HomeMy WebLinkAboutTrussThe Architect's or Architect's representative's shopdrawing approval is NOT a • "double check" of the contractor. -a - The contractor shelf remain responsible It TRUSSES FOR THE 'FIRST MODEL ` HPULD BE SHIPPED AND SUCCESSFULLY SET BEFORE ANY MORE TRUSSES ARE BUILT' FOR T-IAT MODEL. t°rrconsruction measurements Architect's approval covers general roof shape, A ARRANGE WITH CRANE OPERATOR IN ADVANCE FOR A SPREADER BAR OF 18' 24' IN LENGTH review oftruss strapping, and loading on Do not stand on trusses until they are braced per BCSI & properly nailed to straps & hangers - 30' Span or less 30' to 60' Span Spreader Bar I AI 0 degrees or less A— 1 /2 —�. ag , _ Appr. 2/3 to _� TfgLine Span approx. one /2 of span REFER TO BCSI REFER TO BCSI Truss must be set this way if crane used. Truss must be set this truss Y if crane used truss ma y not. match. This is an example, Y exam is ur truss may not match. T V L _ C L mss is an P • Ya Y Insist crone operator sets truss this way. Insist crane operator sets truss this way. MULTIPLE PLY TRUSSES MUST BE ASTENED TOGETHER PER ENGINEERING BEFORE SETTING. REFER TO 14 -_- 22' 11 2r 14' ENGINEERING DRAWING TO DETERMINE— I I I I 1 ® IF MULTIPLE PLY. All SEAT PLATES BY CHAMBERS 12 4.00 r- 2 2.00 8— /h upset--1/4" heel=315/16" PLUMB CUT END 2 x 4 Top Chord WALL HEIGHT 8' END DETAIL: TYPICAL VAULT 12 4.00 I— to 16.1 co 1' upset=1/4" heel=315/16" PLUMB CUT END 2 x 4 Top Chord WALL HEIGHT 8' TYPICAL END DETAIL p Mimi= VA Irzall10=1I �lV, 010%,i !lI.%Ia/�17/////lIrt/�ili���li//iIWIT , 0. i ®% �® / 00 100010A OEM 1 1 ' ' Is I PopG INVERTE 10P000,0 a�. �. ,,, ,. ..LOADS • • -% ® 10000 1 1ATA ® yATB 1 1 _ATA IN Our 1 ' �IMI1111�11��I111�11�■I���IIIIII� : /�,,� 1st 1, ► r '/ 1 I 1• 1 ��11®ICI®ICI®I�I�II®ill®I®I®ICI®I®I- Bo Be C4 C4 f , a v I I I ME i i k INN ../�_hom h=0�_ 1 I1 1 a 1 8 •� /I�I��IN''" I■�II�IOII..��`�'�11®111�I®I\ ' ° • �\ a� IBM \`�`��.•i\\\\A\II`\\\`\ � `\II"\`II\,\. "\ 1Ni`\`�11 ®I�I�I�I�I�I�I�BIf�1111�I�I�IB�1�1�1�11►1 structure from gravity and uplift loads and 9 Y P their res ive locations. Approved Date. Braden 2, Sr=den A.I.A. F.A. FABRICATION AGREEMENT' TRUSSES CANNOT 6E STARTED UNTIL THIS AGREEMENT la SIGNED & RETURNED The legal description of the property where the trusses will be installed Is; .The undersigned acknowledges and agrees: 1,,Trusses will be made In strict accordance with this truss placement diagram layout, which is the sole authodry for determining. successful fabrication of the trusses. 2, All dimensions In this layout have been verified by the undersigned. .3. Unless written notice Is provided by certified mall to Chambers Truss within tan (10) days of delivery the undersigned agrees that no baekcharges will be allowed. In the event such written notice Is furnished Chambers Truss shall have three (3) buyiness days in which - to begin repairs required, or to substitute other trusses, at Chambers option.' 4. The undersigned acknowledges receipt of "SCSI "3' summary sheet by •rpi & wrCA, S. Delivery Is to Job site. It is the buyers'responsiblliry to make the Job site suitable for bars Tmu has the sole authority i da1Ne .Chem od to determine the suitability of b H m he o site only, , ry J f job site fordelive , Chambers responsible or onion o the Truss will be re / dum dative p p oiv Tha boyar Is responsible for additional delivery expenses it Chambers Truss has to redeliver because Job site Is not prepared for delivery or buyer Is not prepared for delivery of trusses. Suyer Is responsible to Chambers Trues for towing caste due to she conditions. - o. Price as shown In paragraph 7 below is subject to change If any changes are, made in this .lo look A $50 per hour fee for revisions maybe charged by Chambers Truss. ' .7: This is a PURCHASE ORDER to Chambers, Truss of the sum agreed to, or If nil agreement a reasonable price. Involoo will be made on delivery and paid within terms of net oo delivery. Invoice may, be made at scheduled date of delivery If buyer cannot accept delivery of fabricated trusses. The undersigned agrees to pay Chambem.Truss masonabld shomeys fee for collections In event of payment not timely made. 1.12 'h, per month service charge will be added for all sums not paidwithln terms. . a. Signature or Initials anywhere on this sheet constitutes agreement to all terns herein. 9,'in consideration of Chambers Truss extending credit for this material the undersigned unconditionally guarantees payment when due of any and all Indebtedness owed to Chambers Truss by any entity receiving material and the undersigned agrees to pay such Indebtedness Including attorneys tees, If default In payment for material be made by the recipient.- 1. 10. in the event of any litigation concerning this agreement, the Items furnished hereunder or payments referred to herein, the. parties agree that the sole venue (or any such action will be Saint Wole County, Florida. 11. Design responsibilities are per -National Standard And Recommended Guidelines On Responsibilities For Construction Using Metal Plate Connected Wood Trusses ANSVTPVWTCA 4 - 2002- DATED ..-'"II SIGNED FOR TITLE --.-, Aspmderbarmaybemgt{ Wper'BCSi1.03"tDpvmtk4uy&damage.. Multiple ply trusses must be fastened togethar per enginee ring before they are set; failure to do so can result in roof collapse. temporary and permanent bracing are required and can save life and property and is the responslbiilty of the truss erector. `Study the contents of the Information packet Included on delivery before sotting trusses. Trussas must ba setand braced por design to Wmrit injury 8, damage. Trusses must be set plumb and square Do riot bunks or stack of plywood, roofing material or any other co'nt:entrated loads on trusses, this can house collapse. b0 NOT SET TRUSSES USING THIS LAYOUT USE LAYOUT DELIVERED WITH TRUSSES TO SET TRUSSES CLAMBERS TRUSS INC 3.105 Oleander Avenue Fort Plercei Florida 34982-6423 800-551-5932 Fort Pierce 772-466-2012 Fax 772-"5.8711 Vero Beach 772-569.2012 Stuart 772-2863302 fLE�IEWED FOR %ODE COMPLIANCE: fir• LUCIE COUNTY 92.0/93.2 MITEK 4.2 D^^^ DESIGN CRITERIA County SAINT LUCIE Building Department ST LUCIE COUNTY Wind Design Criteria ASCE 7-2010 Wind Design Method MWFRS/C-C hybrid Wind ASCE 7-10 Roofing Material Shingle or Shake Loading in PSF Roof R.D.L. T Top Chord Live 20 2, Top Chord Dead 7 4.2 y o Bottom Chord Live 10 Non -Concurrent £I w `I Bottom Chord Dead 10 3 0 = TOTAL Load 37 7.2 .` fillDuration Factor 1.25 10 2 3 I Wind Speed 165mph i 0, Top Chord C.B. Sheeting by builder. `—° Bottom Chord C.B. Sheeting by builder. N N Highest Mean Height 12'-0" Building Type ENCLOSED Building Category II:Non Restrictive Exposure Category C Barrier Island No Conforms to FBC 2017 mi.u.l_.=mesirainm ueaO Loau t,.n.=l,onunuous 13racin Verify DESIGN CRITERIA shown above with the building department and your engineer. Design Criteria is the responsibility of the Building Designer and/or Engineer of Record. Chambers Truss Inc. Drawing Name: M11412 I ® 1 Li� Scale: 1 /4 = 1' �- F 73 total trusses, 18 different trusses. MI 41: RLC ACAD: RLC Reviewed By: Y C Date:11/14/16 Revised:10/23118 FC)R INDICATES LOAD BEARING I x REQUIRED BY TRUSSES WYNNE DEVELOPMENT CORP. SUPPLIED BY BUILDER 15'-10" 5' 4" 3' 4" 11'-6" 11'-6" 3 �• 5 4n 15.10" ATAHEIGHT OFS'-0" e ' DESCRIPTION: ABOVE FINISHED FLOOR GARAGE GARAGERIGHT STERLING PAGE 1 of 1 CUSTOMER INITIALS EACH PAGE —7?0a 1 4O T®1 10C% rll"]AIAIIAIf-%0 ABC AT'TAtLJCrI -rf-% If A%ir,i i-r KAIol oll A 4 f) MiTek"' RE: M11412 MiTek USA, Inc. CARLTON 299 6904 Parke East Blvd. Tampa, FL 33610-4115 Site Information: Customer: Wynne Development Corp Project Name: M11412 Lot/Block: Model: Sterling Address: unknown Subdivision: City: St Lucie County State: FL General Truss Engineering Criteria & Design Loads (Individual Truss Design Drawings Show Special Loading Conditions): Design Code: FBC2017/TP12014 Design Program: MiTek 20/20 8.1 Wind Code: ASCE 7-10 Wind Speed: 165 mph Roof Load: 37.0 psf Floor Load: N/A psf This package includes 18 individual, dated Truss Design Drawings and 0 Additional Drawings. With my seal affixed to this sheet, I hereby certify that I am the Truss Design Engineer and this index sheet conforms to 61 G15-31.003, section 5 of the Florida Board of Professional Engineers Rules. No. Seal# Truss Name Date 1 2 T19884578 T19884579 A Al 9/23/2020 9/23/2020 LE 3 T19884580 A2 9/23/2020 Py 4 T19884581 A3 9/23/2020 5 T19884582 A4 9/23/2020 6 T19884583 A5 9/23/2020 7 T19884584 ATA 9/23/2020 8 9 T19884585 T19884586 ATB ATC 9/23/2020 9/23/2020 REVIEWED FOR 10 T1988458 BHA 9/23/2020 D COMPLIANCE COMPLIANCE 11 T19884588 GRA 9/23/2020 12 T19884589 J2 9/23/2020 T. LUCIE COUNTY 13 T19884590 J4 9/23/2020 i 14 T19884591 J6 9/23/2020 R C M 15 T19884592 J8 9/23/2020 16 T19884593 JA8 9/23/2020 17 T19884594 KJ8 9/23/2020 18 T19884595 KJA8 9/23/2020 This item has been electronically signed and sealed by Velez, Joaquin using a Digital Signature. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies The truss drawing(s) referenced above have been prepared by MiTek USA, Inc under my direct supervision ����� based on the parameters provided by Chambers Truss. `��%.%`QU I N Truss Design Engineer's Name: Velez, Joaquin :�� �..G E IV My license renewal date for the state,of Florida is February 28, 2021. Florida COA: 6634 No 68182 IMPORTANT NOTE: The seal on these truss component designs is a certification that the engineer named is licensed in the jurisdiction(s) identified and that the designs comply with ANSUTPI 1. These designs are based upon parameters shown (e.g., loads, supports, dimensions, shapes and design codes), which were given to MiTek. Any project specific information included is for MiTek customers file reference purpose only, and was not taken into account in the preparation of these designs. MiTek has not independently verified the applicability of the design parameters or the designs for any particular building. Before use, the building designer should verify applicability of design parameters and properly incorporate these designs into the overall building design per ANSI/TPI 1, Chapter 2. --P:, STATE OF .:�� 1 0 N A E�o%' Joaquin Velez PE No.68182 MiTek USA, Inc. FL Cert 6634 6904 Parke East Blvd. Tampa FL 33610 September 23, 2020 1 of 1 Velez, Joaquin Jqb Truss Truss Type City Ply CA 299 T19884578 M11412 A SPECIAL 1 1 Job Reference o tional Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Fri Apr 3 07:64:31 2020 Page 1 • ID:kFvnsnOwY419Zh0_nM3lc6ylJ9g-bgjwittv1 KUZt7bCCap4tgORA6ecgfnWOUJ2SHzUUjs 1-0-0 8-6-0 8-10-0 13-8-0 19-5 3 26-2-0 28-9' 36-0-0 0-0 8-6-0 1 4-0 3-10-0 5-9-3 6-8-13 2-7 4 7-2-12 5x8 = 4x5 = 4.00 12 3x6 \\ 3 4 24 255 �1 5x12 MT18HS = 4x6 = 4x5 = 6 7 26 27 8 3x4 16 15 4x4 = 3x4 3x6 = 3x4 = 5x8 = 2.00 12 36-0-0 4x10 Scale=1:63.0 LOADING (psf) TCLL 20.0 TCDL 7.0 BCLL 0.0 BCDL 10.0 SPACING- 2-0-0 Plate Grip DOL 1.25 Lumber DOL 1.25 Rep Stress Incr YES Code FBC2017rrP12014 CSI. TC 0.94 BC 0.94 WB 0.91 Matrix -MS DEFL. Vert(LL) Vert(CT) Horz(CT) Wind(LL) in (loc) I/deft Ud -0.73 13-14 >595 360 -1.34 13-14 >321 240 0.45 10 n/a n/a 1.01 13-14 >428 240 PLATES MT20 MT18HS Weight: 161 lb GRIP 244/190 244/190 FT = 20% LUMBER- BRACING - TOP CHORD 2x4 SP M 30 *Except' TOP CHORD Structural wood sheathing directly applied. 6-8: 2x4 SP M 31 BOT CHORD Rigid ceiling directly applied or 2-2-0 oc bracing. BOT CHORD 2x4 SP M 30 WEBS 2x4 SP No.3 REACTIONS. (lb/size) 2=1386/0-8-0, 10=1386/0-8-0 Max Harz 2=-119(LC 10) Max Uplift 2=-846(LC 12). 10=-846(LC 12) FORCES. (lb) -Max. Comp./Max. Ten. -All farces 250 (lb) or less except when shown. TOP CHORD 2-3=-3338/2212, 34=3134/2132, 4-5=-3441/2388, 5-7=-5141/3470, 7-8=-6766/4392, 8-9=5629/3608, 9-10=-5945/3856 BOT CHORD 2-16=-1989/3129,15-16=-1777/2918,14-15=-2177/3455,13-14=-3307/5216, 12-13=-3301/5421, 10-12=-3593/5659 WEBS 3-16=-527/480, 4-16=413/669, 4-15=-535/785, 5-15=-975/733, 5-14=-1198/1876, 7-14=-851/667, 7-13=-962/1695, 8-13=-1260/1909, 8-12=45/349, 9-12=-319/328 NOTES - I) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=12ft; B=59ft; L=36ft; eave=5ft; Cat. II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-0-0 to 2-7-3, Intedor(1) 2-7-3 to 37-0-0 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) Provide adequate drainage to prevent water ponding. 4) All plates are MT20 plates unless otherwise indicated. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. This item has been 6) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide electronically signed and Will fit between the bottom chord and any other members. Sealed by Velez, Joaquin, PE 7) Bearing atjoint(s) 10 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should verify using a Digital Signature. capacity of bearing surface. 8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 846 lb uplift at joint 2 and 846 lb uplift at Printed copies of this joint 10. document are not considered signed and sealed and the signature must be verified on any electronic copies. Joaquin Velez PE No.68182 MiTek USA, Inc. FL Cart 6634 6904 Parke East Blvd. Tampa FL 33610 Date: April 3,2020 ®WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE Mll-7473 rev. 5/19/2020 BEFORE USE. Design valid for use only with MTek® connectors. This design Is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall p� building design. Bracing Indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek* Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the fabrication. storage, delivery, erection and bracing of trusses and truss systems, see ANS11TPI1 Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd. Saletylnformaffon available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610 J0 Truss Truss Type City Ply CAR 299 T19884579 M11412 Al SPECIAL 1 1 Job Reference (optional) Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Fri Apr 3 07:54:32 2020 Page 1 1 ID:kFvnsnOwY419Zh0_nM3lc6ylJ9g-30HIwDuXoecQVHAOmIKJQtZh2W_oZCcfd83c?jzUUjr 1-0-0 8-6-0 11-10-0 18-7-4 24-2-0 28.9 4 _ 36-0-0 17-0-Q 10 0 8-6-0 3 4-0 6-9-4 5 6-12 4-7-0 7-2-12 -0-0 Scale = 1:63.0 �1 6 3x6 = 4.00 12 5x6 = 4 22 3x8 = 5x6 = 5 23 6 14 13 3x4 II — 3x4 = 5x6 = 2.00 12 4x10 8-6-0 13-8-0 18-7 4 24 6-0 28-9 4 36-0-0 8-6-0 5-2-0 4-11-4 5-10-12 4-3-4 7-2-12 Plate Offsets (X,Y)— [2:0-0-2,Edge], [8:0-2-10,Edge] [13:0-3-0,0-3-0] LOADING (psf) SPACING- 2-0-0 CSI. DEFL. in (loc) I/deft L/d PLATES GRIP TCLL 20.0 Plate Grip DOL 1.25 TC 0.61 Vert(LL) -0.58 11 >749 360 MT20 244/190 TCDL 7.0 Lumber DOL 1.25 BC 0.95 Vert(CT) -1.07 11-12 >402 240 MT18HS 244/190 BCLL 0.0 Rep Stress Incr YES WB 0.55 Horz(CT) 0.40 8 n/a n/a BCDL 10.0 Code FBC2017/TPI2014 Matrix -MS Wind(LL) 0.80 11 >541 240 Weight: 163 lb FT = 20% LUMBER- BRACING - TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 2-7-2 oc purlins. BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 2-2-0 oc bracing. WEBS 2x4 SP No.3 WEBS 1 Row at midpt 5-13 REACTIONS. (lb/size) 2=1386/0-8-0, 8=1386/0-8-0 Max Horz 2=441(LC 10) Max Uplift 2=-846(LC 12), 8=-846(LC 12) FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown. TOP CHORD 2-3=-3356/2159, 3-4=-3358/2292, 4-5=-2798/1921, 5-6=-4830/3137, 6-7=-5353/3403, 7-8=-5962/3751 BOT CHORD 2-14=-1935/3141,13-14=-1610/2666,12-13=-2399/3926,11-12=-2400/3924, 10-1 1=-3499/5680, 8-10=-3492/5669 WEBS 3-14=-404/391, 4-14=-507/777, 4-13=451/409, 5-13=-13761890, 5-11=-557/1048, 6-11 =-849/1449, 7-11 =-641/463 NOTES- 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=12ft; B=59ft; L=36ft; eave=5ft; Cat. 11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extef or(2) -1-0-0 to 2-7-3, Interior(1) 2-7-3 to 37-0-0 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) Provide adequate drainage to prevent water ponding. 4) All plates are MT20 plates unless otherwise indicated. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. ' This item has been 6) This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. electronically signed and 7) Bearing atjoint(s) 8 considers parallel to grain value using ANSIfrPI 1 angle to grain formula. Building designer should verify sealed by Velez, Joaquin, PE capacity of bearing surface. using a Digital Signature. 8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 846 lb uplift at joint 2 and 846 lb uplift at Printed copies of this p joint 8. document are not considered signed and sealed and the signature must be verified on any electronic copies. Joaquin Velez PE No.68182 MiTek USA, Inc. FL Cart 6634 6904 Parke East Blvd. Tampa FL 33810 Date: April 3,2020 ®WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5119/2020 BEFORE USE. Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and Is for an Individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and property Incorporate this design into the overall building design. Bracing indicated is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek• is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANS11TP/1 Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd. Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610 Jqb Truss Truss Type Oty Ply CARLTON 299 ' T19884580 M11412 A2 SPECIAL 1 1 Job Reference (optional) Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 11 2018 MiTek Industries, Inc. Fri Apr 3 07:54:34 2020 Page 1 I D: kFvnsnOwY419ZhO_nM3l c6ylJ9g-?PO3LvwoKFs7kaKntjNnV l e l5JfN 13Sy4SYi3czUUjp -1-0-0, 8-6-0 13-10-0 18-0-0 i 22-2-0 24-M 28-9-4 36-0-0 $7-0-Q -0-0 8 6-0 5-0-0 4-2-0 4-2-0 2-4-0 4-3 4 7-2-12-0-0' 4.00 5x6 = 3x4 = 5x6 = 5 6 4x6 15 14 7x8 MT18HS = 3x6 = 3x4 II 5x8 = 2.00 12 Scale = 1:63.0 410 zz Plate Offsets (X,Y)— [2:0-0-6,Edge), [9:0-2-10,Edge) LOADING (psi) SPACING- 2-0-0 CSI. DEFL. in (loc) I/deft Ud PLATES GRIP TCLL 20.0 Plate Grip DOL 1.25 TC 0.58 Vert(LL) -0.55 11-12 >779 360 MT20 244/190 TCDL 7.0 Lumber DOL 1.25 BC 0.94 Vert(CT) -1.03 11-12 >419 240 MT18HS 244/190 BCLL 0.0 Rep Stress Incr YES WB 0.72 Horz(CT) 0.39 9 n/a n/a BCDL 10.0 Code FBC2017/rP12014 Matrix -MS Wind(LL) 0.77 11-12 >564 240 Weight: 167 lb FT = 20% LUMBER- BRACING - TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 2-7-0 oc puriins. BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 2-2-0 oc bracing. WEBS 2x4 SP No.3 REACTIONS. (lb/size) 2=1386/0-8-0, 9=1386/0-8-0 Max Horz 2=163(LC 11) Max Uplift 2=-846(LC 12), 9=-846(LC 12) FORCES. (Ib) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown. TOP CHORD 2-3=3359/2129, 3-4=-2661/1761, 4-5=-2445H690, 5-6=-3533/2289, 6-7=-3698/2365, 7-8=5359/3351, 8-9=-5963/3683 BOT CHORD 2-15=1909/3146, 14-15=-1909/3146, 13-14=-1826/3099, 12-13=-3016/5125, 11-12=-3433/5679,9-11=-3426/5669 WEBS 3-15=0/295, 3-14=-807/566, 4-14=-354/620, 5-14=-916/581, 5-13=-261/668, 6-13=-588/1003, 7-13=-2219/1408, 7-12=-1137/1893, B-12=-628/443 NOTES- 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=12ft; B=59ft; L=36ft; eave=5ft; Cat. 11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-0-0 to 2-7-3, Interior(1) 2-7-3 to 37-0-0 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) Provide adequate drainage to prevent water ponding. 4) All plates are MT20 plates unless otherwise indicated. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. ' This item has been 6) This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. electronically Signed and 7) Bearing atjoint(s) 9 considers parallel to grain value using ANSUTPI 1 angle to grain formula. Building designer should verify sealed by Velez, Joaquin, PE capacity of bearing surface. using a Digital Signature. 8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 846 lb uplift at joint 2 and 846 lb uplift at Printed copies of this joint 9. document are not considered signed and sealed and the signature must be verified on any electronic copies. Joaquin Velez PE No.68182 MiTek USA, Inc. FL Cart 6834 6904 Parke East Blvd. Tampa FL 33610 Date: April 3,2020 ®WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE Mll-7473 rev. 5119/2020 BEFORE USE. Design valid for use only with MiTek® connectors. This design Is based only upon parameters shown, and Is for an individual building component, not �� a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall ITS[ building design. Bracing indicated is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing ItllT ek• Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANS11TPll Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd. Safety Information avallable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610 Jrb Truss Truss Type Qty Ply CARLTON 299 ' T19884581 M11412 A3 SPECIAL 1 1 Job Reference (optional) Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Fri Apr 3 07:54:35 2020 Page 1 ID:kFvnsnOwY419Zh0_nM3Ic6ylJ9g-TbyRYExQ5Z_MkvzRQu01 WBD5j?emVO6J6HGb2zUUjo �1-0-q 8-6-0 15-10-0 20-2-0 24.6-0 28-9� %'_0 a7-0-Q 1-0-0' 8-6-0 7 4-0 4-4-0 4.4-0 4-3 4 7-2-12 -0-0 �1 4.00 12 5x6 = 5x6 = Scale: 3/16"=1' 15 „ 3x5 = 3x4 II 5x6 = 4x10 = 2.00 12 LOADING (psf) TCLL 20.0 TCDL 7.0 BCLL 0.0 BCDL 10.0 SPACING- 2-0-0 Plate Grip DOL 1.25 Lumber DOL 1.25 Rep Stress Incr YES Code FBC2017frP12014 CSI. TC 0.56 BC 0.94 WB 0.74 Matrix -MS DEFL. Vert(LL) Vert(CT) Horz(CT) Wind(LL) in (loc) I/deft Ud -0.57 11-12 >761 360 -1.05 11-12 >410 240 0.40 9 n/a n/a 0.78 11-12 >551 240 PLATES MT20 MT18HS Weight: 167 lb GRIP 244/190 244/190 FT = 20% LUMBER- BRACING - TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 2-6-15 oc purlins. BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 2-2-0 oc bracing. WEBS 2x4 SP No.3 WEBS 1 Row at midpt 6-13 OTHERS 2x4 SP No.3 REACTIONS. (lb/size) 2=1386/0-8-0, 9=1386/0-8-0 Max Horz 2=185(LC 11) Max Uplift 2=-846(LC 12), 9=-846(LC 12) FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (Ib) or less except when shown. TOP CHORD 2-3=3371/2103, 3-4=-2633/1707, 4-5=-2803/1850, 5-6=-2968/1899, 6-8=-5371/3290, 8-9=5960/3616 BOT CHORD 2-15=-1886/3159,14-15=-1886/3153,13-14=-1343/2432,12-13=-2958/5146, 11-12=-3368/5675, 9-11=-336215666 WEBS 3-15=0/306, 3-14=-866/626, 4-13=-285/671, 5-13=-379/702, 6-13=-2706/1659, 6-12=-1094/1946, 8-12=-611/435 0 '1° 0 NOTES- 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=12ft; B=59ft; L=36ft; eave=5ft; Cat. II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-0-0 to 2-7-3, Interior(1) 2-7-3 to 37-0-0 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) Provide adequate drainage to prevent water ponding. 4) All plates are MT20 plates unless otherwise indicated. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. This item has been 6) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide electronically signed and will fit between the bottom chord and any other members. Sealed by Velez, Joaquin, PE 7) Bearing atjoint(s) 9 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should verify Digital Signature. ususing Di a using Di capacity of bearing surface. 8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 846 lb uplift at joint 2 and 846 lb uplift at copies Ot this p joint 9. document are not considered signed and sealed and the signature must be verified on any electronic copies. Joaquin Velez PE No.68182 MiTek USA, Inc. FL Cert 6634 6904 Parke East Blvd. Tampa FL 33610 Date: April 3,2020 ® WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5119/2020 BEFORE USE. Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and Is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design Into the overall my buildbuilding design. Bracing Indicated is to prevent buckling of individual truss web and/or chard members only. Additional temporary and permanent bracing MiTek• ing required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSIITP11 Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd. Safety information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610 Job Truss Truss Type Ply CARLTON 299 T19884582 M11412 A4 SPECIAL �Qty 1 1 Job Reference (optional) Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Fri Apr 3 07:54:36 2020 Page 1 f ID:kFvnsnOwY419Zh0_nM3lc6ylJ9g-xoWpmax2st6rzuU978PFaBNK7LxVvOFYmlp8UzUUjn -�1-0-0, 8-6-0 13-8-0 18-0-0 24.6-0 28-9<1 36-0-0 i 000' 8.6-0 5-2-0 4-4-0 6-6-0 4-3-4 7-2-12 -0-0 3x5 = 4.00 12 5x6 = 16 15 3x12 3x4 II 5x8 = 2.00 12 Scale: 3/16"=1' 4x10 = 8-6-0 13 8-0 18-0-0 24 6-0 28-9 4 36 0-0 8.6-0 5-2-0 4-4-0 6-6-0 4-3-4 7-2-12 Plate Offsets (X,Y)— [2:0-1-2,Edgej, [8:0-3-0,Edge), [10:0-2-10,Edge), [15:0-2-12,0-3-01 LOADING (psf) SPACING- 2-0-0 CSI. DEFL. in (loc) I/clef! Ud PLATES GRIP TCLL 20.0 Plate Grip DOL 1.25 TC 0.60 Vert(LL) -0.61 13 >709 360 MT20 244/190 TCDL 7.0 Lumber DOL 1.25 BC 0.93 Vert(CT) -1.13 13 >383 240 MT18HS 244/190 BCLL 0.0 Rep Stress Incr YES WB 0.95 Horz(CT) 0.42 10 n/a n/a BCDL 10.0 Code FBC2017/TPI2014 Matrix -MS Wind(ILL) 0.84 13 >513 240 Weight: 170 lb FT = 20% LUMBER- BRACING - TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 2-6-11 oc purlins. BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 2-2-0 oc bracing. WEBS 2x4 SP No.3 WEBS 1 Row at midpt 7-14 OTHERS 2x4 SP No.3 REACTIONS. (lb/size) 2=1386/0-8-0, 10=1386/0-8-0 Max Horz 2=-207(LC 10) Max Uplift 2=-846(LC 12), 10=-846(LC 12) FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown. TOP CHORD 2-3=-3361/2183, 3-5=-2660/1831, 5-6=-2458/1735, 6-7=-2481/1719, 7-9=-5407/3513, 9-10=5950/3765 BOT CHORD 2-16=-1931/3146, 15-16=-1931/3146, 14-15=-1489/2515, 13-14=-3185/5191, 12-13=-3510/5666,10-12=-3504/5656 WEBS 3-16=0/315, 3-15=-799/546, 5-14=-344/260, 6-14=-731/1202, 7-14=-3120/2048, 7-13=-1130/1972,9-13=-559/376 NOTES- 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=12ft; B=59ft; L=36ft; eave=5ft; Cat. II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-0-0 to 2-7-3, Interior(1) 2-7-3 to 18-0-0, Exterior(2) 18-0-0 to 21-7-3 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) All plates are MT20 plates unless otherwise indicated. 4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. This item has been 5) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. electronically Signed and 6) Bearing atjoint(s) 10 considers parallel to grain value using ANSI/TP! 1 angle to grain formula. Building designer should verify sealed by Velez, Joaquin, PE capacity of bearing surface. using a Digital Signature. 7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 846 lb uplift at joint 2 and 846 lb uplift at printed copies of this p joint 10. document are not considered signed and sealed and the signature must be verified on any electronic copies. Joaquin Velez PE No.68182 MiTek USA, Inc. FL Cert 6634 6904 Parke East Blvd. Tampa FL 33610 Date: April 3,2020 ® WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design Into the overall �• building design. Bracing Indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek* is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/fP/l Quality Criteria, DSB-89 and BCS1 Building Component 6904 Parke East Blvd. Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610 Job Truss Truss Type city CARLTON 299 T19884583 M11412 A5 SPECIAL 7 �Ply 1 Job Reference (optional) Chambers Truss, Inc., Fort Pierce, FL r v ^�L 8.130 s Mar 112018 MiTek Industries, Inc. Fri AprL3 07:54:37 2020 �P 5-2-0 4-0-0 6-6-0 4.00 12 5x6 = Scale=1:61.9 16 15 4xiu 3x5 = 3x4 II Sx8 = 4x10 = 2.00 12 8-6-0 13-8-0 18.0-0 24-6-0 28-9-4 i 36-0-0 8-6-0 5-2-0 4-4-0 6-6-0 4-3-4 7-2-12 Plate Offsets (X,Y)— [2:0-1-2,Edge], [8:0-3-0,Edge], r10:0-2-10,Edge], [15:0-2-12,0-3-0] LOADING (psf) SPACING- 2-0-0 CSI. DEFL. in (loc) I/deft Ud PLATES GRIP TCLL 20.0 Plate Grip DOL 1.25 TC 0.60 Vert(LL) -0.61 13 >709 360 MT20 2441190 TCDL 7.0 Lumber DOL 1.25 BC 0.93 Vert(CT) -1.13 13 >383 240 MT18HS 244/190 BCLL 0.0 Rep Stress Incr YES WB 0.95 Horz(CT) 0.42 10 n/a n/a BCDL 10.0 Code FBC20171TPI2014 Matrix -MS Wind(LL) 0.84 13 >513 240 Weight: 170 lb FT = 20% LUMBER- BRACING - TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 2-6-11 oc pudins. BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 2-2-0 oc bracing. WEBS 2x4 SP No.3 WEBS 1 Row at midpt 7-14 OTHERS 2x4 SP No.3 REACTIONS. (lb/size) 2=138610-8-0, 10=1386/0-8-0 Max Horz 2=-208(LC 10) Max Uplift 2=-846(LC 12), 10=-846(LC 12) FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown. TOP CHORD 2-3=-3361/2183,3-5=-2660/1831,5-6=-2450/1730,6-7=-2472/1713,7-9=-5407/3513, 9-10=-5950/3764 BOT CHORD 2-16=-1931/3146,15-16=-1931/3146,14-15=-1489/2515,13-14=-3184/5190, 12-13=-3510/5666,10-12=-3504/5656 WEBS 3-16=0/315, 3-15=-799/546, 5-14=-355/272, 6-14=-743/1219, 7-14=-3134/2058, 7-13=1130/1972. 9-13=-560/375 NOTES- 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=12ft; B=59ft; L=36ft; eave=5ft; Cat. ll; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-0-0 to 2-7-3, Interior(1) 2-7-3 to 18-0-0, Exterior(2)18-0-0 to 21-7-3 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) All plates are MT20 plates unless otherwise indicated. 4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. ' This item has been 5) This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. electronically Signed and 6) Bearing at joint(s) 10 considers parallel to grain value using ANSIrrPI 1 angle to grain formula. Building designer should verify sealed by Velez, Joaquin, PE capacity of bearing surface. using a Digital Signature. 7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 846 lb uplift at joint 2 and 846 lb uplift at Printed copies of this joint 10. document are not considered signed and sealed and the signature must be verified on any electronic copies. Joaquin Velez PE No.68182 MiTek USA, Inc. FL Cert 6634 6904 Parke East Blvd. Tampa FL 33610 Date: April 3,2020 ® WARNING - Vedfy deslgn parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. W19I2020 BEFORE USE. Design valid for use only with MiTek® connectors. This design Is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify, the applicability of design parameters and properly incorporate this design Into the overall building design. Bracing Indicated is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek' Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANS11TPI1 Quality Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd. Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610 Job Truss Truss Type City Ply CARLTON 299 • T19884584 M11412 ATA COMMON 7 1 Job Reference (optional) Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MjTek Industries, Inc. Fri Apr 3 07:54:39 2020 Page 1 lk ID:kFvnsnOwY419Zh0_nM3lc6y1J9g-MNCyOc w8oUQgMDkgGyyCMLvYKQhiLZhEkFTkpzUUjk �1-0-0 8-1-1 13-10-2 18-0-0 22-1-14 27-10-15 , 36-0-0 17-0-q -0-0 8-1-1 5-9-1 4-1-14 4-1-14 5.9-1 8-1-1 -0-0 �1 6 4.00 12 5x6 = Scale=1:61.0 17 '" 15 "" "' 14 "' 12 3x8 = 3x4 II 4x6 = 3x8 = 3x8 = 4x6 = 3x4 II 3x8 0-2 22-1-14 LOADING (psf) TCLL 20.0 TCDL 7.0 BCLL 0.0 BCDL 10.0 SPACING- 2-0-0 Plate Grip DOL 1.25 Lumber DOL 1.25 Rep Stress Incr YES Code FBC2017/TPI2014 CSI. TC 0.53 BC 0.67 WB 0.60 Matrix -MS DEFL. Vert(LL) Vert(CT) Horz(CT) Wind(ILL) in (loc) I/deft L/d -0.28 14-15 >999 360 -0.59 14-15 >730 240 0.14 10 n/a n/a 0.34 14-15 >999 240 PLATES GRIP MT20 244/190 Weight: 172 lb FT = 20% LUMBER- BRACING - TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 3-2-15 oc puffins. BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 5-2-0 oc bracing. WEBS 2x4 SP No.3 REACTIONS. (lb/size) 2=1436/0-8-0, 10=1436/0-8-0 Max Horz 2=-208(LC 10) Max Uplift 2=-796(LC 12), 10=-796(LC 12) FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown. TOP CHORD 2-3=-3544/2053,3-5=-2824/1651, 5-6=-2817/1766,6-7=-2817/1766, 7-9=-2824/1651, 9-10=-3544/2053 BOT CHORD 2-17=1812/3323, 15-17=-1812/3323, 14-15=-997/2104, 12-14=-1826/3323, 10-12=-1826/3323 WEBS 6-14=-569/1002, 7-14=-299/279, 9-14=-783/581, 9-12=0/271, 6-15=-569/1002, 5-15=-300/279,3-15=782/581,3-17=0/271 NOTES- 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=12ft; B=59ft; L=36ft; eave=5ft; Cat. II; Ex , C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-0-0 to 2-7-3, Interior(1) 2-7-3 to 18-0-0, Exterior(2) 18-0-0 to 21-7-3 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) 100.01b AC unit load placed on the top chord, 18-0-0 from left end, supported at two points, 6-0-0 apart. 4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 5) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide This Item has been will fit between the bottom chord and any other members, with BCDL = 10.0psf. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 796 lb uplift at joint 2 and 796 lb uplift at electronically signed and joint 10. sealed by Velez, Joaquin, PE using a Digital Signature. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Joaquin Velez PE No.68182 MiTek USA, Inc. FL Cert 6634 6904 Parke East Blvd. Tampa FL 33610 Date: April 3,2020 ® WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an Individual building component, not H� a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall building design. Bracing Indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiT®k* is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSUTPH Quality Criteria, DSB-89 and BCS/ Building Component 6904 Parke East Blvd. Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa. FL 36610 Job Truss Truss Type City Ply CARLTON 299 T19884585 M11412 ATB COMMON 1 1 Job Reference (optional) Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Fri Apr 3 07:54:40 2020 Page 1 ■ ID:kFvnsnOwY419Zh0_nM3lc6ylJ9g-gZlKby Zv5cHSWowEzTBkZu6mkgGRnfrSO?1HGzUUjj �1-0-0 13-10-2 18-0-0 , 22-1-14 27-10-15 36-0-0 97-0-q -0-0 8-1-1 5-9-1 4-1-14 4-1-14 5-9-1 8-1-1 1-0-0' i1 6 Scale = 1:60.9 4.00 12 5x6 = 3x5 = 3x4 II 3x6 = 6x8 = 6x8 = 3x6 3x4 II 3x5 = LOADING (psf) TCLL 20.0 TCDL 7.0 BCLL 0.0 BCDL 10.0 SPACING- 2-0-0 Plate Grip DOL 1.25 Lumber DOL 1.25 Rep Stress Incr YES Code FBC2017/TP12014 CSI. TC 0.37 BC 0.40 WB 0.68 Matrix -MS DEFL. in (loc) I/deft Ud Vert(LL) -0.10 18-21 >999 360 Vert(CT) -0.22 18-21 >844 240 Horz(CT) 0.02 15 n/a n/a Wind(LL) 0.16 18-21 >999 240 PLATES GRIP MT20 244/190 Weight: 172 lb FT = 20% LUMBER- BRACING - TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc pudins. BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 6-0-0 oc bracing. WEBS 2x4 SP No.3 WEBS 1 Row at midpt 6-14 REACTIONS. All bearings 0-8-0. (lb) - Max Horz 2=-208(LC 10) Max Uplift All uplift 100 lb or less at joint(s) 15 except 2=-433(LC 12), 14=-866(LC 12), 10=-240(LC 12) Max Grav All reactions 250 lb or less at joints) except 2=687(LC 21), 14=1635(LC 1), 10=399(LC 22), 15=349(LC 17) FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown. TOP CHORD 2-3=-12391757, 3-5=-037/333, 5-6=-432/448, 6-7=-272/773, 7-9=-376/778, 9-10=-334/220 BOT CHORD 2-18=587/1178, 16-18=-587/1178, 12-14=-188/281, 10-12=-188/281 WEBS 6-14=-1096/683,7-14=-303/281, 9-14=-853/614,9-12=-13/307,6-16=-501/665, 5-16=-302/279, 3-16=-890/616, 3-18=-16/332 NOTES- 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=12ft; B=59ft; L=36ft; eave=5ft; Cat. 11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-0-0 to 2-7-3, Interior(1) 2-7-3 to 18-0-0, Exterior(2) 18-0-0 to 21-7-3 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) 100.01b AC unit load placed on the top chord, 18-0-0 from left end, supported at two points, 6-0-0 apart. 4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 5) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide This Item has been will fit between the bottom chord and any other members, with BCDL = 10.Opsf. 6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 15 except (jt=lb) electronically signed and 2=433, 14=866,10=240. sealed by Velez, Joaquin, PE using a Digital Signature. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Joaquin Velez PE No.68182 MiTek USA, Inc. FL Cart 6634 6904 Parke East Blvd. Tampa FL 33610 Date: April 3,2020 ® WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Design valid for use only with MrrekO connectors. This design Is based only upon parameters shown, and is for an individual building component not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design Into the overall building design. Bracing Indicated is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek* is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSIITP11 Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd. Safety information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610 Jgb Truss Truss Type Ply CARLTON 299 ' T19884586 M11412 ATC COMMON �Qty 1 1 Job Reference o tional Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Fri Apr 3 07:54:42 2020 Page 1 I D:kFvnsnOwY419Zh0_nM3lc6ylJ9g-mxt4OeOpRjs?hpxJLOWfq_zSGYWkvh98wiU8L8zUUjh �1-0-0 13-10-2 18-0-0 22-1-14 27-10-15 36-0-0 a7-0-q -0-0 8-1-1 5-9-1 4-1-14 4-1-14 5-9-1 8-1-1 -00 4.00 12 54 = Scale = 1:60.9 3x5 = 3x4 II 3x6 = 6x8 = 6x8 = 3x6 = 3x4 II 3x5 = 8-1-1 13-10-2 15 2-0 22-1-14 22-2-7 27-10-15 8-1-1 5-9-1 3-14 6-11-14 0-0-9 5-8-8 LOADING (psf) SPACING- 2-0-0 CSI. DEFL. in (loc) I/deft Ud TOLL 20.0 Plate Grip DOL 1.25 TC 0.37 Vert(LL) -0.10 18-21 >999 360 TCDL 7.0 Lumber DOL 1.25 BC 0.40 Vert(CT) -0.22 18-21 >844 240 BCLL 0.0 Rep Stress Incr YES WB 0.68 Horz(CT) 0.02 15 n/a n/a BCDL 10.0 Code FBC2017/TP12014 Matrix -MS Wind(LL) 0.15 18-21 >999 240 PLATES GRIP MT20 244/190 Weight: 172 lb FT = 20% LUMBER- BRACING - TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc pudins. BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 6-0-0 oc bracing. WEBS 2x4 SP No.3 WEBS 1 Row at midpt 6-14 REACTIONS. All bearings 0-8-0 except Qt=length) 14=0-11-5. (lb) - Max Horz 2=-208(LC 10) Max Uplift All uplift 100 lb or less at joint(s) 15 except 2=-433(LC 12), 14=-866(LC 12), 10=-240(LC 12) Max Grav All reactions 250 lb or less at joint(s) except 2=687(LC 21), 14=1635(LC 1), 10=399(LC 22). 15=349(LC 17) FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown. TOP CHORD 2-3=1239/757, 3-5=-437/333, "=-432/448, 6-7=-272/773, 7-9=-376/778, 9-10=334/220 BOT CHORD 2-18=-587/1178, 16-18=-587/1178, 12-14=-188/281, 10-12=-188/281 WEBS 6-14=-10961683, 7-14=303/281, 9-14=-853/614,9-12=-13/307, 6-16=-501/665, 5-16=-302/279, 3-16=-890/616, 3-18=-161332 NOTES- 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=1211; B=59ft; L=36ft; eave=5ft; Cat. II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2) -1-0-0 to 2-7-3, Intedon(1) 2-7-3 to 18-0-0, Extedor(2) 18-0-0 to 21-7-3 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) 100.Olb AC unit load placed on the top chord, 18-0-0 from left end, supported at two points, 6-0-0 apart. 4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 5) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide This item has been will fit between the bottom chord and any other members, with BCDL = 10.Opsf. 6) Provide mechanical connection (by others) of truss to bearing plate Capable of withstanding 100 lb uplift at joint(s) 15 except Qt=lb) electronically signed and 2=433,14=866,10=240. sealed by Velez, Joaquin, PE using a Digital Signature. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Joaquin Velez PE No.68182 MiTek USA, Inc. FL Cert 6634 6904 Parke EastBlvd. Tampa FL 33610 Date:. April 3,2020 ® WARNING.- Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an Individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design into the overall building design. Bracing Indicated is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek* Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guldance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/7P/1 Quality Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd. Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MO 20601 Tampa, FL 36610 Job Truss Truss Type Qty Ply CARLTON 299 T19884587 M11412 BHA COMMON 1 1 Job Reference o tional Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 11 2018 MiTek Industries, Inc. Fri Apr 3 07:54:43 2020 Page 1 • ID:kFvnsnOwY419Zh0_nM3lc6ylJ9g-E8RSEzl RCO_sJzW Vv61 uMCWXWxgTe67H9MDhtazUUjg 16-041 24-0-0 i1-0-0 8-0-0 12.0.0 14-0-0 15-6-0 18-0-0 i 20-0-0 22.0-022r10-1S i 28-0-0 i 36-0-0 37-0-0 5-0-0 8-0-0 4-0 0 2- 0 Al 2 M I WN 2-0-0 0-10-1 4-0-0 8-0-0 W. 1-1-1 Scale: 3/16°=1' THIS TRUSS IS NOT SYMMETRIC. PROPER ORIENTATION IS ESSENTIAL. 5x6 = 3x6 II 4x6 = 6x8 = 6x8 = 3x6 II 3x5 = 3x6 = 3x6 = TRUSS DESIGNED FOR WIND LOADS IN THE PLANE OF THE TRUSS ONLY. FOR STUDS EXPOSED TO WIND (NORMAL TO THE FACE), SEE STANDARD INDUSTRY GABLE END DETAILS AS APPLICABLE, OR CONSULT QUALIFIED BUILDING DESIGNER AS PER ANSI/TPI 1. LOADING (psf) TCLL 20.0 TCDL 7.0 BCLL 0.0 BCDL 10.0 SPACING- 2-0-0 Plate Grip DOL 1.25 Lumber DOL 1.25 Rep Stress Incr NO Code FBC2017rrP12014 CSI. TC 0.73 BC 0.56 WE,0.83 Matrix -MS DEFL. in (loc) I/deft Ud Vert(LL) -0.14 28-31 >999 360 Vert(CT) -0.25 23-34 >619 240 Horz(CT) 0.04 21 n/a n/a Wind(LL) 0.20 28-31 >909 240 PLATES MT20 MT18HS Weight: 208 lb GRIP 244/190 244/190 FT = 20% LUMBER- BRACING - TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 4-2-12 oc purlins. BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 6-0-0 oc bracing. WEBS 2x4 SP No.3 WEBS 1 Row at micipt 20-25 2 Rows at 1/3 pis 3-26 JOINTS 1 Brace at Jt(s): 8, 4, 14, 16, 18 REACTIONS. All bearings 0-8-0 except Qt=length) 25=0-11-5. (lb) - Max Horz 2=-208(LC 6) Max Uplift All uplift 100 lb or less at joint(s) except 2=-583(LC 8), 26=-1557(LC 8), 25=-1259(LC 8), 21=-455(LC 8) Max Grav All reactions 250 lb or less at joint(s) except 2=983(LC 13), 26=2911(LC 13), 25=2457(LC 14), 21=757(LC 14) FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown. TOP CHORD 2-3=-2242/1142, 20-21=-1473/724, 3-4=-2131718, 4-6=-2131718, 6-8=-213/718, 8-10=-213/718, 10-11=-213/718, 11-13=-213/718, 13-15=-213/718, 15-17=-213/718, 17-19=-87/610, 19-20=-87/610, 3-5=-199/422, 5-7=-112/391, 7-9=-33/344, 12-14=0/257, 16-18=-67/301,18-20=-206/363 BOT CHORD 2-28=-971/2236, 26-28=-922/2090, 25-26=-855/521, 23-25=-516/1204, 21-23=-569/1344 WEBS 8-26=-1333/1008, 17-25=-9791756, 3-28=-419/1254, 3-26=-3236/1698, 20-23=-458/1210, 20-25=-2385/1201, 9-10=-706/569, 6-7=307/241, 15-16=4621372, 18-19=-497/418 NOTES- 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=12ft; B=59ft; L=36ft; eave=5ft; Cat. This item has been 11; Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60 3) Provide adequate drainage to prevent water ponding. electronically signed and 4) All plates are MT20 plates unless otherwise indicated. Sealed by Velez, Joaquin, PE 5) All plates are 3x4 MT20 unless otherwise indicated. using a Digital Signature. 6) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. • Printed copies of this 7) This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. document are not Considered 8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 583 lb uplift at joint 2, 1557 lb uplift at signed and sealed and the joint 26, 1259 lb uplift at joint 25 and 455 lb uplift at joint 21. Signature must be verified 9) Girder carries hip end with 8-0-0 end setback. electronicc On any e12CtrorllC COPIeS. 10) Graphical puffin representation does not depict the size or the orientation of the pufin along the top and/or bottom chord. Joaquin Velez PE 82 11) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 967 lb down and 461 lb up at MiTek USA, Inc. FL Cert 634 MiTe6904 28-0-0, and 967 lb down and 461 lb up at 8-0-0 on bottom chord. The design/selection of such connection device(s) is the Parke East Blvd. Tampa FL 33610 responsibility of others. Date; 12) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B). April 3,2020 andard ®WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE Mll-7473 rev. 5/19/2020 BEFORE USE. Design valid for use only with MiTek® connectors. This design Is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and property Incorporate this design into the overall tt �� building design. Bracing Indicated is to prevent buckling of Individual truss web and/or chord members only. Addiflonal temporary and permanent bracing MiTek• is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANS11rP11 Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd. Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610 Job Truss Truss Type Ply CARLTON 299 ' T19884587 M11412 BHA COMMON �Qty 1 1 Job Reference o floral Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Fri Apr 3 07:54:43 2020 Page 2 ID:kFvnsnOwY419Zh0_nM3lc6ylJ9g-E8RSEz1 RCO_sJzW Vv61 uMCWXWxgTe6?H9MDhtazUUjg LOAD CASE(S) Standard 1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25 Uniform Loads (plf) Vert: 1-3=-54, 20-22=-54, 28-29=-20, 23-28=47(F=-27), 23-32=-20, 3-12=-126(F=-72), 12-20=-126(F=-72) Concentrated Loads (lb) Vert: 28=-641(F) 23=-641(F) d ®WARNING -Verily design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 511912020 BEFORE USE. Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an Individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design Into the overall A� building design. Bracing indicated is to prevent buckling of Individual truss web andfor chord members only. Additional temporary and permanent bracing 1 VliTe k• Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANS11TPI1 Quality Criteria, DSO.89 and BCSI Building Component 6904 Parke East Blvd. Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610 Job Truss Truss Type Ply CARLTON 299 ' T19884588 M11412 GRA HIP �Qty 1 1 Job Reference o floral Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Fri Apr 3 07:54:45 2020 Page 1 I D:kFvnsnOwY419Zh0_nM31c6y1J9g-BWZDff2hkeFaYHguOW3MRdbtEITp67NacgioyTzUUje 1-0-0 7-10-0 133 8-0 18-0 0 224-0 28-2-07-0- -0-0 7-10-0 510-0 4-4-0 4-0-0 5-10-0 7-10-0 -0-0 Scale = 1:61.9 3x5 = 5x8 MT18HS = 5x8 MT18HS = 4.00 12 3x4 II 5x8 = 3x4 II 3 22 23 24 25 426 27 5 28 629 30 31 32 33 7 -- 34 14 3b 3b 31 :36 "" 11 4u 3x4 11 4x6 = 6x12 = 6x12 = 4x6 = 3x4 II 3x5 = 7-10-0 13-8-0 22-4-0 28-2-0 36-0-0 7-16-0 5-10-0 8-8-0 5-10-0 7-10-0 Plate Offsets (X Y)— [3:0-5-4 0-2-8] [5:0-4-0 0-3-0] [7:0-5-4 0-2-8] LOADING (psf) SPACING- 2-0-0 CSI. DEFL. in (loc) I/deft Ud PLATES GRIP TCLL 20.0 Plate Grip DOL 1.25 TC 0.71 Vert(LL) -0.21 12-13 >999 360 MT20 244/190 TCDL 7.0 Lumber DOL 1.25 BC 0.76 Vert(CT) -0.44 12-13 >609 240 MT18HS 244/190 BCLL 0.0 Rep Stress Incr NO WB 0.84 Horz(CT) 0.06 8 n/a n/a BCDL 10.0 Code FBC2017/TP12014 Matrix -MS Wind(LL) 0.22 10-21 >999 240 Weight: 161 lb FT = 20% LUMBER- BRACING - TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 3-4-6 oc purlins. BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 5-7-0 cc bracing. WEBS 2x4 SP No.3 *Except* WEBS 1 Row at midpt 3-13, 5-13 4-13,6-12: 2x6 SP No.2 REACTIONS. (lb/size) 2=398/0-8-0, 13=3546/0-8-0, 8=125210-8-0 Max Horz 2=-97(LC 6) Max Uplift 2=-292(LC 8), 13=-2107(LC 8), 8=-799(LC 8) Max Grav 2=417(LC 17), 13=3546(LC 1), 8=1256(LC 18) FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown. TOP CHORD 2-3=-369/211, 3-4=-1158/2051, 4-5=-1158/2051, 5-6=-2318/1425, 6-7=-2318/1425, 7-8=-2981 /1789 BOT CHORD 2-15=-196/311, 13-1 5=-201/342,12-13=-246/452, 10-12=-1588/2818, 8-1 0=1 578/2786 WEBS 3-15=-181/648, 3-13=-2568/1568, 4-13=-640/587, 5-13=-2900/1855, 5-12=-1172/2196, 6-12=-611/569, 7-12=-558/375, 7-1 0=-1 841651 NOTES- 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=12ft; B=59ft; L=36ft; eave=5ft; Cat. II; Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60 3) Provide adequate drainage to prevent water ponding. 4) All plates are MT20 plates unless otherwise Indicated. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. This item has been 6) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. electronically Signed and 7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 292 lb uplift at joint 2, 2107 lb uplift at sealed by Velez, Joaquin, PE joint 13 and 799lb uplift at joint 8. using a Digital Signature. 8) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 137 lb down and 301 lb up at Printed copies of this P 7-10-0. 103 lb down and 170 lb up at 10-0-12. 103 lb down and 170 lb up at 12-0-12, 103 lb down and 170 lb up at 14-0-12, 103 lb down and 170 lb up at 16-0-12, 103 lb down and 170 lb up at 18-0-12, 103 lb down and 170 lb up at 19-11-4, 103 lb down and 170 document are not considered Ib up at 21-11-4, 103 lb down and 170 lb up at 23-114, and 103 lb down and 170 lb up at 25-114, and 137 lb down and 301 lb up signed and sealed and the at 28-2-0 on top chord, and 340 lb down and 223 lb up at 7-10-0, 77 lb down and 1 lb up at 8-0-12, 77 lb down and 1 lb up at signature must be verified 10-0-12, 77 lb down and 1 lb up at 12-0-12, 77 lb down and 1 lb up at 14-0-12, 77 lb down and 1 lb up at 16-0-12, 77 lb down and electronic on any copies. 1 lb up at 18-0-12, 77 lb down and 1 lb up at 19-11-4, 77 lb down and 1 lb up at 21-11-4, 77 lb down and 1 lb up at 23-11-4, 77 lb Joaquin Velez PE No.68182 down and 1 lb up at 25-114, and 77 lb down and 1 lb up at 27-114, and 340 lb down and 223 lb up at 28-2-0 on bottom chord. MiTek USA, Inc. FL Cart 6634 The design/selection of such connection device(s) is the responsibility of others. 6904 Parke East Blvd. Tampa FL $3610 9) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B). Date: LOAD CASE(S) Standard April 3,2020 7AWARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. lid for use only with MtTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not stem. Before use, the building designer must verify the applicability of design parameters and property Incorporate this design Into the overall � �eesign. Bracing Indicated is to prevent buckling of individual truss web andlor chord members only. Additional temporary and permanent bracing MiTek• required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the n, storage, delivery, erection and bracing of trusses and truss systems, see ANSUIP/1 Qualify Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd. Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610 Job Truss Truss Type Ply CARLTON 299 T19884588 M11412 GRA HIP �Qty 1 1 Job Reference (optional) Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Fri Apr 3 07:54:45 2020 Page 2 I D: kFvnsnOwY419Zh0_n M3lc6yl J9g-B WZDff2hkeFaYHg uOW 3MRdbtEITp6?NacgioyTzU Uje LOAD CASE(S) Standard 1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25 Uniform Loads (plf) Vert: 1-3=-54, 3-7=-54, 7-9=-54, 16-19=-20 Concentrated Loads (lb) Vert: 3=-137(B) 5=-103(B) 7=-137(B) 14=-49(B) 15=-389(B) 10=-389(B) 1 1=49(B) 22=-103(B) 24=-103(B) 26=-103(B) 27=-103(B) 28=-103(B) 29=-103(B) 31=-103(B) 33=-103(B) 34=-49(B) 35=49(B) 36=49(B) 37=49(13) 38=49(B) 39=49(B) 40=49(B) ® WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE Mll-7473 rev. 511912020 BEFORE USE. Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and Is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and property Incorporate this design Into the overall building design. Bracing Indicated is to prevent buckling of individual truss web andfor chord members only. Additional temporary and permanent bracing MiTek• is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSb TP11 Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd. Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610 Job Truss Truss Type Qty Ply CARLTON 299 ' T79884589 M11412 J2 MONO TRUSS 8 1 Job Reference (optional) Ch.ambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Fri Apr 3 07:64:46 2020 Page 1 I D:kFvns nOwY419Zh0_nM3lc6ylJ9g-fj 7bs73JVxN QARF4a Eab_g8BM9yprfhjrKSLUvzU Ujd 1-0-0 2-0-0 1-0-0 2-0-0 Scale = 1:7.8 3x4 = 2-0-0 2-0-0 LOADING (psi) SPACING- 2-0-0 CSI. DEFL. in (loc) Udefl Ud PLATES GRIP TCLL 20.0 Plate Grip DOL 1.25 TC 0.18 Vert(LL) -0.00 7 >999 360 MT20 244/190 TCDL 7.0 Lumber DOL 1.25 BC 0.07 Vert(CT) -0.00 7 >999 240 BCLL 0.0 Rep Stress Incr YES WB 0.00 Horz(CT) -0.00 3 n/a n/a BCDL 10.0 Code FBC2017rrP12014 Matrix -MP Wind(LL) 0.00 7 >999 240 Weight: 8 lb FT = 20% LUMBER - TOP CHORD 2x4 SP No.3 BOT CHORD 2x4 SP No.3 REACTIONS. (lb/size) 3=37/Mechanical, 2=141/0-8-0, 4=22/Mechanical Max Horz 2=67(LC 12) Max Uplift 3=-27(LC 12), 2=-136(LC 12), 4=-3(LC 9) Max Grav 3=40(LC 17), 2=141(LC 1), 4=31(LC 3) FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown. BRACING - TOP CHORD Structural wood sheathing directly applied or 2-0-0 oc pudins. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. NOTES- 1) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=12ft; B=59ft; L=36ft; eave=5ft; Cat. II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 3) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 4) Refer to girder(s) for truss to truss connections. 5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 27lb uplift at joint 3, 136lb uplift at joint 2 and 3 lb uplift at joint 4. This item has been electronically signed and sealed by Velez, Joaquin, PE using a Digital Signature. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Joaquin Velez PE No.66182 MiTek USA, Inc. FL Cart 6834 6904 Parke East Blvd. Tampa FL 33610 Date: April 3,2020 ®WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII.7473 rev. 5/19/2020 BEFORE USE. Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an Individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall building design. Bracing indicated is to prevent buckling of Individual truss web andlor chord members only. Additional temporary and permanent bracing MiTek' is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANS11TP/1 Quality Crlferla, DSB-89 and BCSI Building Component 6904 Parke East Blvd. Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610 Job s Truss Type City Ply CARLTON 299 TJ4 T19884590 M11412 MONO TRUSS 8 1 Job Reference o tional Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Fri Apr 3 07:54:46 2020 Page 1 I D:kFvns nOwY419Zh0_nM3lc6ylJ9g-fj7bs73J VxNQARF4a Eab_g88H9u9rfhjrKSLUvzU Ujd -1-0-0 4-0-0 1-0-0 4-0-0 3x4 = 4-0-0 LOADING (psf) SPACING- 2-0-0 CSI. DEFL. in (loc) I/deft Ud TCLL 20.0 Plate Grip DOL 1.25 TC 0.37 Vert(LL) -0.01 4-7 >999 360 TCDL 7.0 Lumber DOL 1.25 BC 0.37 Vert(CT) -0.02 4-7 >999 240 BCLL 0.0 Rep Stress Incr YES WB 0.00 Horz(CT) -0.00 3 n/a n/a BCDL 10.0 Code FBC2017frP12014 Matrix -MP Wlnd(LL) 0.02 4-7 >999 240 LUMBER - TOP CHORD 2x4 SP No.3 SOT CHORD 2x4 SP No.3 REACTIONS. (lb/size) 3=87/Mechanical, 2=204/0-8-0, 4=49/Mechanical Max Horz 2=102(LC 12) Max Uplift 3=-77(LC 12), 2=-159(LC 12), 4=7(LC 12) Max Grav 3=91(LC 17), 2=204(LC 1), 4=67(LC 3) FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown. Scale=1:11.1 r; PLATES GRIP MT20 244/190 Weight: 14 lb FT = 20% BRACING - TOP CHORD Structural wood sheathing directly applied or 4-0-0 oc pudins. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. NOTES- 1) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=12ft; B=59ft; L=36ft; eave=5ft; Cat. 11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-0-0 to 2-7-3, Interior(1) 2-7-3 to 3-10-4 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 3) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 4) Refer to girder(s) for truss to truss connections. 5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 77 lb uplift at joint 3, 159 lb uplift at joint 2 and 7 lb uplift at joint 4. This item has been electronically signed and sealed by Velez, Joaquin, PE using a Digital Signature. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Joaquin Velez PE No.68182 MiTek USA, Inc. FL Cert 6634 6904 Parke East Blvd. Tampa FL 33610 Date: April 3,2020 ®WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE Mll-7473 rev. 5119/2020 BEFORE USE. Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall my building design. Bracing Indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek* is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANS11lPI1 Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke Fast Blvd. Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610 Job Truss Truss Type City Ply CARLTON 299 ' T19884591 M11412 J6 MONO TRUSS 8 1 Job Reference (optional) Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Fri Apr 3 07:54:47 2020 Page 1 ID:kFvnsnOwY419Zh0_nM3lc6ylJ9g-7vhz3L4yGFVHoagH8x5gX2gJNZ63a6xt4_BuOMzUUjc -1-0-0 6-0-0 1-0-0 6-0-0 Scale = 1:14.3 3x4 = LOADING (psf) SPACING- 2-0-0 CSI. DEFL. in (loc) I/deft Ud PLATES GRIP TCLL 20.0 Plate Grip DOL 1.25 TC 0.35 Vert(LL) -0.05 4-7 >999 360 MT20 244/190 TCDL 7.0 Lumber DOL 1.25 BC 0.83 Vert(CT) -0.11 4-7 >652 240 BCLL 0.0 Rep Stress Incr YES WS 0.00 Horz(CT) -0.00 3 n/a n/a BCDL 10.0 Code FBC2017frP12014 Matrix -MP Wind(LL) 0.11 4-7 >639 240 Weight: 20Ib FT=20% LUMBER- BRACING - TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc pudins. BOT CHORD 2x4 SP No.3 BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (Ib/size) 3=142/Mechanical, 2=275/0-8-0, 4=70/Mechanical Max Horz 2=140(LC 12) Max Uplift 3=-129(LC 12), 2=-192(LC 12), 4=-8(LC 12) Max Grav 3=148(LC 17), 2=275(LC 1), 4=100(LC 3) FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown NOTES- 1) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=12ft; B=59ft; L=36ft; eave=5ft; Cat. II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-0-0 to 2-7-3, Interior(1) 2-7-3 to 5-10-4 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 3) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 4) Refer to girder(s) for truss to truss connections. 5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 129 lb uplift at joint 3, 192 lb uplift at joint 2 and 8 lb uplift at joint 4. This item has been electronically signed and sealed by Velez, Joaquin, PE using a Digital Signature. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Joaquin Velez PE No.68182 MiTek USA, Inc. FL Cart 6634 6904 Parke East Blvd. Tampa FL 33610 Date: April 3,2020 ®WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and Is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek* Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANS17P/f Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd. Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610 Job Truss Truss Type Ply CARLTON 299 ' �Qty T19884592 M11412 J8 MONO TRUSS 11 1 Job Reference (optional) Cttiambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Fri Apr 3 07:54:48 2020 Page 1 ID:kFvnsnOwY419Zh0_nM3lc6ylJ9g-b5ELHh5a 1 ZdBPkPTifd33FDQ4yY_JZBOlexSZozUUjb -1-0-0 8-0-0 , 1-0 0 8-0-0 3x4 LOADING (psf) SPACING- 2-0-0 CSI. DEFL. in (loc) I/deft Ud TCLL 20.0 Plate Grip DOL 1.25 TC 0.61 Vert(ILL) -0.14 4-7 >676 360 TCDL 7.0 Lumber DOL 1.25 BC 0.47 Vert(CT) -0.30 4-7 >310 240 BCLL 0.0 Rep Stress Incr YES WB 0.00 Horz(CT) -0.00 3 n/a n/a BCDL 10.0 Code FBC2017/TPI2014 Matrix -MP Wind(LL) 0.26 4-7 >368 240 LUMBER - TOP CHORD 2x4 SP M 30 BOT CHORD 2x4 SP M 30 REACTIONS. (lb/size) 3=188/Mechanical, 2=348/0-8-0, 4=99/Mechanical Max Horz 2=178(LC 12) Max Uplift 3=-174(LC 12), 2=-226(LC 12), 4=-13(LC 12) Max Grav 3=195(LC 17), 2=348(LC 1), 4=141(LC 3) FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown. Scale=1:17.4 PLATES GRIP MT20 244/190 Weight: 26 lb FT = 20% BRACING - TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc pudins. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. NOTES- 1) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=12ft; B=59ft; L=36ft; eave=5ft; Cat. II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-0-0 to 2-7-3, Interior(1) 2-7-3 to 7-10-4 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) This truss has been designed for a 10.0 pelf bottom chord live load nonconcurrent with any other live loads. 3) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 4) Refer to girder(s) for truss to truss connections. 5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 174 lb uplift at joint 3, 226 lb uplift at joint 2 and 13 lb uplift at joint 4. This item has been electronically signed and sealed by Velez, Joaquin, PE using a Digital Signature. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Joaquin Velez PE No.68182 MiTek USA, Inc. FL Cent 6634 6904 Parke East Blvd. Tampa FL 33610 Data: April 3,2020 ®WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/1912020 BEFORE USE. Design valid for use only with MiTek® connectors. This design Is based only upon parameters shown, and Is for an Individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall building design. Bracing Indicated is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek' is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSIITP11 Quality Criteria, DSO-89 and BCSI Building Component 6904 Parke East Blvd. Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610 Jpb Truss Truss Type Ply CARLTON 299 ' T19884593 M11412 JA8 MONO TRUSS �Qty 11 1 Job Reference (optional) % Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Fri Apr 3 07:54:49 2020 Page 1 ID:kFvnsnOwY419ZhO_nM3lc6ylJ9g-31okU15Cosl?l u_fFMBlcTmbJMuY20RAXlg?5EzUUja 1-0-0 7-10-0 1-0-1 7-10-0 3x4 = LOADING (psg SPACING- 2-0-0 CSI. DEFL. in (loc) I/deb Lid TCLL 20.0 Plate Grip DOL 1.25 TC 0.58 Vert(LL) -0.13 4-7 >721 360 TCDL 7.0 Lumber DOL 1.25 BC 0.45 Vert(CT) -0.28 4-7 >331 240 BCLL 0.0 Rep Stress Incr YES WB 0.00 Horz(CT) -0.00 3 n/a n/a BCDL 10.0 Code FBC2017/TPI2014 Matrix -MP Wind(LL) 0.24 4-7 >392 240 LUMBER - TOP CHORD 2x4 SP M 30 BOT CHORD 2x4 SP M 30 REACTIONS. (lb/size) 3=184/Mechanical, 2=342/0-8-0, 4=97/Mechanical Max Horz 2=175(LC 12) Max Uplift 3=-170(LC 12), 2=-223(LC 12), 4=13(LC 12) Max Grav 3=191(LC 17), 2=342(LC 1), 4=138(LC 3) FORCES. (lb) -Max. Comp./Max. Ten. -All farces 250 (lb) or less except when shown. Scale = 1:17.2 PLATES GRIP MT20 2441190 Weight: 26 lb FT = 20% BRACING - TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purling. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. NOTES- 1) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=12ft; B=59ft; L=36ft; eave=5ft; Cat. 11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-0-0 to 2-7-3, Interior(1) 2-7-3 to 7-8-4 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) This truss has been designed fora 10.0 psf bottom chord live load nonconcurrent with any other live loads. 3) ' This truss has been designed for a live load of,20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 4) Refer to girder(s) for truss to truss connections. 5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 170 lb uplift at joint 3, 223 lb uplift at joint 2 and 13 lb uplift at joint 4. This item has been electronically signed and sealed by Velez, Joaquin, PE using a Digital Signature. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Joaquin Velez PE No.68162 MiTek USA, Inc. FL Cart 6634 6904 Parke East Blvd. Tampa FL 33610 Date: April 3,2020 ®WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII.7473 rev. 5/19/2020 BEFORE USE. Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an Individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and property Incorporate this design Into the overall building design. Bracing Indicated Is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek* is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI1TPl1 Qualify Criteria, DSB-89 and BCSI Building Component 6904 Parke Fast Blvd. Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610 JQb Truss Truss Type City Ply CARLTON 299 T19884594 M11412 KJ8 MONO TRUSS 2 1 Job Reference (optional) Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 11 2015 MiTek Industries, Inc. Fri Apr 3 U7:54:49 ZUZU Page 1 ID:kFvnsnOwY419Zh0_nM3lc6ylJ9g-31okU15Cosl?1u fFM8lcTmh6Myh2xlAXlg?5EzUUja -1-5-0 7-2-7 , 11-3-0 1-5 0 7-2-7 4-0-9 3x4 = ��- 3x4 = 5 7-2-7 11-0-12 11-3i0 7-2-7 3-10-5 I. LOADING (psf) SPACING- 2-0-0 CSI. DEFL. in (too) Well Lid PLATES GRIP TCLL 20.0 Plate Grip DOL 1.25 TC 0.21 Vert(LL) -0.05 6-9 >999 360 MT20 244/190 TCDL 7.0 Lumber DOL 1.25 BC 0.25 Vert(CT) -0.10 6-9 >999 240 BCLL 0.0 Rep Stress Incr NO WB 0.35 Horz(CT) 0.01 5 n/a n/a BCDL 10.0 Code FBC2017/TPI2014 Matrix -MS Wind(LL) -0.04 6-9 >999 240 Weight: 44 lb FT = 20% LUMBER- BRACING - TOP CHORD 2x4 SP M 30 TOP CHORD BOT CHORD 2x4 SP M 30 BOT CHORD 2x4 SP No.3 WEBS REACTIONS. (lb/size) 4=90/Mechanical, 2=46210-11-5, 5=406/Mechanical Max Horz 2=178(LC 8) Max Uplift 4=-102(LC 8). 2=-187(LC 8), 5=-118(LC 8) FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown. TOP CHORD 2-3=-866/230 BOT CHORD 2-6=-234/833, 5-6=-234/833 WEBS 3-6=0/287.3-5=-913/257 Structural wood sheathing directly applied or 6-0-0 oc pudins. Rigid ceiling directly applied or 10-0-0 oc bracing. NOTES- 1) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=12ft; B=59ft; L=36ft; eave=5ft; Cat. 11; Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60 2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 3) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 4) Refer to girder(s) for truss to truss connections. 5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 102 lb uplift at joint 4, 187 lb uplift at joint 2 and 118 lb uplift at joint 5. 6) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 39 lb down and 58 lb up at 2-11-0, 39 lb down and 58 lb up at 2-11-0, 8 lb down and 101 lb up at 5-8-15, 8 Ib down and 101 lb up at 5-8-15, and 42 lb down and 143 lb up at 8-6-14, and 42 lb down and 143 lb up at 8-6-14 on top chord, and 47 lb down and 28 lb up at 2-11-0, 47 lb.down and 28 lb up at 2-11-0, 47 lb down at 5-8-15, 47 lb down at 5-8-15, and 31 lb down and 14 lb up at 8-6-14, and 31 lb down and 14 lb up at 8-6-14 on bottom chord. The design/selection of such connection device(s) is the responsibility of others. 7) In the LOAD CASE(S) section, loads applied to the face of the truss are noted.as front (F) or back (B). LOAD CASE(S) Standard 1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25 Uniform Loads (plf) Vert: 1-4=-54, 5-7=-20 Concentrated Loads (Ib) Vert: 10=80(F=40, B=40) 11=-2(F=-1, B=-1) 12=-83(F=42, B=42) 13=14(F=7, B=7)14=-20(F=10, B=-10) 15=-50(F=-25, B=-25) This item has been electronically signed and sealed by Velez, Joaquin, PE using a Digital Signature. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Joaquin Velez PE No.68182 MiTek USA, Inc. FL Cert 6634 6904 Parke East Blvd. Tampa FL 33610 Date: April 3,2020 ®WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5119/2020 BEFORE USE. Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and Is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design Into the overall Iva I' building design. Bracing indicated is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek• is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI1TP/1 Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd. Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610 Job Truss Truss Type Qty Ply CARLTON 299 T19884595 M11412 KJAB MONO TRUSS 2 1 Job Reference (optional) CF ambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Fri Apr 3 07:54:50 2020 Page 1 I D: kFvnsnOwY419Zh0_nM3lc6ylJ9g-XUM 6i N 6gYAtsf2Yrp4fX8g I s_ml Dn OSJ myQZdgzU UjZ -1-5-0 6-10-0 11-0-3 1-5-0 6-10-0 4-2-3 Scale = 1:19.9 3x4 = 3x4 = 6-10-0 11-0-3 6-10-0 4-2-3 LOADING (psf) SPACING- 2-0-0 CSI. DEFL. in (loc) I/deft Lid PLATES GRIP TCLL 20.0 Plate Grip DOL 1.25 TC 0.20 Vert(LL) 0.06 6-9 >999 240 MT20 244/190 TCDL 7.0 Lumber DOL 1.25 BC 0.23 Vert(CT) -0.08 6-9 >999 240 BCLL 0.0 ' Rep Stress Incr NO WB 0.34 Horz(CT) 0.01 5 n/a n/a BCDL 10.0 Code FBC2017/TPI2014 Matrix -MS Weight: 43 lb FT = 20% LUMBER- BRACING - TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins. BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. WEBS 2x4 SP No.3 REACTIONS. (lb/size) 4=106/Mechanical, 2=447/0-11-5, 5=385/Mechanical Max Harz 2=175(LC 8) Max Uplift 4=-107(LC 8), 2=-321(LC 8), 5=-202(LC 5) FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown. TOP CHORD 2-3=-846/526 BOT CHORD 2-6=-520/815, 5-6=-520/815 WEBS 3-6=0/268, 3-5=-884/565 NOTES- 1) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=12ft; B=59ft; L=36ft; eave=5ft; Cat. 11; Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60 2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 3) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 4) Refer to girder(s) for truss to truss connections. 5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 107 lb uplift at joint 4, 321 lb uplift at joint 2 and 202 lb uplift at joint 5. 6) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 39 lb down and 58 lb up at 2-11-0, 39 lb down and 58 lb up at 2-11-0, 8 lb down and 101 lb up at 5-8-15, 8 lb down and 101 lb up at 5-8-15, and 42 lb down and 143 lb up at 8-6-14, and 42 lb down and 143 lb up at 8-6-14 on top chord, and 31 lb up at 2-11-0, 31 lb up at 2-11-0, 10 lb This item has been down and 30 lb up at 5-8-16, 10 lb down and 30 lb up at 5-8-15, and 31 lb down and 14 lb up at 8-6-14, and 31 lb down and 14 lb up at 8-6-14 on bottom chord. The design/selection of such connection device(s) is the responsibility of others. electronically Signed and 7) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B). sealed by Velez, Joaquin, PE using a Digital Signature. LOAD CASE(S) Standard 1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25 Printed copies of this Uniform Loads (plf) document are not considered Vert: 1-4=-54, 5-7=-20 signed and sealed and the Concentrated Loads (lb) signature must be verified Vert: 10=80(F=40, B=40)11=-2(F=-1, B=-1)12=-83(F=-42, 13=42) 13=14(F=7, B=7)14=-20(F=-10, B=-10)15=-50(F=-25, on any electronic copies. B=-25) Joaquin Velez PE No.68182 MiTek USA, Inc. FL Cart6634 6904 Parke East Blvd. Tampa FL 33610 Date: April 3,2020 ®WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII.7473 rev. 6/1912020 BEFORE USE. Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an Individual building component, not ITS I a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall building design. Bracing Indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSHfPi1 Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd. Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610 Symbols Numbering System ® General Safety Notes PLATE LOCATION AND ORIENTATION 3/ " Center plate on joint unless x, y 4 offsets are indicated. 6-4-8 dimensions shown in ft-in-sixteenths (Drawings not to scale) 1 Failure to Follow Could Cause Property Damage or Personal Injury Dimensions are in ft-in-sixteenths. 1. Additional stability bracing for truss system, e.g. Apply plates to both sides of truss 1 2 3 diagonal or X-bracing, is always required. See BCSI. and fully embed teeth. TOP CHORDS 2. Truss bracing must be designed by an engineer. For y �r 0 c1-2 c2-3 wide truss spacing, individual lateral braces themselves may require Tor I - WEBS c� 4 O0 �'•� H �� _ 3 y+ 3 O bracing should be considered. 3. Never exceed the design loading shown and never stack materials on inadequately braced trusses. U oP 2 f1 3 U 4. Provide copies of this truss design to the building O 0 ~ 00 designer, erection supervisor, property owner and For 4 x 2 orientation, locate c7-3 C6a c5-6 all other interested parties. plates 0- Vi ' from outside BOTTOM CHORDS 5. Cut members to bear tightly against each other. edge of truss. 8 7 6 5 6. Place plates on each face of truss at each joint and embed fully. Knots and wane at joint This symbol indicates the JOINTS ARE GENERALLY NUMBERED/LETTERED CLOCKWISE locations are regulated by ANSI/TPI 1. required direction of slots in AROUND THE TRUSS STARTING AT THE JOINT FARTHEST TO 7. Design assumes trusses will be suitably protected from connector plates. THE LEFT. the environment in accord with ANSI/TPI 1. Plate location details available in M)Tek 20/20 CHORDS AND WEBS ARE IDENTIFIED BY END JOINT NUMBERS/LETTERS. 8. Unless otherwise noted, moisture content of lumber shall not exceed 19 % at time of fabrication. software or upon request. 9. Unless expressly noted, this design is not applicable for PLATE SIZE PRODUCT CODE APPROVALS use with fire retardant, preservative treated, or green lumber. ICC-ES Reports: 10. Camber is a non-structural consideration and is the The first dimension is the plate responsibility of truss fabricator. General practice is to 4 x 4 width measured perpendicular ESR-1311, ESR-1352, ESR1988 camber for dead load deflection. to slots. Second dimension is ER-3907, ESR-2362, ESR-1397, ESR-3282 11. Plate type, size, orientation and location dimensions the length parallel to slots. indicated are minimum plating requirements. LATERAL BRACING LOCATION 12. Lumber used shall be of the species and size, and in all respects, equal to or better than that specified. Indicated by symbol shown and/or by text in the bracing section of the Trusses are designed for wind loads in the plane of the truss unless otherwise shown. 13. Top chords must be sheathed or pur ins provided at spacing indicated on design. output. Use T or I bracing if indicated. Lumber design values are in accordance with ANSI/TPI 1 14. Bottom chords require lateral bracing at 10 ft. spacing, or less, if no ceiling is installed, unless otherwise noted. section 6.3 These truss designs rely on lumber values BEARING established by Others. 15. Connections not shown are the responsibility of others. 16. Do not cut or alter truss member or plate without prior Indicates location where bearings approval of an engineer. (supports) occur. Icons vary but reaction section indicates joint © 2012 MiTek® All Rights Reserved 17. Install and load vertically unless indicated otherwise. number where bearings occur. Min size shown is for crushing only. 18. Use of green or treated lumber may pose unacceptable environmental, health or performance risks. Consult with project engineer before use. Industry Standards' IA I 19. Review all portions of this design (front, back, words ANSI/TPI1: National Design Specification for Metal and pictures) before use. Reviewing pictures alone is not sufficient. Plate Connected Wood Truss Construction. DSB-89: Design Standard for Bracing. ® 20. Design assumes manufacture in accordance with BCSI: Building Component Safety Information, MiTek ANSI/rPI 1 Quality Criteria. Guide to Good Practice for Handling, Installing & Bracing of Metal Plate 21.The design does not take into account any dynamic Connected Wood Trusses. MiTek Engineering Reference Sheet: MII-7473 rev. 5/19/2020 or other loads other than those expressly stated.