HomeMy WebLinkAboutPOA PLASTPRO-3068-6-PANEL-INSWING-OUTSWING-IMPACTplastpro 5200 W. CENTURY BLVD. LOS ANGELES, CA 90045 Smooth / Wood Grain / White Wood Grain Rustic / Mahogany Series Fiberglass Door INSWING / OUTSWING "IMPACT" GENERAL NOTES 1. This product has been evaluated and is in compliance with the 6th Edition (2017) Florida Building Code (FBC) structural requirements excluding the "High Velocity Hurricane Zone" (HVHZ). 2. Product anchors shall be as listed and spaced as shown on details. Anchor embedment to base material shall be beyond wall dressing or stucco. 3. When used in areas requiring wind borne debris protection this product complies with FBC Sections 1609.1.2 & R301.2.1.2 and does not require an impact resistant covering. This product meets missile level " Y and includes Wind Zone 4 as defined in ASTM E1996 and FBC Sections 1609.1.2.2 & R301.2.1.2.1. 4. For 2x stud framing construction, anchoring of these units shall be the some as that shown for 2x buck masonry construction. 5. Site conditions that deviate from the details of this drawing require further engineering analysis by a licensed engineer or registered architect. TABLE OF CONTENTS SHEET # DESCRIPTION 1 Typical elevation, design pressures, & general notes 2 Door panel details 3 Horizontal cross sections 4 Vertical cross sections 5 Buck and frame anchoring - 2X buck masonry construction 6 Frame anchoring -1 X buck masonry construction 7 Bill of materials & components - cnn 1 I ♦ V / v FRAME WIDTH Z Z V Z O W V = W :�F LU Uf a Ll LL- o O X X Q Q O M 00 co X OVERALL DESIGN PRESSURE (PSF) SWING FRAME INSWING 1 37.50" x 82.00" I +65.0 1 -70.0 OUTSWING 1 37.50" x 80.37" I +65.0 1 -65.0 ♦ �� :i ♦ in � rn CO v to M O�;J:CU M * 0•�� L-rn v �N ° z �:� O IN- o rn i �;.• G`� Q V Lof), M `` � T 111� o M Z U N •• v C9 x Z Q 1 0 m N a zp J C W arm (� IL rn� aD_I.L. `2 M 0 o CZ E 0 0 C W f�Y O -i n. Of 0 w 0 J Q zo oz aJ M 48 �cif w w gw am (Q Q w Q� U 00 � 0 w Of- Q a a °I (DATE: 02/16/12 1 SCALE: N.T.S. DWG. BY: JK CHK. BY: LFS DRAWING NO.: FL-15213.1 SHEET 1 OF 7 0 20) ( 9 i 1 HORIZONTAL CROSS SECTION 2 35.75" MAX. DOOR 1.58" —j PANEL WIDTH z N 2 25 TOP RAIL �- Cellular PVC O W i z a 0 2 X o N ON O N t, BOTTOM RAIL 40 DOOR PANEL 14 Cellular PVC 2.50" co LQ i REINFORCEMENT WOOD For lock 11 Lq 29 HINGE & LATCH STILE Reinforcement N L --I I- - .185" 24 HINGE & LATCH STILE Cellular PVC 24 IKITCDInD 0 rn ., i��'• t�, .. •.ram-r� 4i 6 � X! �O ' M C.� �<=� -n o 0. Zo — LL i, •.... �� >>SD0) ZZ 0 co z N .. n O 0 v tD aZd V m E� z ai m m inM 9 CD a 5O�pap LL o E oZ o �'`a CVTCD1nD 2 VERTICAL CROSS SECTION 2 � J ZO CC w uj a COuj En Of Q O U d d ROT DATE: 02/16/12 SCALE: N. T. S. DWG. BY: JK CHK. BY: LFS DRAWING NO.: FL-15213.1 SHEET 2 of 7 ] - l M" M►N 'ERIOR \ 3 m 3 HORIZONTAL CROSS SECTION 3 Shown w/1X sub -buck 3 1-1/4" MIN. 4 EMB. (TYP.) 4n4 4 17 t M 10 ''''fr�!!!*j O te)C Z �+ U N m t� U Z4 O P�� Z 0 m U s o (0 It Ozm a * m n n. LL m LL O O C O O o Ctj 0 23"n z O f=- cr w — o cn cn �(n?� o V J Cl-CO V) Z G-- Q O O C� O 1-1/4" MIN. Q = IB. (TYP.) 0- 0- 5 4 0.15" 0.15" 3 5 J m CSINK C'SINK -- 6 (TYP.) (TYP.) 6 mT d A 12 23 23 12 O N n a c o 6 00 G Q a. c 16 6 n° to 40 40 00 INTERIOR INTERIOR 16 k%W4 o 0 c Q N O ° 6 31 EXTERIOR EXTERIOR 13 DATE:02116112 SCALE: N.T.S. 3 8 21 40 27 4 1 DWG. BY: JK 1 CHK. BY: LFS 2 HORIZONTAL CROSS SECTION i HORIZONTAL CROSS SECTION DRAWING NO.: 3 Outswing shown - inswing 3 Outswing shown - inswing also approved also approved FL-15213.1 SHEET 3 OF 7 Q�'a'1iII a rn Z -n v CA �. H O 0 a a i13': C Z U0; Q. - .. a - v°. I ••• Q L r Imo' '•-..... • `�� 0) a Q d ° O 3 30 e T Z OZv Z °- a C Ern m m CV Q. t p -j c W m 0) E `t O 2 4 a m a:aUT � m.9LL 6 W ° �6 o U C Uj 0 J D.. 40 40 12 N 16 12 16 23 0 6 oU` 6 zo V) 23 , EXTERIOR INTERIOR EXTERIOR INTERIOR a g m V, cD m amu Q 1 VERTICAL CROSS SECTION 2 VERTICAL CROSS SECTION W 4 Outsshown -inswing 4 Shown wll Xsub-buck � o also approved 0 Q a d ._J m EXTERIOR INTERIOR mm EXTERIOR INTERIOR 40 ao 0 z 00 0 6 WW 40 5 10 to L 16 28 15 Ww 1 » z � N 1 ��w z e J to 6 n u e o n DATE:02116112 to SCALE: N.T.S. ° 3 VERTICAL CROSS SECTION 4 VERTICAL CROSS SECTION DWG. BY: JK m 4 Outswing configuration 4 Inswing configuration CHK. BY: LFS 3 DRAWING NO.: ri FL-15213.1 ro 0 SHEET 4 OF % N 2X BUC MASONRY OPENING BUCK ANCHORING CONCRETE ANCHOR NOTES: 1. Concrete anchor locations at the corners may be adjusted to maintain the min. edge distance to mortar joints. 2. Concrete anchor locations noted as "MAX. ON CENTER" must be adjusted to maintain the min. edge distance to mortar joints, additional concrete anchors may be required to ensure the "MAX. ON CENTER" dimension are not exceeded. 3. Concrete anchor table: HINGE JAMB ANCHOR ANCHOR M/N. MIN•.CLEARANCE :MIN. CLEARANCE TYPE SIZE EMBEDMENT TO MASONRY TO ADJACENT EDGE ANCHOR ITW ® 1/41, 211 411 TAPCON ELCO 1/4" 1-1/4" 1" 4" ULTRACON WOOD SCREW INSTALLATION NOTES: 1. Maintain a minimum 518" edge distance, 1" end distance, & 1" o.c. spacing of wood screws to prevent the splitting of wood. FRAME MASONRY OPENING 7 FRAME ANCHORING Masonry 2X buck construction 6" :Zo W W U z O HINGE JAMB STRIKE JAMB STRIKE PLATE DETAIL �II !rrr rn <t_z - r ��.I/ • Z - 1 +G•: Q� N O 0> 00 z O ap O :2 Z 0 >1( Ern c� o CC) p cw °rOt a It �OOm T m anc m u: F cc o O 0 O cLj J n. O D 0 O Cr CL zo �Ct W w CL m Q W O IOf d U 1= Z � 00 U � Z LL C) m �3 g Y Y U U m m X 0 w 0 a DATE: 02/16/12 SCALE: N.T.S. DWG. BY: JK CHK. BY: LFS DRAWING NO.: FL-15213.1 SHEET 5 OF 7 O. A Q v. Ix - BUCK FRAME MASONRY OPENING e � e a 'a HINGE JAMB CONCRETE ANCHOR NOTES: 1. Concrete anchor locations at the comers may be adjusted to maintain the min. edge distance to mortar joints. 2. Concrete anchor locations noted as "MAX. ON CENTER" must be adjusted to maintain the min. edge distance to mortar joints, additional concrete anchors may be required to ensure the "MAX. ON CENTER" dimension are not exceeded. 3. Concrete anchor table: ANCHOR ANCHOR MIN. MIN. CLEARANCE E; MliP CLEARANC TYpE SIZE EMBEDMENT TO MASONRY TO ADJACENT EDGE: ANCHOR. ITW ® 14" / 1-1/4n 2" tiff TAPCON ELCO 1/4" 1-1/4" in 4" ULTRACON ITW ® 3/16" 1-1/4" 3" TAPCON WOOD SCREW INSTALLATION NOTES: 1. Maintain a minimum 518" edge distance, 1"end distance, & I"o.c. spacing of wood screws to prevent the splitting of wood. TYP. HEAD & JAMBS FRAME ANCHORING Masonry 1 X buck construction De W W �O HINGE JAMB STRIKE PLATE DETAIL A.. in I • z ®'� 1� 0 Qi •• to U N v 0 oz°Q 6 }Yt Cm`a Ea' Q M V into J� °c 1t` a � m m aa� `m g LL U £ oz Lj a JX a Z O U CO � p UO 2: j 6EZ Z Q1 O O 2 U �Lo J ZOf- (!)�.D w Li0 CLm Q LL-� C' o v o m 0- CL x h rn DATE: 02/16/12 SCALE: N.T.S. DWG. BY: JK CHK. BY: LFS DRAWING NO.: FL-15213.1 SHEET 6 OF 7 BILL OF MATERIALS ITEM DESCRIPTION MATERIAL 1 MASONRY - 3,000 PSI MIN. CONCRETE CONFORMING TO ACI 301 OR HOLLOW BLOCK CONFORMING TO ASTM C90 CONCRETE 2 1 X BUCK SG >= 0.55 WOOD 3 2X BUCK SG >= 0.55 WOOD 4 1 /4" MAX. SHIM SPACE - 5 1 /4' X 2-3/4" PFH ELCO OR ITW CONCRETE SCREW STEEL 6 # 10 x 2-1 /2" PFH WOOD SCREW 1.15" MIN. EMBEDMENT) STEEL 8 #9 x 3/4' PFH WOOD SCREW STEEL 9 DOOR SKIN MIN. 0.075" THICK FIBERGLASS 10 INSWING VINYL DOOR BOTTOM SWEEP BY ENDURA VINYL l0A VINYL DOOR BOTTOM SWEEP #3628 BY HOLM IND. VINYL 11 REINFORCEMENT WOOD FOR LOCK WOOD 12 FINGER JOINTED PINE JAMB WOOD 13 #9 x 2-1 /4" PFH WOOD SCREW STEEL 14 BOTTOM RAIL CELLULAR PVC 15 INSWING ADJUSTABLE THRESHOLD BY ENDURA ALUM. / WOOD 15A INSWING ADJUSTABLE ALUMINUM THRESHOLD BY DLP ALUM. / WOOD 16 FORCE 5 WEATHER STRIPPING BY ENDURA FOAM 16A COMPRESSION WEATHER STRIP QLON 650 BY SCHLEGEL FOAM 17 KWIKSET KEYED ENTRY - SIGNATURE SERIES STEEL 18 KWIKSET DEADBOLT - SIGNATURE SERIES 780) STEEL 20 POLYURETHANE FOAM BY NANYA POLYURETHANE 21 4" x 4" BUTT HINGE STEEL 23 POLY FIBER JAMB COMP. / VINYL 24 HINGE & LATCH STILE CELLULAR PVC 25 TOP RAIL CELLULAR PVC 26 DEADBOLT STRIKE PLATE STEEL 27 LATCH STRIKE PLATE STEEL 28 OUTSWING BUMP THRESHOLD ALUM. / WOOD 29 HINGE & LATCH STILE REINFORCEMENT LVL 30 1 /4" X 3-3/4" PFH ITW CONCRETE SCREW STEEL 31 #9 x 1" PFH WOOD SCREW STEEL 32 1 /4" x 3-1 /4" PFH ITW CONCRETE SCREW STEEL 33 3/16" X 3-1 /4" PFH ITW CONCRETE SCREW STEEL 40 DOOR PANEL - SEE DOOR PANEL DETAIL SHEET FOR CONSTRUCTION DETAILS - h c" 4.56" 1— 2.12" —► i I- 2.43' i2 JAMB 15A ADJUSTABLE /NSWING SILL `y .0 to to g' Rire O • LL rn o m jy`` Q V t2 j co m V 04 .. ,N v v 0 x Z Q N " >6 m c W ai a v 5 m do 0a 4.56' _ � � r> s m �V} m C oc c 6 O o c tli I- 2.43' -I vo Q� zo ww 23 PDLY FIBER JAMB o ji g� W �� m Q JR� U 0 D O o a a a Eo cli 4.56" cn (V SAWOWLIMWING SILL 28 OUTSWING BUMP THRESHOLD mIm 00 (oLo RR LU�Lu 00 a a DATE: 02/16/12 SCALE: N. T. S. DWG. BY: JK CHK. BY: LFS DRAWING NO.: FL-15213.1 SHEET 7 OF 7