HomeMy WebLinkAboutfire departmentBuilding Dept.
Project Name
dress
Contractor
SAINT LUCIE COUNTY FIRE DISTRICT
PLAN REVIEW FORM
JG
5160 N.W. Milner Drive
Port Saint Lucie, FL 34983
N x.:
Telephone:772-621-3322
Fax: 772-621-3604
Web Address: www.slcfd.com
Fs-LcFMO Permit #
United Pentecostal Fine Ministries r BLDG Permit #
IFt Pierce
[202 East Midway Road
I
Pike General Construction
ddress �4131 South US Hwy 1 Bldg 2 Ste 3 City Ft Pierce
State FFL Zip 134982
Telephone
Architect/Engineer 1SteveClark
Occupancy Type Assembly Construction Type IIiB
Occupant Load
299 per plar;s Number of Stories F 1 Access Box
FA Permit
City
Required
Telephone
i PG�lired Y FFPPermit
0
General Notes
!B-20-374REV
1905-0020
Square Feet 4652
Access Key Switch
1. An electronic copy of the construction documents submitted on a CD is required. The file format shall be .pdf only.
2. All revisions including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all inspections.
4. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
5. Failed inspections require payment of fee prior to rescheduling of further inspections.
6. Penetrations through rated assemblies shall be of the proper UL design. Design criteria shall be submitted with the construction plans.
7. Fire alarm panels shall be located indoors within air conditioned space.
S. Plans and construction are subject to corrections in the field to maintain coee compliance.
9. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity.
10. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE FLORIDA FIRE PREVENTION CODE, 2015 EDITION IS CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
ARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See General Notes Above and Required Revisions Below
1. Assembly occupancies with an occupant load greater than 100 persons require panic hardware or fire exit hardware on the
required means of egress doors.
2. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity. Provide a remote test and
inspect appliance equipped with an audible/visual indicator for each HVAC duct smoke detector. HVAC duct smoke detector(s)
shall be tied into the fire alarm system.
3. A separate review and permit is required for the installation or alteration of the fire alarm system.
Reviewed by Tony Jerger� Date 12-07-2020
A.