HomeMy WebLinkAboutFire District Plan Review FormSAINT LUCIE COUNTY FIRE DISTRICT : T.
�rV�COUNTj•1.
PLAN REVIEW.FORM
¢SO'-
5160 N.W. Milner Drive
Port Saint Lucie, FL 34983
Y
°a
Telephone: 772-621.3322
9FDIS"�
Fax: 772-621-3604
Web Address: www.sicfd.corn -
Building bept.
FMO Permit ,# B-17-122
SLC
Project Name
Sunshine Kitchen . Y '
BLDG Permit #
1704-0284
Address
7550 Pruitt Research Road'"
City Ft Pierce
Contractor
Jaquin & Sons Inc
Address
7348 Commercial Circle
City Fort
Pierce
Stater
Zip 34951 Telephone (772)46572475
FL
Architect/Engineer EDB Architects
Telephone (772) 569-4320
Occupancy Type
Construction Type.:
VB
Square Feet
5313
Business
Occupant Load
94 per plans
Number of Stories
Access Box'
Required
Access Key Switch
AFS Permit
I FA Permit
F
FFP Permit
Required
General Notes
1. An electronic copy of the construction documents submitted on CD is required. The file format shall be .pdf only.
2. All revisions, including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all Inspections.
4. The respective Building Department shall schedule all final inspections through the Fire Marshal's'Office.
S. Failed inspections require payment of fee prior to rescheduling.of further inspections.'
6. Penetrations through rated assemblies shall be of the proper UL design. Design criteria shall.be'submitted'with the construction plans,
7. Fire alarm panels shall be located indoors within air conditioned space.
B. Plans and construction are subject to corrections in the field to maintain code compliance.
9. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity.
10. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE FLORIDA FIRE PREVENTION CODE, 2012 EDITION IS CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See General Notes Above and Keauired Kevisions 13elow
1, The Installation or Alteration of the Fixed Fire Protection Systems require a separate review and permit.
2. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity. Provide a remote test and
inspect appliance equipped with an audible/visual indicator for each HVAC duct smoke detector.
3. Place emergency lights in the restrooms.
Page 1� of i l Reviewed by. Tony Jerger Date 05-31-17