HomeMy WebLinkAboutENG Ltr ZiembaM.A. CORSON & ASSOCIATES, Inc.
ARCHITECTURE * STRUCTURAL DESIGN
412 Colorado Ave., Stuart, Fl. 34994
(772) 223-8227 * Lic. #AR91665
To: St. Lucie County - Building & Code Regulation Division Date: November 30, 2020
Re: Cynthia Ziemba
8880 S. Ocean Dr., Unit 505, (Middle Unit)
Jensen Beach, FL 34957
It is acceptable to replace existing sliding glass door and window openings for the address
listed above as follows:
1) P.W. - The EGS International Rampart series" 5500" Impact alum. window wall system has a
FL# 21899.2. The nominal wind speed is 132 mph and the ultimate wind speed is 170 mph. It
has a +100 /-130 design pressure and has a small missile "D" approval and HVHZ .
2) S.G.D - The EGS International Atlantic series "S.M. 130" Impact aluminum sliding glass
door has a FL# 29677.2. The nominal wind speed is 132 mph and the ultimate wind speed is 170
mph. It has a +130 /-160 design pressure and has a small missile "D" approval and HVHZ.
The worst case scenario building design pressures of address listed above in Zone 4 is +58.7 / -
63.7 and Zone 5 is +58.7 / -78.5. The building has a type II classification and exposure category
"D" for the 6th Edition of the FBC (2017).
SCOPE OF WORK: New sliding glass door and picture /window wall replacement.
DESIGN PARAMETERS AND ASSUMPTIONS USED:
1. DESIGN CODE: Florida Building Code Sixth Edition (2017) with 2020 Supplements using
ASCE 7-10
2. Structure Designed: Enclosed
3. Risk Category: 11 Exposure Category: D
4. Design Wind Velocity 170 mph End Zone Width: 4 ft
5. Mean Roof Height 70 ft Roof Pitch: 0:12 Parapet: N/A ft
6. Components & Cladding Design Pressures Used: Zone 4: +58.7 / -63.7 P.S.F. &
Zone 5: +58.7 / -78.5 P.S.F. Worst case scenario has been calculated.
7. Design Loads: Floor: N/A Roof/Dead: N/A Roof/Live: N/A Balcony: N/A Dock: N/A
Deck: N/A Stairs: N/A Fence: N/A Railings: N/A
8. Were Shear Walls Considered For Structure? N/A Not Applicable Explain Why Not:
9. Is A Continuous Load Path Provided? N/A
10. Design Soil Bearing Pressure: N/A Soil Test Reports Submitted? N/A
Tic yoaQr ouitime and consideration. If you have any questions please call.
-u 4Ft cv6GOti up i „� �7
V Yv1rJ V J n l
ark ....orson ARB
' esidenl�