Manufacturer: Metal Sales Manufacturing Corporation
Product Name: 5V-Crimp
Panel Description: 24" wide coverage with (5) 1/2" high ribs
Materials: Min. 26 ga., 50 ksi steel. Galvanized coated steel (ASTM A653) or
Galvalume coated steel (ASTM A792) or painted steel (ASTM A755).
Deck Description: Min. 19/32" plywood or min. ¾" thick wood plank (min SG of 0.42)
for new and existing constructions. Designed by others and installed
as per FBC 2017.
Deck Attachment: 8d x 2.5" long ring shank nails or #8 x 2" long wood screws @ 6" o.c.
(Minimum) in the field and @ 4" o.c. at edges. Designed as per FBC 2017.
New Underlayment: Minimum underlayment as per FBC 2017 Section 1507.4.5.1.
Required for new construction and optional for reroofing construction.
Existing Underlayment: One layer of asphalt shingles over one layer of #30 felt. For reroofing
(Optional) construction only.
Slope: 1/2:12 or greater in accordance with FBC 2017 Section 1507.4.2.
Requires applied lap sealant for roof slopes less than 3:12.
Design Uplift Pressure: 41.6 psf @ fastener spacing of 36" o.c.
(Factor of Safety = 2) 74.8 psf @ fastener spacing of 16" o.c.
196.75 psf @ fastener spacing of 8" o.c.
Fastener Pattern:
Type: #9-16 or #10-14 hex head wood screws with sealed washer. Fastener
shall be of sufficient length to penetrate through the deck a minimum
of 3/8".
At panel ends @ 6" o.c. across panel width
At intermediate @ 12" o.c. across panel width
Test Standards: Roof assembly tested in accordance with TAS 125-03 ‘Standard
Requirements for Metal Roofing Systems’.
Code Compliance: The product described herein has demonstrated compliance with FBC
2017 Section 1507.4.
Product Limitations: Design wind loads shall be determined for each project in accordance
with FBC 2017 Section 1609 or ASCE 7-10 using allowable stress
design. The maximum support spacing listed herein shall not be
exceeded. This evaluation report is not applicable in High Velocity
FL 14645.3-R3
C2182-3
9.9.17
Page 3 of 3
Hurricane Zone. Fire classification is not within scope of this
Evaluation Report. Refer to FBC 2017 Section 1505 and current
approved roofing materials directory or ASTM E108/UL790 report
from an accredited laboratory for fire ratings of this product.
Supporting Documents: TAS 125 Test Reports
Farabaugh Engineering and Testing Inc
Project No. T181-05, Reporting Date 7/21/05 (Tests #1 & 2)
Project No. T240-09, Reporting Date 9/22/09
Architectural Testing, Inc. – West Palm Beach, FL
(Formerly Hurricane Test Laboratory, LLC)
Project No. 0103-0712-09, Reporting Date 9/1/09