HomeMy WebLinkAboutfire departmentSAINT LUCIE COUNTY FIRE DISTRICT
PLAN REVIEW FORM
5160 N.W. Milner Drive
Port Saint Lucie, FL 34983
Telephone: 772-621-3322
Fax: 772-621-3604
Web Address: www.slcfd.com
Building Dept. JSLC ---
Project Name Etae'ter—
Address [2299 Swth Rock Road
Contractor
rierman construction Services
Address 10291 NW 46th Street -- —�--
I -----_.-._-----�---� City
FL — -- I zip
.architect/Engineer LT4AE
FMO Permit # B-20-370
BLDG Permit # F 1706-0633
City Ft Pierce
Sunrise
3351
i Telephone
i
Telephone F(954)839-4258
(954) 931-5523
i
Occupancy Type ndustri.3i F ----- ----�
—� ---_ --- i Construction Type !I r Square Feet 14,500
�..._—_
Occupant Load f --- Number of Stories r2 i iced
1_ �— _ Acc`ec r3o ;RequlreC --7 Access Key Switch
AFS Permit Re uired I.__—
q — — I F.APermit (Required _—+ I FFP Permit
6. General Notes
1. An electronir, copy of the construction documents submitted on a CD is required. The file format shall be .pdf only.
2. All revisions, including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all inspections.
4. A Radio coverage Pre -Survey Signal Strength inspection is required before any final inspection is scheduled.
5. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
6. Failed inspections require payment of fee prior to rescheduling of further inspections.
7. Penetrations through rated assemblies shall be of the proper UL design. Design criteria shall be submitted with the construction plans.
8. Fire alarm panels shall be located indoors within air conditioned space.
9. Plans and construction are subject to corrections in the field to maintain code <ompliance.
10. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity.
11. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
IF THE CURRENTLY ADOPTED VERSION OF THE FLORIDA FIRE PREVENTION CODE IS ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL HE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ?;DMINI TRATWE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTiFICATE OF OCCUPANCY.
See Genera; Notee; Above and Required Revisions Bel:rw
1. Automatic fan shuldown is required for HVAC system/s that exceed 2,000 cfm resign czpacity. Provide a remote test and
inspect appliance equipped with an audible/visual indicator for •.,,cr. HVAC dust smoke detector. HVAC duct smoke detector(s)
shall be tied into the Tir_ aiarm system.
2. A separate review and permit i5 required for the. instaliation orr a!teratiorl of the fire alarm a;1d Tire sprinkler systems.
3. Generator installation require a separate review &nd-pernv.
Page 11
I of FI-1
Reviewe:ib rT "—� — �----•
y i s ony 1er5er —_ -`� Date 6-0� 2-2020
iW