HomeMy WebLinkAboutENCODE - HEAT LOADS - EVANS RESIDENCE - 11-11-2020
Evans Residence
HVAC Load Calculations
for
Evans Residence
5911 Birch Drive
Fort Pierce, Florida
Prepared By:
Eric J. Svoboda, PE
Fort Pierce Engineering, Inc.
315 South 7th Street
Fort Pierce, FL
772-672-4636
Monday, October 5, 2020
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
Fort Pierce Engineering Evans Residence
Fort Pierce, FL 34950 Page 2
Project Report
General Project Information
Project Title:Evans Residence
Designed By:Eric J. Svoboda, PE
Project Date:Wednesday, February 18, 2009
Client Name:Evans Residence
Client Address:5911 Birch Drive
Client City:Fort Pierce, Florida
Company Name:Fort Pierce Engineering, Inc.
Company Representative:Eric J. Svoboda, PE
Company Address:315 South 7th Street
Company City:Fort Pierce, FL
Company Phone:772-672-4636
Design Data
Reference City:Fort Pierce, Florida
Building Orientation:Front door faces North
Daily Temperature Range:Medium
Latitude:27 Degrees
Elevation:25 ft.
Altitude Factor:0.999
Outdoor Outdoor Outdoor Indoor Indoor Grains
Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Difference
Winter:42 39.4 n/a n/a 72 n/a
Summer:95 80 53%50%75 66
Check Figures
Total Building Supply CFM:966 CFM Per Square ft.:0.587
Square ft. of Room Area:1,644 Square ft. Per Ton:541
Volume (ft³) of Cond. Space:14,796
Building Loads
Total Heating Required Including Ventilation Air:26,851 Btuh 26.851 MBH
Total Sensible Gain:26,506 Btuh 73 %
Total Latent Gain:9,947 Btuh 27 %
Total Cooling Required Including Ventilation Air:36,453 Btuh 3.04 Tons (Based On Sensible + Latent)
Notes
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
Z:\ ...\Evans Residence Heat Load.rh9 Monday, October 5, 2020, 12:41 PM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
Fort Pierce Engineering Evans Residence
Fort Pierce, FL 34950 Page 3
Load Preview Report
Scope
Net
Ton
ft.²
/Ton Area
Sen
Gain
Lat
Gain
Net
Gain
Sen
Loss
Sys
Htg
CFM
Sys
Clg
CFM
Sys
Act
CFM
Duct
Size
Building 3.04 541 1,644 26,506 9,947 36,453 26,851 337 966 966
System 1 3.04 541 1,644 26,506 9,947 36,453 26,851 337 966 966 12x15
Supply Duct Latent 328 328
Return Duct 5,282 1,994 7,276 916
Zone 1 1,644 21,225 7,625 28,850 25,934 337 966 966 12x15
1-Kitchen 126 4,451 1,247 5,698 4,017 52 203 203 2--6
2-Living / Dining 391 6,211 2,329 8,540 6,346 82 283 283 3--6
3-Bath 2 40 142 56 198 170 2 6 6 1--4
4-Bath 1 110 1,297 765 2,062 2,399 31 59 59 1--4
5-WIC 1 132 527 198 725 1,043 14 24 24 1--4
6-Bedroom 1 225 2,575 1,219 3,794 4,023 52 117 117 2--4
7-Hall 180 797 169 966 1,212 16 36 36 1--4
8-Bedroom 2 220 3,305 990 4,295 4,025 52 150 150 2--5
9-Bedroom 3 220 1,920 652 2,572 2,699 35 87 87 1--5
Z:\ ...\Evans Residence Heat Load.rh9 Monday, October 5, 2020, 12:41 PM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
Fort Pierce Engineering Evans Residence
Fort Pierce, FL 34950 Page 4
System 1 AHU-1 Summary Loads
Component
Description
Area
Quan
Sen
Loss
Lat
Gain
Sen
Gain
Total
Gain
2A-m-o: Glazing-Double pane low-e (e = 0.60), operable
window, metal frame no break, u-value 0.84, SHGC
0.61
91 2,292 0 4,462 4,462
11P: Door-Metal - Polyurethane Core 42 366 0 378 378
12E-0sw: Wall-Frame, R-19 insulation in 2 x 6 stud
cavity, no board insulation, siding finish, wood studs
1145 2,335 0 1,746 1,746
12B-0bw: Part-Frame, R-11 insulation in 2 x 4 stud
cavity, no board insulation, brick finish, wood studs
180 174 0 174 174
12B-0bw: Wall-Frame, R-11 insulation in 2 x 4 stud
cavity, no board insulation, brick finish, wood studs
144 419 0 247 247
18A1-8-19o: Roof/Ceiling-Roof Joists Between Roof
Deck and Ceiling or Foam Encapsulated Roof Joists,
Spray Foam Insulation, Dark or Bold-Color Asphalt
Shingle, Dark Metal, Dark Membrane, Dark Tar and
Gravel, R-19 open cell 1/2 lb. spray foam, 5 inches in
2 x 8 joist cavity
1644 2,565 0 2,650 2,650
22A-ph: Floor-Slab on grade, No edge insulation, no
insulation below floor, any floor cover, passive, heavy
moist soil
176 7,170 0 0 0
Subtotals for structure:15,321 0 9,657 9,657
People:13 2,600 2,990 5,590
Equipment:0 1,200 1,200
Lighting:0 0 0
Ductwork:7,011 2,322 10,208 12,530
Infiltration: Winter CFM: 137, Summer CFM: 112 4,519 5,025 2,451 7,476
Ventilation: Winter CFM: 0, Summer CFM: 0 0 0 0 0
Exhaust: Winter CFM: 100, Summer CFM: 100
System 1 AHU-1 Load Totals:26,851 9,947 26,506 36,453
Check Figures
Supply CFM:966 CFM Per Square ft.:0.587
Square ft. of Room Area:1,644 Square ft. Per Ton:541
Volume (ft³) of Cond. Space:14,796
System Loads
Total Heating Required Including Ventilation Air:26,851 Btuh 26.851 MBH
Total Sensible Gain:26,506 Btuh 73 %
Total Latent Gain:9,947 Btuh 27 %
Total Cooling Required Including Ventilation Air:36,453 Btuh 3.04 Tons (Based On Sensible + Latent)
Notes
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.