HomeMy WebLinkAboutREVISION- Amazon Delivery Station - DVB1 (12-07-2020)EXISTING SYSTEMDEVICES IN THESEAREAS REMAINUNCHANGEDEXISTING SYSTEMDEVICES IN THESEAREAS REMAINUNCHANGEDTHE DESIGN INSTALLATION COMPLIESWITH F.B.C. 2017 6TH EDITION.SHEET:FA-101PARTIAL MAINFLOORFIRE ALARM PLANDRAWN BY:CHECKED BY:ISSUE DATE:JOB #:PROJECT #:SYSTEM:FIRE ALARM SYSTEMLJCCS10/30/20JOHNSON CONTROLS © 2020ISSUE LOG:Revisions shown with # symbol MARK CAD CHK DESCRIPTIONDATE Johnson Controls 7440 Commercial Circle Fort Pierce, FL 34651 DVB1 - Delivery Station 10550 COMMERCE PARKWAY MIRMAR, FLORIDA 33025 Phone: 954-431-3700619620402 Signaling Line Circuit (SLC) ScheduleThere is one signaling line circuit(s) (SLC) within the fire alarm control panel, as configured for thisproject. An SLC serves a maximum of 99 analog addressable sensor addresses (photoelectric,ionization or thermal / spot type or duct mounted smoke detectors). Each SLC also serves a maximumof 99 module addresses (mini-monitor, monitor, NAC control or relay control).The actual custom labels for the addressable devices will be prepared upon approval of the submittals.This list will be available for review by any interested parties and will be updated as required foracceptance by the inspectors who are witnessing the acceptance of the system.Pathway Survivability Level 0 - (12.4.1) Level 0 pathways shall not be required to have any provisionsfor pathway survivability.All pathways shall comply with NFPA 70, National Electrical Code.11/25/2020