Loading...
HomeMy WebLinkAboutFire District Plan ReviewST. LUCIE COUNTY FIRE DISTRICT ._ BUREAU OF FIRE PREVENTION P.O. BOX 3030 TELEPHONE (561)-462-2312 . FT. PIERCE FL. 34948-3030 FAX NO. (561)-462-2323 2400 RHODE ISLAND AVE. FT. PIERCE FL. 34950 PLAN REVIEW r J JURISDICTION: St. Lucie County F.P.B. # 1033 OCCUPANCY: Trl - County Feeds BUILDING DEPT. NO: 98050008 ADDRESS: 5080 S. Federal NUMBER OF STORIES: One CONTRACTOR: Matthew Woemmel Construction PHONE NO: (561)-595-0372 ARCHITECT/ENGINEER: John C Weber PHONE NO: (561)-229-2722 BUILDING OWNER:.Jaatnar, Inc. REVIEW DATE: 5-14-98 Revised 6-18-98 OCCUPANCY TYPE: Mercantile/Storage (S-1) AUTOMATIC SP'IKLRS: No GROSS SQ FT: 6,000 sq ft. NET SQ FT: 2,400 Net Sales Area OCCUPANT LOAD: Sales Only 2400/30= 80 persons BASED ON: 30 sq ft Per Person CONSTRUCTION TYPE:( NFPA-220) Type: III - (200) SBCCI: Type: V - Unprotected New Construction: X ` Automatic Sprinkler: Contractor: Tenant Improvement: Fire Alarm System Contractor: Shell Only: Fixed Fire Suppression: Contractor: Addition: Hood & Duct'System: Contractor: Renovation: Fuel Storage: Contractor: 1. All revisions must be in compliance before the final inspection, or so noted. - 2. The Fire Marshal requires 24 hr. notice on all inspections. 3.. The Building Departments schedule all final inspections by the Fire Marshal. 4. A copy of the. required revisions has been mailed to the Architect: _ Contractor: _ Yes: _ No: _X_ Required Revisions: 1. This building has total area is 6,000 sq ft of which 3240 sq ft is storage S-1. This - — requires compliance to the Standard Building Code for a mixed occupancy. 2. S -1 Storage to Mercantile requires a 2 hour occupancy separation wall which is indicated. A 8 inch concrete block is considered a '2 hour rated assembly. And shall extend from the floor to the underside of the roof deck. 3. All openings in this rated wall shall be protected with a Class B, 1-1/2 hour rated door and jamb assembly. The window opening as indicated from the storage to the office must also be protected with fire rated opening protection, which must be either a rolling steel fire shutter, horizontal or vertical sliding fire door rated for a minimum of one and one-half hours. 4. The required rated doors cannot be a double action swing type these door must be provided with a latching device listed for the door assembly: 5. Both pairs of.doors in the sales room must swing in the direction of exit access when servin an occupant load in excess of 50 persons. r a Tri - County Feeds May-1.4, 1998 Page 2. 6. The A/C units are serving a space is less than 25,000 cubic feet and shall be provided with automatic fan shut down controls by means of a firestat installed in the return air of both units. 7. Provide a 2A - IOBC rated multi -purpose fire extinguisher for the storage area and sales areas. In addition a listed 2A, pressurized water extinguisher shall be provide for each 50 ft of travel distance. I suggest that a 3/4 inch minimum hose bib and hose be provides for both the sales and storage iareas for Class A type fires. Rev awed By:, Date: May 14, 1998 John K. Hayde Revised June 18, 1997