HomeMy WebLinkAboutFL NOA 14608.4 Eastern FWREVISIONS
NOTES:
1. THE PRODUCT SHOWN HEREIN IS DESIGNED AND MANUFACTURED TO COMPLY WITH
REQUIREMENTS OF THE FLORIDA BUILDING CODE INCLUDING THE HVHZ.
2. WOOD FRAMING AND MASONRY OPENING TO BE DESIGNED AND ANCHORED TO PROPERLY
TRANSFER ALL LOADS TO STRUCTURE. FRAMING AND MASONRY OPENING IS THE
RESPONSIBILITY OF THE ARCHITECT OR ENGINEER OF RECORD.
3. 1 X BUCK OVER MASONRY/CONCRETE IS OPTIONAL.
4. WHERE SHIM OR BUCK THICKNESS IS LESS THAN 1 —1 /2" WINDOW UNITS MUST BE
ANCHORED THROUGH THE FRAME IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED
INSTALLATION INSTRUCTIONS. ANCHORS SHALL BE SECURELY FASTENED DIRECTLY INTO
MASONRY, CONCRETE OR OTHER STRUCTURAL SUBSTRATE MATERIAL.
5. WHERE WOOD BUCK THICKNESS IS 1-1/2" OR GREATER, BUCK SHALL BE SECURELY
FASTENED TO MASONRY, CONCRETE OR OTHER STRUCTURAL SUBSTRATE. WINDOW UNITS MAY
BE ANCHORED THROUGH FRAME TO SECURED WOOD BUCK IN ACCORDANCE WITH
MANUFACTURER'S PUBLISHED INSTALLATION INSTRUCTIONS.
6. WHERE 1 X BUCK IS NOT USED DISSIMILAR MATERIALS MUST BE SEPARATED WITH APPROVED
COATING OR MEMBRANE. SELECTION OF COATING OR MEMBRANE IS THE RESPONSIBILITY OF
THE ARCHITECT OR ENGINEER OF RECORD.
7. BUCKS SHALL EXTEND BEYOND WINDOW INTERIOR FACE SO THAT FULL FRAME SUPPORT IS
PROVIDED.
8. FOR FIN INSTALLATION SHIM AS NEEDED. FOR FRAME INSTALLATION SHIM AS REQUIRED AT
EACH ANCHOR LOCATION WITH LOAD BEARING SHIM. SHIM WHERE SPACE OF 1/16" OR
GREATER OCCURS. MAXIMUM ALLOWABLE SHIM STACK TO BE 1 /4".
9. SHIMS SHALL BE LOCATED, APPLIED AND MADE FROM MATERIALS AND THICKNESS CAPABLE
OF SUSTAINING APPLICABLE LOADS.
10. WIND LOAD DURATION FACTOR Cd-1.6 WAS USED FOR WOOD ANCHOR CALCULATIONS.
11. FRAME MATERIAL: EXTRUDED RIGID PVC.
12. UNITS MUST BE GLAZED PER ASTM E1300-04/09, SEE SHEET 6 FOR GLASS DETAILS.
13. APPROVED IMPACT PROTECTIVE SYSTEM IS NOT REQUIRED FOR THIS PRODUCT IN WIND
BORNE DEBRIS REGIONS.
14. FOR ANCHORING FIN INTO WOOD FRAMING OR 2X BUCK USE #8 WOOD SCREWS WITH
SUFFICIENT LENGTH TO ACHIEVE A 1 1 /4" MINIMUM EMBEDMENT INTO SUBSTRATE. LOCATE
ANCHORS AS SHOWN IN ELEVATIONS AND INSTALLATION DETAILS.
REV DESCRIPTION DATE APPROVED
A REMOVED FLUSH INSTALLATION 07/23/14 R.L.
B REVISED INSTALLATION DETAILS 06/23/15 R.L.
C REVISED GLASS DETAILS 08/20/19 R.L.
15. FOR ANCHORING FRAME INTO WOOD FRAMING OR 2X BUCK USE #14 WOOD SCREWS WITH
SUFFICIENT LENGTH TO ACHIEVE A 1 7/16" MINIMUM EMBEDMENT INTO SUBSTRATE. LOCATE
ANCHORS AS SHOWN IN ELEVATIONS AND INSTALLATION DETAILS.
16. FOR ANCHORING FRAME INTO MASONRY/CONCRETE USE 3/16" ELCO ULTRACON WITH
SUFFICIENT LENGTH TO ACHIEVE A 1 1 /4" MINIMUM EMBEDMENT INTO SUBSTRATE WITH 2''
MINIMUM EDGE DISTANCE. LOCATE ANCHORS AS SHOWN IN ELEVATIONS AND INSTALLATION
DETAILS.
17. FOR ANCHORING FRAME INTO METAL STRUCTURE USE #14 SMS OR SELF DRILLING SCREWS
WITH SUFFICIENT LENGTH TO ACHIEVE 3 THREADS MINIMUM BEYOND STRUCTURE INTERIOR
WALL. LOCATE ANCHORS AS SHOWN IN ELEVATIONS AND INSTALLATION DETAILS.
18. ALL FASTENERS TO BE CORROSION RESISTANT.
19. INSTALLATION ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH ANCHOR
MANUFACTURER'S INSTALLATION INSTRUCTIONS AND ANCHORS SHALL NOT BE USED IN
SUBSTRATES WITH STRENGTHS LESS THAN THE MINIMUM STRENGTH SPECIFIED BELOW:
A. WOOD - MINIMUM SPECIFIC GRAVITY OF G=0.42
B. CONCRETE MINIMUM COMPRESSIVE STRENGTH OF 3,192 PSI.
C. MASONRY STRENGTH CONFORMANCE TO ASTM C90, GRADE N, TYPE 1 (OR GREATER).
D. METAL STRUCTURE: STEEL 18GA, 33KS1 OR ALUMINUM 6063T5 .048" THICK MINIMUM
20. GEOMETRIC SHAPES ARE ALSO APPROVED. APPROVED GEOMETRIC SHAPES DIMENSIONS
SHALL NOT EXCEED INSCRIBED DIMENSIONS OF APPROVED RECTANGULAR ASSEMBLY SHOWN
IN SHEET 2. GEOMETRIC SHAPES ARE NOT LIMITED TO SHAPES SHOWN HEREIN.
I TABLE OF CONTENTS 1
SHEET NO.
1 NOTES
2 ELEVATIONS
3 5 INSTALLATION DETAILS
EASTERN
. RN AA DFIVISION OF
�L SYSTEMS
Eastern EASTERN METAL SUPPLY
16341 DOMESTIC AVE
A L LJ M I N lJ M A N Q V I N Y L FORT MYERS, FL 33912
600-432-2204
SERIES 176 PW FIXED WINDOW IMPACT HVHZ
72" X 63"
NOTES
DESCRIPTION DRAWN: DWG NO. REV
J. L. 1 08-02294 C
6 1 COMPONENTS AND GLAZING DETAILS
SCALE NITS I DATE 02/23/14 I SHEET 1 OF 6
L. ROBERTO LOMAS P.E.
1432 WOODFORD RD LEWISVILLE, NC 27023
434-688-0609 rllomasCa-)lrlomaspe.com
SIGNED: 0812812019
Luis R. Lomas P.E.
FL No.: 62514
WOOD FRAMING
OR 2X BUCK
BY OTHERS
APPROVED
SEALANT
BEHIND FLANGE
#14 WOOD
SCREW
C NTCQ I!l Q
APPROVED
SEALANT
BEHIND FLANGE
WOOD FRAMING
OR 2X BUCK
BY OTHERS
5/8" MIN.
EDGE DISTANCE
INTERIOR
5/8" MIN.
EDGE DISTANCE
VERTICAL CROSS SECTION
WOOD FRAMING OR 2X BUCK INSTALLATION
NOTES:
1. INTERIOR AND EXTERIOR FINISHES, BY OTHERS,
NOT SHOWN FOR CLARITY.
2. PERIMETER AND JOINT SEALANT BY OTHERS TO BE
DESIGNED IN ACCORDANCE WITH ASTM E2112
M ETAL
"
STRUCTURE
MIN.
OTHERS
VENTBY
lE
APPROVED
SEALANT
BEHIND FLANGE
CYTCQlnQ
WOOD
W
APPROVED
SEALANT
BEHIND FLANGE
1 /4" MAX
SHIM SPACE META
STRUCTUR
BY OTHER
" MIN
v1ENT
5/8" MIN.
EDGE DISTANCE
INTERIOR
REVISIONS
REV
DESCRIPTION
DATE APPROVED
A REMOVED
FLUSH INSTALLATION
07/23/14 R.L.
B REVISED
INSTALLATION DETAILS
06/23/15 R.L.
C REVISED
GLASS DETAILS
08/20/19 R.L.
METAL
1 /4" MAX.
STRUCTURE
SHIM SPACE
BY
OTHERS
#14
SMS OR
I E7 I
SELF
DRILLING
�E7
CIS OR
SCREWS
0
>RILLING
-�
IA/TCQIrIQ
#14 SMS OR
SELF DRILLING
SCREW
1 /4" MAX.
SHIM SPACE
5/8" MIN.
EDGE DISTANCE
APPROVED
SEALANT
BEHIND FLANGE
1 7/16" MIN.
EMBEDMENT
5/8" MIN.
EDGE DISTANCE
#14 WOOD
SCREW
WOOD FRAMING
OR 2X BUCK
BY OTHERS
CYTCQ Ir1 Q
JAMB INSTALLATION DETAIL
METAL STRUCTURE INSTALLATION
1 /4" MAX.
SHIM SPACE
CYTCQ In jD
JAMB INSTALLATION DETAIL
WOOD FRAMING OR 2X BUCK INSTALLATION
SIGNED: 0812812019
EASTERN ARCHITECTURAL SYSTEMS
5/8" MIN. sPRCHITECTUR , ,
EDGE DISTANCE J EaSern EASTERN METAL SUPPLY ;\, R . L 0 A ///
4 - 16341 DOMESTIC AVE .NN \ r r r • r ��/�
¢ ALLIMINLJM ANQ VINYL FORT MYERS, FL 33912 �+� L' �^,� •
VERTICAL CROSS SECTION `�� 600-432-2204 %'' y� s� •`�'
METAL STRUCTURE INSTALLATION SERIES 176 PW FIXED WINDOW IMPACT HVHZ*4-T?#;gO
72" X63"
INSTALLATION DETAILS 0F �'��
DRAWN: DWG N0. REV ��fi�.•0RlOt'
DATE 08 s02294 C sS10IVA1-
SCALE �aj���\
NITS 02/23/14 3 OF 6 /,116ti
L. ROBERTOLOMASP.E. Luis R. Lomas P.E.
1432 WOODFORD RD LEWISVILLE, NC 27023 F L No.: 62514
434-688-0609 rllomasglrlomaspe.com
APPROVED
SEALANT
BEHIND FLANGE
REVISIONS
CONCRETE/MASONRY
BY OTHERS
OPTIONAL IX BUCK
SEE NOTES 3-7 SHEET 1
APPI
SE
BEHIND F
APPROVED
SEALANT
BEHIND FLANGE
OPTIONAL IX BUCK
SEE NOTES 37 SHEET 1
CONCRETE/MASONRY
BY OTHERS
7" N A I K I
tUht UIJ HNl t
VERTICAL CROSS SECTION
CONCRETE/MASONRY INSTALLATION
REV DESCRIPTION
A REMOVED FLUSH INSTALLATION
B REVISED INSTALLATION DETAILS
MIN.
VIENT C REVISED GLASS DETAILS
1 1 /4" MIN
EMBEDMENT
CONCRETE/MASONRY
BY OTHERS
D
OPTIONAL 1 X BUCK a 1 /4" MAX.
SEE NOTES 37 SHEET 1 0 ° SHIM SPACE
D
D v
3/16" ELCO D�
ULTRACON
v
D
D v
D
DV Q
D
2
v
MIN. D
EDGE a
DISTANCE
D
v v
DATE APPROVED
07/23/14 R.L.
06/23/15 R.L.
08/20/19 R.L.
APPROVED EXTERIOR
SEALANT
BEHIND FLANGE
JAMB INSTALLATION DETAIL
CONCRETE/MASONRY INSTALLATION
NOTES:
1. INTERIOR AND EXTERIOR FINISHES, BY OTHERS,
NOT SHOWN FOR CLARITY.
2. PERIMETER AND JOINT SEALANT BY OTHERS TO BE
DESIGNED IN ACCORDANCE WITH ASTM E2112
EASTERN ARA DIVISION OF EASTERN SYSTEMS
��ern EASTERN METAL SUPPLY
16341 DOMESTIC AVE
A LL1MINlJM ANQ VINYL FORT MYERS, FL 33912
MIN. '��"� ���`• 600-432-2204
V1ENT SERIES 176 PW FIXED WINDOW IMPACT HVHZ
72" X 63"
INSTALLATION DETAILS
DRAWN: DWG NO.
J.L. 08-02294
SCALE NITS DATE 02/23/14 1 SHEET OF 6
L. ROBERTO LOMAS P.E.
1432 WOODFORD RD LEWISVILLE, NC 27023
434-688-0609 rllomasglrlomaspe.com
SIGNED: 0812812019
\ w ilII?////
'.�N \ F. L perz
• �fr
o ,
TAT of
4r
JEV��fi�.s �L0RID�:��`�=
Al -
Luis
R. Lomas P.E.
FL No.: 62514
REVISIONS
APPROVED
SEALANT
BEHIND FIN
#8 WOOD
SCREW
7/16" MII`
EDGE DISTAL
EXT
7/16" MIN
EDGE DISTANCE
#8 WOOD
SCREW
APPROVED
SEALANT
BEHIND FIN
VERTICAL CROSS SECTION
WOOD FRAMING OR 2X BUCK INSTALLATION
WOOD
FRAMING
BY OTHERS
1 /4" MAX.
SHIM SPACE
WOOD FHAM IIN
BY OTHEF
1
N
EMBE
#8 WC
SCR
APPRO�
SEALANI
BEHIND FIN
REV
DESCRIPTION
DATE
APPROVED
A
REMOVED FLUSH INSTALLATION
07/23/14
R.L.
B
REVISED INSTALLATION DETAILS
06/23/15
R.L.
C
REVISED GLASS DETAILS
08/20/19
R.L.
-1 1- 1 /4" MAX
yl rF cA I cnwn
7/16" MIN
EDGE DISTANCE
JAMB INSTALLATION DETAIL
WOOD FRAMING OR 2X BUCK INSTALLATION
1 /4" MAX NOTES:
SHIM SPACE 1. INTERIOR AND EXTERIOR FINISHES, BY OTHERS,
NOT SHOWN FOR CLARITY.
2. PERIMETER AND JOINT SEALANT BY OTHERS TO BE
DESIGNED IN ACCORDANCE WITH ASTM E2112
SIGNED: 08/28/2019
EASTERN ARCHITECTURAL SYSTEMS `5 +
WOOD EASTERNI EION OUPPLY `,\5`I II///
Eastertr \���5 R. L "
16341 DOMESTIC AVE \ , • • • `fJ
FRAMING .w LYMIHLJM rdo VINYL FORT MYERS, FL 33912 •
BY OTHERS _ ""'.o. '"'" oo a Arvo 000,.e
SERIES 176 PW FIXED WINDOW 21M1PA T HVHZ *■ ••�'G�Ns� +�ik r
C �5t
72" X 63" a.
FIN INSTALLATION DETAILS TAT OF :
DRAWN: DWG N0. REV fi �ZORM't' \C��
J.
L. E DATE 08 s02294 C DNAL•EaG��`
NITS 02/23/1 4 5 OF 6 1f IIILI