PLAN REVIEW
r
J JURISDICTION: St. Lucie County F.P.B. # 1033
OCCUPANCY: Trl - County Feeds BUILDING DEPT. NO: 98050008
ADDRESS: 5080 S. Federal NUMBER OF STORIES: One
CONTRACTOR: Matthew Woemmel Construction PHONE NO: (561)-595-0372
ARCHITECT/ENGINEER: John C Weber PHONE NO: (561)-229-2722
BUILDING OWNER:.Jaatnar, Inc. REVIEW DATE: 5-14-98 Revised 6-18-98
OCCUPANCY TYPE: Mercantile/Storage (S-1) AUTOMATIC SP'IKLRS: No
GROSS SQ FT: 6,000 sq ft. NET SQ FT: 2,400 Net Sales Area
OCCUPANT LOAD: Sales Only 2400/30= 80 persons BASED ON: 30 sq ft Per Person
CONSTRUCTION TYPE:( NFPA-220) Type: III - (200) SBCCI: Type: V - Unprotected
New Construction: X ` Automatic Sprinkler: Contractor:
Tenant Improvement: Fire Alarm System Contractor:
Shell Only: Fixed Fire Suppression: Contractor:
Addition: Hood & Duct'System: Contractor:
Renovation: Fuel Storage: Contractor:
1. All revisions must be in compliance before the final inspection, or so noted.
- 2. The Fire Marshal requires 24 hr. notice on all inspections.
3.. The Building Departments schedule all final inspections by the Fire Marshal.
4. A copy of the. required revisions has been mailed to the Architect: _ Contractor: _ Yes: _ No: _X_
Required Revisions:
1. This building has total area is 6,000 sq ft of which 3240 sq ft is storage S-1. This
- — requires compliance to the Standard Building Code for a mixed occupancy.
2. S -1 Storage to Mercantile requires a 2 hour occupancy separation wall which is
indicated. A 8 inch concrete block is considered a '2 hour rated assembly. And shall extend from
the floor to the underside of the roof deck.
3. All openings in this rated wall shall be protected with a Class B, 1-1/2 hour rated door
and jamb assembly. The window opening as indicated from the storage to the office must also
be protected with fire rated opening protection, which must be either a rolling steel fire shutter,
horizontal or vertical sliding fire door rated for a minimum of one and one-half hours.
4. The required rated doors cannot be a double action swing type these door must be
provided with a latching device listed for the door assembly:
5. Both pairs of.doors in the sales room must swing in the direction of exit access when
servin an occupant load in excess of 50 persons.
r a
Tri - County Feeds
May-1.4, 1998
Page 2.
6. The A/C units are serving a space is less than 25,000 cubic feet and shall be provided
with automatic fan shut down controls by means of a firestat installed in the return air of both
units.
7. Provide a 2A - IOBC rated multi -purpose fire extinguisher for the storage area and sales
areas. In addition a listed 2A, pressurized water extinguisher shall be provide for each 50 ft of
travel distance. I suggest that a 3/4 inch minimum hose bib and hose be provides for both the
sales and storage iareas for Class A type fires.
Rev awed By:, Date: May 14, 1998
John K. Hayde Revised June 18, 1997