FBC ENERGY CONSERVATION CODE
Duct Sealing Certification
Prescriptive and Performance Method
Dom; November21,2017
permat 1702-0500
("Lda-osoo
JAN _S018
ST. Lucie County, Permitting
Lott 11
Contractor. W W W Entetp&,es & Sons Inc
Add; 3521 Sunrise Blvd, Fort Pierce, FL 34982
Construction: !S Post Construction Test
rr Rough -in Test
Test Conditions:
Date: 11/21/17
Floor Area (ft2): 1144
Time: 3:00 P.M.
Primary Location of Supply Ductwork Attic
indoor Temperature (F): 79
Primary Location of Return Ductwork NIA
-Outdoor Temperature (F)- 77
Total Leakage Test (Outsidl
Duct Leakage: r Default ❑ Prop. Leak Free r3 Proposed On =
Test Pressure: 25 (Pa)
Baseline Duct Pressure (optional) wn
(Pa)
Duct Press. (Pa)
Flow Ring
Fan Press
Flow (dm)
Results:(A Pawl- ❑ Fail
Installed
Total Leakage (clm): 62 6
To Leakage per 100 spit 3-63
CRR5 x 100 divided by the CFA = Duct Leakage CFM/100 sgtt
24.9
74
53
s, a
25
74
562
52.s
25
74
562
57-6
Testing Company
Company Name: Ecolnnovative Address: 1734 SE Duma Ter, Port St Lucie, FL 34952
t hereby certfiy that the above Duct Sealing Leakage remits demonstrate compliance with. 5" Ediifoa FBG Energy Conservation requirements in accordance with
Section R403 .2.
Signature:
Printed Name: Kathleen Connolly LicenselCertificate #: 5060036