HomeMy WebLinkAboutProject information, mini splitSubmittal Data Sheet CH-12SPH-230VI (INDOOR UNIT)CH-12SPH-230VO (OUTDOOR UNIT)
INDOOR SPECIFICATION
Air flow (Hi/Mi/Lo)306/212/147 CFM
Sound Preassure level (Hi/Mi/Lo)36.5/30/25 dB(A)
Dimension (WxDxH)31.57x7.44x11.69 in
Net/Gross weight 18.1/22.0 Lbs
OUTDOOR SPECIFICATION
Air flow 1120 CFM
Sound Preassure level 57.5 dB(A)
Dimension (WxDxH)31.50x13.11x21.81 in
Net/Gross weight 81.6/88.2 Lbs
Refrigerant type R410A
Refrigerant precharge 25 ft
Additional charge for each ft 0.16 oz
Job Name:_________________________________________________________________________Location:________________________________________________________________________ Engineer:______________________________________________________________________ Submitted to:_____________________________________________________________________ Submitted by:_____________________________________________________________________Reference:_________________________________________________________________________
Date:______________________________________________________________________________Approval:__________________________________________________________________________Сonstruction:______________________________________________________________________Unit #:_____________________________________________________________________________Drawing #:_________________________________________________________________________
EFFICIENCY
Cooling Heating
SEER 21.5 HSPF4/HSPF5 9.8/7.7
EER 13 COP 3.24
SYSTEM PERFORMANCE
Cooling
Capacity 12,000 Btu/h
Input 923 W
Rated current 4.05 A
Heating
Capacity 12,000 Btu/h
Input 1085 W
Rated current 4.72 A
OPERATION TEMPERATURE RANGE
Indoor Outdoor
cooling heating cooling heating
62 – 90 oF 32 – 86 oF -13 – 122 oF -13 – 86 oF
ELECTRICAL
Power supply 208-230V / 60Hz, 1Ph
MCA 12 A
MOCP 16 A
MFA 15 A
Compressor Type ROTARY
Compressor RLA 6.8 A
MCA: Minimum Circuit Ampacity; MFA: Max. fuse amps; MOCP: maximum overcurrent protetive device; RLA: Rated load amps. PIPING
Refrigerant piping Liquid side/Gas side 1/4” - 1/2” in
Max. refrigerant pipe length 82 ft
Max. difference in level 33 ft
WIRING
Connection wiring 16 AWG/4
Power supply wiring 14 AWG/3
SOPHIA
WALL-MOUNTED SERIES
SPLIT AIR CONDITIONER WITH HEAT PUMP
• WiFi Ready• Mute Operation• Silver ion Filter• Anti Cold Air• Sleep Mode• Cold Catalyst Filter• 12 Grades Indoor Fan Speeds• Self Diagnosis Function
• Two-way Draining Connection• Indoor and Outdoor Anticorrosive Coating GoldFin• Two Direction Airflow• Double Level Air Flaps • High Density Filter • Turbo Operation• Refrigerant Leakege Detect
GENERAL FEATURES
This warranty should be registered on our the web-site www.cooperandhunter.us within 60 days of installation.The warranty is only valid when installed by a Licensed HVAC Technician. A war-ranty period of Seven (7) years on compressor to the original registered end-user.A warranty period of Five (5) years on all parts to the original registered end user.Warranty applies only to products remaining in their original installation location.
INDOOR UNIT CH-12SPH-230VI
MOUNTING PLATE
OUTDOOR UNIT CH-12SPH-230VO
W D H
31.57 7.44 11.69
OUTDOOR UNIT DIMENSIONS (in)MOUNTING DIMENSIONS
W x H x D DISTANCE A (in)DISTANCE B (in)
31.50” x 21.81” x 13.11”20.24”13.39”
W
A
BDAir outlet
Air outlet
Air outlet
SOPHIA
WALL-MOUNTED SERIES
SPLIT AIR CONDITIONER WITH HEAT PUMP
Cooper&Hunter products are subject to continuous improvements. Cooper&Hunter reserves the right to modify product design,
specifications and information in this data sheet without notice and without incurring any obligations.