.83
4
Air Distribution System (Sup)
6.00
ID
5
Air Distribution System (Ret)
6.00
ID
6
Energy Recovery Unit
ID
AHU-3
System 8
Variable Air Volume Packaged
System
No. Of Units 1
Component
Category
Capacity. Efficiency
IPLV
1
Cooling System
76000.00 12.50
13.00
-
ID
2
Heating System
61400.00 1.00
ID
3
Air Handling System -Supply
2475.00 0.90
ID
4
Air Distribution System (Sup)
6.00
ID
5
Air Distribution System (Ret)
6.00
ID
AHU-4
System 13
Constant Volume Air Cooled Split
No. Of Units 1
System < 65000 Btu/hr
Component
Category
Capacity Efficiency
IPLV
1
Cooling System
12650.00 21.50
16.00
ID
2
Heating System
17000.00 1.00
ID
3
Air Handling System -Supply
375.00 0.23
3/27/2017 EnergyGauge Summit® v5.20 10
Plant
Equipment Category Size Inst.No Eff. IPLV
Water Heaters
W-Heater Description Capacit3Cap.Unit UP Rt. Efficiency Loss
1 Gas Instantaneous water heater [Gal] 199000 [Btu/h] 0.9500 [Ef/Et] [Btu/h] ❑
Ext-Lighting
Description Category
No. of Watts per Area/Len/No. of units
Control Type
Wattage
Luminaires Luminaire
[sf/ft/No]
[W]
El j
Piping
No Type
Operating Insulation
Nomonal pipe
Insulation
Is Runout?
Temperature Conductivity
Diameter
Thickness
[F] [ Btu-in/h.sf.F]
[in]
[in]
1 Domestic and Service Hot Water Systems
140.00 0.28
1.25
1.00
No
❑
2 Cooling Systems (Chilled Water, Brine and
35.00 0.28
0.25
0.50
No
❑
Refrigerant)
Fenestration Used
Name Glass Type No. of Glass SHGC VLT
Panes Conductance
[Btu/h.sf.F]
3/27/2017
EnergyGauge Summit® v5.20
11
ASHULTp1C1rW User Defined 3 0.4500 0.5200 0.5700 ❑
d-Vy-Fg fm
Materials Used
Only R-Value
RValue Thickness
Conductivity
Density
SpecificHeat
Mat No
Acronym
Description
Used
[h.sf.FBtu]
[ft]
[Btu/h.ft.F]
[lb/cf]
[Btu/1b.F]
187
Mat1187
UYF OR PLAS
No
BOARD,1/2IN
178
Mat1178
CARPET W/RUBBER PAD
Yes
1.2300
❑
265
Mat1265
Soil, 1 ft
No
2.0000
1.0000
0.5000
100.00
0.2000
❑
48
Mat148
6 in. Heavyweight concrete
No
0.5000
0.5000
1.0000
140.00
0.2000
❑
23
Mat123
6 in. Insulation
No
20.0000
0.5000
0.0250
5.70
0.2000
❑
4
Mat14
Steel siding
No
0.0002
0.0050
26.0000
480.00
0.1000
❑
271
Mat1271
2x4@24" oc + RI 1 Batt
No
10.4179
0.2917
0.0280
7.11
0.2000
❑
94
Mat194
BUILT-UP ROOFING,
No
0.3366
0.0313
0.0930
70.00
0.3500
❑
3/81N
Constructs Used
No ' Name
Simple
Massless Conductance Heat Capacity
Density
RValue
Construct
Construct [Btu/h.sf.F]
[Btu/sf.F]
[lb/cf]
[h.sf.F/Btu]
1055
Metal siding/2x4@24"+R11Batt/5/8"Gyp
No
No
0.09
1.07
19.38
10.9
❑
Layer
Material Material
Thickness
Framing
No.
IN
Factor
1
4 Steel siding
0.0050
0.000
❑
2
271 2x4@24" oc + RI 1 Batt
0.2917
0.000
❑
3
187 GYP OR PLAS BOARD,1/21N
0.0417
0.000
❑
3/27/2017 EnergyGauge Summit® v5.20 12
No
Name
Simple
Massless Conductance Heat Capacity
Density
RValue
Construct
Construct [Btu/h.sf.F]
[Btu/sf.F]
[lb/cf]
[h.sf.F/Btu]
1056
Mtl Bldg Roof/R-19 Batt
No
No 0.05
1.34
9.49
20.3
❑
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1
94
BUILT-UP ROOFING, 3/81N
0.0313
0.000
❑
2
23
6 in. Insulation
0.5000
0.000
❑
No
Name
Simple
Massless Conductance Heat Capacity
Density
RValue
Construct
Construct [Btu/h.sf.F]
[Btu/sf.F]
[lb/cf]
[h.sf.F/Btu]
1057
1 ft. soil, concrete floor, carpet and rubber No
No 0.27
34.00
113.33
3.7
❑
pad
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1
265
Soil, 1 ft
1.0000
0.000
❑
2
48
6 in. Heavyweight concrete
0.5000
0.000
❑
3
178
CARPET W/RUBBER PAD
0.000
❑
3/27/2017 EnergyGauge Summit® v5.20 13
TCERDA YPK TI
Location Fort Pierce Florida
Building owner TCERDA
Program user KJC
Company SWC
Comments R13 Wall R20 Roof Window U 0 point 4 Window SC 0 point
4
By Sims Wilkerson Cartier Engineering, Inc.
Dataset name K:11610191DesignIMechITrane TraceX16019.trc
Calculation time
TRACE® 700 version
Location
Latitude
Longitude
Time Zone
Elevation
Barometric pressure
Air density
Air specific heat
Density -specific heat product
Latent heat factor
Enthalpy factor
Summer design dry bulb
Summer design wet bulb
Winter design dry bulb
Summer clearness number
Winter clearness number
Summer ground reflectance
Winter ground reflectance
Carbon Dioxide Level
Design simulation period
Cooling load methodology
Heating load methodology
ir`LUNOT
06:08 PM on 04/14/2016
6.3.1
West Palm Beach, Florida
26.7
deg
80.2
deg
5
15
ft
29.9
in. Hg
0.0760
0.2444
1.1147
4,906.9
4.5604
95.0
78.0
35.0
0.90
0.95
0.20
0.20
Ib/cu ft
Btu/lb-°F
Btu/h-cfm-°F
Btu-min/h-cu ft
lb-min/hr-cu ft
OF
OF
OF
400 ppm
January - December
TETD-TA1
UATD
7
tomvoyrcMmNe EulNfiO, anayeie
mn.aro tnm bane
System Checksums
By Sims Wilkerson Cartier Engineering, Inc.
AHU-1
Single Zone Variable Air Volume
COOLING COIL PEAK
Peaked at Time: Mo/Hr: 8 / 17
Outside Air: OADBMIB/HR: 94 / 77 / 113
Space Plenum Net Percent
Sens. + Lat. Sens. + Lat Total Of Total
Btu/h Btu/h Btu/h (%)
Envelope Loads
Skylite Solar 0 0 0 0
Skylite Cond 0 0 0 0
Roof Cond 0 3,891 3,891 5
CLG SPACE PEAK
Mo/Hr: 6 / 18
OAD_ B: 90
Space Percent
Sensible Of Total
Btu/h (%)
0 0
0 0
0 0
Envelope Loads
Skylite Solar
Skylite Cond
Roof Cond
HEATING COIL PEAK
Mo/Hr: Heating Design
OADB: 35
Space Peak Coil Peak Percent
Space Sens Tot Sens Of Total
Btu/h Btu/h (%)
0 0 0.00
0 0 0.00
0 -1,552 6.89
TEMPERATURES
Cooling Heating
SADB 57.0 74.9
Ra Plenum 75.5 68.5
Return 75.5 68.5
Ret/OA 78.8 49.6
Fn MtrTD 0.0 0.0
Fn BIdTD 0.0 0.0
Fn Frict 0.0 0.0
Glass Solar
6,097
0
6,097
8
8,761
18
Glass Solar
0
0
0.00
AIRFLOWS
Glass/Door Cond
1,054
0
1,054
1
868
2
Glass/Door Cond
-1,900
-1,900
8.44
Cooling
Heating
Wall Cond
1,294
192
1,486
2
1,326
3
Wall Cond
-1,976
-2,276
10.11
Diffuser
2,657
797
Partition/Door
0
0
0
0
0
Partition/Door
0
0
0.00
Floor
0
0
0
0
0
Floor
0
0
0.00
Terminal
2,657
797
Adjacent Floor
0
0
0
0
0
0
Adjacent Floor
0
0
0
Main Fan
2,657
797
Infiltration
0
0
0
0
0
Infiltration
0
0
0.00
Sec Fan
0
0
Sub Total =_>
8,446
4,083
12,528
16
10,955
22
Sub Total =_>
-3,876
-5,728
25.44
Nom Vent
450
450
AHU Vent
450
450
Internal Loads
Internal Loads
Infil
0
0
Lights
2,703
676
3,379
4
2,703
5
Lights
0
0
0.00
MinStop/Rh
797
797
People
3,000
0
3,000
4
1,500
3
People
0
0
0.00
Return
2,657
797
Misc
34,130
0
34,130
44
34,130
69
Misc
0
0
0.00
Exhaust
450
450
Sub Total =_>
39,833
676
40,509
52
38,333
77
Sub Total =_>
0
0
0.00
Rm Exh
0
0
Auxiliary
0
0
Ceiling Load
482
-482
0
0
421
1
Ceiling Load
-483
0
0.00
Leakage Dwn
0
0
Ventilation Load
0
0
25,807
33
0
0
Ventilation Load
0
-17,564
77.99
Leakage Ups
0
0
Adj Air Trans Heat
0
0
0
0
0
Adj Air Trans Heat
0
0
0
Dehumid. Ov Sizing
0
0
Ov/Undr Sizing
0
0
0.00
Ov/UndrSizing
0
0
0
0
0
Exhaust Heat
773
-3.43
ENGINEERING
CKS
Exhaust Heat
-772
-772
-1
OA Preheat Diff.
0
0.00
Sup. Fan Heat
0
0
RA Preheat Diff.
0
0.00
Cooling
Heating
Ret. Fan Heat
0
0
0
Additional Reheat
0
0.00
% OA
16.9
56.5
Duct Heat Pkup
0
0
0
cfm/ftz
2.68
0.81
Underflr Sup Ht Pkup
0
0
Underflr Sup Ht Pkup
0
0.00
cfm/ton
408.46
Supply Air Leakage
0
0
0
Supply Air Leakage
0
0.00
ft=/ton
152.17
Btu/hr-ft2
78.86
-22.75
Grand Total =_>
48,761
3,504
78,073
100.00
49,710 100.00
Grand Total ==>
-4,360
-22,519
100.00
No. People
6
COOLING COIL SELECTION
Total Capacity
Sens Cap. Coil Airflow Enter DB/WB/HR
ton MBh
MBh cfm °F °F
gr/lb
Main Clg 6.5 78.1
60.6 2,513 78.8 65.1
70.8
Aux Clg 0.0 0.0
0.0 0 0.0 0.0
0.0
Opt Vent 0.0 0.0
0.0 0 0.0 0.0
0.0
Total 6.5 78.1
Leave DBIWB/HR
°F °F gr/Ib
57.0 54.9 61.2
0.0 0.0 0.0
0.0 0.0 0.0
AREAS
Gross Total
Glass
ft2
(%)
Floor
990
Part
0
Int Door
0
ExFlr
0
Roof
990
0
0
Wall
952
135
14
Ext Door
0
0
0
HEATING COIL SELECTION
CapacityCoil
Airflow
Ent
Lvg
MBh
cfm
°F
°F
Main Htg
-22.5
797
49.6
74.9
Aux Htg
0.0
0
0.0
0.0
Preheat
0.0
0
0.0
0.0
Humidif
0.0
0
0.0
0.0
Opt Vent
0.0
0
0.0
0.0
Total
-22.5
Project Name: TCERDA YPK TI TRACE® 700 v6.3.1 calculated at 06:08 PM on 04/14/2016
Dataset Name: 16019.trc Alternative - 1 System Checksums Report Page 1 of 4,,
AHU-2
COOLING COIL PEAK
Peaked at Time: Mo/Hr: 8 / 17
Outside Air: OADB/WB/HR: 94 / 77 / 113
Space Plenum Net Percent
Sens. + Lat. Sens. + Lat Total Of Total
Btu/h Btu/h Btu/h (%)
Envelope Loads
Skylite Solar
0
0
0
0
Skylite Cond
0
0
0
0
Roof Cond
0
6,146
6,146
13
Glass Solar
8,818
0
8,818
18
Glass/Door Cond
2,239
0
2,239
5
Wall Cond
2,171
325
2,496
5
Partition/Door
0
0
0
Floor
0
0
0
Adjacent Floor
0
0
0
0
Infiltration
0
0
0
Sub Total =_>
13,228
6,471
19,699
41
Internal Loads
Lights
4,314
1,079
5,393
1'
People
4,500
0
4,500
!
Misc
10,597
0
10,597
2,
Sub Total =_>
19,411
1,079
20,490
4:
Ceiling Load
1,587
-1,587
0
I
Ventilation Load
0
0
7,994
1
Adj Air Trans Heat
0
0
1
Dehumid. Ov Sizing
0
1
Ov/Undr Sizing
0
0
I
Exhaust Heat
-494
-494
-
Sup. Fan Heat
0
1
Ret. Fan Heat
0
0
1
Duct Heat Pkup
0
0
I
Underfir Sup Ht Pkup
0
I
Supply Air Leakage
0
0
I
Grand Total ==>
34,226
5,469
47,689
100.01
System Checksums
By Sims Wilkerson Cartier Engineering, Inc.
CLG SPACE PEAK
Mo/Hr: 7 / 18
OADB: 91
Space Percent
Sensible Of Total
Btu/h (%)
0
0
0
0
0
0
9,638
29
2,030
6
2,500
8
0
0
0
0
0
0
0
0
14,167
43
4,314 13
2,250 7
10,597 32
17,161 52
1,454 4
0 0
0 0
0 0
32,783 100.00
COOLING COIL SELECTION
Total Capacity
Sens Cap. Coil Airflow Enter DB/WB/HR
ton
MBh
MBh cfm °F °F
gr/lb
Main Clg 4.0
47.7
40.5 1,910 78.4 63.9
66.0
Aux Clg 0.0
0.0
'0.0 0 0.0 0.0
0.0
Opt Vent 0.0
0.0
0.0 0 0.0 0.0
0.0
Total 4.0 47.7
envelope Loads
Skylite Solar
Skylite Cond
Roof Cond
Glass Solar
Glass/Door Cond
Wall Cond
Partition/Door
Floor
Adjacent Floor
Infiltration
Sub Total =_>
nternat Loads
Single Zone Variable Air Volume
HEATING COIL PEAK
Mo/Hr:
Heating Design
OADB:
35
Space Peak
Coil Peak Percent
Space Sens
Tot Sens Of Total
Btu/h
Btu/h
(%)
0
0
0.00
0
0
0.00
0
-2,405
16.09
0
0
0.00
-4,082
-4,082
27.31
-2,929
-3,393
22.70
0
0
0.00
0
0
0.00
0
0
0
0
0
0.00
-7,011
-9,880
66.11
Lights
People
Misc
Sub Total =_>
veiling Load
lentilation Load
\dj Air Trans Heat
)v/Undr Sizing
exhaust Heat
)A Preheat Diff.
ZA Preheat Diff.
►dditional Reheat
Jnderfir Sup Ht Pkup
Wpply Air Leakage
3rand Total ==>
Leave DBMB/HR
°F °F gr/lb
57.0 55.7 64.3
0.0 0.0 0.0
0.0 0.0 0.0
0
0
0
0
-1,251
0
0
0
-8,262
0 0.00
0 0.00
0 0.00
0 0.00
0 0.00
-5,454 36.50
0 0
0 0.00
389 -2.61
0 0.00
0 0.00
0 0.00
0 0.00
0 0.00
-14,945 100.00
AREAS
Gross Total
Glass
ft2
(%)
Floor
1,580
Part
0
Int Door
0
ExFlr
0
Roof
1,580
0
0
Wall
1,513
290
19
Ext Door
0
0
0
TEMPERATURES
Cooling
Heating
SADB
57.0
82.8
Ra Plenum
77.2
67.5
Return
77.2
67.5
Ret/OA
78.4
59.7
Fn MtrTD
0.0
0.0
Fn BIdTD
0.0
0.0
Fn Frict
0.0
0.0
AIRFLOWS
Cooling
Heating
Diffuser
1,936
581
Terminal
1,936
581
Main Fan
1,936
581
Sec Fan
- 0
0
Nom Vent
140
140
AHU Vent
140
140
Infil
0
0
MinStop/Rh
581
581
Return
1,936
581
Exhaust
140
140
Rm Exh
0
0
Auxiliary
0
0
Leakage Dwn
0
0
Leakage Ups
0
0
ENGINEERING CKS
Cooling Heating
% OA
7.2 ,. 24.1
cfm/ft2
1.23 0.37
cfm/ton
487.17
ft2/ton
397.58
Btulhr-ft2
30.18 -9.46
No. People
_ 9
HEATING COIL SELECTION
CapacityCoil
Airflow
Ent
MBh
cfm
°F
Main Htg
-15.0
581
59.7
Aux Htg
0.0
0
0.0
Preheat
0.0
0
0.0
Humidif
0.0
0
0.0
Opt Vent
0.0
0
0.0
Total
-15.0
Project Name: TCERDA YPK TI TRACE® 700 v6.3.1 calculated at 06:08 PM on 04/14/2016
Dataset Name: 16019.trc Alternative - 1 System Checksums Report Page 2 of 4
AHU-3
COOLING COIL PEAK
Peaked at Time: Mo/Hr: 7 / 18
Outside Air: OADB/WB/HR: 91 / 76 / 110
Space Plenum Net Percent
Sens. + Lat. Sens. + Lat Total Of Total
Btu/h Btu/h Btu/h (%)
Envelope Loads
Skylite Solar
0
0
0
0
Skylite Cond
0
0
0
0
Roof Cond
0
3,712
3,712
5
Glass Solar
8,234
0
8,234
11
Glass/DoorCond
1,059
0
1,059
1
Wall Cond
1,177
186
1,363
2
Partition/Door
0
0
0
Floor
0
0
0
Adjacent Floor
0
0
0
0
Infiltration
0
0
0
Sub Total =_>
10,470
3,899
14,369
20
Internal Loads
Lights
2,793
698
3,492
;
People
3,500
0
3,500
Misc
28,328
0
28,328
31
Sub Total =_>
34,621
698
35,319
41
Ceiling Load
513
-513
0
1
Ventilation Load
0
0
23,558
3:
Adj Air Trans Heat
0
0
I
Dehumid. Ov Sizing
0
1
Ov/Undr Sizing
0
0
1
Exhaust Heat
-794
-794
-
Sup. Fan Heat
0
I
Ret. Fan Heat
0
0
I
Duct Heat Pkup
0
0
I
UnderfIr Sup Ht Pkup
0
I
Supply Air Leakage
0
0
I
Grand Total ==>
45,605
3,290
72,453
100.01
System Checksums
By Sims Wilkerson Cartier Engineering, Inc.
CLG SPACE PEAK
Mo/Hr: 6 / 18
OADB: 90
Space Percent
Sensible Of Total
Btu/h (%)
0
0
0
0
0
0
8,766
20
985
2
1,126
3
0
0
0
0
0
0
0
0
10,877
25
2,793 6
1,750 4
28,328 64
32,871 74
503 1
0 0
0 0
0 0
44,251 100.00
COOLING COIL SELECTION
Total Capacity
Sens Cap. Coil Airflow Enter DB/WB/HR
ton
MBh
MBh cfm °F °F
gr/lb
Main Clg 6.0
72.5
55.7 2,115 78.9 65.5
73.0
Aux Clg 0.0
0.0
0.0 0 0.0 0.0
0.0
Opt Vent 0.0
0.0
0.0 0 0.0 0.0
0.0
Total 6.0 72.5
Envelope Loads
Skylite Solar
Skylite Cond
Roof Cond
Glass Solar
Glass/Door Cond
Wall Cond
Partition/Door
Floor
Adjacent Floor
Infiltration
Sub Total =_>
Internal Loads
Single Zone Variable Air Volume
HEATING COIL PEAK
Mo/Hr: Heating Design
OADB: 35
Space Peak
Coil Peak Percent
Space Sens
Tot Sens Of Total
Btu/h
Btu/h
(%)
0
0
0.00
0
0
0.00
0
-1,597
7.20
0
0
0.00
-2,126
-2,126
9.59
-1,595
-1,851
8.35
0
0
0.00
0
0
0.00
0
0
0
0
0
0.00
-3,720
-5,574
25.13
Lights
People
Misc
Sub Total =_>
Ceiling Load
Ventilation Load
Adj Air Trans Heat
Ov/Undr Sizing
Exhaust Heat
OA Preheat Diff.
RA Preheat Diff.
Additional Reheat
Underflr Sup Ht Pkup
Supply Air Leakage
Grand Total ==>
Leave DBMB/HR
°F °F gr/lb
57.0 54.4 59.1
0.0 0.0 0.0
0.0 0.0 0.0
0
0
0
0
-543
0
0
0
-4,263
0 0.00
0 0.00
0 0.00
0 0.00
0 0.00
-17,436 78.63
0 0
0 0.00
834 -3.76
0 0.00
0 0.00
0 0.00
0 0.00
0 0.00
-22,175 100.00
AREAS
Gross Total
Glass
ft' (%)
Floor
1,023
Part
0
Int Door
0
ExFlr
0
Roof
1,023
0 0
Wall
816
151 19
Ext Door
0
0 0
TEMPERATURES
Cooling
Heating
SADB
57.0
75.5
Ra Plenum
75.6
68.3
Return
75.6
68.3
Ret/OA
78.9
47.1
Fn MtrTD
0.0
0.0
Fn BIdTD
0.0
0.0
Fn Frict
0.0
0.0
AIRFLOWS
Cooling
Heating
Diffuser
2,339
702
Terminal
2,339
702
Main Fan
2,339
702
Sec Fan
0
0
Nom Vent
450
447
AHU Vent
450
447
Infil
0
0
MinStop/Rh
702
702
Return
2,339
702
Exhaust
450
447
Rm Exh
0
0
Auxiliary
0
0
Leakage Dwn
0
0
Leakage Ups
0
0
ENGINEERING CKS
Cooling Heating
% OA
19.2 63.7
cfm/ft'
2.29 0.69
cfm/ton
387.35
ft'/ton
169.43
Btu/hr-ft'
70.82 -21.68
No. People
7
HEATING COIL SELECTION
CapacityCoil
Airflow
Ent
MBh
cfm
°F
Main Htg
-22.2
702
47.1
Aux Htg
0.0
0
0.0
Preheat
0.0
0
0.0
Humidif
0.0
0
0.0
Opt Vent
0.0
0
0.0
Total
-22.2
Project Name: TCERDA YPK TI TRACE® 700 v6.3.1 calcula$ed at 06:08 PM on 04/14/2016
Dataset Name: 16019.trc Alternative - 1 System Checksums Report Page 3 of a.
AHU-4
COOLING COIL PEAK
Peaked at Time: Mo/Hr: 8 / 15
Outside Air: OADB/WB/HR: 95 / 78 / 118
Space Plenum Net Percent
Sens. + Lat. Sens. + Lat Total Of Total
Btu/h Btu/h Btu/h (%)
Envelope Loads
Skylite Solar
0
0
0
0
Skylite Cond
0
0
0
0
Roof Cond
0
1,009
1,009
29
Glass Solar
0
0
0
0
Glass/Door Cond
0
0
0
0
Wall Cond
0
0
0
0
Partition/Door
0
0
0
Floor
0
0
0
Adjacent Floor
0
0
0
0
Infiltration
0
0
0
Sub Total =_>
0
1,009
1,009
29
Internal Loads
Lights
683
171
853
25
People
0
0
0
0
Misc
0
0
0
0
Sub Total==>
683
171
853
25
Ceiling Load
603
-603
0
0
Ventilation Load
0
0
1,816
53
Adj Air Trans Heat
0
0
0
Dehumid. Ov Sizing
0
0
Ov/Undr Sizing
0
0
0
Exhaust Heat
-254
-254
-7
Sup. Fan Heat
0
0
Ret. Fan Heat
0
0
0
Duct Heat Pkup
0
0
0
Underflr Sup Ht Pkup
0
0
Supply Air Leakage
0
0
0
Grand Total ==>
1,285
322
3,424
100.00
System Checksums
By Sims Wilkerson Cartier Engineering, Inc.
CLG SPACE PEAK
Mo/Hr: Sum of
OADB: Peaks
Space Percent
Sensible Of Total
Btu/h (%)
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
683 53
0 0
0 0
683 53
606 47
0 0
0 0
0 0
1,288 100.00
COOLING COIL SELECTION
Total Capacity Sens Cap. Coil Airflow Enter DBIWBIHR
ton MBh MBh cfm °F °F ` gr/lb
Main Clg 0.3 3.4 2.3 68 87.5 71.1 88.1
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0
Total 0.3 3.4
Envelope Loads
Skylite Solar
Skylite Cond
Roof Cond
Glass Solar
Glass/Door Cond
Wall Cond
Partition/Door
Floor
Adjacent Floor
Infiltration
Sub Total =_>
Internal Loads
HEATING COIL PEAK
Mo/Hr: Heating Design
OADB: 35
Space Peak
Coil Peak Percent
Space Sens
Tot Sens Of Total
Btu/h
Btu/h
(%)
0
0
0.00
0
0
0.00
0
-381
13.82
0
0
0.00
0
0
0.00
0
0
0.00
0
0
0.00
0
0
0.00
0
0
0
0
0
0.00
0
-381
13.82
Lights
People
Misc
Sub Total =_>
Ceiling Load
Ventilation Load
Adj Air Trans Heat
Ov/Undr Sizing
Exhaust Heat
OA Preheat Diff.
RA Preheat Diff.
Additional Reheat
Underflr Sup Ht Pkup
Supply Air Leakage
Grand Total ==>
Leave DB/WB/HR
°F °F gr/lb
57.0 56.0 65.3
0.0 0.0 0.0
0A 0.0 0.0
0
0
0
0
-195
0
0
0
-195
0 0.00
0 0.00
0 0.00
0 0.00
0 0.00
-1,170 42.44
0 0
0 0.00
82 -2.98
0 0.00
0 0.00
-1,288 46.72
0 0.00
0 0.00
-2,758 100.00
AREAS
Gross Total
Glass
ft2
(%)
Floor
250
Part
0
Int Door
0
ExFlr
0
Roof
250
0
0
Wall
0
0
0
Ext Door
0
0
0
Computer Room Unit
TEMPERATURES
Cooling
Heating
SADB
57.0
74.0
Ra Plenum
81.6
67.5
Return
81.6
67.5
Ret/OA
87.5
53.2
Fn MtrTD
0.0
0.0
Fn BIdTD
0.0
0.0
Fn Frict
0.0
0.0
AIRFLOWS
Cooling
Heating
Diffuser
68
68
Terminal
68
68
Main Fan
68
68
Sec Fan
0
0
Nom Vent
30
30
AHU Vent
30
30
Infil
0
0
MinStop/Rh
68
68
Return
68
68
Exhaust
30
30
Rm Exh
0
0
Auxiliary
0
0
Leakage Dwn
0
0
Leakage Ups
0
0
ENGINEERING CKS
Cooling Heating
% OA
44.1 - 44.1
cfm/ft2
0.27 0.27
cfm/ton
238.31
ft=/ton
876.27
Btulhr•ft'
13.69 -6.31
No. People
.0
HEATING COIL SELECTION
CapacityCoil
Airflow Ent
Lvg
MBh
cfm °F
°F
Main Htg
-1.3
68 57.0
74.0
Aux Htg
0.0
0 0.0
0.0
Preheat
-0.3
68 53.2
57.0
Reheat
-1.3
68 57.0
74.0
Humidif
0.0
0 0.0
0.0
Opt Vent
0.0
0 0.0
0.0
Total
-1.6
Project Name: TCERDA YPK TI TRACE® 700 v6.3.1 calculated at 06:08 PM on 04/14/2016
Dataset Name: 16019.trc Alternative - 1 System Checksums Report Page 4 of 4
AHU-1
AHU-1
Zone Room **
01 - Janitor
02 - Service Corridor
03 - Kitchen 104
08 - Lobby
09 - Office 1
10 - Office 2
11 - Office 3
12 - Office 111
13 - Office 112
14 - Office 113
15 -'Office 7
16 - Restrooms
17 - Office 115
18 - Office
19 - Circulation
AHU-2
AHU-2
04 - Office 107
05 - Hallway -
07 - Kitchen 1,05
AHU-3
AHU-3
06 - Caged Dry Storage
AHU-4
AHU-4
Load / Airflow Summary
By Sims Wilkerson Cartier Engineering, Inc.
Coil Coil Space
VAV
Floor Cooling Cooling Design Air
Minimum
Area People Sensible Total Max SA Changes
SA
ft2 # Btu/h Btulh cfm ach/hr
cfm
Main Coil
Heating
VAV Heating
Fan
Minimum Sensible
Max SA
% Btu/h
cfm
Rm Peak`
56 w
0.0
995
1,116
40
2.87
12
30
Rm Peak
154
0.0
9,934
10,293
495-
12.87
149
30
Rm Peak
780
6.0
49,867
66,835
2,122
10.88
637
30
Sys Peak
990
6.0
60,884
78,333
2,657
Sys Block
990
6.0
60,696
78,073
2,657
Rm Peak
440
0.0
17;098
18,120
799
7.26
240
30
Rm Peak
90
1.0
2,696
3,290
120
5.34
36
30
Rm Peak
90
1.0
2,651
3,235
117
5.22
35
30
Rm Peak
90
1.0
3,781
4,400
173
7.69
52
30
Rm Peak
100
1.0
3,452
4,027
165
6.60
50
30
Rm Peak
100
1.0
3,469
4,044. .
166
6.64
50
30
Rm Peak
90
1.0
3,384
3,941
163
7.26
49
30
Rm Peak
72
1.0
1,460
2,021
53
2.94
16
30
Rm Peak
108
0.0
962
1,198
22
0.81
7
30
Rm Peak
100
1.0
1,707
2,329
59
2.34
18
30
Rm Peak
100
1.0
1,707
2,329
59
2.34
18
30
Rm Peak
200
0.0
1,763
2,218
40
0.81
12
30
Sys Peak
1,580
. 9.0
44,427
51,457
1,936
Sys Block
1,580
9.0
40,498
47,689
1,936
Rrn Peak
81
1.0
' 2,565
3,131
112
5.55
34
30
Rm Peak
45
0.0
462
657
8
0.71
2
30
Rm Peak
897
6.0
50,833
68,910
2,218
9.89
666
30
Sys Peak
1,023
7.0
50,057
68,895
2,339
Sys Block
1,023
7.0
55,716
72,453
2,339
Rm Peak
250
0.0
2,309
3,424
68
1.09
68
100
Sys Peak
250
0.0
2,309
3,424
68
Sys Block
250
0.0
2,309
3,424
68
* This report does not display heating only systems.
Percent
OA
-11600
0
1.9
6.2
-20,157
0
20.6
68.7
-22,519
0
16.9
56.5
-22,519
0
16.9
56.5
-4,141
0
3.3
11.0
-1,107
0
8.7
28.9
-1,147
0
8.9
29.5
-1,933
0
6.0
20.0
-1,397
0
.6.7
22.2
-1,398
0
6.6
22.1
-1,366
0
6.4
21.2
-439
0
17.6
58.7
-339
0
29:8
99.2
-527
0
18.8
62.6
-527
0
18.8
62.6
-627
0
29.8
99.2
-14,945
0
7.2
24.1
-14,945
0
7.2
24.1
-1,031
0
8.8
29.3
-229
0
67.8
100.0
L21,027--
0-
-19:6-65.3---
-22,287
0
19.2
63.7
-22,287
0
19.2
63.7
-1,288
0
44.1
44.1
-1,298
0
44.1
44.1
-1,288
0
44.1
44.1
Project Name: TCERDA YPK TI
Dataset Name: 16019.trc
TRACE® 700 v6.3.1 oalculated at 06:08 PM on 04/14/2016